ElmCoup attributesPowerFactory Breaker/Switch

Every attribute of the PowerFactory Breaker/Switch (ElmCoup): 88 input parameters and 825 result variables, with units and meaning. Copy a name into GetAttribute or SetAttribute.

What ElmCoup is

A breaker or switch between two terminals inside a substation. on_off says whether it is closed (1) or open (0).

Class
ElmCoup, element class
PowerFactory name
Breaker/Switch
Type
TypSwitch, through typ_id
Terminal suffix
:bus1 terminal i, :bus2 terminal j
Attributes
88 input parameters and 825 result variables, in 7 calculations

Most used ElmCoup attributes

AttributeUnitDescriptionWhere
on_offยทClosed1 closed, 0 openinput data
aUsageยทSwitch Typebreaker, disconnector, load switch...input data
m:I:bus1kACurrent, MagnitudeLoad flow
m:P:bus1MWActive PowerLoad flow

Read and write ElmCoup in Python

import powerfactory

app = powerfactory.GetApplication()          # GetApplicationExt() from outside PowerFactory
app.GetFromStudyCase("ComLdf").Execute()      # results exist after a calculation

for breaker in app.GetCalcRelevantObjects("*.ElmCoup"):
    i_bus1 = breaker.GetAttribute("m:I:bus1")     # Current, Magnitude, kA
    p_bus1 = breaker.GetAttribute("m:P:bus1")     # Active Power, MW
    print(breaker.loc_name, i_bus1, p_bus1)

breaker = app.GetCalcRelevantObjects("*.ElmCoup")[0]
breaker.SetAttribute("on_off", 0)             # open the breaker
  • A result at a terminal of the breaker/switch needs the terminal in its name: m:P:bus1, not m:P, which raises AttributeError.
  • An input parameter is read and written with or without its e: prefix: GetAttribute("outserv") and GetAttribute("e:outserv") give the same value.
  • RMS and EMT variables change over time: record them in a results object (ElmRes) to read the whole curve. GetAttribute after a run gives the value at the last time step.

ElmCoup input parameters

The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.

AttributeUnitDescription
loc_nameยทName
chr_nameยทCharacteristic Name
for_nameยทForeign Key
dat_srcยทData source
sernumยทSerial Number
commissionDateยทCommissioning Date
appr_modbyยทModified by
aUsageยทSwitch Type
iZoneBusยทZone
iAreaBusยทArea
on_offยทClosed
constrยทYear of Construction
appr_statusยทStatus
iNoOptยทExclude from optimisation
iSepยทSwitch can be opened during restoration
iResDirยทPower Restoration
nphaseยทNo. of Phases
nneutralยทNo. of Neutrals
iNeutInterยทSwitch interrupts neutral wire
logEnvCurveยทLog TRV envelope
iNormOpenSwtยทNormally open switch
iExclRAยทExcluded from Running Arrangement
idetailยทDetailed for calculation
rel_hasProtยทConsider as switch with protection device
rel_hasReclยทConsider as switch with automatic reclosing device
reclAttemptsยทMaximum number of reclosing attempts
ctrl_typeยทSectionalising
revFlowChkยทRelevant for the reversed power flow analysis
TbsBreak Time
GPSlatdegLatitude / Northing
GPSlondegLongitude / Easting
t_del_amsPhase a
t_del_bmsPhase b
t_del_cmsPhase c
t_del_nmsNeutral
TswitchminTime to actuate switch
prot_fail%Circuit breaker fails to open
dep_protOver%Unnecessary backup protection maloperation
spon_prot_f1/aFrequency of spurious protection operation
TprotsProtection Tripping Time
dpl1ยทdpl1
dpl2ยทdpl2
dpl3ยทdpl3
dpl4ยทdpl4
dpl5ยทdpl5
appr_modifยทModified
cimRdfIdยทRDF ID
descยทDescription
fold_idยทIn Folder
typ_idยทTypeObject: TypSwitch
bus1ยทTerminal iObject: StaCubic
bus2ยทTerminal jObject: StaCubic
doc_idยทAdditional Data
pOwnerยทOwnerObject: ElmOwner
pOperatorยทOperatorObject: ElmOperator
pRatingยทThermal RatingObject: IntThrating
pCBratingยทRatingsObject: IntCbrating
cpHeadFoldยทHead Folder
bus1_barยทTerminal i
bus2_barยทTerminal j
cpGridยทGridObject: ElmNet
cpZoneยทZoneObject: ElmZone
cpAreaยทAreaObject: ElmArea
cpFeedยทFeederObject: ElmFeeder
ciDistยทDistance from infeed in number of buses
ciLaterยทLateral Index
ciDistRootยทDistance from first infeed in number of buses
ciDistAllยทDistance from infeed in number of buses including switches
ciDistAllRootยทDistance from first infeed in number of buses including switches
cpOwnerยทOwnerObject: ElmOwner
cpOperatorยทOperatorObject: ElmOperator
cpBranchยทBranchObject: ElmBranch
cpSiteยทSiteObject: ElmSite
cpSubstatยทSubstationObject: ElmSubstat,ElmTrfstat
cpMeteostatยทMeteo StationObject: ElmMeteostat
ciOutagedยทPlanned Outage
ciEnergizedยทEnergized
ciEarthedยทEarthed
cDisplayNameยทDisplay Name
cpSupplyTransformerยทSupplying TransformerObject: ElmTr?,ElmTrmult
cpSupplyTrfStationยทSupplying Secondary SubstationObject: ElmTrfstat
cpSupplySubstationยทSupplying SubstationObject: ElmSubstat
cpBayยทBayObject: ElmBay
cTswitchminTime to open remote controlled switch
isclosedยทActual State
ciScenarioTypeยทScenario Type
InomkANominal Current
TclearsFault Clearing Time

