ElmLod attributesPowerFactory General Load

Every attribute of the PowerFactory General Load (ElmLod): 199 input parameters and 1129 result variables, with units and meaning. Copy a name into GetAttribute or SetAttribute.

What ElmLod is

A general load. Its P and Q are set on the element; how they change with voltage and frequency is set in the load type (TypLod).

Class
ElmLod, element class
PowerFactory name
General Load
Type
TypLod, through typ_id
Terminal suffix
:bus1 terminal
Attributes
199 input parameters and 1129 result variables, in 7 calculations

Most used ElmLod attributes

AttributeUnitDescriptionWhere
m:P:bus1MWActive PowerLoad flow
m:Q:bus1MvarReactive PowerLoad flow
m:I:bus1kACurrent, MagnitudeLoad flow
pliniMWActive Poweractive power demandinput data
qliniMvarReactive Powerreactive power demandinput data
scale0ยทScaling Factorscaling factorinput data
sliniMVAApparent Powerinput data
cosliniยทPower Factorinput data
outservยทOut of Serviceinput data
typ_idยทTypeinput data

Read and write ElmLod in Python

import powerfactory

app = powerfactory.GetApplication()          # GetApplicationExt() from outside PowerFactory
app.GetFromStudyCase("ComLdf").Execute()      # results exist after a calculation

for load in app.GetCalcRelevantObjects("*.ElmLod"):
    p_bus1 = load.GetAttribute("m:P:bus1")        # Active Power, MW
    q_bus1 = load.GetAttribute("m:Q:bus1")        # Reactive Power, Mvar
    print(load.loc_name, p_bus1, q_bus1)

load = app.GetCalcRelevantObjects("*.ElmLod")[0]
load.SetAttribute("plini", 140)               # demand 140 MW
  • A result at a terminal of the general load needs the terminal in its name: m:P:bus1, not m:P, which raises AttributeError.
  • An input parameter is read and written with or without its e: prefix: GetAttribute("outserv") and GetAttribute("e:outserv") give the same value.
  • RMS and EMT variables change over time: record them in a results object (ElmRes) to read the whole curve. GetAttribute after a run gives the value at the last time step.

ElmLod input parameters

The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.

AttributeUnitDescription
loc_nameยทName
chr_nameยทCharacteristic Name
for_nameยทForeign Key
dat_srcยทData source
mode_inpยทInput Mode
sernumยทSerial Number
commissionDateยทCommissioning Date
appr_modbyยทModified by
classifยทLoad Classification
outservยทOut of Service
i_symยทBalanced/Unbalanced
constrยทYear of Construction
appr_statusยทStatus
icurrefยทHarmonic currents referred to
OptCostยทUnit
NrCustยทNumber of connected customers
i_prtyยทPriority
shedยทShedding steps
i_scaleยทAdjusted by Load Scaling
i_piniยทEstimate Active Power
i_qiniยทEstimate Reactive Power
i_scaleiniยทEstimate Scaling Factor
i_remยทRemote Control
iSheddingยทAllow load shedding
isCtrlLdShedยทAllow load shedding
ctrlUsageยทLoad shedding
iecfltcontยทFault Contribution
iecShcModelยทShort-Circuit Model
iLoadTrfยทConsider Load Transformer
i_normPQextยทPext, Qext input signals normalised to load flow voltage
LTCยทLTC flag , LTC
iAstabintยทA-stable integration algorithm
pliniMWActive Power
qliniMvarReactive Power
plinirMWActive Power
qlinirMvarReactive Power
plinisMWActive Power
qlinisMvarReactive Power
plinitMWActive Power
qlinitMvarReactive Power
scale0ยทScaling Factor
u0qvrefp.u.Reference voltage
Q0qvrefMvarQ reference
pcontractMWContracted Active Power
u0p.u.Voltage
fSCDFยทScaling factor
trans%Transferable
shedcostUSD/MVAhCosts for load shedding
shedmax%Max. load shedding
shedmin%Min. load shedding
SkssMVA/MWSubtransient Short-Circuit Level
SksMVA/MWTransient Short-Circuit Level
rtoxยทR to X'' ratio
SkssfixMVASubtransient Short-Circuit Level
SksfixMVATransient Short-Circuit Level
SkssfixminMVASubtransient Short-Circuit Level
SksfixminMVATransient Short-Circuit Level
rtoxminยทR to X'' ratio
StratMVARated Power
r0p.u.r0
x0p.u.x0
xt%Load Transformer Reactance
Bc_hvMvarHV Capacitance
Bc_lvMvarAdditional LV Capacitance
Vminp.u.LTC Vmin, Vmin
Vmaxp.u.LTC Vmax, Vmax
