ElmLne attributesPowerFactory Line

Every attribute of the PowerFactory Line (ElmLne): 279 input parameters and 1084 result variables, with units and meaning. Copy a name into GetAttribute or SetAttribute.

What ElmLne is

An overhead line or cable between two terminals. Its impedance per km and rated current sit in the line type (TypLne) it points to through typ_id; the element holds the length, the number of parallel lines and the derating.

Class
ElmLne, element class
PowerFactory name
Line
Type
TypLne, through typ_id
Terminal suffix
:bus1 terminal i, :bus2 terminal j
Attributes
279 input parameters and 1084 result variables, in 7 calculations

Most used ElmLne attributes

AttributeUnitDescriptionWhere
c:loading%Loadingthermal loadingLoad flow
m:P:bus1MWActive Poweractive power at terminal iLoad flow
m:Q:bus1MvarReactive PowerLoad flow
m:I:bus1kACurrent, Magnitudecurrent at terminal iLoad flow
c:PlossMWLosses (total)lossesLoad flow
dlinekmLength of Linelengthinput data
nlnum·parallel Linesinput data
fline·Derating Factorinput data
outserv·Out of Serviceinput data
typ_id·Typeinput data

Read and write ElmLne in Python

import powerfactory

app = powerfactory.GetApplication()          # GetApplicationExt() from outside PowerFactory
app.GetFromStudyCase("ComLdf").Execute()      # results exist after a calculation

for line in app.GetCalcRelevantObjects("*.ElmLne"):
    loading = line.GetAttribute("c:loading")      # Loading, %
    p_bus1 = line.GetAttribute("m:P:bus1")        # Active Power, MW
    print(line.loc_name, loading, p_bus1)

line = app.GetCalcRelevantObjects("*.ElmLne")[0]
line.SetAttribute("outserv", 1)               # take the line out of service
  • A result at a terminal of the line needs the terminal in its name: m:P:bus1, not m:P, which raises AttributeError.
  • An input parameter is read and written with or without its e: prefix: GetAttribute("outserv") and GetAttribute("e:outserv") give the same value.
  • RMS and EMT variables change over time: record them in a results object (ElmRes) to read the whole curve. GetAttribute after a run gives the value at the last time step.

ElmLne input parameters

The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.

AttributeUnitDescription
loc_name·Name
chr_name·Characteristic Name
for_name·Foreign Key
dat_src·Data source
sernum·Serial Number
commissionDate·Commissioning Date
appr_modby·Modified by
meth·Reference method
meth_vde·Reference method
meth_bs·Reference method
meth_nfc·Reference method
meth_nfcmv·Reference method
iopt_dir·Arrangement
iopt_ord·Cable formation
outserv·Out of Service
iZoneBus·Zone
iAreaBus·Area
lossAssign·Loss assignment
nlnum·parallel Lines
inAir·Laying
i_dist·Line Model
ktrto·Transposition
earthReturn·Earth return formula
i_model·Distributed parameter line model
i_const_rms·Travelling wave
lossModel_rms·Loss model
lossModel_emt·Loss model
iopt_tem·Temperature Dependency
iopt_tem_rms·Temperature dependency
iterVFY·Max. number of iterations
iterVFA·Max. number of iterations
polesVFY·Max. number of poles
polesVFA·Max. number of poles
outputPoles·Output poles
dcCorr·Apply DC correction
tuneDelays·Fine-tune delays
methodVFY·Number of poles
methodVFA·Number of poles
fd_model·Line Model
constr·Year of Construction
appr_status·Status
iperfect·Ideal component
iOPFCload·Max. loading constraint
isConstrLoading·Max. loading constraint for Unit Commitment
isMaxLoadSoftNlin·Penalty costs for soft constraints
allowOutDistFacFilt·Allow filtering by outage distribution factor
allowMarginFilt·Allow filtering by constraint margin
allowCntConstrFilt·Allow contingency filtering by number of critical constraints
isSepCntConstrType·Separate constraint type
cntConstrType·Contingency-constraint type
isSepCntMaxAllowedLoading·Separate max. allowed loading
isConstrLoadingPlacement·Max. loading constraint for Optimal Equipment Placement
dryingoutavoid·Soil drying-out avoided
iopt_engine·Cables for powering mobile gear with drum winding
iopt_turns·Drum winding with multiple turns
v2dratiovde·Height-diameter ratio
v2dratiodctvde·Height-duct diameter ratio
v2dratioIec·Height-diameter ratio
v2dratiodctIec·Height-duct diameter ratio
surfdist·Surface distance
surfdistIec·Surface distance
layingArr·Laying arrangement
layingArr502·Laying arrangement
arrangevde·Arrangement
formatvde·Cable formation
npara·Number of grouped cables (laid together)
asys·Clearance
cbusage·Usage
cabspacing·Spacing
iecspacing·Spacing
trays·Number of trays
ducts·Number of ducts
vducts·Number of vertical ducts
hducts·Number of horizontal ducts
specBurialCnfg·Special burial conditions
iopt_grp·Grouping
soiltyp·Soil type
maxPara·Maximum number of grouped cables
cb_expsun·Exposed to direct sunlight
protCheck·Protection assessment
forTrainSim·Line for train simulation
freqDepPiModel·Lumped parameter line model
numStates·Max. model order
modelPiSec·Circuit configuration
fittingMethod·Fitting method
numPiSec·Number of cascaded PI sections
dlinekmLength of Line
fline·Derating Factor
TopdegCOperating Temperature
ImaxlimkAMax. permissible current
sagCirmMax.sag, phase conductors
sagGndmMax.sag, earth conductors
rearth·Earth resistivity
gshuntuS/kmShunt conductance
maxload%Max. loading
loadfactor·Load factor (lf)
solar_radW/m^2Solar radiation intensity
windvelocitym/sWind velocity
soilThermResK.m/WSoil thermal resistivity
occupCoeff·Occupation coefficient
alphamm^2/sMedium diffusivity
mediumTempdegCMedium mean temperature
soilThermResdryK.m/WDry soil thermal resistivity
thetaXdegCCritical temperature of soil, θx
thd%Third harmonic content