ElmCoup load flow results

Read after ComLdf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:bus1or :bus2p.u.Voltage, Real Part, referred to network
m:uinet:bus1or :bus2p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1or :bus2p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1or :bus2p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1or :bus2p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1or :bus2kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1or :bus2kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1or :bus2degPositive-Sequence-Voltage, Angle
m:irnet:bus1or :bus2p.u.Current, Real Part, referred to network
m:iinet:bus1or :bus2p.u.Current, Imaginary Part, referred to network
m:inet:bus1or :bus2p.u.Current, Magnitude, referred to network
m:I:bus1or :bus2kACurrent, Magnitude
m:phii:bus1or :bus2degCurrent, Angle
m:i1r:bus1or :bus2p.u.Positive-Sequence Current, Real Part
m:i1i:bus1or :bus2p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1or :bus2p.u.Positive-Sequence Current, Magnitude
m:I1:bus1or :bus2kAPositive-Sequence Current, Magnitude
m:phii1:bus1or :bus2degPositive-Sequence Current, Angle
m:P:bus1or :bus2MWActive Power
m:Q:bus1or :bus2MvarReactive Power
m:S:bus1or :bus2MVAApparent Power
m:cosphi:bus1or :bus2ยทPower Factor
m:tanphi:bus1or :bus2ยทtan(phi)
m:Psum:bus1or :bus2MWTotal Active Power
m:Qsum:bus1or :bus2MvarTotal Reactive Power
m:Ssum:bus1or :bus2MVATotal Apparent Power
m:cosphisum:bus1or :bus2ยทTotal Power Factor
m:tanphisum:bus1or :bus2ยทTotal tan(phi)
m:i1P:bus1or :bus2p.u.Positive-Sequence Active Current
m:i1Q:bus1or :bus2p.u.Positive-Sequence Reactive Current
m:I1P:bus1or :bus2kAPositive-Sequence Active Current
m:I1Q:bus1or :bus2kAPositive-Sequence Reactive Current
m:ur:bus1or :bus2p.u.Voltage, Real Part
m:ui:bus1or :bus2p.u.Voltage, Imaginary Part
m:u:bus1or :bus2p.u.Voltage, Magnitude
m:ir:bus1or :bus2p.u.Current, Real Part
m:ii:bus1or :bus2p.u.Current, Imaginary Part
m:i:bus1or :bus2p.u.Current, Magnitude
m:phiui:bus1or :bus2degAngle between Voltage and Current
m:phiu1i1:bus1or :bus2degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1or :bus2sFault Clearing Time
m:Brkload:bus1or :bus2%Breaker Loading
m:Spu:bus1or :bus2MVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bus1or :bus2p.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bus1or :bus2degZero-Sequence-Voltage, Angle
m:u2:bus1or :bus2p.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bus1or :bus2degNegative-Sequence-Voltage, Angle
m:irnet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part, referred to network
m:iinet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part, referred to network
m:inet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude, referred to network
m:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bus1or :bus2p.u.Zero-Sequence Current, Real Part
m:i0i:bus1or :bus2p.u.Zero-Sequence Current, Imaginary Part
m:i0:bus1or :bus2p.u.Zero-Sequence Current, Magnitude
m:I0:bus1or :bus2kAZero-Sequence Current, Magnitude
m:I0x3:bus1or :bus2kA3*I0
m:phii0:bus1or :bus2degZero-Sequence Current, Angle
m:i2r:bus1or :bus2p.u.Negative-Sequence Current, Real Part
m:i2i:bus1or :bus2p.u.Negative-Sequence Current, Imaginary Part
m:i2:bus1or :bus2p.u.Negative-Sequence Current, Magnitude
m:I2:bus1or :bus2kANegative-Sequence Current, Magnitude
m:phii2:bus1or :bus2degNegative-Sequence Current, Angle
m:ubfacI:bus1or :bus2%Current Unbalance Factor
m:ubfacS:bus1or :bus2%Power Unbalance Factor
m:P:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyยทPower Factor
m:tanphi:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyยทtan(phi)
m:Pln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bus1or :bus2MWPositive Sequence Active Power
m:Q1:bus1or :bus2MvarPositive Sequence Reactive Power
m:P2:bus1or :bus2MWNegative Sequence Active Power
m:Q2:bus1or :bus2MvarNegative Sequence Reactive Power
m:P0:bus1or :bus2MWZero Sequence Active Power
m:Q0:bus1or :bus2MvarZero Sequence Reactive Power
m:i2P:bus1or :bus2p.u.Negative-Sequence Active Current
m:i2Q:bus1or :bus2p.u.Negative-Sequence Reactive Current
m:I2P:bus1or :bus2kANegative-Sequence Active Current
m:I2Q:bus1or :bus2kANegative-Sequence Reactive Current
m:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1or :bus2degAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bus1or :bus2degAngle between Voltage and Current in negative sequence system
m:TfctPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Breaker Loading
c:R_onOhmOn Resistance
c:X_onOhmOn Reactance
c:on_offยทFlag Closed
c:InomkARated Current
c:loading%Loading
c:maxload%Max. Loading
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:loadingPh:Aper phase :A, :B, :C, unbalanced only%Loading
c:loading_st%Short Term Loading
n:ur:bus1or :bus2p.u.Voltage, Real Part
n:ui:bus1or :bus2p.u.Voltage, Imaginary Part
n:u:bus1or :bus2p.u.Voltage, Magnitude
n:upc:bus1or :bus2%Voltage, Magnitude
n:du:bus1or :bus2%Voltage Deviation
n:U:bus1or :bus2kVLine-Ground Voltage, Magnitude
n:phiu:bus1or :bus2degVoltage, Angle
n:phiurel:bus1or :bus2degVoltage, Relative Angle
n:Ul:bus1or :bus2kVLine-Line Voltage, Magnitude
n:u1:bus1or :bus2p.u.Voltage, Magnitude
n:u1pc:bus1or :bus2%Voltage, Magnitude
n:u1r:bus1or :bus2p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1or :bus2p.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bus1or :bus2MWGeneration, Active Power
n:Qgen:bus1or :bus2MvarGeneration, Reactive Power
n:Pmot:bus1or :bus2MWMotor Load, Active Power
n:Qmot:bus1or :bus2MvarMotor Load, Reactive Power
n:Pload:bus1or :bus2MWGeneral Load, Active Power
n:Qload:bus1or :bus2MvarGeneral Load, Reactive Power
n:Pcomp:bus1or :bus2MWCompensation (Losses)
n:Qcomp:bus1or :bus2MvarCompensation
n:Pnet:bus1or :bus2MWExternal Networks, Active Power
n:Qnet:bus1or :bus2MvarExternal Networks, Reactive Power
n:Pflow:bus1or :bus2MWPower Flow, Active Power
n:Qflow:bus1or :bus2MvarPower Flow, Reactive Power
n:Pout:bus1or :bus2MWOutgoing Flow, Active Power
n:Qout:bus1or :bus2MvarOutgoing Power, Reactive Power
n:Sout:bus1or :bus2MVAOutgoing Power, Apparent Power
n:cosphiout:bus1or :bus2ยทOutgoing Power, Power Factor
n:Pbalance:bus1or :bus2MWActive Power Balance (=0)
n:Qbalance:bus1or :bus2MvarReactive Power Balance (=0)
n:LossPdown:bus1or :bus2MWLosses, downstream
n:LossQdown:bus1or :bus2MvarLosses, downstream (Reactive Power)
n:LossPdownload:bus1or :bus2MWLoad losses, downstream
n:LossQdownload:bus1or :bus2MvarLoad losses, downstream
n:LossPdownnoload:bus1or :bus2MWNo load losses, downstream
n:LossQdownnoload:bus1or :bus2MvarNo load losses, downstream
n:du_feed:bus1or :bus2%Difference from voltage at start of feeder
n:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1or :bus2p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1or :bus2kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1or :bus2kV3*U0
n:phiu0:bus1or :bus2degZero-Sequence Voltage, Angle
n:U1:bus1or :bus2kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1or :bus2degPositive-Sequence Voltage, Angle
n:u2:bus1or :bus2p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1or :bus2kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1or :bus2degNegative-Sequence Voltage, Angle
n:U1l:bus1or :bus2kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1or :bus2kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1or :bus2p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1or :bus2kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1or :bus2degNeutral-Ground Voltage, Angle
n:upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bus1or :bus2p.u.Average-Voltage, Magnitude
n:Um:bus1or :bus2kVAverage-Voltage, Magnitude
n:uphtmin:bus1or :bus2p.u.Minimum of Phase Technology dependent Voltage, Magnitude
n:uphtmax:bus1or :bus2p.u.Maximum of Phase Technology dependent Voltage, Magnitude
n:ubfac:bus1or :bus2%Unbalance Factor

