ElmSind attributesPowerFactory Series Reactor

Every attribute of the PowerFactory Series Reactor (ElmSind): 111 input parameters and 825 result variables, with units and meaning. Copy a name into GetAttribute or SetAttribute.

What ElmSind is

A series reactor between two terminals, used to limit short-circuit currents or to share load between parallel paths.

Class
ElmSind, element class
PowerFactory name
Series Reactor
Terminal suffix
:bus1 terminal i, :bus2 terminal j
Attributes
111 input parameters and 825 result variables, in 7 calculations

Read and write ElmSind in Python

import powerfactory

app = powerfactory.GetApplication()          # GetApplicationExt() from outside PowerFactory
app.GetFromStudyCase("ComLdf").Execute()      # results exist after a calculation

for obj in app.GetCalcRelevantObjects("*.ElmSind"):
    loading = obj.GetAttribute("c:loading")       # Loading, %
    print(obj.loc_name, loading)

obj = app.GetCalcRelevantObjects("*.ElmSind")[0]
obj.SetAttribute("outserv", 1)                # take it out of service
  • A result at a terminal of the series reactor needs the terminal in its name: m:P:bus1, not m:P, which raises AttributeError.
  • An input parameter is read and written with or without its e: prefix: GetAttribute("outserv") and GetAttribute("e:outserv") give the same value.
  • RMS and EMT variables change over time: record them in a results object (ElmRes) to read the whole curve. GetAttribute after a run gives the value at the last time step.

ElmSind input parameters

The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.

AttributeUnitDescription
loc_name·Name
chr_name·Characteristic Name
for_name·Foreign Key
dat_src·Data source
sernum·Serial Number
manuf·Manufacturer
commissionDate·Commissioning Date
appr_modby·Modified by
outserv·Out of Service
iZoneBus·Zone
iAreaBus·Area
lossAssign·Loss assignment
nphases·Phases
constr·Year of Construction
appr_status·Status
systp·System Type
iAstabint·A-stable integration algorithm
itrmt·Type
iFinalSlope·Set final slope (peak values)
ksat·Saturation Exponent
iLimb·Core
iInterPol·Interpolation
iFit·Data fitting
iHyster·Model
iResFlux·Residual flux
emtLinSig·Variable inductance/reactance via input signals
iperfect·Ideal component
ucnkVRated Voltage
CurnkARated Current
SnMVARated Power
uk%Short-Circuit Voltage uk
ukr%Short-Circuit Voltage (Re(uk)) ukr
PcukWCopper Losses
ZdOhmImpedance (absolute) Zd