temp_envdegCAmbient temperature
fk2·Fusing current factor k2
cbsp·Set point
if_depthmBurial depth
installCostUSD/kmInstallation costs
userDefCurACurrent
userDefPF·Power factor
thick_dmmJoint thickness
dist_ammDistance between cables
kz1OhmSurge Impedance, HF, Mode 1.
kz0OhmSurge Impedance, HF, Mode 0.
kz2OhmSurge Impedance, HF, Mode 2.
a1dcp.u.Wave Propagation, DC, Mode 1
a0dcp.u.Wave Propagation, DC, Mode 0
a2dcp.u.Wave Propagation, DC, Mode 2
fminHzMin. Frequency of Parameter Fitting
fmaxHzMax. Frequency of Parameter Fitting
ftauHzFrequency for Travel-Time Estimation
tolBode%Tolerance for Bode Approximation
maxErrVFYSRMS error
maxErrVFA·RMS error
stMarginY·Stability margin
stMarginA·Stability margin
scalingFacSoftConstrOpf·Weighting factor for soft constraint penalty
scalingFacSoftConstrCost·Cost scaling factor
cntMaxAllowedLoading%Max. allowed loading in Contingencies
dpl1·dpl1
dpl2·dpl2
dpl3·dpl3
dpl4·dpl4
dpl5·dpl5
appr_modif·Modified
GPScoordsdegGeographical Position
cimRdfId·RDF ID
desc·Description
fold_id·In Folder
typ_id·TypeObject: TypLne,TypTow,TypGeo,TypCabsys
bus1·Terminal iObject: StaCubic
bus2·Terminal jObject: StaCubic
pCondCir·Type of phase conductorsObject: TypCon
pCondGnd·Type of earth conductorsObject: TypCon
doc_id·Additional Data
pOwner·OwnerObject: ElmOwner
pOperator·OperatorObject: ElmOperator
pStochStoTyplneElement model
pRating·Thermal RatingObject: IntThrating
cubsecs·Sections/Line Loads/Compensation
cpHeadFold·Head Folder
bus1_bar·Terminal i
bus2_bar·Terminal j
cpGrid·GridObject: ElmNet
cpZone·ZoneObject: ElmZone
cpArea·AreaObject: ElmArea
cpFeed·FeederObject: ElmFeeder
ciDist·Distance from infeed in number of buses
ciLater·Lateral Index
ciDistRoot·Distance from first infeed in number of buses
ciDistAll·Distance from infeed in number of buses including switches
ciDistAllRoot·Distance from first infeed in number of buses including switches
cpOwner·OwnerObject: ElmOwner
cpOperator·OperatorObject: ElmOperator
cpBranch·BranchObject: ElmBranch
cpSite·SiteObject: ElmSite
cpSubstat·SubstationObject: ElmSubstat,ElmTrfstat
cpMeteostat·Meteo StationObject: ElmMeteostat
ciOutaged·Planned Outage
ciEnergized·Energized
ciEarthed·Earthed
cDisplayName·Display Name
cpSupplyTransformer·Supplying TransformerObject: ElmTr?,ElmTrmult
cpSupplyTrfStation·Supplying Secondary SubstationObject: ElmTrfstat
cpSupplySubstation·Supplying SubstationObject: ElmSubstat
ci_model·Distributed parameter line model
c_Ta1usTravel Time, Mode 1
c_Ta0usTravel Time, Mode 0
c_Ta2usTravel Time, Mode 2
cdisp_col·Display data for phase matrix index
cdisp_row·Display data for phase matrix row
c_paULM·A, Number of poles
c_aAtDCp.u.Wave propagation, DC
c_pTadULMusTravel time
R1OhmPos. Seq. Resistance, R1
X1OhmPos. Seq. Reactance, X1
Z1OhmPos. Seq. Impedance, Z1
phiz1degPos. Seq. Impedance, Angle
LdcmHInductance, Ldc
R0OhmZero Seq. Resistance, R0
X0OhmZero Seq. Reactance, X0
k0·Earth Factor, Magnitude
phik0degEarth Factor, Angle
IceAEarth-Fault Current, Ice
InomkANominal Current
Inom_akANominal Current (act.)
IratedkARated current
UnomkVRated Voltage
B1uSSusceptance B1
G1uSConductance G1
C1uFCapacitance C1
B0uSSusceptance B0
G0uSConductance G0
C0uFCapacitance C0
ReRl·Earth Factor, Re/Rl
XeXl·Earth Factor, Xe/Xl
R0mOhmR0m
X0mOhmX0m
G0muSG0m
B0muSB0m
R1_tmaxOhmPos. Seq. Resistance at Max. Operating Temperature, R1 at tmax
rSbasepup.u.r (Sbase)
xSbasepup.u.x (Sbase)
bSbasepup.u.b (Sbase)
r0Sbasepup.u.r0 (Sbase)
x0Sbasepup.u.x0 (Sbase)
b0Sbasepup.u.b0 (Sbase)
r0mSbasepup.u.r0m (Sbase)
x0mSbasepup.u.x0m (Sbase)
c_pCompi·Compensation iObject: ElmLnecomp
c_pCompj·Compensation jObject: ElmLnecomp
txt_typ·Type of Line
c_pz0·Z0, N° Poles/Zeros
c_pa0·A0, N° Poles
c_za0·A0, N° Zeros
c_pz1·Z1, N° Poles/Zeros
c_pa1·A1, N° Poles
c_za1·A1, N° Zeros
c_pz2·Z2, N° Poles/Zeros
c_pa2·A2, N° Poles
c_za2·A2, N° Zeros
ckz0_rmsOhmSurge impedance, HF, mode 0.
ca0dc_rmsp.u.Wave propagation, DC, mode 0
cTa0_rmssTravel time, mode 0
ckz1_rmsOhmSurge Impedance, HF, mode 1.
ca1dc_rmsp.u.Wave propagation, DC, mode 1
cTa1_rmssTravel time, mode 1
ckz2_rmsOhmSurge Impedance, HF, mode 2.
ca2dc_rmsp.u.Wave propagation, DC, mode 2
cTa2_rmssTravel time, mode 2
FOR11/aForced Outage Rate
FOEh/aForced Outage Expectancy
FODhForced Outage Duration
pTypStochStoTyplneType model
c_ptow·Line CouplingsObject: ElmTow,ElmCabsys
c_pcond·Conductor TypeObject: TypCon
c_pcoup·Coupled LineObject: ElmLne
cSmaxkVAMax. Load
cSavkVAAverage Load
ccosphi·Power Factor
cNrCust·Number of Customers
cAllowOutDistFacFilt·Allow filtering by outage distribution factor
cAllowMarginFilt·Allow filtering by constraint margin
cAllowCntConstrFilt·Allow contingency filtering by number of critical constraints
cIsSepCntConstrType·Separate constraint type
cIsSepCntMaxAllowedLoading·Separate max. allowed loading
CCEarFr1/aFrequency of single earth faults
CCEarRepMuhRepair duration
CCEarProb%Conditional probability of a second earth fault
deltaphiu1degVoltage Angle Difference across Line
deltau1p.u.Voltage Difference across Line
trans_ff1/aTransient Fault Frequency
crosssecmm^2Cross section
cGrpVde·Bunched on the wall, on surface, embedded or enclosed
cGrpIec·Bunched on the wall, on surface, embedded or enclosed
cthetaXdegCMust be >
condMat·Conductor material
isoMat·Insulation material
shMat·Sheath insulation
armTyp·Armour type
nCond·Number of conductors
ctmaxdegCMax.operating temperature
cithrARated Short-Time (1s) Current (Conductor)
minResTrainDistmMin. resolution of train distances
nconTrains·No. of trains
conTrain·TrainObject: ElmTrain
conTrainPoskmTrain position