ElmCoup short-circuit results

Read after ComShc with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:I:bus1or :bus2kAShort-Circuit Current, Magnitude
m:phii:bus1or :bus2degPhase Current, Angle
m:i1:bus1or :bus2p.u.Positive-Sequence Current, Magnitude
m:I1:bus1or :bus2kAPositive-Sequence Current, Magnitude
m:phii1:bus1or :bus2degPositive-Sequence Current, Angle
m:P:bus1or :bus2MWActive Power
m:Q:bus1or :bus2MvarReactive Power
m:i1P:bus1or :bus2p.u.Positive-Sequence Active Current
m:i1Q:bus1or :bus2p.u.Positive-Sequence Reactive Current
m:I1P:bus1or :bus2kAPositive-Sequence Active Current
m:I1Q:bus1or :bus2kAPositive-Sequence Reactive Current
m:phiui:bus1or :bus2degAngle between Voltage and Current
m:phiu1i1:bus1or :bus2degAngle between Voltage and Current in Positive-Sequence System
m:Tfct:bus1or :bus2sFault Clearing Time
m:Ikss:bus1or :bus2kAInitial Short-Circuit Current
m:ikss:bus1or :bus2p.u.Initial Short-Circuit Current, Magnitude
m:Skss:bus1or :bus2MVAInitial Short-Circuit Power
m:ip:bus1or :bus2kAPeak Short-Circuit Current
m:maxIkss:bus1or :bus2kAMax. Initial Short-Circuit Current
m:maxip:bus1or :bus2kAMax. Peak Short-Circuit Current
m:maxIth:bus1or :bus2kAMax. Thermal equivalent Short-Circuit Current
m:maxIb:bus1or :bus2kAMax. Breaking Current
m:R:bus1or :bus2OhmFault Impedance, Real Part
m:X:bus1or :bus2OhmFault Impedance, Imaginary Part
m:Z:bus1or :bus2OhmFault Impedance, Magnitude
m:phiz:bus1or :bus2degFault Impedance, Angle
m:Rs:bus1or :bus2OhmSource Impedance, Real Part
m:Xs:bus1or :bus2OhmSource Impedance, Imaginary Part
m:Zs:bus1or :bus2OhmSource Impedance, Magnitude
m:phizs:bus1or :bus2degSource Impedance, Angle
m:BrkIpload:bus1or :bus2%Breaker Loading (peak)
m:Ib:bus1or :bus2kAShort-Circuit Breaking Current
m:Sb:bus1or :bus2MVAShort-Circuit Breaking Power
m:Ith:bus1or :bus2kAThermal equivalent Short-Circuit Current
m:zSbase:bus1or :bus2p.u.Fault Impedance, Magnitude
m:XtoR:bus1or :bus2ยทX/R ratio
m:cosphiui:bus1or :bus2ยทcosphi
m:BrkIbload:bus1or :bus2%Breaker Loading (breaking)
m:BrkmaxIb:bus1or :bus2kAMax. Breaking Current (breaker time)
m:Ik:bus1or :bus2kASteady-State Short-Circuit Current
m:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, Magnitude
m:phii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:I0:bus1or :bus2kAZero-Sequence Current, Magnitude
m:I0x3:bus1or :bus2kA3*I0
m:phii0:bus1or :bus2degZero-Sequence Current, Angle
m:I2:bus1or :bus2kANegative-Sequence Current, Magnitude
m:phii2:bus1or :bus2degNegative-Sequence Current, Angle
m:P:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:Psum:bus1or :bus2MWTotal Active Power
m:Qsum:bus1or :bus2MvarTotal Reactive Power
m:cosphisum:bus1or :bus2ยทTotal Power Factor
m:P2:bus1or :bus2MWP2
m:Q2:bus1or :bus2MvarQ2
m:P0:bus1or :bus2MWP0
m:phiui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1or :bus2degAngle between Voltage and Current in Zero-Sequence System
m:phiu2i2:bus1or :bus2degAngle between Voltage and Current in Negative-Sequence System
m:TfctPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:Ikss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
m:ikss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Initial Short-Circuit Current, Magnitude
m:Skss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
m:Skssx3:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
m:ip:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
m:Z:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmFault Impedance, Magnitude
m:phiz:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegFault Impedance, Angle
m:Zl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmLine-Line Fault Impedance, Magnitude
m:phizl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Line Fault Impedance, Angle
m:Z0:bus1or :bus2OhmZero-Sequence Fault Impedance, Magnitude
m:phiz0:bus1or :bus2degZero-Sequence Fault Impedance, Angle
m:z0Sbase:bus1or :bus2p.u.Zero-Sequence Fault Impedance, Magnitude
m:cosphiu1i1:bus1or :bus2ยทPositive-Sequence cosphi
m:I0x3watt:bus1or :bus2kAEarth-Fault Residual Current
m:I0x3var:bus1or :bus2kACapacitive Earth-Fault Current
m:Q0cap:bus1or :bus2MvarQ0 capacitive
m:Rfrel:bus1or :bus2OhmRelay Impedance, Real Part
m:Xfrel:bus1or :bus2OhmRelay Impedance, Imaginary Part
m:Zfrel:bus1or :bus2OhmRelay Impedance, Magnitude
m:phizfrel:bus1or :bus2degRelay Impedance, Angle
m:Zf:bus1or :bus2OhmMeas. Fault Impedance, Magnitude
m:phizf:bus1or :bus2degMeas. Fault Impedance, Angle
c:R_onOhmOn Resistance
