ElmCoup attributesPowerFactory Breaker/Switch
Every attribute of the PowerFactory Breaker/Switch (ElmCoup): 88 input parameters and 825 result variables, with units and meaning. Copy a name into GetAttribute or SetAttribute.
What ElmCoup is
A breaker or switch between two terminals inside a substation. on_off says whether it is closed (1) or open (0).
- Class
ElmCoup, element class- PowerFactory name
- Breaker/Switch
- Type
TypSwitch, throughtyp_id- Terminal suffix
:bus1terminal i,:bus2terminal j- Attributes
- 88 input parameters and 825 result variables, in 7 calculations
Most used ElmCoup attributes
| Attribute | Unit | Description | Where |
|---|---|---|---|
on_off | ยท | Closed1 closed, 0 open | input data |
aUsage | ยท | Switch Typebreaker, disconnector, load switch... | input data |
m:I:bus1 | kA | Current, Magnitude | Load flow |
m:P:bus1 | MW | Active Power | Load flow |
Read and write ElmCoup in Python
import powerfactory
app = powerfactory.GetApplication() # GetApplicationExt() from outside PowerFactory
app.GetFromStudyCase("ComLdf").Execute() # results exist after a calculation
for breaker in app.GetCalcRelevantObjects("*.ElmCoup"):
i_bus1 = breaker.GetAttribute("m:I:bus1") # Current, Magnitude, kA
p_bus1 = breaker.GetAttribute("m:P:bus1") # Active Power, MW
print(breaker.loc_name, i_bus1, p_bus1)
breaker = app.GetCalcRelevantObjects("*.ElmCoup")[0]
breaker.SetAttribute("on_off", 0) # open the breaker
- A result at a terminal of the breaker/switch needs the terminal in its name:
m:P:bus1, notm:P, which raisesAttributeError. - An input parameter is read and written with or without its
e:prefix:GetAttribute("outserv")andGetAttribute("e:outserv")give the same value. - RMS and EMT variables change over time: record them in a results object (
ElmRes) to read the whole curve.GetAttributeafter a run gives the value at the last time step.
- Input parameters88
- Load flow results182
- Short-circuit results263
- RMS simulation results167
- EMT simulation results85
- DC load flow results23
- Modal analysis results12
- Optimal power flow results93
- Basic data1
ElmCoup input parameters
The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.
| Attribute | Unit | Description |
|---|---|---|
loc_name | ยท | Name |
chr_name | ยท | Characteristic Name |
for_name | ยท | Foreign Key |
dat_src | ยท | Data source |
sernum | ยท | Serial Number |
commissionDate | ยท | Commissioning Date |
appr_modby | ยท | Modified by |
aUsage | ยท | Switch Type |
iZoneBus | ยท | Zone |
iAreaBus | ยท | Area |
on_off | ยท | Closed |
constr | ยท | Year of Construction |
appr_status | ยท | Status |
iNoOpt | ยท | Exclude from optimisation |
iSep | ยท | Switch can be opened during restoration |
iResDir | ยท | Power Restoration |
nphase | ยท | No. of Phases |
nneutral | ยท | No. of Neutrals |
iNeutInter | ยท | Switch interrupts neutral wire |
logEnvCurve | ยท | Log TRV envelope |
iNormOpenSwt | ยท | Normally open switch |
iExclRA | ยท | Excluded from Running Arrangement |
idetail | ยท | Detailed for calculation |
rel_hasProt | ยท | Consider as switch with protection device |
rel_hasRecl | ยท | Consider as switch with automatic reclosing device |
reclAttempts | ยท | Maximum number of reclosing attempts |
ctrl_type | ยท | Sectionalising |
revFlowChk | ยท | Relevant for the reversed power flow analysis |
Tb | s | Break Time |
GPSlat | deg | Latitude / Northing |
GPSlon | deg | Longitude / Easting |
t_del_a | ms | Phase a |
t_del_b | ms | Phase b |
t_del_c | ms | Phase c |
t_del_n | ms | Neutral |
Tswitch | min | Time to actuate switch |
prot_fail | % | Circuit breaker fails to open |
dep_protOver | % | Unnecessary backup protection maloperation |
spon_prot_f | 1/a | Frequency of spurious protection operation |
Tprot | s | Protection Tripping Time |
dpl1 | ยท | dpl1 |
dpl2 | ยท | dpl2 |
dpl3 | ยท | dpl3 |
dpl4 | ยท | dpl4 |
dpl5 | ยท | dpl5 |
appr_modif | ยท | Modified |
cimRdfId | ยท | RDF ID |
desc | ยท | Description |
fold_id | ยท | In Folder |
typ_id | ยท | TypeObject: TypSwitch |
bus1 | ยท | Terminal iObject: StaCubic |
bus2 | ยท | Terminal jObject: StaCubic |
doc_id | ยท | Additional Data |
pOwner | ยท | OwnerObject: ElmOwner |
pOperator | ยท | OperatorObject: ElmOperator |
pRating | ยท | Thermal RatingObject: IntThrating |
pCBrating | ยท | RatingsObject: IntCbrating |
cpHeadFold | ยท | Head Folder |
bus1_bar | ยท | Terminal i |
bus2_bar | ยท | Terminal j |
cpGrid | ยท | GridObject: ElmNet |
cpZone | ยท | ZoneObject: ElmZone |
cpArea | ยท | AreaObject: ElmArea |
cpFeed | ยท | FeederObject: ElmFeeder |
ciDist | ยท | Distance from infeed in number of buses |
ciLater | ยท | Lateral Index |
ciDistRoot | ยท | Distance from first infeed in number of buses |
ciDistAll | ยท | Distance from infeed in number of buses including switches |
ciDistAllRoot | ยท | Distance from first infeed in number of buses including switches |
cpOwner | ยท | OwnerObject: ElmOwner |
cpOperator | ยท | OperatorObject: ElmOperator |
cpBranch | ยท | BranchObject: ElmBranch |
cpSite | ยท | SiteObject: ElmSite |
cpSubstat | ยท | SubstationObject: ElmSubstat,ElmTrfstat |
cpMeteostat | ยท | Meteo StationObject: ElmMeteostat |
ciOutaged | ยท | Planned Outage |
ciEnergized | ยท | Energized |
ciEarthed | ยท | Earthed |
cDisplayName | ยท | Display Name |
cpSupplyTransformer | ยท | Supplying TransformerObject: ElmTr?,ElmTrmult |
cpSupplyTrfStation | ยท | Supplying Secondary SubstationObject: ElmTrfstat |
cpSupplySubstation | ยท | Supplying SubstationObject: ElmSubstat |
cpBay | ยท | BayObject: ElmBay |
cTswitch | min | Time to open remote controlled switch |
isclosed | ยท | Actual State |
ciScenarioType | ยท | Scenario Type |
Inom | kA | Nominal Current |
Tclear | s | Fault Clearing Time |
ElmCoup load flow results
Read after ComLdf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.