ElmLne load flow results

Read after ComLdf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:bus1or :bus2p.u.Voltage, Real Part, referred to network
m:uinet:bus1or :bus2p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1or :bus2p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1or :bus2p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1or :bus2p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1or :bus2kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1or :bus2kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1or :bus2degPositive-Sequence-Voltage, Angle
m:irnet:bus1or :bus2p.u.Current, Real Part, referred to network
m:iinet:bus1or :bus2p.u.Current, Imaginary Part, referred to network
m:inet:bus1or :bus2p.u.Current, Magnitude, referred to network
m:I:bus1or :bus2kACurrent, Magnitude
m:phii:bus1or :bus2degCurrent, Angle
m:i1r:bus1or :bus2p.u.Positive-Sequence Current, Real Part
m:i1i:bus1or :bus2p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1or :bus2p.u.Positive-Sequence Current, Magnitude
m:I1:bus1or :bus2kAPositive-Sequence Current, Magnitude
m:phii1:bus1or :bus2degPositive-Sequence Current, Angle
m:P:bus1or :bus2MWActive Power
m:Q:bus1or :bus2MvarReactive Power
m:S:bus1or :bus2MVAApparent Power
m:cosphi:bus1or :bus2·Power Factor
m:tanphi:bus1or :bus2·tan(phi)
m:Psum:bus1or :bus2MWTotal Active Power
m:Qsum:bus1or :bus2MvarTotal Reactive Power
m:Ssum:bus1or :bus2MVATotal Apparent Power
m:cosphisum:bus1or :bus2·Total Power Factor
m:tanphisum:bus1or :bus2·Total tan(phi)
m:i1P:bus1or :bus2p.u.Positive-Sequence Active Current
m:i1Q:bus1or :bus2p.u.Positive-Sequence Reactive Current
m:I1P:bus1or :bus2kAPositive-Sequence Active Current
m:I1Q:bus1or :bus2kAPositive-Sequence Reactive Current
m:ur:bus1or :bus2p.u.Voltage, Real Part
m:ui:bus1or :bus2p.u.Voltage, Imaginary Part
m:u:bus1or :bus2p.u.Voltage, Magnitude
m:ir:bus1or :bus2p.u.Current, Real Part
m:ii:bus1or :bus2p.u.Current, Imaginary Part
m:i:bus1or :bus2p.u.Current, Magnitude
m:phiui:bus1or :bus2degAngle between Voltage and Current
m:phiu1i1:bus1or :bus2degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1or :bus2sFault Clearing Time
m:Brkload:bus1or :bus2%Breaker Loading
m:Spu:bus1or :bus2MVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bus1or :bus2p.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bus1or :bus2degZero-Sequence-Voltage, Angle
m:u2:bus1or :bus2p.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bus1or :bus2degNegative-Sequence-Voltage, Angle
m:irnet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part, referred to network
m:iinet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part, referred to network
m:inet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude, referred to network
m:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bus1or :bus2p.u.Zero-Sequence Current, Real Part
m:i0i:bus1or :bus2p.u.Zero-Sequence Current, Imaginary Part
m:i0:bus1or :bus2p.u.Zero-Sequence Current, Magnitude
m:I0:bus1or :bus2kAZero-Sequence Current, Magnitude
m:I0x3:bus1or :bus2kA3*I0
m:phii0:bus1or :bus2degZero-Sequence Current, Angle
m:i2r:bus1or :bus2p.u.Negative-Sequence Current, Real Part
m:i2i:bus1or :bus2p.u.Negative-Sequence Current, Imaginary Part
m:i2:bus1or :bus2p.u.Negative-Sequence Current, Magnitude
m:I2:bus1or :bus2kANegative-Sequence Current, Magnitude
m:phii2:bus1or :bus2degNegative-Sequence Current, Angle
m:ubfacI:bus1or :bus2%Current Unbalance Factor
m:ubfacS:bus1or :bus2%Power Unbalance Factor
m:P:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only·Power Factor
m:tanphi:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only·tan(phi)
m:Pln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bus1or :bus2MWPositive Sequence Active Power
m:Q1:bus1or :bus2MvarPositive Sequence Reactive Power
m:P2:bus1or :bus2MWNegative Sequence Active Power
m:Q2:bus1or :bus2MvarNegative Sequence Reactive Power
m:P0:bus1or :bus2MWZero Sequence Active Power
m:Q0:bus1or :bus2MvarZero Sequence Reactive Power
m:i2P:bus1or :bus2p.u.Negative-Sequence Active Current
m:i2Q:bus1or :bus2p.u.Negative-Sequence Reactive Current
m:I2P:bus1or :bus2kANegative-Sequence Active Current
m:I2Q:bus1or :bus2kANegative-Sequence Reactive Current
m:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1or :bus2degAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bus1or :bus2degAngle between Voltage and Current in negative sequence system
m:TfctPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Breaker Loading
c:zlinep.u.Impedance
c:ylinep.u.Admittance
c:frnomHzNominal frequency
c:hpirad/sNominal angular frequency
c:loading%Loading
c:CloadMvarCapacitive Losses, total
c:GloadkWActive no load losses, total
c:LosseskWLosses, total
c:maxload%Max. Loading
c:curnomkANominal Current
c:rtfac·Temperature Factor
c:IsegikAIsegi
c:IsegjkAIsegj
c:loadingseg%Loading (segment)
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:ImaxkAMaximum Current
c:dup.u.Voltage Drop
c:dupc%Voltage Drop
c:zlp.u.Wave Impedance
c:ncust·Number of Customers
c:ildlv·Line Loads Present
c:SldlvkVALoad, Apparent Power
c:PldlvkWLoad, Active Power
c:QldlvkvarLoad, Reactive Power
c:IldlvALoad, Current
c:cosphildlvkLoad, Power Factor
c:SlMVALoad, variable Part, Apparent Power
c:glnep.u.Admittance
c:rlnep.u.Active Resistance
c:zline_1p.u.Impedance (bus1)
c:zline_2p.u.Impedance (bus2)
c:yline_1p.u.Admittance (bus1)
c:yline_2p.u.Admittance (bus2)
c:shclocp.u.Short-Circuit Location
c:dphiudegVoltage Drop Angle
c:du1p.u.Positive Sequence Voltage Drop
c:du1pc%Positive Sequence Voltage Drop
c:dphiu1degPositive Sequence Voltage Drop Angle
c:PcompkWCompensation Losses
c:QcompMvarReactive Power, Compensation
c:Qcomp_iMvarReactive power, Compensation i
c:Qcomp_jMvarReactive power, Compensation j
c:zl1p.u.Characteristic Impedance, 1.-Sequ.
c:a1p.u.Propagation factor, 1.-Sequ.
c:phizl1degCharacteristic Impedance, Angle, 1.-Sequ.
c:phia1degPropagation factor, Angle, 1.-Sequ.
c:maxloadpup.u.Max. Loading
c:ldcosphi·Load, Variable Part, Power Factor
c:posld·Weighted Load Position
c:dUkVVoltage Drop
c:rlne_1OhmActive Resistance (bus1)
c:glne_1SAdmittance (bus1)
c:rlne_2OhmActive Resistance (bus2)
c:glne_2SAdmittance (bus2)
c:loadingPh:Aper phase :A, :B, :C, unbalanced only%Loading
c:loadingPh%Loading
c:loading_st%Short Term Loading
c:CloadPh:Aper phase :A, :B, :C, unbalanced onlyMvarCapacitive Losses
c:CloadPhMvarCapacitive Losses
c:GloadPh:Aper phase :A, :B, :C, unbalanced onlykWActive no load losses
c:GloadPhkWActive no load losses
c:LossesPh:Aper phase :A, :B, :C, unbalanced onlykWLosses
c:LossesPhkWLosses
c:du:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage Drop
c:dupc:Aper phase :A, :B, :C, unbalanced only%Voltage Drop
c:Sl_nomMVALoad, variable part, Nominal Apparent Power
c:dphiu:Aper phase :A, :B, :C, unbalanced onlydegVoltage Drop Angle
c:Sl_aMVALoad, variable part, Apparent Power, Phase A
c:Sl_bMVALoad, variable part, Apparent Power, Phase B
c:Pcomp_ikWCompensation Losses, i
c:Pcomp_jkWCompensation Losses, j
c:zl0OhmCharacteristic Impedance, 0.-Sequ.
c:a0p.u.Propagation factor, 0.-Sequ.
c:phizl0degCharacteristic Impedance, Angle, 0.-Sequ.
c:phia0degPropagation factor, Angle, 0.-Sequ.
c:Sl_cMVALoad, variable part, Apparent Power, Phase C
n:ur:bus1or :bus2p.u.Voltage, Real Part
n:ui:bus1or :bus2p.u.Voltage, Imaginary Part
n:u:bus1or :bus2p.u.Voltage, Magnitude
n:upc:bus1or :bus2%Voltage, Magnitude
n:du:bus1or :bus2%Voltage Deviation
n:U:bus1or :bus2kVLine-Ground Voltage, Magnitude
n:phiu:bus1or :bus2degVoltage, Angle
n:phiurel:bus1or :bus2degVoltage, Relative Angle
n:Ul:bus1or :bus2kVLine-Line Voltage, Magnitude
n:u1:bus1or :bus2p.u.Voltage, Magnitude
n:u1pc:bus1or :bus2%Voltage, Magnitude
n:u1r:bus1or :bus2p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1or :bus2p.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bus1or :bus2MWGeneration, Active Power
n:Qgen:bus1or :bus2MvarGeneration, Reactive Power
n:Pmot:bus1or :bus2MWMotor Load, Active Power
n:Qmot:bus1or :bus2MvarMotor Load, Reactive Power
n:Pload:bus1or :bus2MWGeneral Load, Active Power
n:Qload:bus1or :bus2MvarGeneral Load, Reactive Power
n:Pcomp:bus1or :bus2MWCompensation (Losses)
n:Qcomp:bus1or :bus2MvarCompensation
n:Pnet:bus1or :bus2MWExternal Networks, Active Power
n:Qnet:bus1or :bus2MvarExternal Networks, Reactive Power
n:Pflow:bus1or :bus2MWPower Flow, Active Power
n:Qflow:bus1or :bus2MvarPower Flow, Reactive Power
n:Pout:bus1or :bus2MWOutgoing Flow, Active Power
n:Qout:bus1or :bus2MvarOutgoing Power, Reactive Power
n:Sout:bus1or :bus2MVAOutgoing Power, Apparent Power
n:cosphiout:bus1or :bus2·Outgoing Power, Power Factor
n:Pbalance:bus1or :bus2MWActive Power Balance (=0)
n:Qbalance:bus1or :bus2MvarReactive Power Balance (=0)
n:LossPdown:bus1or :bus2MWLosses, downstream
n:LossQdown:bus1or :bus2MvarLosses, downstream (Reactive Power)
n:LossPdownload:bus1or :bus2MWLoad losses, downstream
n:LossQdownload:bus1or :bus2MvarLoad losses, downstream
n:LossPdownnoload:bus1or :bus2MWNo load losses, downstream
n:LossQdownnoload:bus1or :bus2MvarNo load losses, downstream
n:du_feed:bus1or :bus2%Difference from voltage at start of feeder
n:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1or :bus2p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1or :bus2kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1or :bus2kV3*U0
n:phiu0:bus1or :bus2degZero-Sequence Voltage, Angle
n:U1:bus1or :bus2kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1or :bus2degPositive-Sequence Voltage, Angle
n:u2:bus1or :bus2p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1or :bus2kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1or :bus2degNegative-Sequence Voltage, Angle
n:U1l:bus1or :bus2kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1or :bus2kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1or :bus2p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1or :bus2kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1or :bus2degNeutral-Ground Voltage, Angle
n:upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bus1or :bus2p.u.Average-Voltage, Magnitude
n:Um:bus1or :bus2kVAverage-Voltage, Magnitude
n:uphtmin:bus1or :bus2p.u.Minimum of Phase Technology dependent Voltage, Magnitude
n:uphtmax:bus1or :bus2p.u.Maximum of Phase Technology dependent Voltage, Magnitude
n:ubfac:bus1or :bus2%Unbalance Factor