xreaOhmReactance, X
lreamHInductance, L
rreaOhmResistance, R
X0toX1·X0/X1 ratio
R0toR1·R0/R1 ratio
maxload%Max. Loading
psi0p.u.Knee Flux
xmairp.u.Saturated Reactance
smoothfac%Smoothing Factor
Lwidth%Loop width
PsiresAp.u.Residual flux, ph. A
PsiresBp.u.Residual flux, ph. B
PsiresCp.u.Residual flux, ph. C
GPSlatdegLatitude / Northing
GPSlondegLongitude / Easting
appr_modif·Modified
satcurp.u.Current (peak)
satfluxp.u.Flux (peak)
satcue%Current (RMS)
satvolp.u.Voltage (RMS)
cimRdfId·RDF ID
desc·Description
fold_id·In Folder
bus1·Terminal iObject: StaCubic
bus2·Terminal jObject: StaCubic
doc_id·Additional Data
pOwner·OwnerObject: ElmOwner
pOperator·OperatorObject: ElmOperator
pRating·Thermal RatingObject: IntThrating
fcharRChaPol,ChaVec,ChaMatR(f)
fcharLChaPol,ChaVec,ChaMatL(f)
fcharR0ChaPol,ChaVec,ChaMatR0(f)
fcharL0ChaPol,ChaVec,ChaMatL0(f)
pStochStoTyptrfElement model
cpHeadFold·Head Folder
bus1_bar·Terminal i
bus2_bar·Terminal j
cpGrid·GridObject: ElmNet
cpZone·ZoneObject: ElmZone
cpArea·AreaObject: ElmArea
cpFeed·FeederObject: ElmFeeder
ciDist·Distance from infeed in number of buses
ciLater·Lateral Index
ciDistRoot·Distance from first infeed in number of buses
ciDistAll·Distance from infeed in number of buses including switches
ciDistAllRoot·Distance from first infeed in number of buses including switches
cpOwner·OwnerObject: ElmOwner
cpOperator·OperatorObject: ElmOperator
cpBranch·BranchObject: ElmBranch
cpSite·SiteObject: ElmSite
cpSubstat·SubstationObject: ElmSubstat,ElmTrfstat
cpMeteostat·Meteo StationObject: ElmMeteostat
ciOutaged·Planned Outage
ciEnergized·Energized
ciEarthed·Earthed
cDisplayName·Display Name
cpSupplyTransformer·Supplying TransformerObject: ElmTr?,ElmTrmult
cpSupplyTrfStation·Supplying Secondary SubstationObject: ElmTrfstat
cpSupplySubstation·Supplying SubstationObject: ElmSubstat
xreapup.u.Linear Reactance
cPsiresCp.u.Residual flux, ph. C
aFrolich·Frolich equation coefficient a
bFrolich·Frolich equation coefficient b
cFrolich·Frolich equation coefficient c
xsatFrolich·Frolich equation saturated reactance (p.u.)
mseFrolich·Frolich equation, mean squared error
InomkANominal Current
RfOhmResistance, R
LfmHInductance, L
Rf0OhmResistance, R0
Lf0mHInductance, L0
FOR11/aForced Outage Rate
FOEh/aForced Outage Expectancy
FODhForced Outage Duration
CCEarFr1/aFrequency of single earth faults
CCEarRepMuhRepair duration
CCEarProb%Conditional probability of a second earth fault