| Attribute | Unit | Description |
|---|---|---|
m:urnet:bus1or :bus2 | p.u. | Voltage, Real Part, referred to network |
m:uinet:bus1or :bus2 | p.u. | Voltage, Imaginary Part, referred to network |
m:u1r:bus1or :bus2 | p.u. | Positive-Sequence-Voltage, Real Part |
m:u1i:bus1or :bus2 | p.u. | Positive-Sequence-Voltage, Imaginary Part |
m:u1:bus1or :bus2 | p.u. | Positive-Sequence-Voltage, Magnitude |
m:U1:bus1or :bus2 | kV | Line-Ground Positive-Sequence-Voltage, Magnitude |
m:U1l:bus1or :bus2 | kV | Line-Line Positive-Sequence-Voltage, Magnitude |
m:phiu1:bus1or :bus2 | deg | Positive-Sequence-Voltage, Angle |
m:irnet:bus1or :bus2 | p.u. | Current, Real Part, referred to network |
m:iinet:bus1or :bus2 | p.u. | Current, Imaginary Part, referred to network |
m:inet:bus1or :bus2 | p.u. | Current, Magnitude, referred to network |
m:I:bus1or :bus2 | kA | Current, Magnitude |
m:phii:bus1or :bus2 | deg | Current, Angle |
m:i1r:bus1or :bus2 | p.u. | Positive-Sequence Current, Real Part |
m:i1i:bus1or :bus2 | p.u. | Positive-Sequence Current, Imaginary Part |
m:i1:bus1or :bus2 | p.u. | Positive-Sequence Current, Magnitude |
m:I1:bus1or :bus2 | kA | Positive-Sequence Current, Magnitude |
m:phii1:bus1or :bus2 | deg | Positive-Sequence Current, Angle |
m:P:bus1or :bus2 | MW | Active Power |
m:Q:bus1or :bus2 | Mvar | Reactive Power |
m:S:bus1or :bus2 | MVA | Apparent Power |
m:cosphi:bus1or :bus2 | ยท | Power Factor |
m:tanphi:bus1or :bus2 | ยท | tan(phi) |
m:Psum:bus1or :bus2 | MW | Total Active Power |
m:Qsum:bus1or :bus2 | Mvar | Total Reactive Power |
m:Ssum:bus1or :bus2 | MVA | Total Apparent Power |
m:cosphisum:bus1or :bus2 | ยท | Total Power Factor |
m:tanphisum:bus1or :bus2 | ยท | Total tan(phi) |
m:i1P:bus1or :bus2 | p.u. | Positive-Sequence Active Current |
m:i1Q:bus1or :bus2 | p.u. | Positive-Sequence Reactive Current |
m:I1P:bus1or :bus2 | kA | Positive-Sequence Active Current |
m:I1Q:bus1or :bus2 | kA | Positive-Sequence Reactive Current |
m:ur:bus1or :bus2 | p.u. | Voltage, Real Part |
m:ui:bus1or :bus2 | p.u. | Voltage, Imaginary Part |
m:u:bus1or :bus2 | p.u. | Voltage, Magnitude |
m:ir:bus1or :bus2 | p.u. | Current, Real Part |
m:ii:bus1or :bus2 | p.u. | Current, Imaginary Part |
m:i:bus1or :bus2 | p.u. | Current, Magnitude |
m:phiui:bus1or :bus2 | deg | Angle between Voltage and Current |
m:phiu1i1:bus1or :bus2 | deg | Angle between Voltage and Current in positive sequence system |
m:Tfct:bus1or :bus2 | s | Fault Clearing Time |
m:Brkload:bus1or :bus2 | % | Breaker Loading |
m:Spu:bus1or :bus2 | MVA/p.u. | Apparent Power per p.u. Voltage |
m:urnet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Real Part, referred to network |
m:uinet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Imaginary Part, referred to network |
m:u0:bus1or :bus2 | p.u. | Zero-Sequence-Voltage, Magnitude |
m:phiu0:bus1or :bus2 | deg | Zero-Sequence-Voltage, Angle |
m:u2:bus1or :bus2 | p.u. | Negative-Sequence-Voltage, Magnitude |
m:phiu2:bus1or :bus2 | deg | Negative-Sequence-Voltage, Angle |
m:irnet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Real Part, referred to network |
m:iinet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Imaginary Part, referred to network |
m:inet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Magnitude, referred to network |
m:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kA | Phase Current, Magnitude |
m:phii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Phase Current, Angle |
m:i0r:bus1or :bus2 | p.u. | Zero-Sequence Current, Real Part |
m:i0i:bus1or :bus2 | p.u. | Zero-Sequence Current, Imaginary Part |
m:i0:bus1or :bus2 | p.u. | Zero-Sequence Current, Magnitude |
m:I0:bus1or :bus2 | kA | Zero-Sequence Current, Magnitude |
m:I0x3:bus1or :bus2 | kA | 3*I0 |
m:phii0:bus1or :bus2 | deg | Zero-Sequence Current, Angle |
m:i2r:bus1or :bus2 | p.u. | Negative-Sequence Current, Real Part |
m:i2i:bus1or :bus2 | p.u. | Negative-Sequence Current, Imaginary Part |
m:i2:bus1or :bus2 | p.u. | Negative-Sequence Current, Magnitude |
m:I2:bus1or :bus2 | kA | Negative-Sequence Current, Magnitude |
m:phii2:bus1or :bus2 | deg | Negative-Sequence Current, Angle |
m:ubfacI:bus1or :bus2 | % | Current Unbalance Factor |
m:ubfacS:bus1or :bus2 | % | Power Unbalance Factor |
m:P:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | MW | Active Power |
m:Q:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | Mvar | Reactive Power |
m:S:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | MVA | Apparent Power |
m:cosphi:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | ยท | Power Factor |
m:tanphi:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | ยท | tan(phi) |
m:Pln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | MW | Active Power (Line-Neutral) |
m:Qln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | Mvar | Reactive Power (Line-Neutral) |
m:P1:bus1or :bus2 | MW | Positive Sequence Active Power |
m:Q1:bus1or :bus2 | Mvar | Positive Sequence Reactive Power |
m:P2:bus1or :bus2 | MW | Negative Sequence Active Power |
m:Q2:bus1or :bus2 | Mvar | Negative Sequence Reactive Power |
m:P0:bus1or :bus2 | MW | Zero Sequence Active Power |
m:Q0:bus1or :bus2 | Mvar | Zero Sequence Reactive Power |
m:i2P:bus1or :bus2 | p.u. | Negative-Sequence Active Current |
m:i2Q:bus1or :bus2 | p.u. | Negative-Sequence Reactive Current |
m:I2P:bus1or :bus2 | kA | Negative-Sequence Active Current |
m:I2Q:bus1or :bus2 | kA | Negative-Sequence Reactive Current |
m:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Real Part |
m:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Imaginary Part |
m:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Magnitude |
m:ir:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Real Part |
m:ii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Imaginary Part |
m:i:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Magnitude |
m:phiui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Angle between Voltage and Current |
m:phiu0i0:bus1or :bus2 | deg | Angle between Voltage and Current in zero-sequence system |
m:phiu2i2:bus1or :bus2 | deg | Angle between Voltage and Current in negative sequence system |
m:TfctPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | s | Fault Clearing Time |
m:BrkloadPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | % | Breaker Loading |
c:R_on | Ohm | On Resistance |
c:X_on | Ohm | On Reactance |
c:on_off | ยท | Flag Closed |
c:Inom | kA | Rated Current |
c:loading | % | Loading |
c:maxload | % | Max. Loading |
c:Ploss | MW | Losses (total) |
c:Qloss | Mvar | Reactive-Losses (total) |
c:Plossld | MW | Losses (load) |
c:Qlossld | Mvar | Reactive-Losses (load) |
c:Plossnld | MW | Losses (no load) |
c:Qlossnld | Mvar | Reactive-Losses (no load) |
c:loadingPh:Aper phase :A, :B, :C, unbalanced only | % | Loading |
c:loading_st | % | Short Term Loading |
n:ur:bus1or :bus2 | p.u. | Voltage, Real Part |
n:ui:bus1or :bus2 | p.u. | Voltage, Imaginary Part |
n:u:bus1or :bus2 | p.u. | Voltage, Magnitude |
n:upc:bus1or :bus2 | % | Voltage, Magnitude |
n:du:bus1or :bus2 | % | Voltage Deviation |
n:U:bus1or :bus2 | kV | Line-Ground Voltage, Magnitude |
n:phiu:bus1or :bus2 | deg | Voltage, Angle |
n:phiurel:bus1or :bus2 | deg | Voltage, Relative Angle |
n:Ul:bus1or :bus2 | kV | Line-Line Voltage, Magnitude |
n:u1:bus1or :bus2 | p.u. | Voltage, Magnitude |