ElmLne short-circuit results

Read after ComShc with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:I:bus1or :bus2kAShort-Circuit Current, Magnitude
m:phii:bus1or :bus2degPhase Current, Angle
m:i1:bus1or :bus2p.u.Positive-Sequence Current, Magnitude
m:I1:bus1or :bus2kAPositive-Sequence Current, Magnitude
m:phii1:bus1or :bus2degPositive-Sequence Current, Angle
m:P:bus1or :bus2MWActive Power
m:Q:bus1or :bus2MvarReactive Power
m:i1P:bus1or :bus2p.u.Positive-Sequence Active Current
m:i1Q:bus1or :bus2p.u.Positive-Sequence Reactive Current
m:I1P:bus1or :bus2kAPositive-Sequence Active Current
m:I1Q:bus1or :bus2kAPositive-Sequence Reactive Current
m:phiui:bus1or :bus2degAngle between Voltage and Current
m:phiu1i1:bus1or :bus2degAngle between Voltage and Current in Positive-Sequence System
m:Tfct:bus1or :bus2sFault Clearing Time
m:Ikss:bus1or :bus2kAInitial Short-Circuit Current
m:ikss:bus1or :bus2p.u.Initial Short-Circuit Current, Magnitude
m:Skss:bus1or :bus2MVAInitial Short-Circuit Power
m:ip:bus1or :bus2kAPeak Short-Circuit Current
m:maxIkss:bus1or :bus2kAMax. Initial Short-Circuit Current
m:maxip:bus1or :bus2kAMax. Peak Short-Circuit Current
m:maxIth:bus1or :bus2kAMax. Thermal equivalent Short-Circuit Current
m:maxIb:bus1or :bus2kAMax. Breaking Current
m:R:bus1or :bus2OhmFault Impedance, Real Part
m:X:bus1or :bus2OhmFault Impedance, Imaginary Part
m:Z:bus1or :bus2OhmFault Impedance, Magnitude
m:phiz:bus1or :bus2degFault Impedance, Angle
m:Rs:bus1or :bus2OhmSource Impedance, Real Part
m:Xs:bus1or :bus2OhmSource Impedance, Imaginary Part
m:Zs:bus1or :bus2OhmSource Impedance, Magnitude
m:phizs:bus1or :bus2degSource Impedance, Angle
m:BrkIpload:bus1or :bus2%Breaker Loading (peak)
m:Ib:bus1or :bus2kAShort-Circuit Breaking Current
m:Sb:bus1or :bus2MVAShort-Circuit Breaking Power
m:Ith:bus1or :bus2kAThermal equivalent Short-Circuit Current
m:zSbase:bus1or :bus2p.u.Fault Impedance, Magnitude
m:XtoR:bus1or :bus2·X/R ratio
m:cosphiui:bus1or :bus2·cosphi
m:BrkIbload:bus1or :bus2%Breaker Loading (breaking)
m:BrkmaxIb:bus1or :bus2kAMax. Breaking Current (breaker time)
m:Ik:bus1or :bus2kASteady-State Short-Circuit Current
m:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, Magnitude
m:phii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:I0:bus1or :bus2kAZero-Sequence Current, Magnitude
m:I0x3:bus1or :bus2kA3*I0
m:phii0:bus1or :bus2degZero-Sequence Current, Angle
m:I2:bus1or :bus2kANegative-Sequence Current, Magnitude
m:phii2:bus1or :bus2degNegative-Sequence Current, Angle
m:P:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:Psum:bus1or :bus2MWTotal Active Power
m:Qsum:bus1or :bus2MvarTotal Reactive Power
m:cosphisum:bus1or :bus2·Total Power Factor
m:P2:bus1or :bus2MWP2
m:Q2:bus1or :bus2MvarQ2
m:P0:bus1or :bus2MWP0
m:phiui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1or :bus2degAngle between Voltage and Current in Zero-Sequence System
m:phiu2i2:bus1or :bus2degAngle between Voltage and Current in Negative-Sequence System
m:TfctPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:Ikss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
m:ikss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Initial Short-Circuit Current, Magnitude
m:Skss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
m:Skssx3:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
m:ip:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
m:Z:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmFault Impedance, Magnitude
m:phiz:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegFault Impedance, Angle
m:Zl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmLine-Line Fault Impedance, Magnitude
m:phizl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Line Fault Impedance, Angle
m:Z0:bus1or :bus2OhmZero-Sequence Fault Impedance, Magnitude
m:phiz0:bus1or :bus2degZero-Sequence Fault Impedance, Angle
m:z0Sbase:bus1or :bus2p.u.Zero-Sequence Fault Impedance, Magnitude
m:cosphiu1i1:bus1or :bus2·Positive-Sequence cosphi
m:I0x3watt:bus1or :bus2kAEarth-Fault Residual Current
m:I0x3var:bus1or :bus2kACapacitive Earth-Fault Current
m:Q0cap:bus1or :bus2MvarQ0 capacitive
m:Rfrel:bus1or :bus2OhmRelay Impedance, Real Part
m:Xfrel:bus1or :bus2OhmRelay Impedance, Imaginary Part
m:Zfrel:bus1or :bus2OhmRelay Impedance, Magnitude
m:phizfrel:bus1or :bus2degRelay Impedance, Angle
m:Zf:bus1or :bus2OhmMeas. Fault Impedance, Magnitude
m:phizf:bus1or :bus2degMeas. Fault Impedance, Angle
c:zlinep.u.Impedance
c:ylinep.u.Admittance
c:loading%Loading
c:curnomkANominal Current
c:rtfac·Temperature Factor
c:InomkANominal Current
c:IthrkARated Short-Time (1s) Current (Conductor)
c:IthrtkkARated Short-Time Current (Tk)
c:IthmaxkAMax. Thermal equivalent Short-Circuit Current
c:zline_1p.u.Impedance (bus1)
c:zline_2p.u.Impedance (bus2)
c:yline_1p.u.Admittance (bus1)
c:yline_2p.u.Admittance (bus2)
c:shclocp.u.Short-Circuit Location
c:rlne_1OhmResistance (bus1)
c:rlne_2OhmResistance (bus2)
c:llne_1HInductance (bus1)
c:llne_2HInductance (bus2)
c:zlp.u.Wave impedance matrix
c:k0r·Earth Factor, Real Part
c:k0i·Earth Factor, Imaginary Part
n:ur:bus1or :bus2p.u.Voltage, Real Part
n:ui:bus1or :bus2p.u.Voltage, Imaginary Part
n:u:bus1or :bus2p.u.Voltage, Magnitude
n:upc:bus1or :bus2%Voltage, Magnitude
n:du:bus1or :bus2%Voltage Deviation
n:U:bus1or :bus2kVLine-Ground Voltage, Magnitude
n:phiu:bus1or :bus2degVoltage, Angle
n:Ul:bus1or :bus2kVLine-Line Voltage, Magnitude
n:u1:bus1or :bus2p.u.Voltage, Magnitude
n:u1pc:bus1or :bus2%Voltage, Magnitude
n:u1r:bus1or :bus2p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1or :bus2p.u.Positive-Sequence Voltage, Imaginary Part
n:Ikss:bus1or :bus2kAInitial Short-Circuit Current
n:I:bus1or :bus2kAShort-Circuit Current
n:phii:bus1or :bus2degPhase Current, Angle
n:Skss:bus1or :bus2MVAInitial Short-Circuit Power
n:ip:bus1or :bus2kAPeak Short-Circuit Current
n:Ib:bus1or :bus2kAShort-Circuit Breaking Current
n:Sb:bus1or :bus2MVAShort-Circuit Breaking Power
n:idc:bus1or :bus2kADecaying Component
n:Ith:bus1or :bus2kAThermal equivalent Short-Circuit Current
n:R1toX1:bus1or :bus2·R1/X1 ratio (Zk")
n:X1toR1:bus1or :bus2·X1/R1 ratio (Zk")
n:R:bus1or :bus2OhmShort-Circuit Impedance, Real Part
n:X:bus1or :bus2OhmShort-Circuit Impedance, Imaginary Part
n:Z:bus1or :bus2OhmShort-Circuit Impedance, Magnitude
n:phiz:bus1or :bus2degShort-Circuit Impedance, Angle
n:urpref:bus1or :bus2p.u.Pre-fault Voltage, Real Part
n:uipref:bus1or :bus2p.u.Pre-fault Voltage, Imaginary Part
n:upref:bus1or :bus2p.u.Pre-fault Voltage, Magnitude
n:uprefpc:bus1or :bus2%Pre-fault Voltage, Magnitude
n:Upref:bus1or :bus2kVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bus1or :bus2kVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bus1or :bus2degPre-fault Voltage, Angle
