ElmBranch attributesPowerFactory Branch

Every attribute of the PowerFactory Branch (ElmBranch): 85 input parameters and 773 result variables, with units and meaning. Copy a name into GetAttribute or SetAttribute.

What ElmBranch is

A branch: one element that holds a chain of lines, switches and terminals, reported as a whole with its total impedance, length and rating.

Class
ElmBranch, element class
PowerFactory name
Branch
Terminal suffix
the name of the terminal, as :busN
Attributes
85 input parameters and 773 result variables, in 6 calculations

Read and write ElmBranch in Python

import powerfactory

app = powerfactory.GetApplication()          # GetApplicationExt() from outside PowerFactory
app.GetFromStudyCase("ComLdf").Execute()      # results exist after a calculation

for obj in app.GetCalcRelevantObjects("*.ElmBranch"):
    loading = obj.GetAttribute("c:loading")       # Loading, %
    print(obj.loc_name, loading)

obj = app.GetCalcRelevantObjects("*.ElmBranch")[0]
obj.SetAttribute("loc_name", "Branch A-B")    # rename the branch
  • A result at a terminal of the branch needs the terminal in its name: m:P:busN, not m:P, which raises AttributeError.
  • An input parameter is read and written with or without its e: prefix: GetAttribute("outserv") and GetAttribute("e:outserv") give the same value.
  • RMS and EMT variables change over time: record them in a results object (ElmRes) to read the whole curve. GetAttribute after a run gives the value at the last time step.

ElmBranch input parameters

The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.

AttributeUnitDescription
loc_name·Name
chr_name·Characteristic Name
for_name·Foreign Key
dat_src·Data source
appr_modby·Modified by
sernum·Serial Number
appr_status·Status
iDatCon0·Connection 1
iDatCon1·Connection 2
iperfect·Ideal component
appr_modif·Modified
GPScoordsdegGeographical Position
cimRdfId·RDF ID
desc·Description
fold_id·In Folder
circuit·CircuitObject: ElmCircuit
p_conn0·Connection 1Object: Elm*,Sta*,RelFuse
p_conn1·Connection 2Object: Elm*,Sta*,RelFuse
pOwner·OwnerObject: ElmOwner
pOperator·OperatorObject: ElmOperator
pDiagram·DiagramObject: IntGrfnet
pStochStoTyplneElement model
contents·Contents
cpHeadFold·Head Folder
cpGrid·GridObject: ElmNet
cpZone·ZoneObject: ElmZone
cpArea·AreaObject: ElmArea
cpFeed·FeederObject: ElmFeeder
ciDist·Distance from infeed in number of buses
ciLater·Lateral Index
ciDistRoot·Distance from first infeed in number of buses
ciDistAll·Distance from infeed in number of buses including switches
ciDistAllRoot·Distance from first infeed in number of buses including switches
cpOwner·OwnerObject: ElmOwner
cpOperator·OperatorObject: ElmOperator
cpBranch·BranchObject: ElmBranch
cpSite·SiteObject: ElmSite
cpSubstat·SubstationObject: ElmSubstat,ElmTrfstat
cpMeteostat·Meteo StationObject: ElmMeteostat
ciOutaged·Planned Outage
ciEnergized·Energized
ciEarthed·Earthed
cDisplayName·Display Name
cpSupplyTransformer·Supplying TransformerObject: ElmTr?,ElmTrmult
cpSupplyTrfStation·Supplying Secondary SubstationObject: ElmTrfstat
cpSupplySubstation·Supplying SubstationObject: ElmSubstat
cTerm0·Terminal 0
cTerm1·Terminal 1
ContRatingMVARating
lengthkmLength
InomkANominal Current
Inom_akANominal Current (act.)
R1OhmPos. Seq. Resistance, R1
X1OhmPos. Seq. Reactance, X1
Z1OhmPos. Seq. Impedance, Z1
phiz1degPos. Seq. Impedance, Angle
R0OhmZero Seq. Resistance, R0
X0OhmZero Seq. Reactance, X0
k0·Earth Factor, Magnitude
phik0degEarth Factor, Angle
IceAEarth-Fault Current, Ice
B1uSSusceptance B1
B0uSSusceptance B0
C1uFCapacitance C1
C0uFCapacitance C0
G1uSConductance G1
G0uSConductance G0
ReRl·Earth Factor, Re/Rl
XeXl·Earth Factor, Xe/Xl
rSbasepup.u.r (Sbase)
xSbasepup.u.x (Sbase)
bSbasepup.u.b (Sbase)
r0Sbasepup.u.r0 (Sbase)
x0Sbasepup.u.x0 (Sbase)
b0Sbasepup.u.b0 (Sbase)
deltaphiu1degVoltage Angle Difference across Branch
deltau1p.u.Voltage Difference across Branch
mincrosssecmm^2Minimum Cross Section
containsDCEquip·Contains DC equipment
FOR11/aForced Outage Rate
FOEh/aForced Outage Expectancy
FODhForced Outage Duration
CCEarFr1/aFrequency of single earth faults
CCEarRepMuhRepair duration
CCEarProb%Conditional probability of a second earth fault