n:u1pc:bus1or :bus2 | % | Voltage, Magnitude |
n:u1r:bus1or :bus2 | p.u. | Positive-Sequence Voltage, Real Part |
n:u1i:bus1or :bus2 | p.u. | Positive-Sequence Voltage, Imaginary Part |
n:Pgen:bus1or :bus2 | MW | Generation, Active Power |
n:Qgen:bus1or :bus2 | Mvar | Generation, Reactive Power |
n:Pmot:bus1or :bus2 | MW | Motor Load, Active Power |
n:Qmot:bus1or :bus2 | Mvar | Motor Load, Reactive Power |
n:Pload:bus1or :bus2 | MW | General Load, Active Power |
n:Qload:bus1or :bus2 | Mvar | General Load, Reactive Power |
n:Pcomp:bus1or :bus2 | MW | Compensation (Losses) |
n:Qcomp:bus1or :bus2 | Mvar | Compensation |
n:Pnet:bus1or :bus2 | MW | External Networks, Active Power |
n:Qnet:bus1or :bus2 | Mvar | External Networks, Reactive Power |
n:Pflow:bus1or :bus2 | MW | Power Flow, Active Power |
n:Qflow:bus1or :bus2 | Mvar | Power Flow, Reactive Power |
n:Pout:bus1or :bus2 | MW | Outgoing Flow, Active Power |
n:Qout:bus1or :bus2 | Mvar | Outgoing Power, Reactive Power |
n:Sout:bus1or :bus2 | MVA | Outgoing Power, Apparent Power |
n:cosphiout:bus1or :bus2 | ยท | Outgoing Power, Power Factor |
n:Pbalance:bus1or :bus2 | MW | Active Power Balance (=0) |
n:Qbalance:bus1or :bus2 | Mvar | Reactive Power Balance (=0) |
n:LossPdown:bus1or :bus2 | MW | Losses, downstream |
n:LossQdown:bus1or :bus2 | Mvar | Losses, downstream (Reactive Power) |
n:LossPdownload:bus1or :bus2 | MW | Load losses, downstream |
n:LossQdownload:bus1or :bus2 | Mvar | Load losses, downstream |
n:LossPdownnoload:bus1or :bus2 | MW | No load losses, downstream |
n:LossQdownnoload:bus1or :bus2 | Mvar | No load losses, downstream |
n:du_feed:bus1or :bus2 | % | Difference from voltage at start of feeder |
n:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Real Part |
n:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Imaginary Part |
n:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Magnitude |
n:upc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | % | Line-Ground Voltage, Magnitude |
n:du:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | % | Voltage Deviation |
n:U:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Line-Ground Voltage, Magnitude |
n:phiu:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Line-Ground Voltage, Angle |
n:ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Line Voltage, Magnitude |
n:ulpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | % | Line-Line Voltage, Magnitude |
n:Ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Line-Line Voltage, Magnitude |
n:phiul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Line-Line Voltage, Angle |
n:u0:bus1or :bus2 | p.u. | Zero-Sequence Voltage, Magnitude |
n:U0:bus1or :bus2 | kV | Zero-Sequence Voltage, Magnitude |
n:U0x3:bus1or :bus2 | kV | 3*U0 |
n:phiu0:bus1or :bus2 | deg | Zero-Sequence Voltage, Angle |
n:U1:bus1or :bus2 | kV | Line-Ground Positive-Sequence Voltage, Magnitude |
n:phiu1:bus1or :bus2 | deg | Positive-Sequence Voltage, Angle |
n:u2:bus1or :bus2 | p.u. | Negative-Sequence Voltage, Magnitude |
n:U2:bus1or :bus2 | kV | Line-Ground Negative-Sequence Voltage, Magnitude |
n:phiu2:bus1or :bus2 | deg | Negative-Sequence Voltage, Angle |
n:U1l:bus1or :bus2 | kV | Line-Line Positive-Sequence Voltage, Magnitude |
n:U2l:bus1or :bus2 | kV | Line-Line Negative-Sequence Voltage, Magnitude |
n:uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Neutral Voltage, Magnitude |
n:Uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Line-Neutral Voltage, Magnitude |
n:phiuln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Line-Neutral Voltage, Angle |
n:un:bus1or :bus2 | p.u. | Neutral-Ground Voltage, Magnitude |
n:Un:bus1or :bus2 | kV | Neutral-Ground Voltage, Magnitude |
n:phiun:bus1or :bus2 | deg | Neutral-Ground Voltage, Angle |
n:upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Technology dependent Voltage, Magnitude |
n:Upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Phase Technology dependent Voltage, Magnitude |
n:um:bus1or :bus2 | p.u. | Average-Voltage, Magnitude |
n:Um:bus1or :bus2 | kV | Average-Voltage, Magnitude |
n:uphtmin:bus1or :bus2 | p.u. | Minimum of Phase Technology dependent Voltage, Magnitude |
n:uphtmax:bus1or :bus2 | p.u. | Maximum of Phase Technology dependent Voltage, Magnitude |
n:ubfac:bus1or :bus2 | % | Unbalance Factor |
ElmCoup short-circuit results
Read after ComShc with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.
| Attribute | Unit | Description |
|---|---|---|
m:I:bus1or :bus2 | kA | Short-Circuit Current, Magnitude |
m:phii:bus1or :bus2 | deg | Phase Current, Angle |
m:i1:bus1or :bus2 | p.u. | Positive-Sequence Current, Magnitude |
m:I1:bus1or :bus2 | kA | Positive-Sequence Current, Magnitude |
m:phii1:bus1or :bus2 | deg | Positive-Sequence Current, Angle |
m:P:bus1or :bus2 | MW | Active Power |
m:Q:bus1or :bus2 | Mvar | Reactive Power |
m:i1P:bus1or :bus2 | p.u. | Positive-Sequence Active Current |
m:i1Q:bus1or :bus2 | p.u. | Positive-Sequence Reactive Current |
m:I1P:bus1or :bus2 | kA | Positive-Sequence Active Current |
m:I1Q:bus1or :bus2 | kA | Positive-Sequence Reactive Current |
m:phiui:bus1or :bus2 | deg | Angle between Voltage and Current |
m:phiu1i1:bus1or :bus2 | deg | Angle between Voltage and Current in Positive-Sequence System |
m:Tfct:bus1or :bus2 | s | Fault Clearing Time |
m:Ikss:bus1or :bus2 | kA | Initial Short-Circuit Current |
m:ikss:bus1or :bus2 | p.u. | Initial Short-Circuit Current, Magnitude |
m:Skss:bus1or :bus2 | MVA | Initial Short-Circuit Power |
m:ip:bus1or :bus2 | kA | Peak Short-Circuit Current |
m:maxIkss:bus1or :bus2 | kA | Max. Initial Short-Circuit Current |
m:maxip:bus1or :bus2 | kA | Max. Peak Short-Circuit Current |
m:maxIth:bus1or :bus2 | kA | Max. Thermal equivalent Short-Circuit Current |
m:maxIb:bus1or :bus2 | kA | Max. Breaking Current |
m:R:bus1or :bus2 | Ohm | Fault Impedance, Real Part |
m:X:bus1or :bus2 | Ohm | Fault Impedance, Imaginary Part |
m:Z:bus1or :bus2 | Ohm | Fault Impedance, Magnitude |
m:phiz:bus1or :bus2 | deg | Fault Impedance, Angle |
m:Rs:bus1or :bus2 | Ohm | Source Impedance, Real Part |
m:Xs:bus1or :bus2 | Ohm | Source Impedance, Imaginary Part |
m:Zs:bus1or :bus2 | Ohm | Source Impedance, Magnitude |
m:phizs:bus1or :bus2 | deg | Source Impedance, Angle |
m:BrkIpload:bus1or :bus2 | % | Breaker Loading (peak) |
m:Ib:bus1or :bus2 | kA | Short-Circuit Breaking Current |
m:Sb:bus1or :bus2 | MVA | Short-Circuit Breaking Power |
m:Ith:bus1or :bus2 | kA | Thermal equivalent Short-Circuit Current |
m:zSbase:bus1or :bus2 | p.u. | Fault Impedance, Magnitude |
m:XtoR:bus1or :bus2 | ยท | X/R ratio |
m:cosphiui:bus1or :bus2 | ยท | cosphi |
m:BrkIbload:bus1or :bus2 | % | Breaker Loading (breaking) |
m:BrkmaxIb:bus1or :bus2 | kA | Max. Breaking Current (breaker time) |
m:Ik:bus1or :bus2 | kA | Steady-State Short-Circuit Current |
m:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kA | Short-Circuit Current, Magnitude |
m:phii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Phase Current, Angle |
m:I0:bus1or :bus2 | kA | Zero-Sequence Current, Magnitude |
m:I0x3:bus1or :bus2 | kA | 3*I0 |
m:phii0:bus1or :bus2 | deg | Zero-Sequence Current, Angle |
m:I2:bus1or :bus2 | kA | Negative-Sequence Current, Magnitude |
m:phii2:bus1or :bus2 | deg | Negative-Sequence Current, Angle |
m:P:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | MW | Active Power |