n:phiui:bus1or :bus2degAngle between Voltage and Current
n:Ithload:bus1or :bus2%Loading, Thermal equivalent Current
n:Ipload:bus1or :bus2%Loading, Peak Short-Circuit Current
n:Ithrtk:bus1or :bus2kARated Short-Time Current (Tk)
n:XtoR:bus1or :bus2·X/R ratio (peak)
n:RtoX:bus1or :bus2·R/X ratio (peak)
n:XtoR_b:bus1or :bus2·X/R ratio (dc)
n:RtoX_b:bus1or :bus2·R/X ratio (dc)
n:fctof_b:bus1or :bus2·Equivalent Frequency fc/f (dc)
n:rSbase:bus1or :bus2p.u.Short-Circuit Impedance, Real Part
n:xSbase:bus1or :bus2p.u.Short-Circuit Impedance, Imaginary Part
n:zSbase:bus1or :bus2p.u.Short-Circuit Impedance, Magnitude
n:Tn:bus1or :bus2msGrid Time Constant
n:Ik:bus1or :bus2kASteady-State Short-Circuit Current
n:cfac:bus1or :bus2·Voltage Factor
n:Iasy:bus1or :bus2kAAsymmetrical Breaking Current
n:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1or :bus2p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1or :bus2kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1or :bus2kV3*U0
n:phiu0:bus1or :bus2degZero-Sequence Voltage, Angle
n:U1:bus1or :bus2kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1or :bus2degPositive-Sequence Voltage, Angle
n:u2:bus1or :bus2p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1or :bus2kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1or :bus2degNegative-Sequence Voltage, Angle
n:U1l:bus1or :bus2kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1or :bus2kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1or :bus2p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1or :bus2kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1or :bus2degNeutral-Ground Voltage, Angle
n:upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:Ikss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
n:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:phii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
n:Skss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
n:Skssx3:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
n:ip:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
n:Ib:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Breaking Current
n:Sb:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVAShort-Circuit Breaking Power
n:Ith:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAThermal equivalent Short-Circuit Current
n:Ithmax:bus1or :bus2kAMax. Thermal equivalent Short-Circuit Current
n:R0:bus1or :bus2OhmZero-Sequence Impedance, Real Part
n:X0:bus1or :bus2OhmZero-Sequence Impedance, Imaginary Part
n:Z0:bus1or :bus2OhmZero-Sequence Impedance, Magnitude
n:phiz0:bus1or :bus2degZero-Sequence Impedance, Angle
n:r0Sbase:bus1or :bus2p.u.Zero-Sequence Impedance, Real Part
n:x0Sbase:bus1or :bus2p.u.Zero-Sequence Impedance, Imaginary Part
n:z0Sbase:bus1or :bus2p.u.Zero-Sequence Impedance, Magnitude
n:R1:bus1or :bus2OhmPositive-Sequence Impedance, Real Part
n:X1:bus1or :bus2OhmPositive-Sequence Impedance, Imaginary Part
n:Z1:bus1or :bus2OhmPositive-Sequence Impedance, Magnitude
n:phiz1:bus1or :bus2degPositive-Sequence Impedance, Angle
n:r1Sbase:bus1or :bus2p.u.Positive-Sequence Impedance, Real Part
n:x1Sbase:bus1or :bus2p.u.Positive-Sequence Impedance, Imaginary Part
n:z1Sbase:bus1or :bus2p.u.Positive-Sequence Impedance, Magnitude
n:R2:bus1or :bus2OhmNegative-Sequence Impedance, Real Part
n:X2:bus1or :bus2OhmNegative-Sequence Impedance, Imaginary Part
n:Z2:bus1or :bus2OhmNegative-Sequence Impedance, Magnitude
n:phiz2:bus1or :bus2degNegative-Sequence Impedance, Angle
n:r2Sbase:bus1or :bus2p.u.Negative-Sequence Impedance, Real Part
n:x2Sbase:bus1or :bus2p.u.Negative-Sequence Impedance, Imaginary Part
n:z2Sbase:bus1or :bus2p.u.Negative-Sequence Impedance, Magnitude
n:R0toX0:bus1or :bus2·R0/X0 ratio (Zk")
n:X0toR0:bus1or :bus2·X0/R0 ratio (Zk")
n:R2toX2:bus1or :bus2·R2/X2 ratio (Zk")
n:X2toR2:bus1or :bus2·X2/R2 ratio (Zk")
n:R:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Ground
n:X:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Ground
n:Z:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Ground
n:phiz:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Ground
n:Rl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Line
n:Xl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Line
n:Zl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Line
n:phizl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Line
n:Rln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Neutral
n:Xln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Neutral
n:Zln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Neutral
n:phizln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Neutral
n:Rn:bus1or :bus2OhmNetwork Resistance, Neutral
n:Xn:bus1or :bus2OhmNetwork Reactance, Neutral
n:Zn:bus1or :bus2OhmNetwork Impedance, Neutral
n:phizn:bus1or :bus2degAngle of Network Impedance, Neutral
n:eff:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only·Earth Fault Factor
n:X0toX1:bus1or :bus2·X0/X1
n:In:bus1or :bus2kANeutral Current, Magnitude
n:phiin:bus1or :bus2degNeutral Current, Angle
n:I0:bus1or :bus2kAZero-Sequence Current, Magnitude
n:I0x3:bus1or :bus2kA3*I0
n:phii0:bus1or :bus2degZero-Sequence Current, Angle
n:I1:bus1or :bus2kAPositive-Sequence Current, Magnitude
n:phii1:bus1or :bus2degPositive-Sequence Current, Angle
n:I2:bus1or :bus2kANegative-Sequence Current, Magnitude
n:phii2:bus1or :bus2degNegative-Sequence Current, Angle
n:urpref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Real Part
n:uipref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Imaginary Part
n:upref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Magnitude
n:uprefpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Pre-fault Voltage, Magnitude
n:Upref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegPre-fault Voltage, Angle
n:phiui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
n:phiu1i1:bus1or :bus2degAngle between Voltage and Current in positive sequence system
n:phiu2i2:bus1or :bus2degAngle between Voltage and Current in negative sequence system
n:phiu0i0:bus1or :bus2degAngle between Voltage and Current in zero-sequence system
n:Ik:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykASteady-State Short-Circuit Current
n:in:bus1or :bus2p.u.Neutral Current, Magnitude
n:i0r:bus1or :bus2p.u.Zero-Sequence Current, Real Part
n:i0i:bus1or :bus2p.u.Zero-Sequence Current, Imaginary Part
n:i0:bus1or :bus2p.u.Zero-Sequence Current, Magnitude
n:i1r:bus1or :bus2p.u.Positive-Sequence Current, Real Part
n:i1i:bus1or :bus2p.u.Positive-Sequence Current, Imaginary Part
n:i1:bus1or :bus2p.u.Positive-Sequence Current, Magnitude
n:i2r:bus1or :bus2p.u.Negative-Sequence Current, Real Part
n:i2i:bus1or :bus2p.u.Negative-Sequence Current, Imaginary Part
n:i2:bus1or :bus2p.u.Negative-Sequence Current, Magnitude