ElmBranch load flow results

Read after ComLdf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:busNbusN: the terminalp.u.Voltage, Real Part, referred to network
m:uinet:busNbusN: the terminalp.u.Voltage, Imaginary Part, referred to network
m:u1r:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Real Part
m:u1i:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Magnitude
m:U1:busNbusN: the terminalkVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:busNbusN: the terminalkVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:busNbusN: the terminaldegPositive-Sequence-Voltage, Angle
m:irnet:busNbusN: the terminalp.u.Current, Real Part, referred to network
m:iinet:busNbusN: the terminalp.u.Current, Imaginary Part, referred to network
m:inet:busNbusN: the terminalp.u.Current, Magnitude, referred to network
m:I:busNbusN: the terminalkACurrent, Magnitude
m:phii:busNbusN: the terminaldegCurrent, Angle
m:i1r:busNbusN: the terminalp.u.Positive-Sequence Current, Real Part
m:i1i:busNbusN: the terminalp.u.Positive-Sequence Current, Imaginary Part
m:i1:busNbusN: the terminalp.u.Positive-Sequence Current, Magnitude
m:I1:busNbusN: the terminalkAPositive-Sequence Current, Magnitude
m:phii1:busNbusN: the terminaldegPositive-Sequence Current, Angle
m:P:busNbusN: the terminalMWActive Power
m:Q:busNbusN: the terminalMvarReactive Power
m:S:busNbusN: the terminalMVAApparent Power
m:cosphi:busNbusN: the terminal·Power Factor
m:tanphi:busNbusN: the terminal·tan(phi)
m:Psum:busNbusN: the terminalMWTotal Active Power
m:Qsum:busNbusN: the terminalMvarTotal Reactive Power
m:Ssum:busNbusN: the terminalMVATotal Apparent Power
m:cosphisum:busNbusN: the terminal·Total Power Factor
m:tanphisum:busNbusN: the terminal·Total tan(phi)
m:i1P:busNbusN: the terminalp.u.Positive-Sequence Active Current
m:i1Q:busNbusN: the terminalp.u.Positive-Sequence Reactive Current
m:I1P:busNbusN: the terminalkAPositive-Sequence Active Current
m:I1Q:busNbusN: the terminalkAPositive-Sequence Reactive Current
m:ur:busNbusN: the terminalp.u.Voltage, Real Part
m:ui:busNbusN: the terminalp.u.Voltage, Imaginary Part
m:u:busNbusN: the terminalp.u.Voltage, Magnitude
m:ir:busNbusN: the terminalp.u.Current, Real Part
m:ii:busNbusN: the terminalp.u.Current, Imaginary Part
m:i:busNbusN: the terminalp.u.Current, Magnitude
m:phiui:busNbusN: the terminaldegAngle between Voltage and Current
m:phiu1i1:busNbusN: the terminaldegAngle between Voltage and Current in positive sequence system
m:Tfct:busNbusN: the terminalsFault Clearing Time
m:Brkload:busNbusN: the terminal%Breaker Loading
m:Spu:busNbusN: the terminalMVA/p.u.Apparent Power per p.u. Voltage
m:urnet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:busNbusN: the terminalp.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:busNbusN: the terminaldegZero-Sequence-Voltage, Angle
m:u2:busNbusN: the terminalp.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:busNbusN: the terminaldegNegative-Sequence-Voltage, Angle
m:irnet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part, referred to network
m:iinet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part, referred to network
m:inet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude, referred to network
m:I:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:busNbusN: the terminalp.u.Zero-Sequence Current, Real Part
m:i0i:busNbusN: the terminalp.u.Zero-Sequence Current, Imaginary Part
m:i0:busNbusN: the terminalp.u.Zero-Sequence Current, Magnitude
m:I0:busNbusN: the terminalkAZero-Sequence Current, Magnitude
m:I0x3:busNbusN: the terminalkA3*I0
m:phii0:busNbusN: the terminaldegZero-Sequence Current, Angle
m:i2r:busNbusN: the terminalp.u.Negative-Sequence Current, Real Part
m:i2i:busNbusN: the terminalp.u.Negative-Sequence Current, Imaginary Part
m:i2:busNbusN: the terminalp.u.Negative-Sequence Current, Magnitude
m:I2:busNbusN: the terminalkANegative-Sequence Current, Magnitude
m:phii2:busNbusN: the terminaldegNegative-Sequence Current, Angle
m:ubfacI:busNbusN: the terminal%Current Unbalance Factor
m:ubfacS:busNbusN: the terminal%Power Unbalance Factor
m:P:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only·Power Factor
m:tanphi:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only·tan(phi)
m:Pln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:busNbusN: the terminalMWPositive Sequence Active Power
m:Q1:busNbusN: the terminalMvarPositive Sequence Reactive Power
m:P2:busNbusN: the terminalMWNegative Sequence Active Power
m:Q2:busNbusN: the terminalMvarNegative Sequence Reactive Power
m:P0:busNbusN: the terminalMWZero Sequence Active Power
m:Q0:busNbusN: the terminalMvarZero Sequence Reactive Power
m:i2P:busNbusN: the terminalp.u.Negative-Sequence Active Current
m:i2Q:busNbusN: the terminalp.u.Negative-Sequence Reactive Current
m:I2P:busNbusN: the terminalkANegative-Sequence Active Current
m:I2Q:busNbusN: the terminalkANegative-Sequence Reactive Current