m:Q:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | Mvar | Reactive Power |
m:Psum:bus1or :bus2 | MW | Total Active Power |
m:Qsum:bus1or :bus2 | Mvar | Total Reactive Power |
m:cosphisum:bus1or :bus2 | ยท | Total Power Factor |
m:P2:bus1or :bus2 | MW | P2 |
m:Q2:bus1or :bus2 | Mvar | Q2 |
m:P0:bus1or :bus2 | MW | P0 |
m:phiui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Angle between Voltage and Current |
m:phiu0i0:bus1or :bus2 | deg | Angle between Voltage and Current in Zero-Sequence System |
m:phiu2i2:bus1or :bus2 | deg | Angle between Voltage and Current in Negative-Sequence System |
m:TfctPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | s | Fault Clearing Time |
m:Ikss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kA | Initial Short-Circuit Current |
m:ikss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Initial Short-Circuit Current, Magnitude |
m:Skss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | MVA | Initial Short-Circuit Power |
m:Skssx3:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | MVA | 3*Initial Short-Circuit Power |
m:ip:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kA | Peak Short-Circuit Current |
m:Z:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | Ohm | Fault Impedance, Magnitude |
m:phiz:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Fault Impedance, Angle |
m:Zl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | Ohm | Line-Line Fault Impedance, Magnitude |
m:phizl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Line-Line Fault Impedance, Angle |
m:Z0:bus1or :bus2 | Ohm | Zero-Sequence Fault Impedance, Magnitude |
m:phiz0:bus1or :bus2 | deg | Zero-Sequence Fault Impedance, Angle |
m:z0Sbase:bus1or :bus2 | p.u. | Zero-Sequence Fault Impedance, Magnitude |
m:cosphiu1i1:bus1or :bus2 | ยท | Positive-Sequence cosphi |
m:I0x3watt:bus1or :bus2 | kA | Earth-Fault Residual Current |
m:I0x3var:bus1or :bus2 | kA | Capacitive Earth-Fault Current |
m:Q0cap:bus1or :bus2 | Mvar | Q0 capacitive |
m:Rfrel:bus1or :bus2 | Ohm | Relay Impedance, Real Part |
m:Xfrel:bus1or :bus2 | Ohm | Relay Impedance, Imaginary Part |
m:Zfrel:bus1or :bus2 | Ohm | Relay Impedance, Magnitude |
m:phizfrel:bus1or :bus2 | deg | Relay Impedance, Angle |
m:Zf:bus1or :bus2 | Ohm | Meas. Fault Impedance, Magnitude |
m:phizf:bus1or :bus2 | deg | Meas. Fault Impedance, Angle |
c:R_on | Ohm | On Resistance |
c:X_on | Ohm | On Reactance |
c:on_off | ยท | Flag Closed |
c:Inom | kA | Rated Current |
c:loading | % | Max. Loading |
c:t_open | s | Opening Time |
c:Ibload | % | Loading, Interrupting |
c:Ipload | % | Loading, Peak Short-Circuit Current |
c:Tb | s | Break Time |
c:XtoR | ยท | X/R ratio (dc) |
c:XtoR_p | ยท | X/R ratio (peak) |
c:Ibmax | kA | Breaking Current |
c:ibmax | kA | Peak Breaking Current |
c:Ibasymmax | kA | Asymmetrical Breaking Current |
c:idcmax | kA | Decaying Component |
c:Ikssmax | kA | Initial Short-Circuit Current |
c:ipmax | kA | Peak Short-Circuit Current |
c:fctof | ยท | Equivalent Frequency fc/f (dc) |
n:ur:bus1or :bus2 | p.u. | Voltage, Real Part |
n:ui:bus1or :bus2 | p.u. | Voltage, Imaginary Part |
n:u:bus1or :bus2 | p.u. | Voltage, Magnitude |
n:upc:bus1or :bus2 | % | Voltage, Magnitude |
n:du:bus1or :bus2 | % | Voltage Deviation |
n:U:bus1or :bus2 | kV | Line-Ground Voltage, Magnitude |
n:phiu:bus1or :bus2 | deg | Voltage, Angle |
n:Ul:bus1or :bus2 | kV | Line-Line Voltage, Magnitude |
n:u1:bus1or :bus2 | p.u. | Voltage, Magnitude |
n:u1pc:bus1or :bus2 | % | Voltage, Magnitude |
n:u1r:bus1or :bus2 | p.u. | Positive-Sequence Voltage, Real Part |
n:u1i:bus1or :bus2 | p.u. | Positive-Sequence Voltage, Imaginary Part |
n:Ikss:bus1or :bus2 | kA | Initial Short-Circuit Current |
n:I:bus1or :bus2 | kA | Short-Circuit Current |
n:phii:bus1or :bus2 | deg | Phase Current, Angle |
n:Skss:bus1or :bus2 | MVA | Initial Short-Circuit Power |
n:ip:bus1or :bus2 | kA | Peak Short-Circuit Current |
n:Ib:bus1or :bus2 | kA | Short-Circuit Breaking Current |
n:Sb:bus1or :bus2 | MVA | Short-Circuit Breaking Power |
n:idc:bus1or :bus2 | kA | Decaying Component |
n:Ith:bus1or :bus2 | kA | Thermal equivalent Short-Circuit Current |
n:R1toX1:bus1or :bus2 | ยท | R1/X1 ratio (Zk") |
n:X1toR1:bus1or :bus2 | ยท | X1/R1 ratio (Zk") |
n:R:bus1or :bus2 | Ohm | Short-Circuit Impedance, Real Part |
n:X:bus1or :bus2 | Ohm | Short-Circuit Impedance, Imaginary Part |
n:Z:bus1or :bus2 | Ohm | Short-Circuit Impedance, Magnitude |
n:phiz:bus1or :bus2 | deg | Short-Circuit Impedance, Angle |
n:urpref:bus1or :bus2 | p.u. | Pre-fault Voltage, Real Part |
n:uipref:bus1or :bus2 | p.u. | Pre-fault Voltage, Imaginary Part |
n:upref:bus1or :bus2 | p.u. | Pre-fault Voltage, Magnitude |
n:uprefpc:bus1or :bus2 | % | Pre-fault Voltage, Magnitude |
n:Upref:bus1or :bus2 | kV | Line-Ground Pre-fault Voltage, Magnitude |
n:Ulpref:bus1or :bus2 | kV | Line-Line Pre-fault Voltage, Magnitude |
n:phiupref:bus1or :bus2 | deg | Pre-fault Voltage, Angle |
n:phiui:bus1or :bus2 | deg | Angle between Voltage and Current |
n:Ithload:bus1or :bus2 | % | Loading, Thermal equivalent Current |
n:Ipload:bus1or :bus2 | % | Loading, Peak Short-Circuit Current |
n:Ithrtk:bus1or :bus2 | kA | Rated Short-Time Current (Tk) |
n:XtoR:bus1or :bus2 | ยท | X/R ratio (peak) |
n:RtoX:bus1or :bus2 | ยท | R/X ratio (peak) |
n:XtoR_b:bus1or :bus2 | ยท | X/R ratio (dc) |
n:RtoX_b:bus1or :bus2 | ยท | R/X ratio (dc) |
n:fctof_b:bus1or :bus2 | ยท | Equivalent Frequency fc/f (dc) |
n:rSbase:bus1or :bus2 | p.u. | Short-Circuit Impedance, Real Part |
n:xSbase:bus1or :bus2 | p.u. | Short-Circuit Impedance, Imaginary Part |
n:zSbase:bus1or :bus2 | p.u. | Short-Circuit Impedance, Magnitude |
n:Tn:bus1or :bus2 | ms | Grid Time Constant |
n:Ik:bus1or :bus2 | kA | Steady-State Short-Circuit Current |
n:cfac:bus1or :bus2 | ยท | Voltage Factor |
n:Iasy:bus1or :bus2 | kA | Asymmetrical Breaking Current |
n:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Real Part |
n:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Imaginary Part |
n:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Magnitude |
n:upc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | % | Line-Ground Voltage, Magnitude |
n:du:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | % | Voltage Deviation |
n:U:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Line-Ground Voltage, Magnitude |
n:phiu:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Line-Ground Voltage, Angle |
n:ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Line Voltage, Magnitude |
n:ulpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | % | Line-Line Voltage, Magnitude |
n:Ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Line-Line Voltage, Magnitude |
n:phiul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Line-Line Voltage, Angle |
n:u0:bus1or :bus2 | p.u. | Zero-Sequence Voltage, Magnitude |
n:U0:bus1or :bus2 | kV | Zero-Sequence Voltage, Magnitude |
n:U0x3:bus1or :bus2 | kV | 3*U0 |
n:phiu0:bus1or :bus2 | deg | Zero-Sequence Voltage, Angle |
n:U1:bus1or :bus2 | kV | Line-Ground Positive-Sequence Voltage, Magnitude |
n:phiu1:bus1or :bus2 | deg | Positive-Sequence Voltage, Angle |
n:u2:bus1or :bus2 | p.u. | Negative-Sequence Voltage, Magnitude |
n:U2:bus1or :bus2 | kV | Line-Ground Negative-Sequence Voltage, Magnitude |
n:phiu2:bus1or :bus2 | deg | Negative-Sequence Voltage, Angle |