ElmLne rms simulation results

Read after ComInc (RMS) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bus1or :bus2p.u.Voltage, Real Part, referred to network
m:uinet:bus1or :bus2p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1or :bus2p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1or :bus2p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1or :bus2p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1or :bus2kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1or :bus2kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1or :bus2degPositive-Sequence-Voltage, Angle
m:irnet:bus1or :bus2p.u.Current, Real Part, referred to network
m:iinet:bus1or :bus2p.u.Current, Imaginary Part, referred to network
m:inet:bus1or :bus2p.u.Current, Magnitude, referred to network
m:I:bus1or :bus2kACurrent, Magnitude
m:phii:bus1or :bus2degCurrent, Angle
m:i1r:bus1or :bus2p.u.Positive-Sequence Current, Real Part
m:i1i:bus1or :bus2p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1or :bus2p.u.Positive-Sequence Current, Magnitude
m:I1:bus1or :bus2kAPositive-Sequence Current, Magnitude
m:phii1:bus1or :bus2degPositive-Sequence Current, Angle
m:P:bus1or :bus2MWActive Power
m:Q:bus1or :bus2MvarReactive Power
m:S:bus1or :bus2MVAApparent Power
m:cosphi:bus1or :bus2·Power Factor
m:tanphi:bus1or :bus2·tan(phi)
m:Psum:bus1or :bus2MWTotal Active Power
m:Qsum:bus1or :bus2MvarTotal Reactive Power
m:Ssum:bus1or :bus2MVATotal Apparent Power
m:cosphisum:bus1or :bus2·Total Power Factor
m:tanphisum:bus1or :bus2·Total tan(phi)
m:i1P:bus1or :bus2p.u.Positive-Sequence Active Current
m:i1Q:bus1or :bus2p.u.Positive-Sequence Reactive Current
m:I1P:bus1or :bus2kAPositive-Sequence Active Current
m:I1Q:bus1or :bus2kAPositive-Sequence Reactive Current
m:ur:bus1or :bus2p.u.Voltage, Real Part
m:ui:bus1or :bus2p.u.Voltage, Imaginary Part
m:u:bus1or :bus2p.u.Voltage, Magnitude
m:ir:bus1or :bus2p.u.Current, Real Part
m:ii:bus1or :bus2p.u.Current, Imaginary Part
m:i:bus1or :bus2p.u.Current, Magnitude
m:phiui:bus1or :bus2degAngle between Voltage and Current
m:phiu1i1:bus1or :bus2degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1or :bus2sFault Clearing Time
m:Brkload:bus1or :bus2%Breaker Loading
m:Spu:bus1or :bus2MVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bus1or :bus2p.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bus1or :bus2degZero-Sequence-Voltage, Angle
m:u2:bus1or :bus2p.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bus1or :bus2degNegative-Sequence-Voltage, Angle
m:irnet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:iinet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:inet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bus1or :bus2p.u.Zero-Sequence Current, Real Part
m:i0i:bus1or :bus2p.u.Zero-Sequence Current, Imaginary Part
m:i0:bus1or :bus2p.u.Zero-Sequence Current, Magnitude
m:I0:bus1or :bus2kAZero-Sequence Current, Magnitude
m:I0x3:bus1or :bus2kA3*I0
m:phii0:bus1or :bus2degZero-Sequence Current, Angle
m:i2r:bus1or :bus2p.u.Negative-Sequence Current, Real Part
m:i2i:bus1or :bus2p.u.Negative-Sequence Current, Imaginary Part
m:i2:bus1or :bus2p.u.Negative-Sequence Current, Magnitude
m:I2:bus1or :bus2kANegative-Sequence Current, Magnitude
m:phii2:bus1or :bus2degNegative-Sequence Current, Angle
m:P:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only·Power Factor
m:tanphi:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only·tan(phi)
m:Pln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bus1or :bus2MWPositive Sequence Active Power
m:Q1:bus1or :bus2MvarPositive Sequence Reactive Power
m:P2:bus1or :bus2MWNegative Sequence Active Power
m:Q2:bus1or :bus2MvarNegative Sequence Reactive Power
m:P0:bus1or :bus2MWZero Sequence Active Power
m:Q0:bus1or :bus2MvarZero Sequence Reactive Power
m:i2P:bus1or :bus2p.u.Negative-Sequence Active Current
m:i2Q:bus1or :bus2p.u.Negative-Sequence Reactive Current
m:I2P:bus1or :bus2kANegative-Sequence Active Current
m:I2Q:bus1or :bus2kANegative-Sequence Reactive Current
m:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1or :bus2degAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bus1or :bus2degAngle between Voltage and Current in negative sequence system
m:TfctPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Breaker Loading
c:zlinep.u.Impedance
c:ylinep.u.Admittance
c:frnomHzNominal frequency
c:hpirad/sNominal angular frequency
c:loading%Loading
c:CloadMvarCapacitive Losses
c:GloadkWActive no load losses
c:LosseskWLosses
c:curnomkANominal Current
c:rtfac·Temperature Factor
c:zlp.u.Wave Impedance
c:InomkANominal Current
c:a·Damping constant
c:tausDelay Time
c:glneSConductance
c:clneFLine Capacitance
c:RsOhmResistance
c:LsHInductance
c:rlneOhmActive Resistance
c:zline_1p.u.Impedance (bus1)
c:zline_2p.u.Impedance (bus2)
c:yline_1p.u.Admittance (bus1)
c:yline_2p.u.Admittance (bus2)
c:shclocp.u.Short-Circuit Location
c:PcompkWCompensation Losses
c:QcompMvarReactive Power, Compensation
c:Qcomp_iMvarReactive Power, Compensation i
c:Qcomp_jMvarReactive Power, Compensation j
c:zl1p.u.Characteristic Impedance, 1.-Sequ.
c:a1p.u.Propagation factor, 1.-Sequ.
c:phizl1degCharacteristic Impedance, Angle, 1.-Sequ.
c:phia1degPropagation factor, Angle, 1.-Sequ.
c:zl1appp.u.Characteristic Impedance, 1.-Sequ., approx.
c:a1appp.u.Propagation factor, 1.-Sequ., approx.
c:phizl1appdegCharacteristic Impedance, Angle, 1.-Sequ., approx.
c:phia1appdegPropagation factor, Angle, 1.-Sequ., approx.
c:llneHInductance
c:rlne_1OhmActive Resistance (bus1)
c:glne_1SConductance (bus1)
c:rlne_2OhmActive Resistance (bus2)
c:glne_2SConductance (bus2)
c:llne_1HInductance (bus1)
c:clne_1FLine Capacitance (bus1)
c:llne_2HInductance (bus2)
c:clne_2FLine Capacitance (bus2)
c:loadingPh%Loading
c:loadingPh:Aper phase :A, :B, :C, unbalanced only%Loading
c:CloadPhMvarCapacitive Losses
c:CloadPh:Aper phase :A, :B, :C, unbalanced onlyMvarCapacitive Losses
c:GloadPhkWActive no load losses
c:GloadPh:Aper phase :A, :B, :C, unbalanced onlykWActive no load losses
c:LossesPhkWLosses
c:LossesPh:Aper phase :A, :B, :C, unbalanced onlykWLosses
c:Pcomp_ikWCompensation Losses, i
c:Pcomp_jkWCompensation Losses, j
c:zl0OhmCharacteristic Impedance, 0.-Sequ.
c:a0p.u.Propagation factor, 0.-Sequ.
c:phizl0degCharacteristic Impedance, Angle, 0.-Sequ.
c:phia0degPropagation factor, Angle, 0.-Sequ.
c:zl0appp.u.Characteristic Impedance, 0.-Sequ., approx.
c:a0appp.u.Propagation factor, 0.-Sequ., approx.
c:phizl0appdegCharacteristic Impedance, Angle, 0.-Sequ., approx.
c:phia0appdegPropagation factor, Angle, 0.-Sequ., approx.
n:ur:bus1or :bus2p.u.Voltage, Real Part
n:ui:bus1or :bus2p.u.Voltage, Imaginary Part
n:u:bus1or :bus2p.u.Voltage, Magnitude
n:upc:bus1or :bus2%Voltage, Magnitude
n:du:bus1or :bus2%Voltage Deviation
n:U:bus1or :bus2kVLine-Ground Voltage, Magnitude
n:phiu:bus1or :bus2degVoltage, Angle
n:phiurel:bus1or :bus2degVoltage, Relative Angle
n:Ul:bus1or :bus2kVLine-Line Voltage, Magnitude
n:u1:bus1or :bus2p.u.Voltage, Magnitude
n:u1pc:bus1or :bus2%Voltage, Magnitude
n:u1r:bus1or :bus2p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1or :bus2p.u.Positive-Sequence Voltage, Imaginary Part
n:ishc:bus1or :bus2p.u.Short-Circuit Current, magnitude
n:Ishc:bus1or :bus2kAShort-Circuit Current, magnitude
n:fe:bus1or :bus2p.u.Electrical Frequency
n:dfehz:bus1or :bus2HzDeviation of the El. Frequency
n:fehz:bus1or :bus2HzElectrical Frequency
n:frnom:bus1or :bus2HzNominal Frequency
n:ishcr:bus1or :bus2p.u.Short-Circuit Current, real
n:ishci:bus1or :bus2p.u.Short-Circuit Current, imag
n:dfedt:bus1or :bus2p.u./sDerivative of El. Frequency
n:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1or :bus2p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1or :bus2kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1or :bus2kV3*U0
n:phiu0:bus1or :bus2degZero-Sequence Voltage, Angle
n:U1:bus1or :bus2kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1or :bus2degPositive-Sequence Voltage, Angle
n:u2:bus1or :bus2p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1or :bus2kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1or :bus2degNegative-Sequence Voltage, Angle
n:U1l:bus1or :bus2kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1or :bus2kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1or :bus2p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1or :bus2kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1or :bus2degNeutral-Ground Voltage, Angle
n:upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bus1or :bus2p.u.Average-Voltage, Magnitude
n:Um:bus1or :bus2kVAverage-Voltage, Magnitude
n:ishc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, magnitude
n:Ishc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, magnitude
n:inshc:bus1or :bus2p.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bus1or :bus2kANeutral Short-Circuit Current, magnitude
n:ishcr:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, real
n:ishci:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, imag
s:iLp.u.Line-Current
s:iL1p.u.Line-Current (bus1)
s:iL2p.u.Line-Current (bus2)