Bssp.u.Shunt capacitor at LV bus, Bss
Rfdrp.u.Feeder R, Rfdr
Xfdrp.u.Feeder X, Xfdr
FbยทFraction of feeder Q-comp., Fb
FmaยทMotor A fraction
FmbยทMotor B fraction
FmcยทMotor C fraction
FmdยทMotor D fraction
FelยทElectronic load fraction
GPSlatdegLatitude / Northing
GPSlondegLongitude / Easting
curativeLim%Max. curative power deviation
curativeCostsUSD/MVAhCosts for curative power deviation
dudropLVfeed%Maximum Voltage Drop (LV Grid)
duriseLVfeed%Maximum Voltage Rise (LV Grid)
dpl1ยทdpl1
dpl2ยทdpl2
dpl3ยทdpl3
dpl4ยทdpl4
dpl5ยทdpl5
appr_modifยทModified
cimRdfIdยทRDF ID
descยทDescription
fold_idยทIn Folder
typ_idยทTypeObject: TypLod,TypLodind,TypLodwecc
bus1ยทTerminalObject: StaCubic
pQPcurveยทQ(P)-CurveObject: IntQpcurve
pQVcurveยทQ(V)-CurveObject: IntQvcurve
doc_idยทAdditional Data
pOwnerยทOwnerObject: ElmOwner
pOperatorยทOperatorObject: ElmOperator
phmcยทHarmonic CurrentsObject: TypHmccur,TypHmcopcur
pSCDFยทTariffObject: IntTariffenergy,IntTarifftime,ChaVec
pTransยทAlternative Supply (Load)Object: ElmLod,ElmLodlv,ElmLodmv
p_cubยทControlled Branch (Cubicle)Object: StaCubic*
cpHeadFoldยทHead Folder
bus1_barยทTerminal
cpGridยทGridObject: ElmNet
cpZoneยทZoneObject: ElmZone
cpAreaยทAreaObject: ElmArea
cpFeedยทFeederObject: ElmFeeder
ciDistยทDistance from infeed in number of buses
ciLaterยทLateral Index
ciDistRootยทDistance from first infeed in number of buses
ciDistAllยทDistance from infeed in number of buses including switches
ciDistAllRootยทDistance from first infeed in number of buses including switches
cpOwnerยทOwnerObject: ElmOwner
cpOperatorยทOperatorObject: ElmOperator
cpBranchยทBranchObject: ElmBranch
cpSiteยทSiteObject: ElmSite
cpSubstatยทSubstationObject: ElmSubstat,ElmTrfstat
cpMeteostatยทMeteo StationObject: ElmMeteostat
ciOutagedยทPlanned Outage
ciEnergizedยทEnergized
ciEarthedยทEarthed
cDisplayNameยทDisplay Name
cpSupplyTransformerยทSupplying TransformerObject: ElmTr?,ElmTrmult
cpSupplyTrfStationยทSupplying Secondary SubstationObject: ElmTrfstat
cpSupplySubstationยทSupplying SubstationObject: ElmSubstat
sliniMVAApparent Power
cosliniยทPower Factor
ilinikACurrent
pf_recapยทPower Factor
p_direcยทPower Direction
slinirMVAApparent Power
coslinirยทPower Factor
ilinirkACurrent
pf_recaprยทPower Factor
p_direcrยทPower Direction
slinisMVAApparent Power
coslinisยทPower Factor
iliniskACurrent
pf_recapsยทPower Factor
p_direcsยทPower Direction
slinitMVAApparent Power
coslinitยทPower Factor
ilinitkACurrent
pf_recaptยทPower Factor
p_directยทPower Direction
av_modeยทLocal Controller
q0qvrefp.u.Q reference
phtechยทTechnology
InomkANominal Current
cTypHmcยทType of harmonic sources
IratedkARated Current
cTrans%Resulting
cEstPhasesยทEstimate phases
plini_aMWP(act.)
qlini_aMvarQ(act.)
slini_aMVAS(act.)
coslini_aยทcos(phi)(act.)
ilini_akAI(act.)
scale0_aยทScaling Factor(act.)
zonefactยทZone Scaling Factor
qdslCtrlยทQuasi-Dynamic ModelObject: ElmQdsl
plinir_aMWPh 1
qlinir_aMvarPh 1
slinir_aMVAPh 1
coslinir_aยทPh 1
ilinir_akAPh 1
plinis_aMWPh 2
qlinis_aMvarPh 2
slinis_aMVAPh 2
coslinis_aยทPh 2
ilinis_akAPh 2
plinit_aMWPh 3
qlinit_aMvarPh 3
slinit_aMVAPh 3
coslinit_aยทPh 3
ilinit_akAPh 3
IksskA/MWSubtransient Short-Circuit Current
IkskA/MWTransient Short-Circuit Current
xtorยทX'' to R ratio
IkssfixkASubtransient Short-Circuit Level
IksfixkATransient Short-Circuit Level
IkssfixminkASubtransient Short-Circuit Level
IksfixminkATransient Short-Circuit Level
xtorminยทX'' to R ratio
cBasedOnMVAbased on
ctotSkssMVATotal contribution (subtransient)
ctotSksMVATotal contribution (transient)
ctotIksskATotal contribution (subtransient)
ctotIkskATotal contribution (transient)
ctotSkssminMVATotal contribution (subtransient)
ctotSksminMVATotal contribution (transient)
ctotIkssminkATotal contribution (subtransient)
ctotIksminkATotal contribution (transient)
r2Sbasepup.u.r2(shc) (Sbase)
x2Sbasepup.u.x2(shc) (Sbase)
r1Sbasepup.u.r1(shc) (Sbase)
x1ssSbasepup.u.x1''(shc) (Sbase)
x1sSbasepup.u.x1'(shc) (Sbase)
ramp_typeยทAllow Load-Ramp Event