m:ur:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:busNbusN: the terminaldegAngle between Voltage and Current in zero-sequence system
m:phiu2i2:busNbusN: the terminaldegAngle between Voltage and Current in negative sequence system
m:TfctPh:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Breaker Loading
c:loading%Loading
c:bayloading%Bay loading
c:CloadMvarCapacitive Losses
c:GloadkWActive no load losses
c:LosseskWLosses
c:LossesQkvarReactive-Losses
c:ImaxkAMaximum Current
c:dup.u.Voltage Drop
c:dupc%Voltage Drop
c:dphiudegVoltage Drop Angle
c:du1p.u.Positive Sequence Voltage Drop
c:du1pc%Positive Sequence Voltage Drop
c:dphiu1degPositive Sequence Voltage Drop Angle
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:loadingPh:Aper phase :A, :B, :C, unbalanced only%Loading
c:loading_st%Short Term Loading
c:CloadPh:Aper phase :A, :B, :C, unbalanced onlyMvarCapacitive Losses
c:GloadPh:Aper phase :A, :B, :C, unbalanced onlykWActive no load losses
c:LossesPh:Aper phase :A, :B, :C, unbalanced onlykWLosses
c:du:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage Drop
c:dupc:Aper phase :A, :B, :C, unbalanced only%Voltage Drop
c:dphiu:Aper phase :A, :B, :C, unbalanced onlydegVoltage Drop Angle
n:ur:busNbusN: the terminalp.u.Voltage, Real Part
n:ui:busNbusN: the terminalp.u.Voltage, Imaginary Part
n:u:busNbusN: the terminalp.u.Voltage, Magnitude
n:upc:busNbusN: the terminal%Voltage, Magnitude
n:du:busNbusN: the terminal%Voltage Deviation
n:U:busNbusN: the terminalkVLine-Ground Voltage, Magnitude
n:phiu:busNbusN: the terminaldegVoltage, Angle
n:phiurel:busNbusN: the terminaldegVoltage, Relative Angle
n:Ul:busNbusN: the terminalkVLine-Line Voltage, Magnitude
n:u1:busNbusN: the terminalp.u.Voltage, Magnitude
n:u1pc:busNbusN: the terminal%Voltage, Magnitude
n:u1r:busNbusN: the terminalp.u.Positive-Sequence Voltage, Real Part
n:u1i:busNbusN: the terminalp.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:busNbusN: the terminalMWGeneration, Active Power
n:Qgen:busNbusN: the terminalMvarGeneration, Reactive Power
n:Pmot:busNbusN: the terminalMWMotor Load, Active Power
n:Qmot:busNbusN: the terminalMvarMotor Load, Reactive Power
n:Pload:busNbusN: the terminalMWGeneral Load, Active Power
n:Qload:busNbusN: the terminalMvarGeneral Load, Reactive Power
n:Pcomp:busNbusN: the terminalMWCompensation (Losses)
n:Qcomp:busNbusN: the terminalMvarCompensation
n:Pnet:busNbusN: the terminalMWExternal Networks, Active Power
n:Qnet:busNbusN: the terminalMvarExternal Networks, Reactive Power
n:Pflow:busNbusN: the terminalMWPower Flow, Active Power
n:Qflow:busNbusN: the terminalMvarPower Flow, Reactive Power
n:Pout:busNbusN: the terminalMWOutgoing Flow, Active Power
n:Qout:busNbusN: the terminalMvarOutgoing Power, Reactive Power
n:Sout:busNbusN: the terminalMVAOutgoing Power, Apparent Power
n:cosphiout:busNbusN: the terminal·Outgoing Power, Power Factor
n:Pbalance:busNbusN: the terminalMWActive Power Balance (=0)
n:Qbalance:busNbusN: the terminalMvarReactive Power Balance (=0)
n:LossPdown:busNbusN: the terminalMWLosses, downstream
n:LossQdown:busNbusN: the terminalMvarLosses, downstream (Reactive Power)
n:LossPdownload:busNbusN: the terminalMWLoad losses, downstream
n:LossQdownload:busNbusN: the terminalMvarLoad losses, downstream
n:LossPdownnoload:busNbusN: the terminalMWNo load losses, downstream
n:LossQdownnoload:busNbusN: the terminalMvarNo load losses, downstream
n:du_feed:busNbusN: the terminal%Difference from voltage at start of feeder
n:ur:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:busNbusN: the terminalp.u.Zero-Sequence Voltage, Magnitude
n:U0:busNbusN: the terminalkVZero-Sequence Voltage, Magnitude
n:U0x3:busNbusN: the terminalkV3*U0
n:phiu0:busNbusN: the terminaldegZero-Sequence Voltage, Angle
n:U1:busNbusN: the terminalkVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:busNbusN: the terminaldegPositive-Sequence Voltage, Angle
n:u2:busNbusN: the terminalp.u.Negative-Sequence Voltage, Magnitude
n:U2:busNbusN: the terminalkVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:busNbusN: the terminaldegNegative-Sequence Voltage, Angle
n:U1l:busNbusN: the terminalkVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:busNbusN: the terminalkVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:busNbusN: the terminalp.u.Neutral-Ground Voltage, Magnitude
n:Un:busNbusN: the terminalkVNeutral-Ground Voltage, Magnitude
n:phiun:busNbusN: the terminaldegNeutral-Ground Voltage, Angle
n:upht:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:busNbusN: the terminalp.u.Average-Voltage, Magnitude
n:Um:busNbusN: the terminalkVAverage-Voltage, Magnitude
n:uphtmin:busNbusN: the terminalp.u.Minimum of Phase Technology dependent Voltage, Magnitude
n:uphtmax:busNbusN: the terminalp.u.Maximum of Phase Technology dependent Voltage, Magnitude
n:ubfac:busNbusN: the terminal%Unbalance Factor