ElmLne emt simulation results

Read after ComInc (EMT) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:u0:bus1or :bus2p.u.Zero-Sequence-Voltage
m:u1r:bus1or :bus2p.u.Voltage Phasor, Real Part
m:u1i:bus1or :bus2p.u.Voltage Phasor, Imaginary Part
m:u1:bus1or :bus2p.u.Voltage Phasor, Magnitude
m:U1:bus1or :bus2kVLine-Ground Voltage Phasor, Magnitude
m:U1l:bus1or :bus2kVLine-Line Voltage Phasor, Magnitude
m:phiu1:bus1or :bus2degVoltage Phasor, Angle
m:inet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, referred to network
m:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAPhase Current
m:i0:bus1or :bus2p.u.Zero-Sequence Current
m:I0:bus1or :bus2kAZero-Sequence Current
m:I0x3:bus1or :bus2kA3*I0
m:i1r:bus1or :bus2p.u.Current Phasor, Real Part
m:i1i:bus1or :bus2p.u.Current Phasor, Imaginary Part
m:i1:bus1or :bus2p.u.Current Phasor, Magnitude
m:I1:bus1or :bus2kACurrent Phasor, Magnitude
m:phii1:bus1or :bus2degCurrent Phasor, Angle
m:P:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Psum:bus1or :bus2MWPower-Phasor, Active Power
m:Qsum:bus1or :bus2MvarPower Phasor, Reactive Part
m:Ssum:bus1or :bus2MVAPower Phasor, Apparent Power
m:i1P:bus1or :bus2p.u.Current Phasor, Active Current
m:i1Q:bus1or :bus2p.u.Current Phasor, Reactive Current
m:I1P:bus1or :bus2kACurrent Phasor, Active Current
m:I1Q:bus1or :bus2kACurrent Phasor, Reactive Current
m:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
m:i:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current
m:phiu1i1:bus1or :bus2degAngle between Voltage and Current Phasor
m:Tfct:bus1or :bus2sFault Clearing Time
m:TfctPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:unet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, referred to network
m:cosphi1:bus1or :bus2·Power-Phasor, Power-Factor
c:frnomHzNominal frequency
c:hpirad/sNominal angular frequency
c:loading%Loading
c:LosseskWLosses
c:curnomkAgline1_l
c:rtfac·Temperature Factor
c:zlOhm/kmclne_1
c:a·z1_2
c:tausz1_2
c:glneSConductance
c:clneFLine Capacitance
c:RsOhmResistance
c:LsHInductance
c:rlneOhmActive Resistance
c:shclocp.u.Short-Circuit Location
c:rline1_lp.u.Resistance matrix
c:lline1_lp.u.Inductance matrix
c:gline1_lp.u.Conductance matrix
c:cline1_lp.u.Capacitance matrix
c:rline2_lp.u.Resistance matrix
c:lline2_lp.u.Inductance matrix
c:gline2_lp.u.Conductance matrix
c:cline2_lp.u.Capacitance matrix
c:rline_lp.u.Resistance matrix
c:lline_lp.u.Inductance matrix
c:gline_lp.u.Conductance matrix
c:cline_lp.u.Capacitance matrix
c:llneHInductance
c:rlne_1OhmActive Resistance (bus1)
c:glne_1SConductance (bus1)
c:rlne_2OhmActive Resistance (bus2)
c:glne_2SConductance (bus2)
c:llne_1HInductance (bus1)
c:clne_1FLine Capacitance (bus1)
c:llne_2HInductance (bus2)
c:clne_2FLine Capacitance (bus2)
n:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
n:upc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Phase Voltage
n:U:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVPhase Voltage
n:ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage
n:ulpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Line Voltage
n:Ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage
n:u0:bus1or :bus2p.u.Zero-Sequence-Voltage
n:U0:bus1or :bus2kVZero-Sequence-Voltage
n:U0x3:bus1or :bus2kV3*U0
n:u1:bus1or :bus2p.u.Voltage Phasor, Magnitude
n:u1pc:bus1or :bus2%Voltage Phasor, Magnitude
n:u1r:bus1or :bus2p.u.Voltage Phasor, Real Part
n:u1i:bus1or :bus2p.u.Voltage Phasor, Imaginary Part
n:U1:bus1or :bus2kVVoltage Phasor, Magnitude
n:phiu1:bus1or :bus2degVoltage Phasor, Angle
n:U1l:bus1or :bus2kVLine-Line Voltage Phasor, Magnitude
n:uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage
n:Uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage
n:un:bus1or :bus2p.u.Neutral-Ground Voltage
n:Un:bus1or :bus2kVNeutral-Ground Voltage
n:ishc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current
n:Ishc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:inshc:bus1or :bus2p.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bus1or :bus2kANeutral Short-Circuit Current, magnitude
n:fe:bus1or :bus2p.u.Electrical Frequency
n:dfehz:bus1or :bus2HzDeviation of the El. Frequency
n:fehz:bus1or :bus2HzElectrical Frequency
n:frnom:bus1or :bus2HzNominal Frequency
s:iLA_1p.u.Current through inductance 1, Phase A
s:iLB_1p.u.Current through inductance 1, Phase B
s:iLA_2p.u.Current through inductance 2, Phase A
s:iLB_2p.u.Current through inductance 2, Phase B
s:iLAp.u.Current through inductance, Phase A
s:iLBp.u.Current through inductance, Phase B
s:iLCp.u.Current through inductance, Phase C
s:iLp.u.Current through inductance
s:iLNp.u.Current through inductance, Phase N
s:iL1p.u.Line-Current (bus1)
s:iL2p.u.Line-Current (bus2)
s:iL_1p.u.Current through inductance 1
s:iL_2p.u.Current through inductance 2
s:iLC_1p.u.Current through inductance 1, Phase C
s:iLC_2p.u.Current through inductance 2, Phase C
s:iLN_1p.u.Current through inductance 1, Phase N
s:iLN_2p.u.Current through inductance 2, Phase N

ElmLne dc load flow results

Read after ComLdf (DC) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:P:bus1or :bus2MWActive Power
m:Q:bus1or :bus2MvarReactive Power
c:zlinep.u.zline
c:ylinep.u.yline
c:frnomHzNominal frequency
c:hpirad/sNominal angular frequency
c:loading%Loading
c:maxload%Max. Loading
c:curnomkANominal Current
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:zlp.u.Wave Impedance
c:ncust·Number of Customers
c:ildlv·Line Loads Present
c:SldlvkVALoad, Apparent Power
c:PldlvkWLoad, Active Power
c:QldlvkvarLoad, Reactive Power
c:IldlvALoad, Current
c:cosphildlvkLoad, Power Factor
c:SlMVALoad, variable Part, Apparent Power
c:glneSAdmittance
c:rlneOhmActive Resistance
c:zline_1p.u.Impedance (bus1)
c:zline_2p.u.Impedance (bus2)
c:yline_1p.u.Admittance (bus1)
c:yline_2p.u.Admittance (bus2)
c:shclocp.u.Short-Circuit Location
c:dphiudegVoltage Drop Angle
c:zl1p.u.Characteristic Impedance, 1.-Sequ.
c:a1p.u.Propagation factor, 1.-Sequ.
c:phizl1degCharacteristic Impedance, Angle, 1.-Sequ.
c:phia1degPropagation factor, Angle, 1.-Sequ.
c:maxloadpup.u.Max. Loading
c:ldcosphi·Load, Variable Part, Power Factor
c:posld·Weighted Load Position
c:rlne_1OhmActive Resistance (bus1)
c:glne_1SAdmittance (bus1)
c:rlne_2OhmActive Resistance (bus2)
c:glne_2SAdmittance (bus2)
n:u:bus1or :bus2p.u.Voltage, Magnitude
n:upc:bus1or :bus2%Voltage, Magnitude
n:U:bus1or :bus2kVLine-Ground Voltage, Magnitude
n:phiu:bus1or :bus2degVoltage, Angle
n:phiurel:bus1or :bus2degVoltage, Relative Angle
n:Ul:bus1or :bus2kVLine-Line Voltage, Magnitude
n:u1:bus1or :bus2p.u.Voltage, Magnitude
n:Pgen:bus1or :bus2MWGeneration, Active Power
n:Pmot:bus1or :bus2MWMotor Load, Active Power
n:Pload:bus1or :bus2MWGeneral Load, Active Power
n:Pcomp:bus1or :bus2MWCompensation (Losses)
n:Pnet:bus1or :bus2MWExternal Networks, Active Power
n:Pflow:bus1or :bus2MWPower Flow, Active Power

Read after ComMod with GetAttribute. c: calculation parameter, s: signal (state or model variable).

AttributeUnitDescription
c:zlinep.u.Impedance
c:ylinep.u.Admittance
c:frnomHzNominal frequency
c:hpirad/sNominal angular frequency
c:loading%Loading
c:CloadMvarCapacitive Losses
c:GloadkWActive no load losses
c:LosseskWLosses
c:curnomkANominal Current
c:rtfac·Temperature Factor
c:zlp.u.Wave Impedance
c:InomkANominal Current
c:a·Damping constant
c:tausDelay Time
c:glneSConductance
c:clneFLine Capacitance
c:RsOhmResistance
c:LsHInductance
c:rlneOhmActive Resistance
c:zline_1p.u.Impedance (bus1)
c:zline_2p.u.Impedance (bus2)
c:yline_1p.u.Admittance (bus1)
c:yline_2p.u.Admittance (bus2)
c:shclocp.u.Short-Circuit Location
c:PcompkWCompensation Losses
c:QcompMvarReactive Power, Compensation
c:Qcomp_iMvarReactive Power, Compensation i
c:Qcomp_jMvarReactive Power, Compensation j
c:zl1p.u.Characteristic Impedance, 1.-Sequ.
c:a1p.u.Propagation factor, 1.-Sequ.
c:phizl1degCharacteristic Impedance, Angle, 1.-Sequ.
c:phia1degPropagation factor, Angle, 1.-Sequ.
c:zl1appp.u.Characteristic Impedance, 1.-Sequ., approx.
c:a1appp.u.Propagation factor, 1.-Sequ., approx.
c:phizl1appdegCharacteristic Impedance, Angle, 1.-Sequ., approx.
c:phia1appdegPropagation factor, Angle, 1.-Sequ., approx.
c:llneHInductance
c:rlne_1OhmActive Resistance (bus1)
c:glne_1SConductance (bus1)
c:rlne_2OhmActive Resistance (bus2)
c:glne_2SConductance (bus2)
c:llne_1HInductance (bus1)
c:clne_1FLine Capacitance (bus1)
c:llne_2HInductance (bus2)
c:clne_2FLine Capacitance (bus2)
s:iLp.u.Line-Current
s:iL1p.u.Line-Current (bus1)
s:iL2p.u.Line-Current (bus2)