ElmLod load flow results

Read after ComLdf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bus1p.u.Voltage, Real Part, referred to network
m:uinet:bus1p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1degPositive-Sequence-Voltage, Angle
m:irnet:bus1p.u.Current, Real Part, referred to network
m:iinet:bus1p.u.Current, Imaginary Part, referred to network
m:inet:bus1p.u.Current, Magnitude, referred to network
m:I:bus1kACurrent, Magnitude
m:phii:bus1degCurrent, Angle
m:i1r:bus1p.u.Positive-Sequence Current, Real Part
m:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:S:bus1MVAApparent Power
m:cosphi:bus1ยทPower Factor
m:tanphi:bus1ยทtan(phi)
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:Ssum:bus1MVATotal Apparent Power
m:cosphisum:bus1ยทTotal Power Factor
m:tanphisum:bus1ยทTotal tan(phi)
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:ur:bus1p.u.Voltage, Real Part
m:ui:bus1p.u.Voltage, Imaginary Part
m:u:bus1p.u.Voltage, Magnitude
m:ir:bus1p.u.Current, Real Part
m:ii:bus1p.u.Current, Imaginary Part
m:i:bus1p.u.Current, Magnitude
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1sFault Clearing Time
m:Brkload:bus1%Breaker Loading
m:Spu:bus1MVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bus1p.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bus1degZero-Sequence-Voltage, Angle
m:u2:bus1p.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bus1degNegative-Sequence-Voltage, Angle
m:irnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part, referred to network
m:iinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part, referred to network
m:inet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude, referred to network
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bus1p.u.Zero-Sequence Current, Real Part
m:i0i:bus1p.u.Zero-Sequence Current, Imaginary Part
m:i0:bus1p.u.Zero-Sequence Current, Magnitude
m:I0:bus1kAZero-Sequence Current, Magnitude
m:I0x3:bus1kA3*I0
m:phii0:bus1degZero-Sequence Current, Angle
m:i2r:bus1p.u.Negative-Sequence Current, Real Part
m:i2i:bus1p.u.Negative-Sequence Current, Imaginary Part
m:i2:bus1p.u.Negative-Sequence Current, Magnitude
m:I2:bus1kANegative-Sequence Current, Magnitude
m:phii2:bus1degNegative-Sequence Current, Angle
m:ubfacI:bus1%Current Unbalance Factor
m:ubfacS:bus1%Power Unbalance Factor
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bus1:Aper phase :A, :B, :C, unbalanced onlyยทPower Factor
m:tanphi:bus1:Aper phase :A, :B, :C, unbalanced onlyยทtan(phi)
m:Pln:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bus1MWPositive Sequence Active Power
m:Q1:bus1MvarPositive Sequence Reactive Power
m:P2:bus1MWNegative Sequence Active Power
m:Q2:bus1MvarNegative Sequence Reactive Power
m:P0:bus1MWZero Sequence Active Power
m:Q0:bus1MvarZero Sequence Reactive Power
m:i2P:bus1p.u.Negative-Sequence Active Current
m:i2Q:bus1p.u.Negative-Sequence Reactive Current
m:I2P:bus1kANegative-Sequence Active Current
m:I2Q:bus1kANegative-Sequence Reactive Current
m:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1degAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bus1degAngle between Voltage and Current in negative sequence system
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bus1:Aper phase :A, :B, :C, unbalanced only%Breaker Loading
c:frnomHzNominal Frequency
c:hpirad/sNominal angular frequency
c:piniMWNominal Active Power
c:scale0ยทInitial Scale Factor
c:sยทComplex Power (P+jQ)
c:u0p.u.Nominal Voltage
c:kpu0ยทVolt. Dependence I on P
c:kqu0ยทVolt. Dependence I on Q
c:kpu1ยทVolt. Dependence II on P
c:kqu1ยทVolt. Dependence II on Q
c:kpuยทVolt. Dependence III on P
c:kquยทVolt. Dependence III on Q
c:aPยทPercent of Volt. Dep. I on P
c:bPยทPercent of Volt. Dep. II on P
c:aQยทPercent of Volt. Dep. I on Q
c:bQยทPercent of Volt. Dep. II on Q
c:QnomMvarNominal Reactive Power
c:ncustยทNumber of Connected Customers
c:i_remยทRemote Control
c:zonescaleยทZone Scale Factor
c:iRefElementยทReference Element
c:PmismMWActive Power Mismatch
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:qiniMvarNominal Reactive Power
c:PnomMWNominal Active Power
c:PpeakMWPeak Active Power
c:QpeakMvarPeak Reactive Power
c:pMWPower
c:gs0p.u.Conductance
c:bs0p.u.Susceptance
c:xp.u.Reactance
c:rp.u.Resistance
c:slipp.u.Slip
c:srMVAComplex Power (P+jQ), ph. A
c:ssMVAComplex Power (P+jQ), ph. B
c:stMVAComplex Power (P+jQ), ph. C
c:z0p.u.z0
c:priniMWNominal Active Power, ph. A
c:qriniMvarNominal Reactive Power, ph. A
c:psiniMWNominal Active Power, ph. B
c:qsiniMvarNominal Reactive Power, ph. B
c:ptiniMWNominal Active Power, ph. C
c:qtiniMvarNominal Reactive Power, ph. C
c:cnmยทConnection
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bus1MWGeneration, Active Power
n:Qgen:bus1MvarGeneration, Reactive Power
n:Pmot:bus1MWMotor Load, Active Power
n:Qmot:bus1MvarMotor Load, Reactive Power
n:Pload:bus1MWGeneral Load, Active Power
n:Qload:bus1MvarGeneral Load, Reactive Power
n:Pcomp:bus1MWCompensation (Losses)
n:Qcomp:bus1MvarCompensation
n:Pnet:bus1MWExternal Networks, Active Power
n:Qnet:bus1MvarExternal Networks, Reactive Power
n:Pflow:bus1MWPower Flow, Active Power
n:Qflow:bus1MvarPower Flow, Reactive Power
n:Pout:bus1MWOutgoing Flow, Active Power
n:Qout:bus1MvarOutgoing Power, Reactive Power
n:Sout:bus1MVAOutgoing Power, Apparent Power
n:cosphiout:bus1ยทOutgoing Power, Power Factor
n:Pbalance:bus1MWActive Power Balance (=0)
n:Qbalance:bus1MvarReactive Power Balance (=0)
n:LossPdown:bus1MWLosses, downstream
n:LossQdown:bus1MvarLosses, downstream (Reactive Power)
n:LossPdownload:bus1MWLoad losses, downstream
n:LossQdownload:bus1MvarLoad losses, downstream
n:LossPdownnoload:bus1MWNo load losses, downstream
n:LossQdownnoload:bus1MvarNo load losses, downstream
n:du_feed:bus1%Difference from voltage at start of feeder
n:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aper phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1kV3*U0
n:phiu0:bus1degZero-Sequence Voltage, Angle
n:U1:bus1kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1degPositive-Sequence Voltage, Angle
n:u2:bus1p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1degNegative-Sequence Voltage, Angle
n:U1l:bus1kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1degNeutral-Ground Voltage, Angle
n:upht:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bus1p.u.Average-Voltage, Magnitude
n:Um:bus1kVAverage-Voltage, Magnitude
n:uphtmin:bus1p.u.Minimum of Phase Technology dependent Voltage, Magnitude
n:uphtmax:bus1p.u.Maximum of Phase Technology dependent Voltage, Magnitude
n:ubfac:bus1%Unbalance Factor
s:scaleยทScale Factor
s:scalephiradLoad Scaling
s:pini_setMWNominal Active Power
s:qini_setMvarNominal Reactive Power
s:prini_setMWActive Power Setpoint, ph. A
s:qrini_setMvarReactive Power Setpoint, ph. A
s:psini_setMWActive Power Setpoint, ph. B
s:qsini_setMvarReactive Power Setpoint, ph. B
s:ptini_setMWActive Power Setpoint, ph. C
s:qtini_setMvarReactive Power Setpoint, ph. C
s:scalerยทScale Factor, ph. A
s:scalesยทScale Factor, ph. B
s:scaletยทScale Factor, ph. C