c:X_onOhmOn Reactance
c:on_offยทFlag Closed
c:InomkARated Current
c:loading%Max. Loading
c:t_opensOpening Time
c:Ibload%Loading, Interrupting
c:Ipload%Loading, Peak Short-Circuit Current
c:TbsBreak Time
c:XtoRยทX/R ratio (dc)
c:XtoR_pยทX/R ratio (peak)
c:IbmaxkABreaking Current
c:ibmaxkAPeak Breaking Current
c:IbasymmaxkAAsymmetrical Breaking Current
c:idcmaxkADecaying Component
c:IkssmaxkAInitial Short-Circuit Current
c:ipmaxkAPeak Short-Circuit Current
c:fctofยทEquivalent Frequency fc/f (dc)
n:ur:bus1or :bus2p.u.Voltage, Real Part
n:ui:bus1or :bus2p.u.Voltage, Imaginary Part
n:u:bus1or :bus2p.u.Voltage, Magnitude
n:upc:bus1or :bus2%Voltage, Magnitude
n:du:bus1or :bus2%Voltage Deviation
n:U:bus1or :bus2kVLine-Ground Voltage, Magnitude
n:phiu:bus1or :bus2degVoltage, Angle
n:Ul:bus1or :bus2kVLine-Line Voltage, Magnitude
n:u1:bus1or :bus2p.u.Voltage, Magnitude
n:u1pc:bus1or :bus2%Voltage, Magnitude
n:u1r:bus1or :bus2p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1or :bus2p.u.Positive-Sequence Voltage, Imaginary Part
n:Ikss:bus1or :bus2kAInitial Short-Circuit Current
n:I:bus1or :bus2kAShort-Circuit Current
n:phii:bus1or :bus2degPhase Current, Angle
n:Skss:bus1or :bus2MVAInitial Short-Circuit Power
n:ip:bus1or :bus2kAPeak Short-Circuit Current
n:Ib:bus1or :bus2kAShort-Circuit Breaking Current
n:Sb:bus1or :bus2MVAShort-Circuit Breaking Power
n:idc:bus1or :bus2kADecaying Component
n:Ith:bus1or :bus2kAThermal equivalent Short-Circuit Current
n:R1toX1:bus1or :bus2ยทR1/X1 ratio (Zk")
n:X1toR1:bus1or :bus2ยทX1/R1 ratio (Zk")
n:R:bus1or :bus2OhmShort-Circuit Impedance, Real Part
n:X:bus1or :bus2OhmShort-Circuit Impedance, Imaginary Part
n:Z:bus1or :bus2OhmShort-Circuit Impedance, Magnitude
n:phiz:bus1or :bus2degShort-Circuit Impedance, Angle
n:urpref:bus1or :bus2p.u.Pre-fault Voltage, Real Part
n:uipref:bus1or :bus2p.u.Pre-fault Voltage, Imaginary Part
n:upref:bus1or :bus2p.u.Pre-fault Voltage, Magnitude
n:uprefpc:bus1or :bus2%Pre-fault Voltage, Magnitude
n:Upref:bus1or :bus2kVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bus1or :bus2kVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bus1or :bus2degPre-fault Voltage, Angle
n:phiui:bus1or :bus2degAngle between Voltage and Current
n:Ithload:bus1or :bus2%Loading, Thermal equivalent Current
n:Ipload:bus1or :bus2%Loading, Peak Short-Circuit Current
n:Ithrtk:bus1or :bus2kARated Short-Time Current (Tk)
n:XtoR:bus1or :bus2ยทX/R ratio (peak)
n:RtoX:bus1or :bus2ยทR/X ratio (peak)
n:XtoR_b:bus1or :bus2ยทX/R ratio (dc)
n:RtoX_b:bus1or :bus2ยทR/X ratio (dc)
n:fctof_b:bus1or :bus2ยทEquivalent Frequency fc/f (dc)
n:rSbase:bus1or :bus2p.u.Short-Circuit Impedance, Real Part
n:xSbase:bus1or :bus2p.u.Short-Circuit Impedance, Imaginary Part
n:zSbase:bus1or :bus2p.u.Short-Circuit Impedance, Magnitude
n:Tn:bus1or :bus2msGrid Time Constant
n:Ik:bus1or :bus2kASteady-State Short-Circuit Current
n:cfac:bus1or :bus2ยทVoltage Factor
n:Iasy:bus1or :bus2kAAsymmetrical Breaking Current
n:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1or :bus2p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1or :bus2kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1or :bus2kV3*U0
n:phiu0:bus1or :bus2degZero-Sequence Voltage, Angle
n:U1:bus1or :bus2kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1or :bus2degPositive-Sequence Voltage, Angle
n:u2:bus1or :bus2p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1or :bus2kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1or :bus2degNegative-Sequence Voltage, Angle
n:U1l:bus1or :bus2kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1or :bus2kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1or :bus2p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1or :bus2kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1or :bus2degNeutral-Ground Voltage, Angle
n:upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:Ikss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
n:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:phii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
n:Skss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
n:Skssx3:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
n:ip:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
n:Ib:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Breaking Current
n:Sb:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVAShort-Circuit Breaking Power
n:Ith:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAThermal equivalent Short-Circuit Current