ElmLne optimal power flow results

Read after ComOpf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:bus1or :bus2p.u.Voltage, Real Part, referred to network
m:uinet:bus1or :bus2p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1or :bus2p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1or :bus2p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1or :bus2p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1or :bus2kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1or :bus2kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1or :bus2degPositive-Sequence-Voltage, Angle
m:irnet:bus1or :bus2p.u.Current, Real Part, referred to network
m:iinet:bus1or :bus2p.u.Current, Imaginary Part, referred to network
m:inet:bus1or :bus2p.u.Current, Magnitude, referred to network
m:I:bus1or :bus2kACurrent, Magnitude
m:phii:bus1or :bus2degCurrent, Angle
m:i1r:bus1or :bus2p.u.Positive-Sequence Current, Real Part
m:i1i:bus1or :bus2p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1or :bus2p.u.Positive-Sequence Current, Magnitude
m:I1:bus1or :bus2kAPositive-Sequence Current, Magnitude
m:phii1:bus1or :bus2degPositive-Sequence Current, Angle
m:P:bus1or :bus2MWActive Power
m:Q:bus1or :bus2MvarReactive Power
m:S:bus1or :bus2MVAApparent Power
m:cosphi:bus1or :bus2·Power Factor
m:tanphi:bus1or :bus2·tan(phi)
m:Psum:bus1or :bus2MWTotal Active Power
m:Qsum:bus1or :bus2MvarTotal Reactive Power
m:Ssum:bus1or :bus2MVATotal Apparent Power
m:cosphisum:bus1or :bus2·Total Power Factor
m:tanphisum:bus1or :bus2·Total tan(phi)
m:i1P:bus1or :bus2p.u.Positive-Sequence Active Current
m:i1Q:bus1or :bus2p.u.Positive-Sequence Reactive Current
m:I1P:bus1or :bus2kAPositive-Sequence Active Current
m:I1Q:bus1or :bus2kAPositive-Sequence Reactive Current
m:ur:bus1or :bus2p.u.Voltage, Real Part
m:ui:bus1or :bus2p.u.Voltage, Imaginary Part
m:u:bus1or :bus2p.u.Voltage, Magnitude
m:ir:bus1or :bus2p.u.Current, Real Part
m:ii:bus1or :bus2p.u.Current, Imaginary Part
m:i:bus1or :bus2p.u.Current, Magnitude
m:phiui:bus1or :bus2degAngle between Voltage and Current
m:phiu1i1:bus1or :bus2degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1or :bus2sFault Clearing Time
m:Brkload:bus1or :bus2%Breaker Loading
m:Spu:bus1or :bus2MVA/p.u.Apparent Power per p.u. Voltage
c:zlinep.u.Impedance
c:ylinep.u.Admittance
c:frnomHzNominal frequency
c:hpirad/sNominal angular frequency
c:loading%Loading
c:CloadMvarCapacitive Losses
c:GloadkWActive no load losses
c:LosseskWLosses
c:maxload%Max. Loading
c:curnomkANominal Current
c:rtfac·Temperature Factor
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:ImaxkAMaximum Current
c:dup.u.Voltage Drop
c:dupc%Voltage Drop
c:zlp.u.Wave Impedance
c:ncust·Number of Customers
c:ildlv·Line Loads Present
c:SldlvkVALoad, Apparent Power
c:PldlvkWLoad, Active Power
c:QldlvkvarLoad, Reactive Power
c:IldlvALoad, Current
c:cosphildlvkLoad, Power Factor
c:SlMVALoad, variable Part, Apparent Power
c:glneSAdmittance
c:rlneOhmActive Resistance
c:zline_1p.u.Impedance (bus1)
c:zline_2p.u.Impedance (bus2)
c:yline_1p.u.Admittance (bus1)
c:yline_2p.u.Admittance (bus2)
c:shclocp.u.Short-Circuit Location
c:dphiudegVoltage Drop Angle
c:du1p.u.Positive Sequence Voltage Drop
c:du1pc%Positive Sequence Voltage Drop
c:dphiu1degPositive Sequence Voltage Drop Angle
c:PcompkWCompensation Losses
c:QcompMvarReactive Power, Compensation
c:Qcomp_iMvarReactive power, Compensation i
c:Qcomp_jMvarReactive power, Compensation j
c:zl1p.u.Characteristic Impedance, 1.-Sequ.
c:a1p.u.Propagation factor, 1.-Sequ.
c:phizl1degCharacteristic Impedance, Angle, 1.-Sequ.
c:phia1degPropagation factor, Angle, 1.-Sequ.
c:maxloadpup.u.Max. Loading
c:ldcosphi·Load, Variable Part, Power Factor
c:posld·Weighted Load Position
c:dUkVVoltage Drop
c:rlne_1OhmActive Resistance (bus1)
c:glne_1SAdmittance (bus1)
c:rlne_2OhmActive Resistance (bus2)
c:glne_2SAdmittance (bus2)
n:ur:bus1or :bus2p.u.Voltage, Real Part
n:ui:bus1or :bus2p.u.Voltage, Imaginary Part
n:u:bus1or :bus2p.u.Voltage, Magnitude
n:upc:bus1or :bus2%Voltage, Magnitude
n:du:bus1or :bus2%Voltage Deviation
n:U:bus1or :bus2kVLine-Ground Voltage, Magnitude
n:phiu:bus1or :bus2degVoltage, Angle
n:phiurel:bus1or :bus2degVoltage, Relative Angle
n:Ul:bus1or :bus2kVLine-Line Voltage, Magnitude
n:u1:bus1or :bus2p.u.Voltage, Magnitude
n:u1pc:bus1or :bus2%Voltage, Magnitude
n:u1r:bus1or :bus2p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1or :bus2p.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bus1or :bus2MWGeneration, Active Power
n:Qgen:bus1or :bus2MvarGeneration, Reactive Power
n:Pmot:bus1or :bus2MWMotor Load, Active Power
n:Qmot:bus1or :bus2MvarMotor Load, Reactive Power
n:Pload:bus1or :bus2MWGeneral Load, Active Power
n:Qload:bus1or :bus2MvarGeneral Load, Reactive Power
n:Pcomp:bus1or :bus2MWCompensation (Losses)
n:Qcomp:bus1or :bus2MvarCompensation
n:Pnet:bus1or :bus2MWExternal Networks, Active Power
n:Qnet:bus1or :bus2MvarExternal Networks, Reactive Power
n:Pflow:bus1or :bus2MWPower Flow, Active Power
n:Qflow:bus1or :bus2MvarPower Flow, Reactive Power
n:Pout:bus1or :bus2MWOutgoing Flow, Active Power
n:Qout:bus1or :bus2MvarOutgoing Power, Reactive Power
n:Sout:bus1or :bus2MVAOutgoing Power, Apparent Power
n:cosphiout:bus1or :bus2·Outgoing Power, Power Factor
n:Pbalance:bus1or :bus2MWActive Power Balance (=0)
n:Qbalance:bus1or :bus2MvarReactive Power Balance (=0)
n:LossPdown:bus1or :bus2MWLosses, downstream
n:LossQdown:bus1or :bus2MvarLosses, downstream (Reactive Power)
n:LossPdownload:bus1or :bus2MWLoad losses, downstream
n:LossQdownload:bus1or :bus2MvarLoad losses, downstream
n:LossPdownnoload:bus1or :bus2MWNo load losses, downstream
n:LossQdownnoload:bus1or :bus2MvarNo load losses, downstream
n:du_feed:bus1or :bus2%Difference from voltage at start of feeder

ElmLne basic data

b: values are worked out from the input data. Read them; they are not set.

AttributeUnitDescription
b:loc_name·Name
b:i_ohl·Overhead Line/Cable
b:dlinekmLength
b:fline·Derating Factor
b:np_a0·Number of Poles in A0
b:np_a1·Number of Poles in A1
b:np_a2·Number of Poles in A2
b:nz_a0·Number of Zeros in A0
b:nz_a1·Number of Zeros in A1
b:nz_a2·Number of Zeros in A2
b:np_z0·Number of Poles in Zl0
b:np_z1·Number of Poles in Zl1
b:np_z2·Number of Poles in Zl2
b:nz_z0·Number of Zeros in Zl0
b:nz_z1·Number of Zeros in Zl1
b:nz_z2·Number of Zeros in Zl2

Related

← ElmCabsys Cable System · ElmLnesec Line Sub-Section →