ElmBranch short-circuit results

Read after ComShc with GetAttribute. m: currents, voltages and powers, n: bus result at a terminal.

AttributeUnitDescription
m:I:busNbusN: the terminalkAShort-Circuit Current, Magnitude
m:phii:busNbusN: the terminaldegPhase Current, Angle
m:i1:busNbusN: the terminalp.u.Positive-Sequence Current, Magnitude
m:I1:busNbusN: the terminalkAPositive-Sequence Current, Magnitude
m:phii1:busNbusN: the terminaldegPositive-Sequence Current, Angle
m:P:busNbusN: the terminalMWActive Power
m:Q:busNbusN: the terminalMvarReactive Power
m:i1P:busNbusN: the terminalp.u.Positive-Sequence Active Current
m:i1Q:busNbusN: the terminalp.u.Positive-Sequence Reactive Current
m:I1P:busNbusN: the terminalkAPositive-Sequence Active Current
m:I1Q:busNbusN: the terminalkAPositive-Sequence Reactive Current
m:phiui:busNbusN: the terminaldegAngle between Voltage and Current
m:phiu1i1:busNbusN: the terminaldegAngle between Voltage and Current in Positive-Sequence System
m:Tfct:busNbusN: the terminalsFault Clearing Time
m:Ikss:busNbusN: the terminalkAInitial Short-Circuit Current
m:ikss:busNbusN: the terminalp.u.Initial Short-Circuit Current, Magnitude
m:Skss:busNbusN: the terminalMVAInitial Short-Circuit Power
m:ip:busNbusN: the terminalkAPeak Short-Circuit Current
m:maxIkss:busNbusN: the terminalkAMax. Initial Short-Circuit Current
m:maxip:busNbusN: the terminalkAMax. Peak Short-Circuit Current
m:maxIth:busNbusN: the terminalkAMax. Thermal equivalent Short-Circuit Current
m:maxIb:busNbusN: the terminalkAMax. Breaking Current
m:R:busNbusN: the terminalOhmFault Impedance, Real Part
m:X:busNbusN: the terminalOhmFault Impedance, Imaginary Part
m:Z:busNbusN: the terminalOhmFault Impedance, Magnitude
m:phiz:busNbusN: the terminaldegFault Impedance, Angle
m:Rs:busNbusN: the terminalOhmSource Impedance, Real Part
m:Xs:busNbusN: the terminalOhmSource Impedance, Imaginary Part
m:Zs:busNbusN: the terminalOhmSource Impedance, Magnitude
m:phizs:busNbusN: the terminaldegSource Impedance, Angle
m:BrkIpload:busNbusN: the terminal%Breaker Loading (peak)
m:Ib:busNbusN: the terminalkAShort-Circuit Breaking Current
m:Sb:busNbusN: the terminalMVAShort-Circuit Breaking Power
m:Ith:busNbusN: the terminalkAThermal equivalent Short-Circuit Current
m:zSbase:busNbusN: the terminalp.u.Fault Impedance, Magnitude
m:XtoR:busNbusN: the terminal·X/R ratio
m:cosphiui:busNbusN: the terminal·cosphi
m:BrkIbload:busNbusN: the terminal%Breaker Loading (breaking)
m:BrkmaxIb:busNbusN: the terminalkAMax. Breaking Current (breaker time)
m:Ik:busNbusN: the terminalkASteady-State Short-Circuit Current
m:I:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, Magnitude
m:phii:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:I0:busNbusN: the terminalkAZero-Sequence Current, Magnitude
m:I0x3:busNbusN: the terminalkA3*I0
m:phii0:busNbusN: the terminaldegZero-Sequence Current, Angle
m:I2:busNbusN: the terminalkANegative-Sequence Current, Magnitude
m:phii2:busNbusN: the terminaldegNegative-Sequence Current, Angle
m:P:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:Psum:busNbusN: the terminalMWTotal Active Power
m:Qsum:busNbusN: the terminalMvarTotal Reactive Power
m:cosphisum:busNbusN: the terminal·Total Power Factor
m:P2:busNbusN: the terminalMWP2
m:Q2:busNbusN: the terminalMvarQ2
m:P0:busNbusN: the terminalMWP0
m:phiui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:busNbusN: the terminaldegAngle between Voltage and Current in Zero-Sequence System
m:phiu2i2:busNbusN: the terminaldegAngle between Voltage and Current in Negative-Sequence System
m:TfctPh:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:Ikss:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
m:ikss:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Initial Short-Circuit Current, Magnitude
m:Skss:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
m:Skssx3:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
m:ip:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
m:Z:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmFault Impedance, Magnitude
m:phiz:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegFault Impedance, Angle
m:Zl:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmLine-Line Fault Impedance, Magnitude
m:phizl:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Line Fault Impedance, Angle
m:Z0:busNbusN: the terminalOhmZero-Sequence Fault Impedance, Magnitude
m:phiz0:busNbusN: the terminaldegZero-Sequence Fault Impedance, Angle
m:z0Sbase:busNbusN: the terminalp.u.Zero-Sequence Fault Impedance, Magnitude
m:cosphiu1i1:busNbusN: the terminal·Positive-Sequence cosphi
m:I0x3watt:busNbusN: the terminalkAEarth-Fault Residual Current
m:I0x3var:busNbusN: the terminalkACapacitive Earth-Fault Current
m:Q0cap:busNbusN: the terminalMvarQ0 capacitive
m:Rfrel:busNbusN: the terminalOhmRelay Impedance, Real Part
m:Xfrel:busNbusN: the terminalOhmRelay Impedance, Imaginary Part
m:Zfrel:busNbusN: the terminalOhmRelay Impedance, Magnitude
m:phizfrel:busNbusN: the terminaldegRelay Impedance, Angle
m:Zf:busNbusN: the terminalOhmMeas. Fault Impedance, Magnitude
m:phizf:busNbusN: the terminaldegMeas. Fault Impedance, Angle
n:ur:busNbusN: the terminalp.u.Voltage, Real Part
n:ui:busNbusN: the terminalp.u.Voltage, Imaginary Part
n:u:busNbusN: the terminalp.u.Voltage, Magnitude
n:upc:busNbusN: the terminal%Voltage, Magnitude
n:du:busNbusN: the terminal%Voltage Deviation
n:U:busNbusN: the terminalkVLine-Ground Voltage, Magnitude
n:phiu:busNbusN: the terminaldegVoltage, Angle
n:Ul:busNbusN: the terminalkVLine-Line Voltage, Magnitude
n:u1:busNbusN: the terminalp.u.Voltage, Magnitude
n:u1pc:busNbusN: the terminal%Voltage, Magnitude
n:u1r:busNbusN: the terminalp.u.Positive-Sequence Voltage, Real Part
n:u1i:busNbusN: the terminalp.u.Positive-Sequence Voltage, Imaginary Part
n:Ikss:busNbusN: the terminalkAInitial Short-Circuit Current
n:I:busNbusN: the terminalkAShort-Circuit Current
n:phii:busNbusN: the terminaldegPhase Current, Angle
n:Skss:busNbusN: the terminalMVAInitial Short-Circuit Power
n:ip:busNbusN: the terminalkAPeak Short-Circuit Current
n:Ib:busNbusN: the terminalkAShort-Circuit Breaking Current
n:Sb:busNbusN: the terminalMVAShort-Circuit Breaking Power
n:idc:busNbusN: the terminalkADecaying Component
n:Ith:busNbusN: the terminalkAThermal equivalent Short-Circuit Current
n:R1toX1:busNbusN: the terminal·R1/X1 ratio (Zk")
n:X1toR1:busNbusN: the terminal·X1/R1 ratio (Zk")
n:R:busNbusN: the terminalOhmShort-Circuit Impedance, Real Part
n:X:busNbusN: the terminalOhmShort-Circuit Impedance, Imaginary Part
n:Z:busNbusN: the terminalOhmShort-Circuit Impedance, Magnitude
n:phiz:busNbusN: the terminaldegShort-Circuit Impedance, Angle
n:urpref:busNbusN: the terminalp.u.Pre-fault Voltage, Real Part
n:uipref:busNbusN: the terminalp.u.Pre-fault Voltage, Imaginary Part
n:upref:busNbusN: the terminalp.u.Pre-fault Voltage, Magnitude
n:uprefpc:busNbusN: the terminal%Pre-fault Voltage, Magnitude
n:Upref:busNbusN: the terminalkVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:busNbusN: the terminalkVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:busNbusN: the terminaldegPre-fault Voltage, Angle
n:phiui:busNbusN: the terminaldegAngle between Voltage and Current
n:Ithload:busNbusN: the terminal%Loading, Thermal equivalent Current
n:Ipload:busNbusN: the terminal%Loading, Peak Short-Circuit Current