n:Ithmax:bus1or :bus2kAMax. Thermal equivalent Short-Circuit Current
n:R0:bus1or :bus2OhmZero-Sequence Impedance, Real Part
n:X0:bus1or :bus2OhmZero-Sequence Impedance, Imaginary Part
n:Z0:bus1or :bus2OhmZero-Sequence Impedance, Magnitude
n:phiz0:bus1or :bus2degZero-Sequence Impedance, Angle
n:r0Sbase:bus1or :bus2p.u.Zero-Sequence Impedance, Real Part
n:x0Sbase:bus1or :bus2p.u.Zero-Sequence Impedance, Imaginary Part
n:z0Sbase:bus1or :bus2p.u.Zero-Sequence Impedance, Magnitude
n:R1:bus1or :bus2OhmPositive-Sequence Impedance, Real Part
n:X1:bus1or :bus2OhmPositive-Sequence Impedance, Imaginary Part
n:Z1:bus1or :bus2OhmPositive-Sequence Impedance, Magnitude
n:phiz1:bus1or :bus2degPositive-Sequence Impedance, Angle
n:r1Sbase:bus1or :bus2p.u.Positive-Sequence Impedance, Real Part
n:x1Sbase:bus1or :bus2p.u.Positive-Sequence Impedance, Imaginary Part
n:z1Sbase:bus1or :bus2p.u.Positive-Sequence Impedance, Magnitude
n:R2:bus1or :bus2OhmNegative-Sequence Impedance, Real Part
n:X2:bus1or :bus2OhmNegative-Sequence Impedance, Imaginary Part
n:Z2:bus1or :bus2OhmNegative-Sequence Impedance, Magnitude
n:phiz2:bus1or :bus2degNegative-Sequence Impedance, Angle
n:r2Sbase:bus1or :bus2p.u.Negative-Sequence Impedance, Real Part
n:x2Sbase:bus1or :bus2p.u.Negative-Sequence Impedance, Imaginary Part
n:z2Sbase:bus1or :bus2p.u.Negative-Sequence Impedance, Magnitude
n:R0toX0:bus1or :bus2ยทR0/X0 ratio (Zk")
n:X0toR0:bus1or :bus2ยทX0/R0 ratio (Zk")
n:R2toX2:bus1or :bus2ยทR2/X2 ratio (Zk")
n:X2toR2:bus1or :bus2ยทX2/R2 ratio (Zk")
n:R:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Ground
n:X:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Ground
n:Z:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Ground
n:phiz:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Ground
n:Rl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Line
n:Xl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Line
n:Zl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Line
n:phizl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Line
n:Rln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Neutral
n:Xln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Neutral
n:Zln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Neutral
n:phizln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Neutral
n:Rn:bus1or :bus2OhmNetwork Resistance, Neutral
n:Xn:bus1or :bus2OhmNetwork Reactance, Neutral
n:Zn:bus1or :bus2OhmNetwork Impedance, Neutral
n:phizn:bus1or :bus2degAngle of Network Impedance, Neutral
n:eff:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyยทEarth Fault Factor
n:X0toX1:bus1or :bus2ยทX0/X1
n:In:bus1or :bus2kANeutral Current, Magnitude
n:phiin:bus1or :bus2degNeutral Current, Angle
n:I0:bus1or :bus2kAZero-Sequence Current, Magnitude
n:I0x3:bus1or :bus2kA3*I0
n:phii0:bus1or :bus2degZero-Sequence Current, Angle
n:I1:bus1or :bus2kAPositive-Sequence Current, Magnitude
n:phii1:bus1or :bus2degPositive-Sequence Current, Angle
n:I2:bus1or :bus2kANegative-Sequence Current, Magnitude
n:phii2:bus1or :bus2degNegative-Sequence Current, Angle
n:urpref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Real Part
n:uipref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Imaginary Part
n:upref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Magnitude
n:uprefpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Pre-fault Voltage, Magnitude
n:Upref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegPre-fault Voltage, Angle
n:phiui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
n:phiu1i1:bus1or :bus2degAngle between Voltage and Current in positive sequence system
n:phiu2i2:bus1or :bus2degAngle between Voltage and Current in negative sequence system
n:phiu0i0:bus1or :bus2degAngle between Voltage and Current in zero-sequence system
n:Ik:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykASteady-State Short-Circuit Current
n:in:bus1or :bus2p.u.Neutral Current, Magnitude
n:i0r:bus1or :bus2p.u.Zero-Sequence Current, Real Part
n:i0i:bus1or :bus2p.u.Zero-Sequence Current, Imaginary Part
n:i0:bus1or :bus2p.u.Zero-Sequence Current, Magnitude
n:i1r:bus1or :bus2p.u.Positive-Sequence Current, Real Part
n:i1i:bus1or :bus2p.u.Positive-Sequence Current, Imaginary Part
n:i1:bus1or :bus2p.u.Positive-Sequence Current, Magnitude
n:i2r:bus1or :bus2p.u.Negative-Sequence Current, Real Part
n:i2i:bus1or :bus2p.u.Negative-Sequence Current, Imaginary Part
n:i2:bus1or :bus2p.u.Negative-Sequence Current, Magnitude