ElmLod short-circuit results

Read after ComShc with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:I:bus1kAShort-Circuit Current, Magnitude
m:phii:bus1degPhase Current, Angle
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in Positive-Sequence System
m:Tfct:bus1sFault Clearing Time
m:Ikss:bus1kAInitial Short-Circuit Current
m:ikss:bus1p.u.Initial Short-Circuit Current, Magnitude
m:Skss:bus1MVAInitial Short-Circuit Power
m:ip:bus1kAPeak Short-Circuit Current
m:maxIkss:bus1kAMax. Initial Short-Circuit Current
m:maxip:bus1kAMax. Peak Short-Circuit Current
m:maxIth:bus1kAMax. Thermal equivalent Short-Circuit Current
m:maxIb:bus1kAMax. Breaking Current
m:R:bus1OhmFault Impedance, Real Part
m:X:bus1OhmFault Impedance, Imaginary Part
m:Z:bus1OhmFault Impedance, Magnitude
m:phiz:bus1degFault Impedance, Angle
m:Rs:bus1OhmSource Impedance, Real Part
m:Xs:bus1OhmSource Impedance, Imaginary Part
m:Zs:bus1OhmSource Impedance, Magnitude
m:phizs:bus1degSource Impedance, Angle
m:BrkIpload:bus1%Breaker Loading (peak)
m:Ib:bus1kAShort-Circuit Breaking Current
m:Sb:bus1MVAShort-Circuit Breaking Power
m:Ith:bus1kAThermal equivalent Short-Circuit Current
m:zSbase:bus1p.u.Fault Impedance, Magnitude
m:XtoR:bus1ยทX/R ratio
m:cosphiui:bus1ยทcosphi
m:BrkIbload:bus1%Breaker Loading (breaking)
m:BrkmaxIb:bus1kAMax. Breaking Current (breaker time)
m:Ik:bus1kASteady-State Short-Circuit Current
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, Magnitude
m:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:I0:bus1kAZero-Sequence Current, Magnitude
m:I0x3:bus1kA3*I0
m:phii0:bus1degZero-Sequence Current, Angle
m:I2:bus1kANegative-Sequence Current, Magnitude
m:phii2:bus1degNegative-Sequence Current, Angle
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:cosphisum:bus1ยทTotal Power Factor
m:P2:bus1MWP2
m:Q2:bus1MvarQ2
m:P0:bus1MWP0
m:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1degAngle between Voltage and Current in Zero-Sequence System
m:phiu2i2:bus1degAngle between Voltage and Current in Negative-Sequence System
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:Ikss:bus1:Aper phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
m:ikss:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Initial Short-Circuit Current, Magnitude
m:Skss:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
m:Skssx3:bus1:Aper phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
m:ip:bus1:Aper phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
m:Z:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmFault Impedance, Magnitude
m:phiz:bus1:Aper phase :A, :B, :C, unbalanced onlydegFault Impedance, Angle
m:Zl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmLine-Line Fault Impedance, Magnitude
m:phizl:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Fault Impedance, Angle
m:Z0:bus1OhmZero-Sequence Fault Impedance, Magnitude
m:phiz0:bus1degZero-Sequence Fault Impedance, Angle
m:z0Sbase:bus1p.u.Zero-Sequence Fault Impedance, Magnitude
m:cosphiu1i1:bus1ยทPositive-Sequence cosphi
m:I0x3watt:bus1kAEarth-Fault Residual Current
m:I0x3var:bus1kACapacitive Earth-Fault Current
m:Q0cap:bus1MvarQ0 capacitive
m:Rfrel:bus1OhmRelay Impedance, Real Part
m:Xfrel:bus1OhmRelay Impedance, Imaginary Part
m:Zfrel:bus1OhmRelay Impedance, Magnitude
m:phizfrel:bus1degRelay Impedance, Angle
m:Zf:bus1OhmMeas. Fault Impedance, Magnitude
m:phizf:bus1degMeas. Fault Impedance, Angle
c:RsOhmStatic Resistance
c:i_pureยทPurely inductive/capacitive
c:icsrcยทCurrent Source/Impedance
c:ussยทnormPQext
c:Rp.u.Resistance
c:Lp.u.Inductance
c:Cp.u.Capacitance
c:C_lvp.u.LV-Capacitance
c:y1p.u.Admittance
c:i1p.u.Harmonic current
c:i1iecp.u.Harmonic IEC current
c:zdp.u.Dynamic Impedance
c:zsp.u.Static Impedance
c:RdOhmDynamic Resistance
c:XdOhmDynamic Reactance
c:ZdOhmDynamic Impedance
c:XsOhmStatic Reactance
c:ZsOhmStatic Impedance
c:rnetp.u.Total Resistance
c:xnetp.u.Total Reactance
c:cnยทConnection Mode
c:z0p.u.z0
c:Rap.u.Resistance, Phase a
c:Rbp.u.Resistance, Phase b
c:Rcp.u.Resistance, Phase c
c:Lap.u.Inductance, Phase a
c:Lbp.u.Inductance, Phase b
c:Lcp.u.Inductance, Phase c
c:Cap.u.Capacitance, Phase a
c:Cbp.u.Capacitance, Phase b
c:Ccp.u.Capacitance, Phase c
c:y_ap.u.Admittance, Phase a
c:y_bp.u.Admittance, Phase b
c:y_cp.u.Admittance, Phase c
c:Ca_lvp.u.LV-Capacitance, Phase a
c:Cb_lvp.u.LV-Capacitance, Phase b
c:Cc_lvp.u.LV-Capacitance, Phase c
c:i_abcp.u.Harmonic currents
c:i_abc_iecp.u.Harmonic IEC current
c:i_abp.u.Harmonic currents
c:i_ab_iecp.u.Harmonic IEC current
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:Ikss:bus1kAInitial Short-Circuit Current
n:I:bus1kAShort-Circuit Current
n:phii:bus1degPhase Current, Angle
n:Skss:bus1MVAInitial Short-Circuit Power
n:ip:bus1kAPeak Short-Circuit Current
n:Ib:bus1kAShort-Circuit Breaking Current
n:Sb:bus1MVAShort-Circuit Breaking Power
n:idc:bus1kADecaying Component
n:Ith:bus1kAThermal equivalent Short-Circuit Current
n:R1toX1:bus1ยทR1/X1 ratio (Zk")
n:X1toR1:bus1ยทX1/R1 ratio (Zk")
n:R:bus1OhmShort-Circuit Impedance, Real Part
n:X:bus1OhmShort-Circuit Impedance, Imaginary Part
n:Z:bus1OhmShort-Circuit Impedance, Magnitude
n:phiz:bus1degShort-Circuit Impedance, Angle
n:urpref:bus1p.u.Pre-fault Voltage, Real Part
n:uipref:bus1p.u.Pre-fault Voltage, Imaginary Part
n:upref:bus1p.u.Pre-fault Voltage, Magnitude
n:uprefpc:bus1%Pre-fault Voltage, Magnitude
n:Upref:bus1kVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bus1kVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bus1degPre-fault Voltage, Angle
n:phiui:bus1degAngle between Voltage and Current
n:Ithload:bus1%Loading, Thermal equivalent Current
n:Ipload:bus1%Loading, Peak Short-Circuit Current