ElmSind load flow results

Read after ComLdf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bus1or :bus2p.u.Voltage, Real Part, referred to network
m:uinet:bus1or :bus2p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1or :bus2p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1or :bus2p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1or :bus2p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1or :bus2kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1or :bus2kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1or :bus2degPositive-Sequence-Voltage, Angle
m:irnet:bus1or :bus2p.u.Current, Real Part, referred to network
m:iinet:bus1or :bus2p.u.Current, Imaginary Part, referred to network
m:inet:bus1or :bus2p.u.Current, Magnitude, referred to network
m:I:bus1or :bus2kACurrent, Magnitude
m:phii:bus1or :bus2degCurrent, Angle
m:i1r:bus1or :bus2p.u.Positive-Sequence Current, Real Part
m:i1i:bus1or :bus2p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1or :bus2p.u.Positive-Sequence Current, Magnitude
m:I1:bus1or :bus2kAPositive-Sequence Current, Magnitude
m:phii1:bus1or :bus2degPositive-Sequence Current, Angle
m:P:bus1or :bus2MWActive Power
m:Q:bus1or :bus2MvarReactive Power
m:S:bus1or :bus2MVAApparent Power
m:cosphi:bus1or :bus2·Power Factor
m:tanphi:bus1or :bus2·tan(phi)
m:Psum:bus1or :bus2MWTotal Active Power
m:Qsum:bus1or :bus2MvarTotal Reactive Power
m:Ssum:bus1or :bus2MVATotal Apparent Power
m:cosphisum:bus1or :bus2·Total Power Factor
m:tanphisum:bus1or :bus2·Total tan(phi)
m:i1P:bus1or :bus2p.u.Positive-Sequence Active Current
m:i1Q:bus1or :bus2p.u.Positive-Sequence Reactive Current
m:I1P:bus1or :bus2kAPositive-Sequence Active Current
m:I1Q:bus1or :bus2kAPositive-Sequence Reactive Current
m:ur:bus1or :bus2p.u.Voltage, Real Part
m:ui:bus1or :bus2p.u.Voltage, Imaginary Part
m:u:bus1or :bus2p.u.Voltage, Magnitude
m:ir:bus1or :bus2p.u.Current, Real Part
m:ii:bus1or :bus2p.u.Current, Imaginary Part
m:i:bus1or :bus2p.u.Current, Magnitude
m:phiui:bus1or :bus2degAngle between Voltage and Current
m:phiu1i1:bus1or :bus2degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1or :bus2sFault Clearing Time
m:Brkload:bus1or :bus2%Breaker Loading
m:Spu:bus1or :bus2MVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bus1or :bus2p.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bus1or :bus2degZero-Sequence-Voltage, Angle
m:u2:bus1or :bus2p.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bus1or :bus2degNegative-Sequence-Voltage, Angle
m:irnet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part, referred to network
m:iinet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part, referred to network
m:inet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude, referred to network
m:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bus1or :bus2p.u.Zero-Sequence Current, Real Part
m:i0i:bus1or :bus2p.u.Zero-Sequence Current, Imaginary Part
m:i0:bus1or :bus2p.u.Zero-Sequence Current, Magnitude
m:I0:bus1or :bus2kAZero-Sequence Current, Magnitude
m:I0x3:bus1or :bus2kA3*I0
m:phii0:bus1or :bus2degZero-Sequence Current, Angle
m:i2r:bus1or :bus2p.u.Negative-Sequence Current, Real Part
m:i2i:bus1or :bus2p.u.Negative-Sequence Current, Imaginary Part
m:i2:bus1or :bus2p.u.Negative-Sequence Current, Magnitude
m:I2:bus1or :bus2kANegative-Sequence Current, Magnitude
m:phii2:bus1or :bus2degNegative-Sequence Current, Angle
m:ubfacI:bus1or :bus2%Current Unbalance Factor
m:ubfacS:bus1or :bus2%Power Unbalance Factor
m:P:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only·Power Factor
m:tanphi:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only·tan(phi)
m:Pln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bus1or :bus2MWPositive Sequence Active Power
m:Q1:bus1or :bus2MvarPositive Sequence Reactive Power
m:P2:bus1or :bus2MWNegative Sequence Active Power
m:Q2:bus1or :bus2MvarNegative Sequence Reactive Power
m:P0:bus1or :bus2MWZero Sequence Active Power
m:Q0:bus1or :bus2MvarZero Sequence Reactive Power
m:i2P:bus1or :bus2p.u.Negative-Sequence Active Current
m:i2Q:bus1or :bus2p.u.Negative-Sequence Reactive Current
m:I2P:bus1or :bus2kANegative-Sequence Active Current