ElmCoup rms simulation results

Read after ComInc (RMS) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:bus1or :bus2p.u.Voltage, Real Part, referred to network
m:uinet:bus1or :bus2p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1or :bus2p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1or :bus2p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1or :bus2p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1or :bus2kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1or :bus2kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1or :bus2degPositive-Sequence-Voltage, Angle
m:irnet:bus1or :bus2p.u.Current, Real Part, referred to network
m:iinet:bus1or :bus2p.u.Current, Imaginary Part, referred to network
m:inet:bus1or :bus2p.u.Current, Magnitude, referred to network
m:I:bus1or :bus2kACurrent, Magnitude
m:phii:bus1or :bus2degCurrent, Angle
m:i1r:bus1or :bus2p.u.Positive-Sequence Current, Real Part
m:i1i:bus1or :bus2p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1or :bus2p.u.Positive-Sequence Current, Magnitude
m:I1:bus1or :bus2kAPositive-Sequence Current, Magnitude
m:phii1:bus1or :bus2degPositive-Sequence Current, Angle
m:P:bus1or :bus2MWActive Power
m:Q:bus1or :bus2MvarReactive Power
m:S:bus1or :bus2MVAApparent Power
m:cosphi:bus1or :bus2ยทPower Factor
m:tanphi:bus1or :bus2ยทtan(phi)
m:Psum:bus1or :bus2MWTotal Active Power
m:Qsum:bus1or :bus2MvarTotal Reactive Power
m:Ssum:bus1or :bus2MVATotal Apparent Power
m:cosphisum:bus1or :bus2ยทTotal Power Factor
m:tanphisum:bus1or :bus2ยทTotal tan(phi)
m:i1P:bus1or :bus2p.u.Positive-Sequence Active Current
m:i1Q:bus1or :bus2p.u.Positive-Sequence Reactive Current
m:I1P:bus1or :bus2kAPositive-Sequence Active Current
m:I1Q:bus1or :bus2kAPositive-Sequence Reactive Current
m:ur:bus1or :bus2p.u.Voltage, Real Part
m:ui:bus1or :bus2p.u.Voltage, Imaginary Part
m:u:bus1or :bus2p.u.Voltage, Magnitude
m:ir:bus1or :bus2p.u.Current, Real Part
m:ii:bus1or :bus2p.u.Current, Imaginary Part
m:i:bus1or :bus2p.u.Current, Magnitude
m:phiui:bus1or :bus2degAngle between Voltage and Current
m:phiu1i1:bus1or :bus2degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1or :bus2sFault Clearing Time
m:Brkload:bus1or :bus2%Breaker Loading
m:Spu:bus1or :bus2MVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bus1or :bus2p.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bus1or :bus2degZero-Sequence-Voltage, Angle
m:u2:bus1or :bus2p.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bus1or :bus2degNegative-Sequence-Voltage, Angle
m:irnet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:iinet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:inet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bus1or :bus2p.u.Zero-Sequence Current, Real Part
m:i0i:bus1or :bus2p.u.Zero-Sequence Current, Imaginary Part
m:i0:bus1or :bus2p.u.Zero-Sequence Current, Magnitude
m:I0:bus1or :bus2kAZero-Sequence Current, Magnitude
m:I0x3:bus1or :bus2kA3*I0
m:phii0:bus1or :bus2degZero-Sequence Current, Angle
m:i2r:bus1or :bus2p.u.Negative-Sequence Current, Real Part
m:i2i:bus1or :bus2p.u.Negative-Sequence Current, Imaginary Part
m:i2:bus1or :bus2p.u.Negative-Sequence Current, Magnitude
m:I2:bus1or :bus2kANegative-Sequence Current, Magnitude
m:phii2:bus1or :bus2degNegative-Sequence Current, Angle
m:P:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyยทPower Factor
m:tanphi:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyยทtan(phi)
m:Pln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bus1or :bus2MWPositive Sequence Active Power
m:Q1:bus1or :bus2MvarPositive Sequence Reactive Power
m:P2:bus1or :bus2MWNegative Sequence Active Power
m:Q2:bus1or :bus2MvarNegative Sequence Reactive Power
m:P0:bus1or :bus2MWZero Sequence Active Power
m:Q0:bus1or :bus2MvarZero Sequence Reactive Power
m:i2P:bus1or :bus2p.u.Negative-Sequence Active Current
m:i2Q:bus1or :bus2p.u.Negative-Sequence Reactive Current
m:I2P:bus1or :bus2kANegative-Sequence Active Current
m:I2Q:bus1or :bus2kANegative-Sequence Reactive Current
m:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1or :bus2degAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bus1or :bus2degAngle between Voltage and Current in negative sequence system
m:TfctPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Breaker Loading
c:inputยทControl Input
c:R_onOhmOn Resistance
c:X_onOhmOn Reactance
c:InomkARated Current
c:loading%Loading
c:t_opensOpening Time
c:i_ctrlยทInternal
c:closedยทBreaker Closed
c:lockedยทLocked
c:IdFailureยทIndication Failure
c:IndicationยทIndication
c:TCMยทTrip Coil Monitor
c:loadingPh:Aper phase :A, :B, :C, unbalanced only%Loading
c:closedPh:Aper phase :A, :B, :C, unbalanced onlyยทBreaker Closed
n:ur:bus1or :bus2p.u.Voltage, Real Part
n:ui:bus1or :bus2p.u.Voltage, Imaginary Part
n:u:bus1or :bus2p.u.Voltage, Magnitude
n:upc:bus1or :bus2%Voltage, Magnitude
n:du:bus1or :bus2%Voltage Deviation
n:U:bus1or :bus2kVLine-Ground Voltage, Magnitude
n:phiu:bus1or :bus2degVoltage, Angle
n:phiurel:bus1or :bus2degVoltage, Relative Angle
n:Ul:bus1or :bus2kVLine-Line Voltage, Magnitude
n:u1:bus1or :bus2p.u.Voltage, Magnitude
n:u1pc:bus1or :bus2%Voltage, Magnitude
n:u1r:bus1or :bus2p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1or :bus2p.u.Positive-Sequence Voltage, Imaginary Part
n:ishc:bus1or :bus2p.u.Short-Circuit Current, magnitude
n:Ishc:bus1or :bus2kAShort-Circuit Current, magnitude
n:fe:bus1or :bus2p.u.Electrical Frequency
n:dfehz:bus1or :bus2HzDeviation of the El. Frequency
n:fehz:bus1or :bus2HzElectrical Frequency
n:frnom:bus1or :bus2HzNominal Frequency
n:ishcr:bus1or :bus2p.u.Short-Circuit Current, real
n:ishci:bus1or :bus2p.u.Short-Circuit Current, imag
n:dfedt:bus1or :bus2p.u./sDerivative of El. Frequency
n:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1or :bus2p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1or :bus2kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1or :bus2kV3*U0
n:phiu0:bus1or :bus2degZero-Sequence Voltage, Angle
n:U1:bus1or :bus2kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1or :bus2degPositive-Sequence Voltage, Angle
n:u2:bus1or :bus2p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1or :bus2kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1or :bus2degNegative-Sequence Voltage, Angle
n:U1l:bus1or :bus2kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1or :bus2kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1or :bus2p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1or :bus2kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1or :bus2degNeutral-Ground Voltage, Angle
n:upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bus1or :bus2p.u.Average-Voltage, Magnitude
n:Um:bus1or :bus2kVAverage-Voltage, Magnitude
n:ishc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, magnitude
n:Ishc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, magnitude
n:inshc:bus1or :bus2p.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bus1or :bus2kANeutral Short-Circuit Current, magnitude
n:ishcr:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, real
n:ishci:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, imag