n:Ithrtk:bus1kARated Short-Time Current (Tk)
n:XtoR:bus1ยทX/R ratio (peak)
n:RtoX:bus1ยทR/X ratio (peak)
n:XtoR_b:bus1ยทX/R ratio (dc)
n:RtoX_b:bus1ยทR/X ratio (dc)
n:fctof_b:bus1ยทEquivalent Frequency fc/f (dc)
n:rSbase:bus1p.u.Short-Circuit Impedance, Real Part
n:xSbase:bus1p.u.Short-Circuit Impedance, Imaginary Part
n:zSbase:bus1p.u.Short-Circuit Impedance, Magnitude
n:Tn:bus1msGrid Time Constant
n:Ik:bus1kASteady-State Short-Circuit Current
n:cfac:bus1ยทVoltage Factor
n:Iasy:bus1kAAsymmetrical Breaking Current
n:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aper phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1kV3*U0
n:phiu0:bus1degZero-Sequence Voltage, Angle
n:U1:bus1kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1degPositive-Sequence Voltage, Angle
n:u2:bus1p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1degNegative-Sequence Voltage, Angle
n:U1l:bus1kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1degNeutral-Ground Voltage, Angle
n:upht:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:Ikss:bus1:Aper phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
n:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
n:Skss:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
n:Skssx3:bus1:Aper phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
n:ip:bus1:Aper phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
n:Ib:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Breaking Current
n:Sb:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAShort-Circuit Breaking Power
n:Ith:bus1:Aper phase :A, :B, :C, unbalanced onlykAThermal equivalent Short-Circuit Current
n:Ithmax:bus1kAMax. Thermal equivalent Short-Circuit Current
n:R0:bus1OhmZero-Sequence Impedance, Real Part
n:X0:bus1OhmZero-Sequence Impedance, Imaginary Part
n:Z0:bus1OhmZero-Sequence Impedance, Magnitude
n:phiz0:bus1degZero-Sequence Impedance, Angle
n:r0Sbase:bus1p.u.Zero-Sequence Impedance, Real Part
n:x0Sbase:bus1p.u.Zero-Sequence Impedance, Imaginary Part
n:z0Sbase:bus1p.u.Zero-Sequence Impedance, Magnitude
n:R1:bus1OhmPositive-Sequence Impedance, Real Part
n:X1:bus1OhmPositive-Sequence Impedance, Imaginary Part
n:Z1:bus1OhmPositive-Sequence Impedance, Magnitude
n:phiz1:bus1degPositive-Sequence Impedance, Angle
n:r1Sbase:bus1p.u.Positive-Sequence Impedance, Real Part
n:x1Sbase:bus1p.u.Positive-Sequence Impedance, Imaginary Part
n:z1Sbase:bus1p.u.Positive-Sequence Impedance, Magnitude
n:R2:bus1OhmNegative-Sequence Impedance, Real Part
n:X2:bus1OhmNegative-Sequence Impedance, Imaginary Part
n:Z2:bus1OhmNegative-Sequence Impedance, Magnitude
n:phiz2:bus1degNegative-Sequence Impedance, Angle
n:r2Sbase:bus1p.u.Negative-Sequence Impedance, Real Part
n:x2Sbase:bus1p.u.Negative-Sequence Impedance, Imaginary Part
n:z2Sbase:bus1p.u.Negative-Sequence Impedance, Magnitude
n:R0toX0:bus1ยทR0/X0 ratio (Zk")
n:X0toR0:bus1ยทX0/R0 ratio (Zk")
n:R2toX2:bus1ยทR2/X2 ratio (Zk")
n:X2toR2:bus1ยทX2/R2 ratio (Zk")
n:R:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Ground
n:X:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Ground
n:Z:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Ground
n:phiz:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Ground
n:Rl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Line
n:Xl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Line
n:Zl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Line
n:phizl:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Line
n:Rln:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Neutral
n:Xln:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Neutral
n:Zln:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Neutral
n:phizln:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Neutral
n:Rn:bus1OhmNetwork Resistance, Neutral
n:Xn:bus1OhmNetwork Reactance, Neutral
n:Zn:bus1OhmNetwork Impedance, Neutral
n:phizn:bus1degAngle of Network Impedance, Neutral
n:eff:bus1:Aper phase :A, :B, :C, unbalanced onlyยทEarth Fault Factor
n:X0toX1:bus1ยทX0/X1
n:In:bus1kANeutral Current, Magnitude
n:phiin:bus1degNeutral Current, Angle
n:I0:bus1kAZero-Sequence Current, Magnitude
n:I0x3:bus1kA3*I0
n:phii0:bus1degZero-Sequence Current, Angle
n:I1:bus1kAPositive-Sequence Current, Magnitude
n:phii1:bus1degPositive-Sequence Current, Angle
n:I2:bus1kANegative-Sequence Current, Magnitude
n:phii2:bus1degNegative-Sequence Current, Angle
n:urpref:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Real Part
n:uipref:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Imaginary Part
n:upref:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Magnitude
n:uprefpc:bus1:Aper phase :A, :B, :C, unbalanced only%Pre-fault Voltage, Magnitude
n:Upref:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bus1:Aper phase :A, :B, :C, unbalanced onlydegPre-fault Voltage, Angle
n:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
n:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
n:phiu2i2:bus1degAngle between Voltage and Current in negative sequence system
n:phiu0i0:bus1degAngle between Voltage and Current in zero-sequence system
n:Ik:bus1:Aper phase :A, :B, :C, unbalanced onlykASteady-State Short-Circuit Current
n:in:bus1p.u.Neutral Current, Magnitude
n:i0r:bus1p.u.Zero-Sequence Current, Real Part
n:i0i:bus1p.u.Zero-Sequence Current, Imaginary Part
n:i0:bus1p.u.Zero-Sequence Current, Magnitude
n:i1r:bus1p.u.Positive-Sequence Current, Real Part
n:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
n:i1:bus1p.u.Positive-Sequence Current, Magnitude
n:i2r:bus1p.u.Negative-Sequence Current, Real Part
n:i2i:bus1p.u.Negative-Sequence Current, Imaginary Part
n:i2:bus1p.u.Negative-Sequence Current, Magnitude