m:I2Q:bus1or :bus2kANegative-Sequence Reactive Current
m:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1or :bus2degAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bus1or :bus2degAngle between Voltage and Current in negative sequence system
m:TfctPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Breaker Loading
c:ROhmResistance
c:loading%Loading
c:maxload%Max. Loading
c:dup.u.Voltage Drop
c:dupc%Voltage Drop
c:dphiudegVoltage Drop Angle
c:du1p.u.Positive Sequence Voltage Drop
c:du1pc%Positive Sequence Voltage Drop
c:dphiu1degPositive Sequence Voltage Drop Angle
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:Zind_1OhmImpedance
c:dUkVVoltage Drop
c:Zind_rOhmImpedance, Phase a
c:Zind_sOhmImpedance, Phase b
c:Zind_tOhmImpedance, Phase c
c:Z0OhmZero Sequence Impedance
c:loading_st%Short Term Loading
c:du:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage Drop
c:dupc:Aper phase :A, :B, :C, unbalanced only%Voltage Drop
c:dphiu:Aper phase :A, :B, :C, unbalanced onlydegVoltage Drop Angle
c:ZindOhmImpedance
n:ur:bus1or :bus2p.u.Voltage, Real Part
n:ui:bus1or :bus2p.u.Voltage, Imaginary Part
n:u:bus1or :bus2p.u.Voltage, Magnitude
n:upc:bus1or :bus2%Voltage, Magnitude
n:du:bus1or :bus2%Voltage Deviation
n:U:bus1or :bus2kVLine-Ground Voltage, Magnitude
n:phiu:bus1or :bus2degVoltage, Angle
n:phiurel:bus1or :bus2degVoltage, Relative Angle
n:Ul:bus1or :bus2kVLine-Line Voltage, Magnitude
n:u1:bus1or :bus2p.u.Voltage, Magnitude
n:u1pc:bus1or :bus2%Voltage, Magnitude
n:u1r:bus1or :bus2p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1or :bus2p.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bus1or :bus2MWGeneration, Active Power
n:Qgen:bus1or :bus2MvarGeneration, Reactive Power
n:Pmot:bus1or :bus2MWMotor Load, Active Power
n:Qmot:bus1or :bus2MvarMotor Load, Reactive Power
n:Pload:bus1or :bus2MWGeneral Load, Active Power
n:Qload:bus1or :bus2MvarGeneral Load, Reactive Power
n:Pcomp:bus1or :bus2MWCompensation (Losses)
n:Qcomp:bus1or :bus2MvarCompensation
n:Pnet:bus1or :bus2MWExternal Networks, Active Power
n:Qnet:bus1or :bus2MvarExternal Networks, Reactive Power
n:Pflow:bus1or :bus2MWPower Flow, Active Power
n:Qflow:bus1or :bus2MvarPower Flow, Reactive Power
n:Pout:bus1or :bus2MWOutgoing Flow, Active Power
n:Qout:bus1or :bus2MvarOutgoing Power, Reactive Power
n:Sout:bus1or :bus2MVAOutgoing Power, Apparent Power
n:cosphiout:bus1or :bus2·Outgoing Power, Power Factor
n:Pbalance:bus1or :bus2MWActive Power Balance (=0)
n:Qbalance:bus1or :bus2MvarReactive Power Balance (=0)
n:LossPdown:bus1or :bus2MWLosses, downstream
n:LossQdown:bus1or :bus2MvarLosses, downstream (Reactive Power)
n:LossPdownload:bus1or :bus2MWLoad losses, downstream
n:LossQdownload:bus1or :bus2MvarLoad losses, downstream
n:LossPdownnoload:bus1or :bus2MWNo load losses, downstream
n:LossQdownnoload:bus1or :bus2MvarNo load losses, downstream
n:du_feed:bus1or :bus2%Difference from voltage at start of feeder
n:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1or :bus2p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1or :bus2kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1or :bus2kV3*U0
n:phiu0:bus1or :bus2degZero-Sequence Voltage, Angle
n:U1:bus1or :bus2kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1or :bus2degPositive-Sequence Voltage, Angle
n:u2:bus1or :bus2p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1or :bus2kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1or :bus2degNegative-Sequence Voltage, Angle
n:U1l:bus1or :bus2kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1or :bus2kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1or :bus2p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1or :bus2kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1or :bus2degNeutral-Ground Voltage, Angle
n:upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bus1or :bus2p.u.Average-Voltage, Magnitude
n:Um:bus1or :bus2kVAverage-Voltage, Magnitude
n:uphtmin:bus1or :bus2p.u.Minimum of Phase Technology dependent Voltage, Magnitude
n:uphtmax:bus1or :bus2p.u.Maximum of Phase Technology dependent Voltage, Magnitude
n:ubfac:bus1or :bus2%Unbalance Factor
s:RinOhmResistance (Input)
s:XinOhmReactance (Input)