ElmCoup emt simulation results

Read after ComInc (EMT) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:u0:bus1or :bus2p.u.Zero-Sequence-Voltage
m:u1r:bus1or :bus2p.u.Voltage Phasor, Real Part
m:u1i:bus1or :bus2p.u.Voltage Phasor, Imaginary Part
m:u1:bus1or :bus2p.u.Voltage Phasor, Magnitude
m:U1:bus1or :bus2kVLine-Ground Voltage Phasor, Magnitude
m:U1l:bus1or :bus2kVLine-Line Voltage Phasor, Magnitude
m:phiu1:bus1or :bus2degVoltage Phasor, Angle
m:inet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, referred to network
m:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAPhase Current
m:i0:bus1or :bus2p.u.Zero-Sequence Current
m:I0:bus1or :bus2kAZero-Sequence Current
m:I0x3:bus1or :bus2kA3*I0
m:i1r:bus1or :bus2p.u.Current Phasor, Real Part
m:i1i:bus1or :bus2p.u.Current Phasor, Imaginary Part
m:i1:bus1or :bus2p.u.Current Phasor, Magnitude
m:I1:bus1or :bus2kACurrent Phasor, Magnitude
m:phii1:bus1or :bus2degCurrent Phasor, Angle
m:P:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Psum:bus1or :bus2MWPower-Phasor, Active Power
m:Qsum:bus1or :bus2MvarPower Phasor, Reactive Part
m:Ssum:bus1or :bus2MVAPower Phasor, Apparent Power
m:i1P:bus1or :bus2p.u.Current Phasor, Active Current
m:i1Q:bus1or :bus2p.u.Current Phasor, Reactive Current
m:I1P:bus1or :bus2kACurrent Phasor, Active Current
m:I1Q:bus1or :bus2kACurrent Phasor, Reactive Current
m:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
m:i:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current
m:phiu1i1:bus1or :bus2degAngle between Voltage and Current Phasor
m:Tfct:bus1or :bus2sFault Clearing Time
m:TfctPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:unet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, referred to network
m:cosphi1:bus1or :bus2ยทPower-Phasor, Power-Factor
c:inputยทControl Input
c:R_onOhmOn Resistance
c:iNeutInterยทSwitch interrupts neutral wire
c:i_ctrlยทInternal
c:closedยทBreaker Closed
c:closedPh:Aper phase :A, :B, :C, unbalanced onlyยทBreaker Closed
c:lockedยทLocked
c:IdFailureยทIndication Failure
c:IndicationยทIndication
c:TCMยทTrip Coil Monitor
c:i_instยทInstant of Closing
c:t_delElmsDelay Time from network element and type
c:t_delTypesDelay Time from network element and type
c:t_delAccsAccumulated delay time
c:v_limp.u.Voltage Limit
c:i_schemeยทScheme
c:i_larlowยทLarger or lower than voltage threshold
c:L_onOhmOn Inductance
c:i_trigPhยทPhase that triggers
c:i_openยทOpen at executions time or zero crossing
c:TRV_pos:Aper phase :A, :B, :C, unbalanced onlyยทCB TRV envelope positive
c:TRV_neg:Aper phase :A, :B, :C, unbalanced onlyยทCB TRV envelope negative
n:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
n:upc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Phase Voltage
n:U:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVPhase Voltage
n:ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage
n:ulpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Line Voltage
n:Ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage
n:u0:bus1or :bus2p.u.Zero-Sequence-Voltage
n:U0:bus1or :bus2kVZero-Sequence-Voltage
n:U0x3:bus1or :bus2kV3*U0
n:u1:bus1or :bus2p.u.Voltage Phasor, Magnitude
n:u1pc:bus1or :bus2%Voltage Phasor, Magnitude
n:u1r:bus1or :bus2p.u.Voltage Phasor, Real Part
n:u1i:bus1or :bus2p.u.Voltage Phasor, Imaginary Part
n:U1:bus1or :bus2kVVoltage Phasor, Magnitude
n:phiu1:bus1or :bus2degVoltage Phasor, Angle
n:U1l:bus1or :bus2kVLine-Line Voltage Phasor, Magnitude
n:uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage
n:Uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage
n:un:bus1or :bus2p.u.Neutral-Ground Voltage
n:Un:bus1or :bus2kVNeutral-Ground Voltage
n:ishc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current
n:Ishc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:inshc:bus1or :bus2p.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bus1or :bus2kANeutral Short-Circuit Current, magnitude
n:fe:bus1or :bus2p.u.Electrical Frequency
n:dfehz:bus1or :bus2HzDeviation of the El. Frequency
n:fehz:bus1or :bus2HzElectrical Frequency
n:frnom:bus1or :bus2HzNominal Frequency
s:dU_AkVVoltage Difference
s:dU_BkVVoltage Difference
s:dU_CkVVoltage Difference

ElmCoup dc load flow results

Read after ComLdf (DC) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:P:bus1or :bus2MWActive Power
m:Q:bus1or :bus2MvarReactive Power
c:R_onOhmOn Resistance
c:X_onOhmOn Reactance
c:on_offยทFlag Closed
c:InomkARated Current
c:loading%Loading
c:maxload%Max. Loading
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
n:u:bus1or :bus2p.u.Voltage, Magnitude
n:upc:bus1or :bus2%Voltage, Magnitude
n:U:bus1or :bus2kVLine-Ground Voltage, Magnitude
n:phiu:bus1or :bus2degVoltage, Angle
n:phiurel:bus1or :bus2degVoltage, Relative Angle
n:Ul:bus1or :bus2kVLine-Line Voltage, Magnitude
n:u1:bus1or :bus2p.u.Voltage, Magnitude
n:Pgen:bus1or :bus2MWGeneration, Active Power
n:Pmot:bus1or :bus2MWMotor Load, Active Power
n:Pload:bus1or :bus2MWGeneral Load, Active Power
n:Pcomp:bus1or :bus2MWCompensation (Losses)
n:Pnet:bus1or :bus2MWExternal Networks, Active Power
n:Pflow:bus1or :bus2MWPower Flow, Active Power

Read after ComMod with GetAttribute. c: calculation parameter.