n:U1l:bus1or :bus2 | kV | Line-Line Positive-Sequence Voltage, Magnitude |
n:U2l:bus1or :bus2 | kV | Line-Line Negative-Sequence Voltage, Magnitude |
n:uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Neutral Voltage, Magnitude |
n:Uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Line-Neutral Voltage, Magnitude |
n:phiuln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Line-Neutral Voltage, Angle |
n:un:bus1or :bus2 | p.u. | Neutral-Ground Voltage, Magnitude |
n:Un:bus1or :bus2 | kV | Neutral-Ground Voltage, Magnitude |
n:phiun:bus1or :bus2 | deg | Neutral-Ground Voltage, Angle |
n:upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Technology dependent Voltage, Magnitude |
n:Upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Phase Technology dependent Voltage, Magnitude |
n:Ikss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kA | Initial Short-Circuit Current |
n:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kA | Short-Circuit Current |
n:phii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Phase Current, Angle |
n:Skss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | MVA | Initial Short-Circuit Power |
n:Skssx3:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | MVA | 3*Initial Short-Circuit Power |
n:ip:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kA | Peak Short-Circuit Current |
n:Ib:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kA | Short-Circuit Breaking Current |
n:Sb:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | MVA | Short-Circuit Breaking Power |
n:Ith:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kA | Thermal equivalent Short-Circuit Current |
n:Ithmax:bus1or :bus2 | kA | Max. Thermal equivalent Short-Circuit Current |
n:R0:bus1or :bus2 | Ohm | Zero-Sequence Impedance, Real Part |
n:X0:bus1or :bus2 | Ohm | Zero-Sequence Impedance, Imaginary Part |
n:Z0:bus1or :bus2 | Ohm | Zero-Sequence Impedance, Magnitude |
n:phiz0:bus1or :bus2 | deg | Zero-Sequence Impedance, Angle |
n:r0Sbase:bus1or :bus2 | p.u. | Zero-Sequence Impedance, Real Part |
n:x0Sbase:bus1or :bus2 | p.u. | Zero-Sequence Impedance, Imaginary Part |
n:z0Sbase:bus1or :bus2 | p.u. | Zero-Sequence Impedance, Magnitude |
n:R1:bus1or :bus2 | Ohm | Positive-Sequence Impedance, Real Part |
n:X1:bus1or :bus2 | Ohm | Positive-Sequence Impedance, Imaginary Part |
n:Z1:bus1or :bus2 | Ohm | Positive-Sequence Impedance, Magnitude |
n:phiz1:bus1or :bus2 | deg | Positive-Sequence Impedance, Angle |
n:r1Sbase:bus1or :bus2 | p.u. | Positive-Sequence Impedance, Real Part |
n:x1Sbase:bus1or :bus2 | p.u. | Positive-Sequence Impedance, Imaginary Part |
n:z1Sbase:bus1or :bus2 | p.u. | Positive-Sequence Impedance, Magnitude |
n:R2:bus1or :bus2 | Ohm | Negative-Sequence Impedance, Real Part |
n:X2:bus1or :bus2 | Ohm | Negative-Sequence Impedance, Imaginary Part |
n:Z2:bus1or :bus2 | Ohm | Negative-Sequence Impedance, Magnitude |
n:phiz2:bus1or :bus2 | deg | Negative-Sequence Impedance, Angle |
n:r2Sbase:bus1or :bus2 | p.u. | Negative-Sequence Impedance, Real Part |
n:x2Sbase:bus1or :bus2 | p.u. | Negative-Sequence Impedance, Imaginary Part |
n:z2Sbase:bus1or :bus2 | p.u. | Negative-Sequence Impedance, Magnitude |
n:R0toX0:bus1or :bus2 | ยท | R0/X0 ratio (Zk") |
n:X0toR0:bus1or :bus2 | ยท | X0/R0 ratio (Zk") |
n:R2toX2:bus1or :bus2 | ยท | R2/X2 ratio (Zk") |
n:X2toR2:bus1or :bus2 | ยท | X2/R2 ratio (Zk") |
n:R:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | Ohm | Network Resistance, Line-Ground |
n:X:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | Ohm | Network Reactance, Line-Ground |
n:Z:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | Ohm | Network Impedance, Line-Ground |
n:phiz:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Angle of Network Impedance, Line-Ground |
n:Rl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | Ohm | Network Resistance, Line-Line |
n:Xl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | Ohm | Network Reactance, Line-Line |
n:Zl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | Ohm | Network Impedance, Line-Line |
n:phizl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Angle of Network Impedance, Line-Line |
n:Rln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | Ohm | Network Resistance, Line-Neutral |
n:Xln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | Ohm | Network Reactance, Line-Neutral |
n:Zln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | Ohm | Network Impedance, Line-Neutral |
n:phizln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Angle of Network Impedance, Line-Neutral |
n:Rn:bus1or :bus2 | Ohm | Network Resistance, Neutral |
n:Xn:bus1or :bus2 | Ohm | Network Reactance, Neutral |
n:Zn:bus1or :bus2 | Ohm | Network Impedance, Neutral |
n:phizn:bus1or :bus2 | deg | Angle of Network Impedance, Neutral |
n:eff:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | ยท | Earth Fault Factor |
n:X0toX1:bus1or :bus2 | ยท | X0/X1 |
n:In:bus1or :bus2 | kA | Neutral Current, Magnitude |
n:phiin:bus1or :bus2 | deg | Neutral Current, Angle |
n:I0:bus1or :bus2 | kA | Zero-Sequence Current, Magnitude |
n:I0x3:bus1or :bus2 | kA | 3*I0 |
n:phii0:bus1or :bus2 | deg | Zero-Sequence Current, Angle |
n:I1:bus1or :bus2 | kA | Positive-Sequence Current, Magnitude |
n:phii1:bus1or :bus2 | deg | Positive-Sequence Current, Angle |
n:I2:bus1or :bus2 | kA | Negative-Sequence Current, Magnitude |
n:phii2:bus1or :bus2 | deg | Negative-Sequence Current, Angle |
n:urpref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Pre-fault Voltage, Real Part |
n:uipref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Pre-fault Voltage, Imaginary Part |
n:upref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Pre-fault Voltage, Magnitude |
n:uprefpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | % | Pre-fault Voltage, Magnitude |
n:Upref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Line-Ground Pre-fault Voltage, Magnitude |
n:Ulpref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Line-Line Pre-fault Voltage, Magnitude |
n:phiupref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Pre-fault Voltage, Angle |
n:phiui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Angle between Voltage and Current |
n:phiu1i1:bus1or :bus2 | deg | Angle between Voltage and Current in positive sequence system |
n:phiu2i2:bus1or :bus2 | deg | Angle between Voltage and Current in negative sequence system |
n:phiu0i0:bus1or :bus2 | deg | Angle between Voltage and Current in zero-sequence system |
n:Ik:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kA | Steady-State Short-Circuit Current |
n:in:bus1or :bus2 | p.u. | Neutral Current, Magnitude |
n:i0r:bus1or :bus2 | p.u. | Zero-Sequence Current, Real Part |
n:i0i:bus1or :bus2 | p.u. | Zero-Sequence Current, Imaginary Part |
n:i0:bus1or :bus2 | p.u. | Zero-Sequence Current, Magnitude |
n:i1r:bus1or :bus2 | p.u. | Positive-Sequence Current, Real Part |
n:i1i:bus1or :bus2 | p.u. | Positive-Sequence Current, Imaginary Part |
n:i1:bus1or :bus2 | p.u. | Positive-Sequence Current, Magnitude |
n:i2r:bus1or :bus2 | p.u. | Negative-Sequence Current, Real Part |
n:i2i:bus1or :bus2 | p.u. | Negative-Sequence Current, Imaginary Part |
n:i2:bus1or :bus2 | p.u. | Negative-Sequence Current, Magnitude |
ElmCoup rms simulation results
Read after ComInc (RMS) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.