ElmLod rms simulation results

Read after ComInc (RMS) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bus1p.u.Voltage, Real Part, referred to network
m:uinet:bus1p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1degPositive-Sequence-Voltage, Angle
m:irnet:bus1p.u.Current, Real Part, referred to network
m:iinet:bus1p.u.Current, Imaginary Part, referred to network
m:inet:bus1p.u.Current, Magnitude, referred to network
m:I:bus1kACurrent, Magnitude
m:phii:bus1degCurrent, Angle
m:i1r:bus1p.u.Positive-Sequence Current, Real Part
m:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:S:bus1MVAApparent Power
m:cosphi:bus1ยทPower Factor
m:tanphi:bus1ยทtan(phi)
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:Ssum:bus1MVATotal Apparent Power
m:cosphisum:bus1ยทTotal Power Factor
m:tanphisum:bus1ยทTotal tan(phi)
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:ur:bus1p.u.Voltage, Real Part
m:ui:bus1p.u.Voltage, Imaginary Part
m:u:bus1p.u.Voltage, Magnitude
m:ir:bus1p.u.Current, Real Part
m:ii:bus1p.u.Current, Imaginary Part
m:i:bus1p.u.Current, Magnitude
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1sFault Clearing Time
m:Brkload:bus1%Breaker Loading
m:Spu:bus1MVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bus1p.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bus1degZero-Sequence-Voltage, Angle
m:u2:bus1p.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bus1degNegative-Sequence-Voltage, Angle
m:irnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:iinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:inet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bus1p.u.Zero-Sequence Current, Real Part
m:i0i:bus1p.u.Zero-Sequence Current, Imaginary Part
m:i0:bus1p.u.Zero-Sequence Current, Magnitude
m:I0:bus1kAZero-Sequence Current, Magnitude
m:I0x3:bus1kA3*I0
m:phii0:bus1degZero-Sequence Current, Angle
m:i2r:bus1p.u.Negative-Sequence Current, Real Part
m:i2i:bus1p.u.Negative-Sequence Current, Imaginary Part
m:i2:bus1p.u.Negative-Sequence Current, Magnitude
m:I2:bus1kANegative-Sequence Current, Magnitude
m:phii2:bus1degNegative-Sequence Current, Angle
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bus1:Aper phase :A, :B, :C, unbalanced onlyยทPower Factor
m:tanphi:bus1:Aper phase :A, :B, :C, unbalanced onlyยทtan(phi)
m:Pln:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bus1MWPositive Sequence Active Power
m:Q1:bus1MvarPositive Sequence Reactive Power
m:P2:bus1MWNegative Sequence Active Power
m:Q2:bus1MvarNegative Sequence Reactive Power
m:P0:bus1MWZero Sequence Active Power
m:Q0:bus1MvarZero Sequence Reactive Power
m:i2P:bus1p.u.Negative-Sequence Active Current
m:i2Q:bus1p.u.Negative-Sequence Reactive Current
m:I2P:bus1kANegative-Sequence Active Current
m:I2Q:bus1kANegative-Sequence Reactive Current
m:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1degAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bus1degAngle between Voltage and Current in negative sequence system
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bus1:Aper phase :A, :B, :C, unbalanced only%Breaker Loading
c:hpirad/spini
c:piniMWloddy_l
c:lodst_lยทStatic
c:loddy_lยทDynamic
c:kpfยทStatic Frequency Dependence
c:kqfยทStatic Frequency Dependence
c:t1sDynamic Load Time Constant
c:sd0MVANominal power of dynamic load
c:sd00MVANominal power of dynamic load
c:udmaxp.u.Upper Voltage Limit
c:udminp.u.Lower Voltage Limit
c:fep.u.Electrical Frequency
c:scaleยทbQ
c:lodsp_lยทSpecial
c:tpuยทTransient Voltage Dependence
c:tqusTransient Voltage Dependence
c:ssp0MVANominal power of special load
c:ssp00MVANominal power of special load
c:u0p.u.Nominal voltage
c:i_nlnยทInternal Flag
c:kpu0ยทVolt. Dependence I on P
c:kqu0ยทVolt. Dependence I on Q
c:kpu1ยทVolt. Dependence II on P
c:kqu1ยทVolt. Dependence II on Q
c:kpuยทVolt. Dependence III on P
c:kquยทVolt. Dependence III on Q
c:aPยทPercent of Volt. Dep. I on P
c:bPยทPercent of Volt. Dep. II on P
c:aQยทPercent of Volt. Dep. I on Q
c:bQยทPercent of Volt. Dep. II on Q
c:motorACalLodwecc1pac,CalLodweccasmMotor A
c:motorBCalLodwecc1pac,CalLodweccasmMotor B
c:motorCCalLodwecc1pac,CalLodweccasmMotor C
c:motorDCalLodwecc1pac,CalLodweccasmMotor D
c:Tapp.u.Transformer tap
c:Rfdrp.u.Feeder R (p.u. of MVA base)
c:Xfdrp.u.Feeder X (p.u. of MVA base)
c:Bfdrp.u.Value of the total feeder reactive compensation
c:Vlsp.u.Voltage at substation low-side bus
c:Vldp.u.Voltage at load end of feeder
c:PstยทPst
c:QstยทQst
c:PelยทPel
c:QelยทQel
c:Fv1ยทFv1
c:qiniMvarNominal Reactive Power
c:tpfsTransient Frequency Dependence
c:tqfsTransient Frequency Dependence
c:glodp.u.Conductance
c:gs0p.u.Conductance
c:bs0p.u.Susceptance
c:xp.u.Reactance
c:rp.u.Resistance
c:slipp.u.Slip
c:s0pup.u.Slip at Normal Operation Point
c:scrpup.u.Critical Slip
c:tm00p.u.Ratio of Dynamic Load (Normal Operating Torque)
c:TjsAcceleration time constant
c:i_dynยทi_dyn
c:xmep.u.Electrical Torque
c:xmt0p.u.Initial mechanical torque
c:tm1ยทMechanical Torque Exponent
c:speed0p.u.Initial speed
c:xmtp.u.Mechanical Torque
c:ushedp.u.Voltage setting for load shedding
c:shapeยทShape of Load Shedding Probability Function
c:fshedp.u.Load-Shedding Factor
c:ureclosep.u.Voltage setting for reclosing
c:currrp.u.Rotor Current, Real Part
c:currip.u.Rotor Current, Imaginary Part
c:cnยทConnection Mode
c:srMWComplex Power (P+jQ), ph. A
c:ssMWComplex Power (P+jQ), ph. B
c:stMWComplex Power (P+jQ), ph. C
c:yrp.u.Load Admittance, ph. A
c:ysp.u.Load Admittance, ph. B
c:ytp.u.Load Admittance, ph. C
c:yr0p.u.Load Admittance, ph. A
c:ys0p.u.Load Admittance, ph. B
c:yt0p.u.Load Admittance, ph. C
c:z0p.u.z0
c:FmaยทMotor A fraction
c:FmbยทMotor B fraction
c:FmcยทMotor C fraction
c:FmdยทMotor D fraction
c:FelยทElectronic load fraction
c:FstยทStatic load fraction
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:ishc:bus1p.u.Short-Circuit Current, magnitude
n:Ishc:bus1kAShort-Circuit Current, magnitude
n:fe:bus1p.u.Electrical Frequency
n:dfehz:bus1HzDeviation of the El. Frequency
n:fehz:bus1HzElectrical Frequency
n:frnom:bus1HzNominal Frequency
n:ishcr:bus1p.u.Short-Circuit Current, real
n:ishci:bus1p.u.Short-Circuit Current, imag
n:dfedt:bus1p.u./sDerivative of El. Frequency
n:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aper phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1kV3*U0
n:phiu0:bus1degZero-Sequence Voltage, Angle
n:U1:bus1kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1degPositive-Sequence Voltage, Angle
n:u2:bus1p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1degNegative-Sequence Voltage, Angle
n:U1l:bus1kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1degNeutral-Ground Voltage, Angle
n:upht:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bus1p.u.Average-Voltage, Magnitude
n:Um:bus1kVAverage-Voltage, Magnitude
n:ishc:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, magnitude
n:Ishc:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, magnitude
n:inshc:bus1p.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bus1kANeutral Short-Circuit Current, magnitude
n:ishcr:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, real
n:ishci:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, imag
s:xup.u.State Variable
s:PextMWActive Power Input
s:QextMvarReactive Power Input
s:frefp.u.Reference Frequency
s:xfp.u.State Variable
s:speedp.u.Speed
s:xmdmp.u.MDM-Torque
s:psirrp.u.Rotor Flux, Real Part
s:psirip.u.Rotor Flux, Imaginary Part
s:fshedinp.u.Load-Shedding Factor