n:Ithrtk:busNbusN: the terminalkARated Short-Time Current (Tk)
n:XtoR:busNbusN: the terminal·X/R ratio (peak)
n:RtoX:busNbusN: the terminal·R/X ratio (peak)
n:XtoR_b:busNbusN: the terminal·X/R ratio (dc)
n:RtoX_b:busNbusN: the terminal·R/X ratio (dc)
n:fctof_b:busNbusN: the terminal·Equivalent Frequency fc/f (dc)
n:rSbase:busNbusN: the terminalp.u.Short-Circuit Impedance, Real Part
n:xSbase:busNbusN: the terminalp.u.Short-Circuit Impedance, Imaginary Part
n:zSbase:busNbusN: the terminalp.u.Short-Circuit Impedance, Magnitude
n:Tn:busNbusN: the terminalmsGrid Time Constant
n:Ik:busNbusN: the terminalkASteady-State Short-Circuit Current
n:cfac:busNbusN: the terminal·Voltage Factor
n:Iasy:busNbusN: the terminalkAAsymmetrical Breaking Current
n:ur:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:busNbusN: the terminalp.u.Zero-Sequence Voltage, Magnitude
n:U0:busNbusN: the terminalkVZero-Sequence Voltage, Magnitude
n:U0x3:busNbusN: the terminalkV3*U0
n:phiu0:busNbusN: the terminaldegZero-Sequence Voltage, Angle
n:U1:busNbusN: the terminalkVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:busNbusN: the terminaldegPositive-Sequence Voltage, Angle
n:u2:busNbusN: the terminalp.u.Negative-Sequence Voltage, Magnitude
n:U2:busNbusN: the terminalkVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:busNbusN: the terminaldegNegative-Sequence Voltage, Angle
n:U1l:busNbusN: the terminalkVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:busNbusN: the terminalkVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:busNbusN: the terminalp.u.Neutral-Ground Voltage, Magnitude
n:Un:busNbusN: the terminalkVNeutral-Ground Voltage, Magnitude
n:phiun:busNbusN: the terminaldegNeutral-Ground Voltage, Angle
n:upht:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:Ikss:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
n:I:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:phii:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
n:Skss:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
n:Skssx3:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
n:ip:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
n:Ib:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Breaking Current
n:Sb:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMVAShort-Circuit Breaking Power
n:Ith:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAThermal equivalent Short-Circuit Current
n:Ithmax:busNbusN: the terminalkAMax. Thermal equivalent Short-Circuit Current
n:R0:busNbusN: the terminalOhmZero-Sequence Impedance, Real Part
n:X0:busNbusN: the terminalOhmZero-Sequence Impedance, Imaginary Part
n:Z0:busNbusN: the terminalOhmZero-Sequence Impedance, Magnitude
n:phiz0:busNbusN: the terminaldegZero-Sequence Impedance, Angle
n:r0Sbase:busNbusN: the terminalp.u.Zero-Sequence Impedance, Real Part
n:x0Sbase:busNbusN: the terminalp.u.Zero-Sequence Impedance, Imaginary Part
n:z0Sbase:busNbusN: the terminalp.u.Zero-Sequence Impedance, Magnitude
n:R1:busNbusN: the terminalOhmPositive-Sequence Impedance, Real Part
n:X1:busNbusN: the terminalOhmPositive-Sequence Impedance, Imaginary Part
n:Z1:busNbusN: the terminalOhmPositive-Sequence Impedance, Magnitude
n:phiz1:busNbusN: the terminaldegPositive-Sequence Impedance, Angle
n:r1Sbase:busNbusN: the terminalp.u.Positive-Sequence Impedance, Real Part
n:x1Sbase:busNbusN: the terminalp.u.Positive-Sequence Impedance, Imaginary Part
n:z1Sbase:busNbusN: the terminalp.u.Positive-Sequence Impedance, Magnitude
n:R2:busNbusN: the terminalOhmNegative-Sequence Impedance, Real Part
n:X2:busNbusN: the terminalOhmNegative-Sequence Impedance, Imaginary Part
n:Z2:busNbusN: the terminalOhmNegative-Sequence Impedance, Magnitude
n:phiz2:busNbusN: the terminaldegNegative-Sequence Impedance, Angle
n:r2Sbase:busNbusN: the terminalp.u.Negative-Sequence Impedance, Real Part
n:x2Sbase:busNbusN: the terminalp.u.Negative-Sequence Impedance, Imaginary Part
n:z2Sbase:busNbusN: the terminalp.u.Negative-Sequence Impedance, Magnitude
n:R0toX0:busNbusN: the terminal·R0/X0 ratio (Zk")
n:X0toR0:busNbusN: the terminal·X0/R0 ratio (Zk")
n:R2toX2:busNbusN: the terminal·R2/X2 ratio (Zk")
n:X2toR2:busNbusN: the terminal·X2/R2 ratio (Zk")
n:R:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Ground
n:X:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Ground
n:Z:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Ground
n:phiz:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Ground
n:Rl:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Line
n:Xl:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Line
n:Zl:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Line
n:phizl:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Line
n:Rln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Neutral
n:Xln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Neutral
n:Zln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Neutral
n:phizln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Neutral
n:Rn:busNbusN: the terminalOhmNetwork Resistance, Neutral
n:Xn:busNbusN: the terminalOhmNetwork Reactance, Neutral
n:Zn:busNbusN: the terminalOhmNetwork Impedance, Neutral
n:phizn:busNbusN: the terminaldegAngle of Network Impedance, Neutral
n:eff:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only·Earth Fault Factor
n:X0toX1:busNbusN: the terminal·X0/X1
n:In:busNbusN: the terminalkANeutral Current, Magnitude
n:phiin:busNbusN: the terminaldegNeutral Current, Angle
n:I0:busNbusN: the terminalkAZero-Sequence Current, Magnitude
n:I0x3:busNbusN: the terminalkA3*I0
n:phii0:busNbusN: the terminaldegZero-Sequence Current, Angle
n:I1:busNbusN: the terminalkAPositive-Sequence Current, Magnitude
n:phii1:busNbusN: the terminaldegPositive-Sequence Current, Angle
n:I2:busNbusN: the terminalkANegative-Sequence Current, Magnitude
n:phii2:busNbusN: the terminaldegNegative-Sequence Current, Angle
n:urpref:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Real Part
n:uipref:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Imaginary Part
n:upref:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Magnitude
n:uprefpc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Pre-fault Voltage, Magnitude
n:Upref:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegPre-fault Voltage, Angle
n:phiui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
n:phiu1i1:busNbusN: the terminaldegAngle between Voltage and Current in positive sequence system
n:phiu2i2:busNbusN: the terminaldegAngle between Voltage and Current in negative sequence system
n:phiu0i0:busNbusN: the terminaldegAngle between Voltage and Current in zero-sequence system
n:Ik:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykASteady-State Short-Circuit Current
n:in:busNbusN: the terminalp.u.Neutral Current, Magnitude
n:i0r:busNbusN: the terminalp.u.Zero-Sequence Current, Real Part
n:i0i:busNbusN: the terminalp.u.Zero-Sequence Current, Imaginary Part
n:i0:busNbusN: the terminalp.u.Zero-Sequence Current, Magnitude
n:i1r:busNbusN: the terminalp.u.Positive-Sequence Current, Real Part
n:i1i:busNbusN: the terminalp.u.Positive-Sequence Current, Imaginary Part
n:i1:busNbusN: the terminalp.u.Positive-Sequence Current, Magnitude
n:i2r:busNbusN: the terminalp.u.Negative-Sequence Current, Real Part
n:i2i:busNbusN: the terminalp.u.Negative-Sequence Current, Imaginary Part
n:i2:busNbusN: the terminalp.u.Negative-Sequence Current, Magnitude