ElmSind short-circuit results

Read after ComShc with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:I:bus1or :bus2kAShort-Circuit Current, Magnitude
m:phii:bus1or :bus2degPhase Current, Angle
m:i1:bus1or :bus2p.u.Positive-Sequence Current, Magnitude
m:I1:bus1or :bus2kAPositive-Sequence Current, Magnitude
m:phii1:bus1or :bus2degPositive-Sequence Current, Angle
m:P:bus1or :bus2MWActive Power
m:Q:bus1or :bus2MvarReactive Power
m:i1P:bus1or :bus2p.u.Positive-Sequence Active Current
m:i1Q:bus1or :bus2p.u.Positive-Sequence Reactive Current
m:I1P:bus1or :bus2kAPositive-Sequence Active Current
m:I1Q:bus1or :bus2kAPositive-Sequence Reactive Current
m:phiui:bus1or :bus2degAngle between Voltage and Current
m:phiu1i1:bus1or :bus2degAngle between Voltage and Current in Positive-Sequence System
m:Tfct:bus1or :bus2sFault Clearing Time
m:Ikss:bus1or :bus2kAInitial Short-Circuit Current
m:ikss:bus1or :bus2p.u.Initial Short-Circuit Current, Magnitude
m:Skss:bus1or :bus2MVAInitial Short-Circuit Power
m:ip:bus1or :bus2kAPeak Short-Circuit Current
m:maxIkss:bus1or :bus2kAMax. Initial Short-Circuit Current
m:maxip:bus1or :bus2kAMax. Peak Short-Circuit Current
m:maxIth:bus1or :bus2kAMax. Thermal equivalent Short-Circuit Current
m:maxIb:bus1or :bus2kAMax. Breaking Current
m:R:bus1or :bus2OhmFault Impedance, Real Part
m:X:bus1or :bus2OhmFault Impedance, Imaginary Part
m:Z:bus1or :bus2OhmFault Impedance, Magnitude
m:phiz:bus1or :bus2degFault Impedance, Angle
m:Rs:bus1or :bus2OhmSource Impedance, Real Part
m:Xs:bus1or :bus2OhmSource Impedance, Imaginary Part
m:Zs:bus1or :bus2OhmSource Impedance, Magnitude
m:phizs:bus1or :bus2degSource Impedance, Angle
m:BrkIpload:bus1or :bus2%Breaker Loading (peak)
m:Ib:bus1or :bus2kAShort-Circuit Breaking Current
m:Sb:bus1or :bus2MVAShort-Circuit Breaking Power
m:Ith:bus1or :bus2kAThermal equivalent Short-Circuit Current
m:zSbase:bus1or :bus2p.u.Fault Impedance, Magnitude
m:XtoR:bus1or :bus2·X/R ratio
m:cosphiui:bus1or :bus2·cosphi
m:BrkIbload:bus1or :bus2%Breaker Loading (breaking)
m:BrkmaxIb:bus1or :bus2kAMax. Breaking Current (breaker time)
m:Ik:bus1or :bus2kASteady-State Short-Circuit Current
m:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, Magnitude
m:phii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:I0:bus1or :bus2kAZero-Sequence Current, Magnitude
m:I0x3:bus1or :bus2kA3*I0
m:phii0:bus1or :bus2degZero-Sequence Current, Angle
m:I2:bus1or :bus2kANegative-Sequence Current, Magnitude
m:phii2:bus1or :bus2degNegative-Sequence Current, Angle
m:P:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:Psum:bus1or :bus2MWTotal Active Power
m:Qsum:bus1or :bus2MvarTotal Reactive Power
m:cosphisum:bus1or :bus2·Total Power Factor
m:P2:bus1or :bus2MWP2
m:Q2:bus1or :bus2MvarQ2
m:P0:bus1or :bus2MWP0
m:phiui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1or :bus2degAngle between Voltage and Current in Zero-Sequence System
m:phiu2i2:bus1or :bus2degAngle between Voltage and Current in Negative-Sequence System
m:TfctPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:Ikss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
m:ikss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Initial Short-Circuit Current, Magnitude
m:Skss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
m:Skssx3:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
m:ip:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