| Attribute | Unit | Description |
|---|---|---|
m:urnet:bus1or :bus2 | p.u. | Voltage, Real Part, referred to network |
m:uinet:bus1or :bus2 | p.u. | Voltage, Imaginary Part, referred to network |
m:u1r:bus1or :bus2 | p.u. | Positive-Sequence-Voltage, Real Part |
m:u1i:bus1or :bus2 | p.u. | Positive-Sequence-Voltage, Imaginary Part |
m:u1:bus1or :bus2 | p.u. | Positive-Sequence-Voltage, Magnitude |
m:U1:bus1or :bus2 | kV | Line-Ground Positive-Sequence-Voltage, Magnitude |
m:U1l:bus1or :bus2 | kV | Line-Line Positive-Sequence-Voltage, Magnitude |
m:phiu1:bus1or :bus2 | deg | Positive-Sequence-Voltage, Angle |
m:irnet:bus1or :bus2 | p.u. | Current, Real Part, referred to network |
m:iinet:bus1or :bus2 | p.u. | Current, Imaginary Part, referred to network |
m:inet:bus1or :bus2 | p.u. | Current, Magnitude, referred to network |
m:I:bus1or :bus2 | kA | Current, Magnitude |
m:phii:bus1or :bus2 | deg | Current, Angle |
m:i1r:bus1or :bus2 | p.u. | Positive-Sequence Current, Real Part |
m:i1i:bus1or :bus2 | p.u. | Positive-Sequence Current, Imaginary Part |
m:i1:bus1or :bus2 | p.u. | Positive-Sequence Current, Magnitude |
m:I1:bus1or :bus2 | kA | Positive-Sequence Current, Magnitude |
m:phii1:bus1or :bus2 | deg | Positive-Sequence Current, Angle |
m:P:bus1or :bus2 | MW | Active Power |
m:Q:bus1or :bus2 | Mvar | Reactive Power |
m:S:bus1or :bus2 | MVA | Apparent Power |
m:cosphi:bus1or :bus2 | ยท | Power Factor |
m:tanphi:bus1or :bus2 | ยท | tan(phi) |
m:Psum:bus1or :bus2 | MW | Total Active Power |
m:Qsum:bus1or :bus2 | Mvar | Total Reactive Power |
m:Ssum:bus1or :bus2 | MVA | Total Apparent Power |
m:cosphisum:bus1or :bus2 | ยท | Total Power Factor |
m:tanphisum:bus1or :bus2 | ยท | Total tan(phi) |
m:i1P:bus1or :bus2 | p.u. | Positive-Sequence Active Current |
m:i1Q:bus1or :bus2 | p.u. | Positive-Sequence Reactive Current |
m:I1P:bus1or :bus2 | kA | Positive-Sequence Active Current |
m:I1Q:bus1or :bus2 | kA | Positive-Sequence Reactive Current |
m:ur:bus1or :bus2 | p.u. | Voltage, Real Part |
m:ui:bus1or :bus2 | p.u. | Voltage, Imaginary Part |
m:u:bus1or :bus2 | p.u. | Voltage, Magnitude |
m:ir:bus1or :bus2 | p.u. | Current, Real Part |
m:ii:bus1or :bus2 | p.u. | Current, Imaginary Part |
m:i:bus1or :bus2 | p.u. | Current, Magnitude |
m:phiui:bus1or :bus2 | deg | Angle between Voltage and Current |
m:phiu1i1:bus1or :bus2 | deg | Angle between Voltage and Current in positive sequence system |
m:Tfct:bus1or :bus2 | s | Fault Clearing Time |
m:Brkload:bus1or :bus2 | % | Breaker Loading |
m:Spu:bus1or :bus2 | MVA/p.u. | Apparent Power per p.u. Voltage |
m:urnet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Real Part, referred to network |
m:uinet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Imaginary Part, referred to network |
m:u0:bus1or :bus2 | p.u. | Zero-Sequence-Voltage, Magnitude |
m:phiu0:bus1or :bus2 | deg | Zero-Sequence-Voltage, Angle |
m:u2:bus1or :bus2 | p.u. | Negative-Sequence-Voltage, Magnitude |
m:phiu2:bus1or :bus2 | deg | Negative-Sequence-Voltage, Angle |
m:irnet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Real Part |
m:iinet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Imaginary Part |
m:inet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Magnitude |
m:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kA | Phase Current, Magnitude |
m:phii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Phase Current, Angle |
m:i0r:bus1or :bus2 | p.u. | Zero-Sequence Current, Real Part |
m:i0i:bus1or :bus2 | p.u. | Zero-Sequence Current, Imaginary Part |
m:i0:bus1or :bus2 | p.u. | Zero-Sequence Current, Magnitude |
m:I0:bus1or :bus2 | kA | Zero-Sequence Current, Magnitude |
m:I0x3:bus1or :bus2 | kA | 3*I0 |
m:phii0:bus1or :bus2 | deg | Zero-Sequence Current, Angle |
m:i2r:bus1or :bus2 | p.u. | Negative-Sequence Current, Real Part |
m:i2i:bus1or :bus2 | p.u. | Negative-Sequence Current, Imaginary Part |
m:i2:bus1or :bus2 | p.u. | Negative-Sequence Current, Magnitude |
m:I2:bus1or :bus2 | kA | Negative-Sequence Current, Magnitude |
m:phii2:bus1or :bus2 | deg | Negative-Sequence Current, Angle |
m:P:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | MW | Active Power |
m:Q:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | Mvar | Reactive Power |
m:S:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | MVA | Apparent Power |
m:cosphi:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | ยท | Power Factor |
m:tanphi:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | ยท | tan(phi) |
m:Pln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | MW | Active Power (Line-Neutral) |
m:Qln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | Mvar | Reactive Power (Line-Neutral) |
m:P1:bus1or :bus2 | MW | Positive Sequence Active Power |
m:Q1:bus1or :bus2 | Mvar | Positive Sequence Reactive Power |
m:P2:bus1or :bus2 | MW | Negative Sequence Active Power |
m:Q2:bus1or :bus2 | Mvar | Negative Sequence Reactive Power |
m:P0:bus1or :bus2 | MW | Zero Sequence Active Power |
m:Q0:bus1or :bus2 | Mvar | Zero Sequence Reactive Power |
m:i2P:bus1or :bus2 | p.u. | Negative-Sequence Active Current |
m:i2Q:bus1or :bus2 | p.u. | Negative-Sequence Reactive Current |
m:I2P:bus1or :bus2 | kA | Negative-Sequence Active Current |
m:I2Q:bus1or :bus2 | kA | Negative-Sequence Reactive Current |
m:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Real Part |
m:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Imaginary Part |
m:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Magnitude |
m:ir:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Real Part |
m:ii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Imaginary Part |
m:i:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Magnitude |
m:phiui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Angle between Voltage and Current |
m:phiu0i0:bus1or :bus2 | deg | Angle between Voltage and Current in zero-sequence system |
m:phiu2i2:bus1or :bus2 | deg | Angle between Voltage and Current in negative sequence system |
m:TfctPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | s | Fault Clearing Time |
m:BrkloadPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | % | Breaker Loading |
c:input | ยท | Control Input |
c:R_on | Ohm | On Resistance |
c:X_on | Ohm | On Reactance |
c:Inom | kA | Rated Current |
c:loading | % | Loading |
c:t_open | s | Opening Time |
c:i_ctrl | ยท | Internal |
c:closed | ยท | Breaker Closed |
c:locked | ยท | Locked |
c:IdFailure | ยท | Indication Failure |
c:Indication | ยท | Indication |
c:TCM | ยท | Trip Coil Monitor |
c:loadingPh:Aper phase :A, :B, :C, unbalanced only | % | Loading |
c:closedPh:Aper phase :A, :B, :C, unbalanced only | ยท | Breaker Closed |
n:ur:bus1or :bus2 | p.u. | Voltage, Real Part |
n:ui:bus1or :bus2 | p.u. | Voltage, Imaginary Part |
n:u:bus1or :bus2 | p.u. | Voltage, Magnitude |
n:upc:bus1or :bus2 | % | Voltage, Magnitude |
n:du:bus1or :bus2 | % | Voltage Deviation |
n:U:bus1or :bus2 | kV | Line-Ground Voltage, Magnitude |
n:phiu:bus1or :bus2 | deg | Voltage, Angle |
n:phiurel:bus1or :bus2 | deg | Voltage, Relative Angle |
n:Ul:bus1or :bus2 | kV | Line-Line Voltage, Magnitude |
n:u1:bus1or :bus2 | p.u. | Voltage, Magnitude |
n:u1pc:bus1or :bus2 | % | Voltage, Magnitude |
n:u1r:bus1or :bus2 | p.u. | Positive-Sequence Voltage, Real Part |
n:u1i:bus1or :bus2 | p.u. | Positive-Sequence Voltage, Imaginary Part |
n:ishc:bus1or :bus2 | p.u. | Short-Circuit Current, magnitude |
n:Ishc:bus1or :bus2 | kA | Short-Circuit Current, magnitude |
n:fe:bus1or :bus2 | p.u. | Electrical Frequency |
n:dfehz:bus1or :bus2 | Hz | Deviation of the El. Frequency |
n:fehz:bus1or :bus2 | Hz | Electrical Frequency |
n:frnom:bus1or :bus2 | Hz | Nominal Frequency |
n:ishcr:bus1or :bus2 | p.u. | Short-Circuit Current, real |
n:ishci:bus1or :bus2 | p.u. | Short-Circuit Current, imag |
n:dfedt:bus1or :bus2 | p.u./s | Derivative of El. Frequency |
n:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Real Part |
n:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Imaginary Part |
n:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Magnitude |
n:upc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | % | Line-Ground Voltage, Magnitude |
n:du:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | % | Voltage Deviation |
n:U:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Line-Ground Voltage, Magnitude |
n:phiu:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Line-Ground Voltage, Angle |
n:ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Line Voltage, Magnitude |
n:ulpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | % | Line-Line Voltage, Magnitude |
n:Ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Line-Line Voltage, Magnitude |
n:phiul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Line-Line Voltage, Angle |
n:u0:bus1or :bus2 | p.u. | Zero-Sequence Voltage, Magnitude |
n:U0:bus1or :bus2 | kV | Zero-Sequence Voltage, Magnitude |
n:U0x3:bus1or :bus2 | kV | 3*U0 |
n:phiu0:bus1or :bus2 | deg | Zero-Sequence Voltage, Angle |
n:U1:bus1or :bus2 | kV | Line-Ground Positive-Sequence Voltage, Magnitude |
n:phiu1:bus1or :bus2 | deg | Positive-Sequence Voltage, Angle |
n:u2:bus1or :bus2 | p.u. | Negative-Sequence Voltage, Magnitude |
n:U2:bus1or :bus2 | kV | Line-Ground Negative-Sequence Voltage, Magnitude |
n:phiu2:bus1or :bus2 | deg | Negative-Sequence Voltage, Angle |
n:U1l:bus1or :bus2 | kV | Line-Line Positive-Sequence Voltage, Magnitude |
n:U2l:bus1or :bus2 | kV | Line-Line Negative-Sequence Voltage, Magnitude |
n:uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Neutral Voltage, Magnitude |
n:Uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Line-Neutral Voltage, Magnitude |
n:phiuln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | deg | Line-Neutral Voltage, Angle |
n:un:bus1or :bus2 | p.u. | Neutral-Ground Voltage, Magnitude |
n:Un:bus1or :bus2 | kV | Neutral-Ground Voltage, Magnitude |
n:phiun:bus1or :bus2 | deg | Neutral-Ground Voltage, Angle |
n:upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Technology dependent Voltage, Magnitude |
n:Upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Phase Technology dependent Voltage, Magnitude |
n:um:bus1or :bus2 | p.u. | Average-Voltage, Magnitude |
n:Um:bus1or :bus2 | kV | Average-Voltage, Magnitude |
n:ishc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Short-Circuit Current, magnitude |
n:Ishc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kA | Short-Circuit Current, magnitude |
n:inshc:bus1or :bus2 | p.u. | Neutral Short-Circuit Current, magnitude |
n:Inshc:bus1or :bus2 | kA | Neutral Short-Circuit Current, magnitude |
n:ishcr:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Short-Circuit Current, real |
n:ishci:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Short-Circuit Current, imag |
ElmCoup emt simulation results
Read after ComInc (EMT) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).