ElmBranch rms simulation results

Read after ComInc (RMS) with GetAttribute. m: currents, voltages and powers, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:busNbusN: the terminalp.u.Voltage, Real Part, referred to network
m:uinet:busNbusN: the terminalp.u.Voltage, Imaginary Part, referred to network
m:u1r:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Real Part
m:u1i:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Magnitude
m:U1:busNbusN: the terminalkVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:busNbusN: the terminalkVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:busNbusN: the terminaldegPositive-Sequence-Voltage, Angle
m:irnet:busNbusN: the terminalp.u.Current, Real Part, referred to network
m:iinet:busNbusN: the terminalp.u.Current, Imaginary Part, referred to network
m:inet:busNbusN: the terminalp.u.Current, Magnitude, referred to network
m:I:busNbusN: the terminalkACurrent, Magnitude
m:phii:busNbusN: the terminaldegCurrent, Angle
m:i1r:busNbusN: the terminalp.u.Positive-Sequence Current, Real Part
m:i1i:busNbusN: the terminalp.u.Positive-Sequence Current, Imaginary Part
m:i1:busNbusN: the terminalp.u.Positive-Sequence Current, Magnitude
m:I1:busNbusN: the terminalkAPositive-Sequence Current, Magnitude
m:phii1:busNbusN: the terminaldegPositive-Sequence Current, Angle
m:P:busNbusN: the terminalMWActive Power
m:Q:busNbusN: the terminalMvarReactive Power
m:S:busNbusN: the terminalMVAApparent Power
m:cosphi:busNbusN: the terminal·Power Factor
m:tanphi:busNbusN: the terminal·tan(phi)
m:Psum:busNbusN: the terminalMWTotal Active Power
m:Qsum:busNbusN: the terminalMvarTotal Reactive Power
m:Ssum:busNbusN: the terminalMVATotal Apparent Power
m:cosphisum:busNbusN: the terminal·Total Power Factor
m:tanphisum:busNbusN: the terminal·Total tan(phi)
m:i1P:busNbusN: the terminalp.u.Positive-Sequence Active Current
m:i1Q:busNbusN: the terminalp.u.Positive-Sequence Reactive Current
m:I1P:busNbusN: the terminalkAPositive-Sequence Active Current
m:I1Q:busNbusN: the terminalkAPositive-Sequence Reactive Current
m:ur:busNbusN: the terminalp.u.Voltage, Real Part
m:ui:busNbusN: the terminalp.u.Voltage, Imaginary Part
m:u:busNbusN: the terminalp.u.Voltage, Magnitude
m:ir:busNbusN: the terminalp.u.Current, Real Part
m:ii:busNbusN: the terminalp.u.Current, Imaginary Part
m:i:busNbusN: the terminalp.u.Current, Magnitude
m:phiui:busNbusN: the terminaldegAngle between Voltage and Current
m:phiu1i1:busNbusN: the terminaldegAngle between Voltage and Current in positive sequence system
m:Tfct:busNbusN: the terminalsFault Clearing Time
m:Brkload:busNbusN: the terminal%Breaker Loading
m:Spu:busNbusN: the terminalMVA/p.u.Apparent Power per p.u. Voltage
m:urnet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:busNbusN: the terminalp.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:busNbusN: the terminaldegZero-Sequence-Voltage, Angle
m:u2:busNbusN: the terminalp.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:busNbusN: the terminaldegNegative-Sequence-Voltage, Angle
m:irnet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:iinet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:inet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:I:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:busNbusN: the terminalp.u.Zero-Sequence Current, Real Part
m:i0i:busNbusN: the terminalp.u.Zero-Sequence Current, Imaginary Part
m:i0:busNbusN: the terminalp.u.Zero-Sequence Current, Magnitude
m:I0:busNbusN: the terminalkAZero-Sequence Current, Magnitude
m:I0x3:busNbusN: the terminalkA3*I0
m:phii0:busNbusN: the terminaldegZero-Sequence Current, Angle
m:i2r:busNbusN: the terminalp.u.Negative-Sequence Current, Real Part
m:i2i:busNbusN: the terminalp.u.Negative-Sequence Current, Imaginary Part
m:i2:busNbusN: the terminalp.u.Negative-Sequence Current, Magnitude
m:I2:busNbusN: the terminalkANegative-Sequence Current, Magnitude
m:phii2:busNbusN: the terminaldegNegative-Sequence Current, Angle
m:P:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only·Power Factor
m:tanphi:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only·tan(phi)
m:Pln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:busNbusN: the terminalMWPositive Sequence Active Power
m:Q1:busNbusN: the terminalMvarPositive Sequence Reactive Power
m:P2:busNbusN: the terminalMWNegative Sequence Active Power
m:Q2:busNbusN: the terminalMvarNegative Sequence Reactive Power
m:P0:busNbusN: the terminalMWZero Sequence Active Power
m:Q0:busNbusN: the terminalMvarZero Sequence Reactive Power
m:i2P:busNbusN: the terminalp.u.Negative-Sequence Active Current
m:i2Q:busNbusN: the terminalp.u.Negative-Sequence Reactive Current
m:I2P:busNbusN: the terminalkANegative-Sequence Active Current
m:I2Q:busNbusN: the terminalkANegative-Sequence Reactive Current
m:ur:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:busNbusN: the terminaldegAngle between Voltage and Current in zero-sequence system
m:phiu2i2:busNbusN: the terminaldegAngle between Voltage and Current in negative sequence system
m:TfctPh:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Breaker Loading
n:ur:busNbusN: the terminalp.u.Voltage, Real Part
n:ui:busNbusN: the terminalp.u.Voltage, Imaginary Part
n:u:busNbusN: the terminalp.u.Voltage, Magnitude
n:upc:busNbusN: the terminal%Voltage, Magnitude
n:du:busNbusN: the terminal%Voltage Deviation
n:U:busNbusN: the terminalkVLine-Ground Voltage, Magnitude
n:phiu:busNbusN: the terminaldegVoltage, Angle
n:phiurel:busNbusN: the terminaldegVoltage, Relative Angle
n:Ul:busNbusN: the terminalkVLine-Line Voltage, Magnitude
n:u1:busNbusN: the terminalp.u.Voltage, Magnitude
n:u1pc:busNbusN: the terminal%Voltage, Magnitude
n:u1r:busNbusN: the terminalp.u.Positive-Sequence Voltage, Real Part
n:u1i:busNbusN: the terminalp.u.Positive-Sequence Voltage, Imaginary Part
n:ishc:busNbusN: the terminalp.u.Short-Circuit Current, magnitude
n:Ishc:busNbusN: the terminalkAShort-Circuit Current, magnitude
n:fe:busNbusN: the terminalp.u.Electrical Frequency
n:dfehz:busNbusN: the terminalHzDeviation of the El. Frequency
n:fehz:busNbusN: the terminalHzElectrical Frequency
n:frnom:busNbusN: the terminalHzNominal Frequency
n:ishcr:busNbusN: the terminalp.u.Short-Circuit Current, real
n:ishci:busNbusN: the terminalp.u.Short-Circuit Current, imag
n:dfedt:busNbusN: the terminalp.u./sDerivative of El. Frequency
n:ur:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:busNbusN: the terminalp.u.Zero-Sequence Voltage, Magnitude
n:U0:busNbusN: the terminalkVZero-Sequence Voltage, Magnitude
n:U0x3:busNbusN: the terminalkV3*U0
n:phiu0:busNbusN: the terminaldegZero-Sequence Voltage, Angle
n:U1:busNbusN: the terminalkVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:busNbusN: the terminaldegPositive-Sequence Voltage, Angle
n:u2:busNbusN: the terminalp.u.Negative-Sequence Voltage, Magnitude
n:U2:busNbusN: the terminalkVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:busNbusN: the terminaldegNegative-Sequence Voltage, Angle
n:U1l:busNbusN: the terminalkVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:busNbusN: the terminalkVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:busNbusN: the terminalp.u.Neutral-Ground Voltage, Magnitude
n:Un:busNbusN: the terminalkVNeutral-Ground Voltage, Magnitude
n:phiun:busNbusN: the terminaldegNeutral-Ground Voltage, Angle
n:upht:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:busNbusN: the terminalp.u.Average-Voltage, Magnitude
n:Um:busNbusN: the terminalkVAverage-Voltage, Magnitude
n:ishc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, magnitude
n:Ishc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, magnitude
n:inshc:busNbusN: the terminalp.u.Neutral Short-Circuit Current, magnitude
n:Inshc:busNbusN: the terminalkANeutral Short-Circuit Current, magnitude
n:ishcr:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, real
n:ishci:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, imag