m:Z:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmFault Impedance, Magnitude
m:phiz:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegFault Impedance, Angle
m:Zl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmLine-Line Fault Impedance, Magnitude
m:phizl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Line Fault Impedance, Angle
m:Z0:bus1or :bus2OhmZero-Sequence Fault Impedance, Magnitude
m:phiz0:bus1or :bus2degZero-Sequence Fault Impedance, Angle
m:z0Sbase:bus1or :bus2p.u.Zero-Sequence Fault Impedance, Magnitude
m:cosphiu1i1:bus1or :bus2·Positive-Sequence cosphi
m:I0x3watt:bus1or :bus2kAEarth-Fault Residual Current
m:I0x3var:bus1or :bus2kACapacitive Earth-Fault Current
m:Q0cap:bus1or :bus2MvarQ0 capacitive
m:Rfrel:bus1or :bus2OhmRelay Impedance, Real Part
m:Xfrel:bus1or :bus2OhmRelay Impedance, Imaginary Part
m:Zfrel:bus1or :bus2OhmRelay Impedance, Magnitude
m:phizfrel:bus1or :bus2degRelay Impedance, Angle
m:Zf:bus1or :bus2OhmMeas. Fault Impedance, Magnitude
m:phizf:bus1or :bus2degMeas. Fault Impedance, Angle
c:Zind_1OhmImpedance
c:Zind_rOhmImpedance, Phase a
c:Zind_sOhmImpedance, Phase b
c:Zind_tOhmImpedance, Phase c
c:Z0OhmZero Sequence Impedance
c:ZindOhmImpedance
n:ur:bus1or :bus2p.u.Voltage, Real Part
n:ui:bus1or :bus2p.u.Voltage, Imaginary Part
n:u:bus1or :bus2p.u.Voltage, Magnitude
n:upc:bus1or :bus2%Voltage, Magnitude
n:du:bus1or :bus2%Voltage Deviation
n:U:bus1or :bus2kVLine-Ground Voltage, Magnitude
n:phiu:bus1or :bus2degVoltage, Angle
n:Ul:bus1or :bus2kVLine-Line Voltage, Magnitude
n:u1:bus1or :bus2p.u.Voltage, Magnitude
n:u1pc:bus1or :bus2%Voltage, Magnitude
n:u1r:bus1or :bus2p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1or :bus2p.u.Positive-Sequence Voltage, Imaginary Part
n:Ikss:bus1or :bus2kAInitial Short-Circuit Current
n:I:bus1or :bus2kAShort-Circuit Current
n:phii:bus1or :bus2degPhase Current, Angle
n:Skss:bus1or :bus2MVAInitial Short-Circuit Power
n:ip:bus1or :bus2kAPeak Short-Circuit Current
n:Ib:bus1or :bus2kAShort-Circuit Breaking Current
n:Sb:bus1or :bus2MVAShort-Circuit Breaking Power
n:idc:bus1or :bus2kADecaying Component
n:Ith:bus1or :bus2kAThermal equivalent Short-Circuit Current
n:R1toX1:bus1or :bus2·R1/X1 ratio (Zk")
n:X1toR1:bus1or :bus2·X1/R1 ratio (Zk")
n:R:bus1or :bus2OhmShort-Circuit Impedance, Real Part
n:X:bus1or :bus2OhmShort-Circuit Impedance, Imaginary Part
n:Z:bus1or :bus2OhmShort-Circuit Impedance, Magnitude
n:phiz:bus1or :bus2degShort-Circuit Impedance, Angle
n:urpref:bus1or :bus2p.u.Pre-fault Voltage, Real Part
n:uipref:bus1or :bus2p.u.Pre-fault Voltage, Imaginary Part
n:upref:bus1or :bus2p.u.Pre-fault Voltage, Magnitude
n:uprefpc:bus1or :bus2%Pre-fault Voltage, Magnitude
n:Upref:bus1or :bus2kVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bus1or :bus2kVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bus1or :bus2degPre-fault Voltage, Angle
n:phiui:bus1or :bus2degAngle between Voltage and Current
n:Ithload:bus1or :bus2%Loading, Thermal equivalent Current
n:Ipload:bus1or :bus2%Loading, Peak Short-Circuit Current
n:Ithrtk:bus1or :bus2kARated Short-Time Current (Tk)
n:XtoR:bus1or :bus2·X/R ratio (peak)
n:RtoX:bus1or :bus2·R/X ratio (peak)
n:XtoR_b:bus1or :bus2·X/R ratio (dc)
n:RtoX_b:bus1or :bus2·R/X ratio (dc)
n:fctof_b:bus1or :bus2·Equivalent Frequency fc/f (dc)
n:rSbase:bus1or :bus2p.u.Short-Circuit Impedance, Real Part
n:xSbase:bus1or :bus2p.u.Short-Circuit Impedance, Imaginary Part