AttributeUnitDescription
c:inputยทControl Input
c:R_onOhmOn Resistance
c:X_onOhmOn Reactance
c:InomkARated Current
c:loading%Loading
c:t_opensOpening Time
c:i_ctrlยทInternal
c:closedยทBreaker Closed
c:lockedยทLocked
c:IdFailureยทIndication Failure
c:IndicationยทIndication
c:TCMยทTrip Coil Monitor

ElmCoup optimal power flow results

Read after ComOpf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:bus1or :bus2p.u.Voltage, Real Part, referred to network
m:uinet:bus1or :bus2p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1or :bus2p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1or :bus2p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1or :bus2p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1or :bus2kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1or :bus2kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1or :bus2degPositive-Sequence-Voltage, Angle
m:irnet:bus1or :bus2p.u.Current, Real Part, referred to network
m:iinet:bus1or :bus2p.u.Current, Imaginary Part, referred to network
m:inet:bus1or :bus2p.u.Current, Magnitude, referred to network
m:I:bus1or :bus2kACurrent, Magnitude
m:phii:bus1or :bus2degCurrent, Angle
m:i1r:bus1or :bus2p.u.Positive-Sequence Current, Real Part
m:i1i:bus1or :bus2p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1or :bus2p.u.Positive-Sequence Current, Magnitude
m:I1:bus1or :bus2kAPositive-Sequence Current, Magnitude
m:phii1:bus1or :bus2degPositive-Sequence Current, Angle
m:P:bus1or :bus2MWActive Power
m:Q:bus1or :bus2MvarReactive Power
m:S:bus1or :bus2MVAApparent Power
m:cosphi:bus1or :bus2ยทPower Factor
m:tanphi:bus1or :bus2ยทtan(phi)
m:Psum:bus1or :bus2MWTotal Active Power
m:Qsum:bus1or :bus2MvarTotal Reactive Power
m:Ssum:bus1or :bus2MVATotal Apparent Power
m:cosphisum:bus1or :bus2ยทTotal Power Factor
m:tanphisum:bus1or :bus2ยทTotal tan(phi)
m:i1P:bus1or :bus2p.u.Positive-Sequence Active Current
m:i1Q:bus1or :bus2p.u.Positive-Sequence Reactive Current
m:I1P:bus1or :bus2kAPositive-Sequence Active Current
m:I1Q:bus1or :bus2kAPositive-Sequence Reactive Current
m:ur:bus1or :bus2p.u.Voltage, Real Part
m:ui:bus1or :bus2p.u.Voltage, Imaginary Part
m:u:bus1or :bus2p.u.Voltage, Magnitude
m:ir:bus1or :bus2p.u.Current, Real Part
m:ii:bus1or :bus2p.u.Current, Imaginary Part
m:i:bus1or :bus2p.u.Current, Magnitude
m:phiui:bus1or :bus2degAngle between Voltage and Current
m:phiu1i1:bus1or :bus2degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1or :bus2sFault Clearing Time
m:Brkload:bus1or :bus2%Breaker Loading
m:Spu:bus1or :bus2MVA/p.u.Apparent Power per p.u. Voltage
c:R_onOhmOn Resistance
c:X_onOhmOn Reactance
c:on_offยทFlag Closed
c:InomkARated Current
c:loading%Loading
c:maxload%Max. Loading
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
n:ur:bus1or :bus2p.u.Voltage, Real Part
n:ui:bus1or :bus2p.u.Voltage, Imaginary Part
n:u:bus1or :bus2p.u.Voltage, Magnitude
n:upc:bus1or :bus2%Voltage, Magnitude
n:du:bus1or :bus2%Voltage Deviation
n:U:bus1or :bus2kVLine-Ground Voltage, Magnitude
n:phiu:bus1or :bus2degVoltage, Angle
n:phiurel:bus1or :bus2degVoltage, Relative Angle
n:Ul:bus1or :bus2kVLine-Line Voltage, Magnitude
n:u1:bus1or :bus2p.u.Voltage, Magnitude
n:u1pc:bus1or :bus2%Voltage, Magnitude
n:u1r:bus1or :bus2p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1or :bus2p.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bus1or :bus2MWGeneration, Active Power
n:Qgen:bus1or :bus2MvarGeneration, Reactive Power
n:Pmot:bus1or :bus2MWMotor Load, Active Power
n:Qmot:bus1or :bus2MvarMotor Load, Reactive Power
n:Pload:bus1or :bus2MWGeneral Load, Active Power
n:Qload:bus1or :bus2MvarGeneral Load, Reactive Power
n:Pcomp:bus1or :bus2MWCompensation (Losses)
n:Qcomp:bus1or :bus2MvarCompensation
n:Pnet:bus1or :bus2MWExternal Networks, Active Power
n:Qnet:bus1or :bus2MvarExternal Networks, Reactive Power
n:Pflow:bus1or :bus2MWPower Flow, Active Power
n:Qflow:bus1or :bus2MvarPower Flow, Reactive Power
n:Pout:bus1or :bus2MWOutgoing Flow, Active Power
n:Qout:bus1or :bus2MvarOutgoing Power, Reactive Power
n:Sout:bus1or :bus2MVAOutgoing Power, Apparent Power
n:cosphiout:bus1or :bus2ยทOutgoing Power, Power Factor
n:Pbalance:bus1or :bus2MWActive Power Balance (=0)
n:Qbalance:bus1or :bus2MvarReactive Power Balance (=0)
n:LossPdown:bus1or :bus2MWLosses, downstream
n:LossQdown:bus1or :bus2MvarLosses, downstream (Reactive Power)
n:LossPdownload:bus1or :bus2MWLoad losses, downstream
n:LossQdownload:bus1or :bus2MvarLoad losses, downstream
n:LossPdownnoload:bus1or :bus2MWNo load losses, downstream
n:LossQdownnoload:bus1or :bus2MvarNo load losses, downstream
n:du_feed:bus1or :bus2%Difference from voltage at start of feeder

ElmCoup basic data

b: values are worked out from the input data. Read them; they are not set.

AttributeUnitDescription
b:loc_nameยทName

Related