ElmBranch emt simulation results

Read after ComInc (EMT) with GetAttribute. m: currents, voltages and powers, n: bus result at a terminal.

AttributeUnitDescription
m:u0:busNbusN: the terminalp.u.Zero-Sequence-Voltage
m:u1r:busNbusN: the terminalp.u.Voltage Phasor, Real Part
m:u1i:busNbusN: the terminalp.u.Voltage Phasor, Imaginary Part
m:u1:busNbusN: the terminalp.u.Voltage Phasor, Magnitude
m:U1:busNbusN: the terminalkVLine-Ground Voltage Phasor, Magnitude
m:U1l:busNbusN: the terminalkVLine-Line Voltage Phasor, Magnitude
m:phiu1:busNbusN: the terminaldegVoltage Phasor, Angle
m:inet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, referred to network
m:I:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAPhase Current
m:i0:busNbusN: the terminalp.u.Zero-Sequence Current
m:I0:busNbusN: the terminalkAZero-Sequence Current
m:I0x3:busNbusN: the terminalkA3*I0
m:i1r:busNbusN: the terminalp.u.Current Phasor, Real Part
m:i1i:busNbusN: the terminalp.u.Current Phasor, Imaginary Part
m:i1:busNbusN: the terminalp.u.Current Phasor, Magnitude
m:I1:busNbusN: the terminalkACurrent Phasor, Magnitude
m:phii1:busNbusN: the terminaldegCurrent Phasor, Angle
m:P:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Psum:busNbusN: the terminalMWPower-Phasor, Active Power
m:Qsum:busNbusN: the terminalMvarPower Phasor, Reactive Part
m:Ssum:busNbusN: the terminalMVAPower Phasor, Apparent Power
m:i1P:busNbusN: the terminalp.u.Current Phasor, Active Current
m:i1Q:busNbusN: the terminalp.u.Current Phasor, Reactive Current
m:I1P:busNbusN: the terminalkACurrent Phasor, Active Current
m:I1Q:busNbusN: the terminalkACurrent Phasor, Reactive Current
m:u:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
m:i:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current
m:phiu1i1:busNbusN: the terminaldegAngle between Voltage and Current Phasor
m:Tfct:busNbusN: the terminalsFault Clearing Time
m:TfctPh:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:unet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, referred to network
m:cosphi1:busNbusN: the terminal·Power-Phasor, Power-Factor
n:u:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
n:upc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Phase Voltage
n:U:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVPhase Voltage
n:ul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage
n:ulpc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Line-Line Voltage
n:Ul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage
n:u0:busNbusN: the terminalp.u.Zero-Sequence-Voltage
n:U0:busNbusN: the terminalkVZero-Sequence-Voltage
n:U0x3:busNbusN: the terminalkV3*U0
n:u1:busNbusN: the terminalp.u.Voltage Phasor, Magnitude
n:u1pc:busNbusN: the terminal%Voltage Phasor, Magnitude
n:u1r:busNbusN: the terminalp.u.Voltage Phasor, Real Part
n:u1i:busNbusN: the terminalp.u.Voltage Phasor, Imaginary Part
n:U1:busNbusN: the terminalkVVoltage Phasor, Magnitude
n:phiu1:busNbusN: the terminaldegVoltage Phasor, Angle
n:U1l:busNbusN: the terminalkVLine-Line Voltage Phasor, Magnitude
n:uln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage
n:Uln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage
n:un:busNbusN: the terminalp.u.Neutral-Ground Voltage
n:Un:busNbusN: the terminalkVNeutral-Ground Voltage
n:ishc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current
n:Ishc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:inshc:busNbusN: the terminalp.u.Neutral Short-Circuit Current, magnitude
n:Inshc:busNbusN: the terminalkANeutral Short-Circuit Current, magnitude
n:fe:busNbusN: the terminalp.u.Electrical Frequency
n:dfehz:busNbusN: the terminalHzDeviation of the El. Frequency
n:fehz:busNbusN: the terminalHzElectrical Frequency
n:frnom:busNbusN: the terminalHzNominal Frequency

ElmBranch dc load flow results

Read after ComLdf (DC) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:P:busNbusN: the terminalMWActive Power
m:Q:busNbusN: the terminalMvarReactive Power
c:loading%Loading
c:bayloading%Bay loading
c:dphiudegVoltage Drop Angle
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
n:u:busNbusN: the terminalp.u.Voltage, Magnitude
n:upc:busNbusN: the terminal%Voltage, Magnitude
n:U:busNbusN: the terminalkVLine-Ground Voltage, Magnitude
n:phiu:busNbusN: the terminaldegVoltage, Angle
n:phiurel:busNbusN: the terminaldegVoltage, Relative Angle
n:Ul:busNbusN: the terminalkVLine-Line Voltage, Magnitude
n:u1:busNbusN: the terminalp.u.Voltage, Magnitude
n:Pgen:busNbusN: the terminalMWGeneration, Active Power
n:Pmot:busNbusN: the terminalMWMotor Load, Active Power
n:Pload:busNbusN: the terminalMWGeneral Load, Active Power
n:Pcomp:busNbusN: the terminalMWCompensation (Losses)
n:Pnet:busNbusN: the terminalMWExternal Networks, Active Power
n:Pflow:busNbusN: the terminalMWPower Flow, Active Power