| Attribute | Unit | Description |
|---|---|---|
m:u0:bus1or :bus2 | p.u. | Zero-Sequence-Voltage |
m:u1r:bus1or :bus2 | p.u. | Voltage Phasor, Real Part |
m:u1i:bus1or :bus2 | p.u. | Voltage Phasor, Imaginary Part |
m:u1:bus1or :bus2 | p.u. | Voltage Phasor, Magnitude |
m:U1:bus1or :bus2 | kV | Line-Ground Voltage Phasor, Magnitude |
m:U1l:bus1or :bus2 | kV | Line-Line Voltage Phasor, Magnitude |
m:phiu1:bus1or :bus2 | deg | Voltage Phasor, Angle |
m:inet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, referred to network |
m:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kA | Phase Current |
m:i0:bus1or :bus2 | p.u. | Zero-Sequence Current |
m:I0:bus1or :bus2 | kA | Zero-Sequence Current |
m:I0x3:bus1or :bus2 | kA | 3*I0 |
m:i1r:bus1or :bus2 | p.u. | Current Phasor, Real Part |
m:i1i:bus1or :bus2 | p.u. | Current Phasor, Imaginary Part |
m:i1:bus1or :bus2 | p.u. | Current Phasor, Magnitude |
m:I1:bus1or :bus2 | kA | Current Phasor, Magnitude |
m:phii1:bus1or :bus2 | deg | Current Phasor, Angle |
m:P:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | MW | Active Power |
m:Psum:bus1or :bus2 | MW | Power-Phasor, Active Power |
m:Qsum:bus1or :bus2 | Mvar | Power Phasor, Reactive Part |
m:Ssum:bus1or :bus2 | MVA | Power Phasor, Apparent Power |
m:i1P:bus1or :bus2 | p.u. | Current Phasor, Active Current |
m:i1Q:bus1or :bus2 | p.u. | Current Phasor, Reactive Current |
m:I1P:bus1or :bus2 | kA | Current Phasor, Active Current |
m:I1Q:bus1or :bus2 | kA | Current Phasor, Reactive Current |
m:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage |
m:i:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current |
m:phiu1i1:bus1or :bus2 | deg | Angle between Voltage and Current Phasor |
m:Tfct:bus1or :bus2 | s | Fault Clearing Time |
m:TfctPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | s | Fault Clearing Time |
m:unet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, referred to network |
m:cosphi1:bus1or :bus2 | ยท | Power-Phasor, Power-Factor |
c:input | ยท | Control Input |
c:R_on | Ohm | On Resistance |
c:iNeutInter | ยท | Switch interrupts neutral wire |
c:i_ctrl | ยท | Internal |
c:closed | ยท | Breaker Closed |
c:closedPh:Aper phase :A, :B, :C, unbalanced only | ยท | Breaker Closed |
c:locked | ยท | Locked |
c:IdFailure | ยท | Indication Failure |
c:Indication | ยท | Indication |
c:TCM | ยท | Trip Coil Monitor |
c:i_inst | ยท | Instant of Closing |
c:t_delElm | s | Delay Time from network element and type |
c:t_delType | s | Delay Time from network element and type |
c:t_delAcc | s | Accumulated delay time |
c:v_lim | p.u. | Voltage Limit |
c:i_scheme | ยท | Scheme |
c:i_larlow | ยท | Larger or lower than voltage threshold |
c:L_on | Ohm | On Inductance |
c:i_trigPh | ยท | Phase that triggers |
c:i_open | ยท | Open at executions time or zero crossing |
c:TRV_pos:Aper phase :A, :B, :C, unbalanced only | ยท | CB TRV envelope positive |
c:TRV_neg:Aper phase :A, :B, :C, unbalanced only | ยท | CB TRV envelope negative |
n:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage |
n:upc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | % | Phase Voltage |
n:U:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Phase Voltage |
n:ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Line Voltage |
n:ulpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | % | Line-Line Voltage |
n:Ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Line-Line Voltage |
n:u0:bus1or :bus2 | p.u. | Zero-Sequence-Voltage |
n:U0:bus1or :bus2 | kV | Zero-Sequence-Voltage |
n:U0x3:bus1or :bus2 | kV | 3*U0 |
n:u1:bus1or :bus2 | p.u. | Voltage Phasor, Magnitude |
n:u1pc:bus1or :bus2 | % | Voltage Phasor, Magnitude |
n:u1r:bus1or :bus2 | p.u. | Voltage Phasor, Real Part |
n:u1i:bus1or :bus2 | p.u. | Voltage Phasor, Imaginary Part |
n:U1:bus1or :bus2 | kV | Voltage Phasor, Magnitude |
n:phiu1:bus1or :bus2 | deg | Voltage Phasor, Angle |
n:U1l:bus1or :bus2 | kV | Line-Line Voltage Phasor, Magnitude |
n:uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Line-Neutral Voltage |
n:Uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kV | Line-Neutral Voltage |
n:un:bus1or :bus2 | p.u. | Neutral-Ground Voltage |
n:Un:bus1or :bus2 | kV | Neutral-Ground Voltage |
n:ishc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | p.u. | Short-Circuit Current |
n:Ishc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only | kA | Short-Circuit Current |
n:inshc:bus1or :bus2 | p.u. | Neutral Short-Circuit Current, magnitude |
n:Inshc:bus1or :bus2 | kA | Neutral Short-Circuit Current, magnitude |
n:fe:bus1or :bus2 | p.u. | Electrical Frequency |
n:dfehz:bus1or :bus2 | Hz | Deviation of the El. Frequency |
n:fehz:bus1or :bus2 | Hz | Electrical Frequency |
n:frnom:bus1or :bus2 | Hz | Nominal Frequency |
s:dU_A | kV | Voltage Difference |
s:dU_B | kV | Voltage Difference |
s:dU_C | kV | Voltage Difference |
ElmCoup dc load flow results
Read after ComLdf (DC) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.
| Attribute | Unit | Description |
|---|---|---|
m:P:bus1or :bus2 | MW | Active Power |
m:Q:bus1or :bus2 | Mvar | Reactive Power |
c:R_on | Ohm | On Resistance |
c:X_on | Ohm | On Reactance |
c:on_off | ยท | Flag Closed |
c:Inom | kA | Rated Current |
c:loading | % | Loading |
c:maxload | % | Max. Loading |
c:Ploss | MW | Losses (total) |
c:Qloss | Mvar | Reactive-Losses (total) |
n:u:bus1or :bus2 | p.u. | Voltage, Magnitude |
n:upc:bus1or :bus2 | % | Voltage, Magnitude |
n:U:bus1or :bus2 | kV | Line-Ground Voltage, Magnitude |
n:phiu:bus1or :bus2 | deg | Voltage, Angle |
n:phiurel:bus1or :bus2 | deg | Voltage, Relative Angle |
n:Ul:bus1or :bus2 | kV | Line-Line Voltage, Magnitude |
n:u1:bus1or :bus2 | p.u. | Voltage, Magnitude |
n:Pgen:bus1or :bus2 | MW | Generation, Active Power |
n:Pmot:bus1or :bus2 | MW | Motor Load, Active Power |
n:Pload:bus1or :bus2 | MW | General Load, Active Power |
n:Pcomp:bus1or :bus2 | MW | Compensation (Losses) |
n:Pnet:bus1or :bus2 | MW | External Networks, Active Power |
n:Pflow:bus1or :bus2 | MW | Power Flow, Active Power |
ElmCoup modal analysis results
Read after ComMod with GetAttribute. c: calculation parameter.