ElmLod emt simulation results

Read after ComInc (EMT) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:u0:bus1p.u.Zero-Sequence-Voltage
m:u1r:bus1p.u.Voltage Phasor, Real Part
m:u1i:bus1p.u.Voltage Phasor, Imaginary Part
m:u1:bus1p.u.Voltage Phasor, Magnitude
m:U1:bus1kVLine-Ground Voltage Phasor, Magnitude
m:U1l:bus1kVLine-Line Voltage Phasor, Magnitude
m:phiu1:bus1degVoltage Phasor, Angle
m:inet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, referred to network
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAPhase Current
m:i0:bus1p.u.Zero-Sequence Current
m:I0:bus1kAZero-Sequence Current
m:I0x3:bus1kA3*I0
m:i1r:bus1p.u.Current Phasor, Real Part
m:i1i:bus1p.u.Current Phasor, Imaginary Part
m:i1:bus1p.u.Current Phasor, Magnitude
m:I1:bus1kACurrent Phasor, Magnitude
m:phii1:bus1degCurrent Phasor, Angle
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Psum:bus1MWPower-Phasor, Active Power
m:Qsum:bus1MvarPower Phasor, Reactive Part
m:Ssum:bus1MVAPower Phasor, Apparent Power
m:i1P:bus1p.u.Current Phasor, Active Current
m:i1Q:bus1p.u.Current Phasor, Reactive Current
m:I1P:bus1kACurrent Phasor, Active Current
m:I1Q:bus1kACurrent Phasor, Reactive Current
m:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
m:i:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current
m:phiu1i1:bus1degAngle between Voltage and Current Phasor
m:Tfct:bus1sFault Clearing Time
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:unet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, referred to network
m:cosphi1:bus1ยทPower-Phasor, Power-Factor
c:frnomHzNominal Frequency
c:hpirad/sNominal angular frequency
c:piniMWys0
c:ys0:Aper phase :A, :B, :C, unbalanced onlyp.u.Admittance
c:scaleยทScale Factor of Load Shedding Probability Function
c:u0p.u.Nominal Voltage
c:kpu0ยทVolt. Dependence I on P
c:kqu0ยทVolt. Dependence I on Q
c:kpu1ยทVolt. Dependence II on P
c:kqu1ยทVolt. Dependence II on Q
c:kpuยทVolt. Dependence III on P
c:kquยทVolt. Dependence III on Q
c:aPยทPercent of Volt. Dep. I on P
c:bPยทPercent of Volt. Dep. II on P
c:aQยทPercent of Volt. Dep. I on Q
c:bQยทPercent of Volt. Dep. II on Q
c:qiniMvarNominal Reactive Power
c:RaOhmResistance
c:RbOhmResistance
c:RcOhmResistance
c:LamHInductance
c:LbmHInductance
c:LcmHInductance
c:CauFCapacitance
c:CbuFCapacitance
c:CcuFCapacitance
c:ROhmResistance
c:R:Aper phase :A, :B, :C, unbalanced onlyp.u.normPQext
c:LmHInductance
c:L:Aper phase :A, :B, :C, unbalanced onlyp.u.normPQext
c:CuFCapacitance
c:C:Aper phase :A, :B, :C, unbalanced onlyp.u.normPQext
c:glodp.u.Conductance
c:xp.u.Reactance
c:rp.u.Resistance
c:slipp.u.Slip
c:cnmยทConnection
c:s0pup.u.Slip at Normal Operation Point
c:scrpup.u.Critical Slip
c:tm00p.u.Ratio of Dynamic Load (Normal Operating Torque)
c:TjsAcceleration time constant
c:i_dynยทi_dyn
c:xmep.u.Electrical Torque
c:xmt0p.u.Initial mechanical torque
c:tm1ยทMechanical Torque Exponent
c:speed0p.u.Initial speed
c:xmtp.u.Mechanical Torque
c:ushedp.u.Voltage setting for load shedding
c:shapeยทShape of Load Shedding Probability Function
c:fshedp.u.Load-Shedding Factor
c:ureclosep.u.Voltage setting for reclosing
c:pinirMWNominal Active Power, ph. A
c:qinirMvarNominal Reactive Power, ph. A
c:pinisMWNominal Active Power, ph. B
c:qinisMvarNominal Reactive Power, ph. B
c:pinitMWNominal Active Power, ph. C
c:qinitMvarNominal Reactive Power, ph. C
c:u0abc:Aper phase :A, :B, :C, unbalanced onlyp.u.u0abc
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Phase Voltage
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Voltage
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage
n:u0:bus1p.u.Zero-Sequence-Voltage
n:U0:bus1kVZero-Sequence-Voltage
n:U0x3:bus1kV3*U0
n:u1:bus1p.u.Voltage Phasor, Magnitude
n:u1pc:bus1%Voltage Phasor, Magnitude
n:u1r:bus1p.u.Voltage Phasor, Real Part
n:u1i:bus1p.u.Voltage Phasor, Imaginary Part
n:U1:bus1kVVoltage Phasor, Magnitude
n:phiu1:bus1degVoltage Phasor, Angle
n:U1l:bus1kVLine-Line Voltage Phasor, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage
n:un:bus1p.u.Neutral-Ground Voltage
n:Un:bus1kVNeutral-Ground Voltage
n:ishc:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current
n:Ishc:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:inshc:bus1p.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bus1kANeutral Short-Circuit Current, magnitude
n:fe:bus1p.u.Electrical Frequency
n:dfehz:bus1HzDeviation of the El. Frequency
n:fehz:bus1HzElectrical Frequency
n:frnom:bus1HzNominal Frequency
s:RinOhmResistance (Input)
s:LinmHInductance (Input)
s:CinuFCapacitance (Input)
s:Rin_AOhmResistance (Input)
s:Rin_BOhmResistance (Input)
s:Lin_AmHInductance (Input)
s:Lin_BmHInductance (Input)
s:Cin_AuFCapacitance (Input)
s:Cin_BuFCapacitance (Input)
s:Rin_COhmResistance (Input)
s:Lin_CmHInductance (Input)
s:Cin_CuFCapacitance (Input)
s:speedp.u.Speed
s:xmdmp.u.MDM-Torque
s:fshedinp.u.Load-Shedding Factor
s:psirp.u.Flux, real part
s:psiip.u.Flux, imaginary part

ElmLod dc load flow results

Read after ComLdf (DC) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
c:piniMWNominal Active Power
c:scale0ยทInitial Scale Factor
c:ncustยทNumber of Connected Customers
c:i_remยทRemote Control
c:zonescaleยทZone Scale Factor
c:iRefElementยทReference Element
c:PmismMWActive Power Mismatch
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PnomMWNominal Active Power
c:PpeakMWPeak Active Power
c:pMWPower
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:Pgen:bus1MWGeneration, Active Power
n:Pmot:bus1MWMotor Load, Active Power
n:Pload:bus1MWGeneral Load, Active Power
n:Pcomp:bus1MWCompensation (Losses)
n:Pnet:bus1MWExternal Networks, Active Power
n:Pflow:bus1MWPower Flow, Active Power
s:scaleยทScale Factor
s:pini_setยทNominal Active Power

Read after ComMod with GetAttribute. c: calculation parameter, s: signal (state or model variable).