ElmBranch optimal power flow results

Read after ComOpf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:busNbusN: the terminalp.u.Voltage, Real Part, referred to network
m:uinet:busNbusN: the terminalp.u.Voltage, Imaginary Part, referred to network
m:u1r:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Real Part
m:u1i:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Magnitude
m:U1:busNbusN: the terminalkVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:busNbusN: the terminalkVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:busNbusN: the terminaldegPositive-Sequence-Voltage, Angle
m:irnet:busNbusN: the terminalp.u.Current, Real Part, referred to network
m:iinet:busNbusN: the terminalp.u.Current, Imaginary Part, referred to network
m:inet:busNbusN: the terminalp.u.Current, Magnitude, referred to network
m:I:busNbusN: the terminalkACurrent, Magnitude
m:phii:busNbusN: the terminaldegCurrent, Angle
m:i1r:busNbusN: the terminalp.u.Positive-Sequence Current, Real Part
m:i1i:busNbusN: the terminalp.u.Positive-Sequence Current, Imaginary Part
m:i1:busNbusN: the terminalp.u.Positive-Sequence Current, Magnitude
m:I1:busNbusN: the terminalkAPositive-Sequence Current, Magnitude
m:phii1:busNbusN: the terminaldegPositive-Sequence Current, Angle
m:P:busNbusN: the terminalMWActive Power
m:Q:busNbusN: the terminalMvarReactive Power
m:S:busNbusN: the terminalMVAApparent Power
m:cosphi:busNbusN: the terminal·Power Factor
m:tanphi:busNbusN: the terminal·tan(phi)
m:Psum:busNbusN: the terminalMWTotal Active Power
m:Qsum:busNbusN: the terminalMvarTotal Reactive Power
m:Ssum:busNbusN: the terminalMVATotal Apparent Power
m:cosphisum:busNbusN: the terminal·Total Power Factor
m:tanphisum:busNbusN: the terminal·Total tan(phi)
m:i1P:busNbusN: the terminalp.u.Positive-Sequence Active Current
m:i1Q:busNbusN: the terminalp.u.Positive-Sequence Reactive Current
m:I1P:busNbusN: the terminalkAPositive-Sequence Active Current
m:I1Q:busNbusN: the terminalkAPositive-Sequence Reactive Current
m:ur:busNbusN: the terminalp.u.Voltage, Real Part
m:ui:busNbusN: the terminalp.u.Voltage, Imaginary Part
m:u:busNbusN: the terminalp.u.Voltage, Magnitude
m:ir:busNbusN: the terminalp.u.Current, Real Part
m:ii:busNbusN: the terminalp.u.Current, Imaginary Part
m:i:busNbusN: the terminalp.u.Current, Magnitude
m:phiui:busNbusN: the terminaldegAngle between Voltage and Current
m:phiu1i1:busNbusN: the terminaldegAngle between Voltage and Current in positive sequence system
m:Tfct:busNbusN: the terminalsFault Clearing Time
m:Brkload:busNbusN: the terminal%Breaker Loading
m:Spu:busNbusN: the terminalMVA/p.u.Apparent Power per p.u. Voltage
c:loading%Loading
c:bayloading%Bay loading
c:CloadMvarCapacitive Losses
c:GloadkWActive no load losses
c:LosseskWLosses
c:LossesQkvarReactive-Losses
c:ImaxkAMaximum Current
c:dup.u.Voltage Drop
c:dupc%Voltage Drop
c:dphiudegVoltage Drop Angle
c:du1p.u.Positive Sequence Voltage Drop
c:du1pc%Positive Sequence Voltage Drop
c:dphiu1degPositive Sequence Voltage Drop Angle
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
n:ur:busNbusN: the terminalp.u.Voltage, Real Part
n:ui:busNbusN: the terminalp.u.Voltage, Imaginary Part
n:u:busNbusN: the terminalp.u.Voltage, Magnitude
n:upc:busNbusN: the terminal%Voltage, Magnitude
n:du:busNbusN: the terminal%Voltage Deviation
n:U:busNbusN: the terminalkVLine-Ground Voltage, Magnitude
n:phiu:busNbusN: the terminaldegVoltage, Angle
n:phiurel:busNbusN: the terminaldegVoltage, Relative Angle
n:Ul:busNbusN: the terminalkVLine-Line Voltage, Magnitude
n:u1:busNbusN: the terminalp.u.Voltage, Magnitude
n:u1pc:busNbusN: the terminal%Voltage, Magnitude
n:u1r:busNbusN: the terminalp.u.Positive-Sequence Voltage, Real Part
n:u1i:busNbusN: the terminalp.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:busNbusN: the terminalMWGeneration, Active Power
n:Qgen:busNbusN: the terminalMvarGeneration, Reactive Power
n:Pmot:busNbusN: the terminalMWMotor Load, Active Power
n:Qmot:busNbusN: the terminalMvarMotor Load, Reactive Power
n:Pload:busNbusN: the terminalMWGeneral Load, Active Power
n:Qload:busNbusN: the terminalMvarGeneral Load, Reactive Power
n:Pcomp:busNbusN: the terminalMWCompensation (Losses)
n:Qcomp:busNbusN: the terminalMvarCompensation
n:Pnet:busNbusN: the terminalMWExternal Networks, Active Power
n:Qnet:busNbusN: the terminalMvarExternal Networks, Reactive Power
n:Pflow:busNbusN: the terminalMWPower Flow, Active Power
n:Qflow:busNbusN: the terminalMvarPower Flow, Reactive Power
n:Pout:busNbusN: the terminalMWOutgoing Flow, Active Power
n:Qout:busNbusN: the terminalMvarOutgoing Power, Reactive Power
n:Sout:busNbusN: the terminalMVAOutgoing Power, Apparent Power
n:cosphiout:busNbusN: the terminal·Outgoing Power, Power Factor
n:Pbalance:busNbusN: the terminalMWActive Power Balance (=0)
n:Qbalance:busNbusN: the terminalMvarReactive Power Balance (=0)
n:LossPdown:busNbusN: the terminalMWLosses, downstream
n:LossQdown:busNbusN: the terminalMvarLosses, downstream (Reactive Power)
n:LossPdownload:busNbusN: the terminalMWLoad losses, downstream
n:LossQdownload:busNbusN: the terminalMvarLoad losses, downstream
n:LossPdownnoload:busNbusN: the terminalMWNo load losses, downstream
n:LossQdownnoload:busNbusN: the terminalMvarNo load losses, downstream
n:du_feed:busNbusN: the terminal%Difference from voltage at start of feeder

ElmBranch basic data

b: values are worked out from the input data. Read them; they are not set.

AttributeUnitDescription
b:loc_name·Name

Related

ElmCabsys Cable System →