| Attribute | Unit | Description |
|---|---|---|
c:input | ยท | Control Input |
c:R_on | Ohm | On Resistance |
c:X_on | Ohm | On Reactance |
c:Inom | kA | Rated Current |
c:loading | % | Loading |
c:t_open | s | Opening Time |
c:i_ctrl | ยท | Internal |
c:closed | ยท | Breaker Closed |
c:locked | ยท | Locked |
c:IdFailure | ยท | Indication Failure |
c:Indication | ยท | Indication |
c:TCM | ยท | Trip Coil Monitor |
ElmCoup optimal power flow results
Read after ComOpf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.
| Attribute | Unit | Description |
|---|---|---|
m:urnet:bus1or :bus2 | p.u. | Voltage, Real Part, referred to network |
m:uinet:bus1or :bus2 | p.u. | Voltage, Imaginary Part, referred to network |
m:u1r:bus1or :bus2 | p.u. | Positive-Sequence-Voltage, Real Part |
m:u1i:bus1or :bus2 | p.u. | Positive-Sequence-Voltage, Imaginary Part |
m:u1:bus1or :bus2 | p.u. | Positive-Sequence-Voltage, Magnitude |
m:U1:bus1or :bus2 | kV | Line-Ground Positive-Sequence-Voltage, Magnitude |
m:U1l:bus1or :bus2 | kV | Line-Line Positive-Sequence-Voltage, Magnitude |
m:phiu1:bus1or :bus2 | deg | Positive-Sequence-Voltage, Angle |
m:irnet:bus1or :bus2 | p.u. | Current, Real Part, referred to network |
m:iinet:bus1or :bus2 | p.u. | Current, Imaginary Part, referred to network |
m:inet:bus1or :bus2 | p.u. | Current, Magnitude, referred to network |
m:I:bus1or :bus2 | kA | Current, Magnitude |
m:phii:bus1or :bus2 | deg | Current, Angle |
m:i1r:bus1or :bus2 | p.u. | Positive-Sequence Current, Real Part |
m:i1i:bus1or :bus2 | p.u. | Positive-Sequence Current, Imaginary Part |
m:i1:bus1or :bus2 | p.u. | Positive-Sequence Current, Magnitude |
m:I1:bus1or :bus2 | kA | Positive-Sequence Current, Magnitude |
m:phii1:bus1or :bus2 | deg | Positive-Sequence Current, Angle |
m:P:bus1or :bus2 | MW | Active Power |
m:Q:bus1or :bus2 | Mvar | Reactive Power |
m:S:bus1or :bus2 | MVA | Apparent Power |
m:cosphi:bus1or :bus2 | ยท | Power Factor |
m:tanphi:bus1or :bus2 | ยท | tan(phi) |
m:Psum:bus1or :bus2 | MW | Total Active Power |
m:Qsum:bus1or :bus2 | Mvar | Total Reactive Power |
m:Ssum:bus1or :bus2 | MVA | Total Apparent Power |
m:cosphisum:bus1or :bus2 | ยท | Total Power Factor |
m:tanphisum:bus1or :bus2 | ยท | Total tan(phi) |
m:i1P:bus1or :bus2 | p.u. | Positive-Sequence Active Current |
m:i1Q:bus1or :bus2 | p.u. | Positive-Sequence Reactive Current |
m:I1P:bus1or :bus2 | kA | Positive-Sequence Active Current |
m:I1Q:bus1or :bus2 | kA | Positive-Sequence Reactive Current |
m:ur:bus1or :bus2 | p.u. | Voltage, Real Part |
m:ui:bus1or :bus2 | p.u. | Voltage, Imaginary Part |
m:u:bus1or :bus2 | p.u. | Voltage, Magnitude |
m:ir:bus1or :bus2 | p.u. | Current, Real Part |
m:ii:bus1or :bus2 | p.u. | Current, Imaginary Part |
m:i:bus1or :bus2 | p.u. | Current, Magnitude |
m:phiui:bus1or :bus2 | deg | Angle between Voltage and Current |
m:phiu1i1:bus1or :bus2 | deg | Angle between Voltage and Current in positive sequence system |
m:Tfct:bus1or :bus2 | s | Fault Clearing Time |
m:Brkload:bus1or :bus2 | % | Breaker Loading |
m:Spu:bus1or :bus2 | MVA/p.u. | Apparent Power per p.u. Voltage |
c:R_on | Ohm | On Resistance |
c:X_on | Ohm | On Reactance |
c:on_off | ยท | Flag Closed |
c:Inom | kA | Rated Current |
c:loading | % | Loading |
c:maxload | % | Max. Loading |
c:Ploss | MW | Losses (total) |
c:Qloss | Mvar | Reactive-Losses (total) |
c:Plossld | MW | Losses (load) |
c:Qlossld | Mvar | Reactive-Losses (load) |
c:Plossnld | MW | Losses (no load) |
c:Qlossnld | Mvar | Reactive-Losses (no load) |
n:ur:bus1or :bus2 | p.u. | Voltage, Real Part |
n:ui:bus1or :bus2 | p.u. | Voltage, Imaginary Part |
n:u:bus1or :bus2 | p.u. | Voltage, Magnitude |
n:upc:bus1or :bus2 | % | Voltage, Magnitude |
n:du:bus1or :bus2 | % | Voltage Deviation |
n:U:bus1or :bus2 | kV | Line-Ground Voltage, Magnitude |
n:phiu:bus1or :bus2 | deg | Voltage, Angle |
n:phiurel:bus1or :bus2 | deg | Voltage, Relative Angle |
n:Ul:bus1or :bus2 | kV | Line-Line Voltage, Magnitude |
n:u1:bus1or :bus2 | p.u. | Voltage, Magnitude |
n:u1pc:bus1or :bus2 | % | Voltage, Magnitude |
n:u1r:bus1or :bus2 | p.u. | Positive-Sequence Voltage, Real Part |
n:u1i:bus1or :bus2 | p.u. | Positive-Sequence Voltage, Imaginary Part |
n:Pgen:bus1or :bus2 | MW | Generation, Active Power |
n:Qgen:bus1or :bus2 | Mvar | Generation, Reactive Power |
n:Pmot:bus1or :bus2 | MW | Motor Load, Active Power |
n:Qmot:bus1or :bus2 | Mvar | Motor Load, Reactive Power |
n:Pload:bus1or :bus2 | MW | General Load, Active Power |
n:Qload:bus1or :bus2 | Mvar | General Load, Reactive Power |
n:Pcomp:bus1or :bus2 | MW | Compensation (Losses) |
n:Qcomp:bus1or :bus2 | Mvar | Compensation |
n:Pnet:bus1or :bus2 | MW | External Networks, Active Power |
n:Qnet:bus1or :bus2 | Mvar | External Networks, Reactive Power |
n:Pflow:bus1or :bus2 | MW | Power Flow, Active Power |
n:Qflow:bus1or :bus2 | Mvar | Power Flow, Reactive Power |
n:Pout:bus1or :bus2 | MW | Outgoing Flow, Active Power |
n:Qout:bus1or :bus2 | Mvar | Outgoing Power, Reactive Power |
n:Sout:bus1or :bus2 | MVA | Outgoing Power, Apparent Power |
n:cosphiout:bus1or :bus2 | ยท | Outgoing Power, Power Factor |
n:Pbalance:bus1or :bus2 | MW | Active Power Balance (=0) |
n:Qbalance:bus1or :bus2 | Mvar | Reactive Power Balance (=0) |
n:LossPdown:bus1or :bus2 | MW | Losses, downstream |
n:LossQdown:bus1or :bus2 | Mvar | Losses, downstream (Reactive Power) |
n:LossPdownload:bus1or :bus2 | MW | Load losses, downstream |
n:LossQdownload:bus1or :bus2 | Mvar | Load losses, downstream |
n:LossPdownnoload:bus1or :bus2 | MW | No load losses, downstream |
n:LossQdownnoload:bus1or :bus2 | Mvar | No load losses, downstream |
n:du_feed:bus1or :bus2 | % | Difference from voltage at start of feeder |
ElmCoup basic data
b: values are worked out from the input data. Read them; they are not set.
| Attribute | Unit | Description |
|---|---|---|
b:loc_name | ยท | Name |
Related
- All 73 classes in the attribute reference
- Run a load flow and export the results with Python
- PowerFactory Python API: getting started
โ ElmZpu Common Impedance ยท ElmGndswt Grounding Switch โ