AttributeUnitDescription
c:hpirad/spini
c:piniMWloddy_l
c:lodst_lยทStatic
c:loddy_lยทDynamic
c:kpfยทStatic Frequency Dependence
c:kqfยทStatic Frequency Dependence
c:t1sDynamic Load Time Constant
c:sd0MVANominal power of dynamic load
c:sd00MVANominal power of dynamic load
c:udmaxp.u.Upper Voltage Limit
c:udminp.u.Lower Voltage Limit
c:fep.u.Electrical Frequency
c:scaleยทbQ
c:lodsp_lยทSpecial
c:tpuยทTransient Voltage Dependence
c:tqusTransient Voltage Dependence
c:ssp0MVANominal power of special load
c:ssp00MVANominal power of special load
c:u0p.u.Nominal voltage
c:i_nlnยทInternal Flag
c:kpu0ยทVolt. Dependence I on P
c:kqu0ยทVolt. Dependence I on Q
c:kpu1ยทVolt. Dependence II on P
c:kqu1ยทVolt. Dependence II on Q
c:kpuยทVolt. Dependence III on P
c:kquยทVolt. Dependence III on Q
c:aPยทPercent of Volt. Dep. I on P
c:bPยทPercent of Volt. Dep. II on P
c:aQยทPercent of Volt. Dep. I on Q
c:bQยทPercent of Volt. Dep. II on Q
c:motorACalLodwecc1pac,CalLodweccasmMotor A
c:motorBCalLodwecc1pac,CalLodweccasmMotor B
c:motorCCalLodwecc1pac,CalLodweccasmMotor C
c:motorDCalLodwecc1pac,CalLodweccasmMotor D
c:Tapp.u.Transformer tap
c:Rfdrp.u.Feeder R (p.u. of MVA base)
c:Xfdrp.u.Feeder X (p.u. of MVA base)
c:Bfdrp.u.Value of the total feeder reactive compensation
c:Vlsp.u.Voltage at substation low-side bus
c:Vldp.u.Voltage at load end of feeder
c:PstยทPst
c:QstยทQst
c:PelยทPel
c:QelยทQel
c:Fv1ยทFv1
c:qiniMvarNominal Reactive Power
c:tpfsTransient Frequency Dependence
c:tqfsTransient Frequency Dependence
c:glodp.u.Conductance
c:gs0p.u.Conductance
c:bs0p.u.Susceptance
c:xp.u.Reactance
c:rp.u.Resistance
c:slipp.u.Slip
c:s0pup.u.Slip at Normal Operation Point
c:scrpup.u.Critical Slip
c:tm00p.u.Ratio of Dynamic Load (Normal Operating Torque)
c:TjsAcceleration time constant
c:i_dynยทi_dyn
c:xmep.u.Electrical Torque
c:xmt0p.u.Initial mechanical torque
c:tm1ยทMechanical Torque Exponent
c:speed0p.u.Initial speed
c:xmtp.u.Mechanical Torque
c:ushedp.u.Voltage setting for load shedding
c:shapeยทShape of Load Shedding Probability Function
c:fshedp.u.Load-Shedding Factor
c:ureclosep.u.Voltage setting for reclosing
c:currrp.u.Rotor Current, Real Part
c:currip.u.Rotor Current, Imaginary Part
s:xup.u.State Variable
s:PextMWActive Power Input
s:QextMvarReactive Power Input
s:frefp.u.Reference Frequency
s:xfp.u.State Variable
s:speedp.u.Speed
s:xmdmp.u.MDM-Torque
s:psirrp.u.Rotor Flux, Real Part
s:psirip.u.Rotor Flux, Imaginary Part
s:fshedinp.u.Load-Shedding Factor

ElmLod optimal power flow results

Read after ComOpf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:bus1p.u.Voltage, Real Part, referred to network
m:uinet:bus1p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1degPositive-Sequence-Voltage, Angle
m:irnet:bus1p.u.Current, Real Part, referred to network
m:iinet:bus1p.u.Current, Imaginary Part, referred to network
m:inet:bus1p.u.Current, Magnitude, referred to network
m:I:bus1kACurrent, Magnitude
m:phii:bus1degCurrent, Angle
m:i1r:bus1p.u.Positive-Sequence Current, Real Part
m:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:S:bus1MVAApparent Power
m:cosphi:bus1ยทPower Factor
m:tanphi:bus1ยทtan(phi)
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:Ssum:bus1MVATotal Apparent Power
m:cosphisum:bus1ยทTotal Power Factor
m:tanphisum:bus1ยทTotal tan(phi)
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:ur:bus1p.u.Voltage, Real Part
m:ui:bus1p.u.Voltage, Imaginary Part
m:u:bus1p.u.Voltage, Magnitude
m:ir:bus1p.u.Current, Real Part
m:ii:bus1p.u.Current, Imaginary Part
m:i:bus1p.u.Current, Magnitude
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1sFault Clearing Time
m:Brkload:bus1%Breaker Loading
m:Spu:bus1MVA/p.u.Apparent Power per p.u. Voltage
c:frnomHzNominal Frequency
c:hpirad/sNominal angular frequency
c:piniMWNominal Active Power
c:scale0ยทInitial Scale Factor
c:sยทComplex Power (P+jQ)
c:u0p.u.Nominal Voltage
c:kpu0ยทVolt. Dependence I on P
c:kqu0ยทVolt. Dependence I on Q
c:kpu1ยทVolt. Dependence II on P
c:kqu1ยทVolt. Dependence II on Q
c:kpuยทVolt. Dependence III on P
c:kquยทVolt. Dependence III on Q
c:aPยทPercent of Volt. Dep. I on P
c:bPยทPercent of Volt. Dep. II on P
c:aQยทPercent of Volt. Dep. I on Q
c:bQยทPercent of Volt. Dep. II on Q
c:QnomMvarNominal Reactive Power
c:ncustยทNumber of Connected Customers
c:i_remยทRemote Control
c:zonescaleยทZone Scale Factor
c:iRefElementยทReference Element
c:PmismMWActive Power Mismatch
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:qiniMvarNominal Reactive Power
c:PnomMWNominal Active Power
c:PpeakMWPeak Active Power
c:QpeakMvarPeak Reactive Power
c:pMWPower
c:gs0p.u.Conductance
c:bs0p.u.Susceptance
c:xp.u.Reactance
c:rp.u.Resistance
c:slipp.u.Slip
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bus1MWGeneration, Active Power
n:Qgen:bus1MvarGeneration, Reactive Power
n:Pmot:bus1MWMotor Load, Active Power
n:Qmot:bus1MvarMotor Load, Reactive Power
n:Pload:bus1MWGeneral Load, Active Power
n:Qload:bus1MvarGeneral Load, Reactive Power
n:Pcomp:bus1MWCompensation (Losses)
n:Qcomp:bus1MvarCompensation
n:Pnet:bus1MWExternal Networks, Active Power
n:Qnet:bus1MvarExternal Networks, Reactive Power
n:Pflow:bus1MWPower Flow, Active Power
n:Qflow:bus1MvarPower Flow, Reactive Power
n:Pout:bus1MWOutgoing Flow, Active Power
n:Qout:bus1MvarOutgoing Power, Reactive Power
n:Sout:bus1MVAOutgoing Power, Apparent Power
n:cosphiout:bus1ยทOutgoing Power, Power Factor
n:Pbalance:bus1MWActive Power Balance (=0)
n:Qbalance:bus1MvarReactive Power Balance (=0)
n:LossPdown:bus1MWLosses, downstream
n:LossQdown:bus1MvarLosses, downstream (Reactive Power)
n:LossPdownload:bus1MWLoad losses, downstream
n:LossQdownload:bus1MvarLoad losses, downstream
n:LossPdownnoload:bus1MWNo load losses, downstream
n:LossQdownnoload:bus1MvarNo load losses, downstream
n:du_feed:bus1%Difference from voltage at start of feeder

ElmLod basic data