n:zSbase:bus1or :bus2p.u.Short-Circuit Impedance, Magnitude
n:Tn:bus1or :bus2msGrid Time Constant
n:Ik:bus1or :bus2kASteady-State Short-Circuit Current
n:cfac:bus1or :bus2·Voltage Factor
n:Iasy:bus1or :bus2kAAsymmetrical Breaking Current
n:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1or :bus2p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1or :bus2kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1or :bus2kV3*U0
n:phiu0:bus1or :bus2degZero-Sequence Voltage, Angle
n:U1:bus1or :bus2kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1or :bus2degPositive-Sequence Voltage, Angle
n:u2:bus1or :bus2p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1or :bus2kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1or :bus2degNegative-Sequence Voltage, Angle
n:U1l:bus1or :bus2kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1or :bus2kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1or :bus2p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1or :bus2kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1or :bus2degNeutral-Ground Voltage, Angle
n:upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:Ikss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
n:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:phii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
n:Skss:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
n:Skssx3:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
n:ip:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
n:Ib:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Breaking Current
n:Sb:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVAShort-Circuit Breaking Power
n:Ith:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAThermal equivalent Short-Circuit Current
n:Ithmax:bus1or :bus2kAMax. Thermal equivalent Short-Circuit Current
n:R0:bus1or :bus2OhmZero-Sequence Impedance, Real Part
n:X0:bus1or :bus2OhmZero-Sequence Impedance, Imaginary Part
n:Z0:bus1or :bus2OhmZero-Sequence Impedance, Magnitude
n:phiz0:bus1or :bus2degZero-Sequence Impedance, Angle
n:r0Sbase:bus1or :bus2p.u.Zero-Sequence Impedance, Real Part
n:x0Sbase:bus1or :bus2p.u.Zero-Sequence Impedance, Imaginary Part
n:z0Sbase:bus1or :bus2p.u.Zero-Sequence Impedance, Magnitude
n:R1:bus1or :bus2OhmPositive-Sequence Impedance, Real Part
n:X1:bus1or :bus2OhmPositive-Sequence Impedance, Imaginary Part
n:Z1:bus1or :bus2OhmPositive-Sequence Impedance, Magnitude
n:phiz1:bus1or :bus2degPositive-Sequence Impedance, Angle
n:r1Sbase:bus1or :bus2p.u.Positive-Sequence Impedance, Real Part
n:x1Sbase:bus1or :bus2p.u.Positive-Sequence Impedance, Imaginary Part
n:z1Sbase:bus1or :bus2p.u.Positive-Sequence Impedance, Magnitude
n:R2:bus1or :bus2OhmNegative-Sequence Impedance, Real Part
n:X2:bus1or :bus2OhmNegative-Sequence Impedance, Imaginary Part
n:Z2:bus1or :bus2OhmNegative-Sequence Impedance, Magnitude
n:phiz2:bus1or :bus2degNegative-Sequence Impedance, Angle
n:r2Sbase:bus1or :bus2p.u.Negative-Sequence Impedance, Real Part
n:x2Sbase:bus1or :bus2p.u.Negative-Sequence Impedance, Imaginary Part
n:z2Sbase:bus1or :bus2p.u.Negative-Sequence Impedance, Magnitude
n:R0toX0:bus1or :bus2·R0/X0 ratio (Zk")
n:X0toR0:bus1or :bus2·X0/R0 ratio (Zk")
n:R2toX2:bus1or :bus2·R2/X2 ratio (Zk")
n:X2toR2:bus1or :bus2·X2/R2 ratio (Zk")
n:R:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Ground
n:X:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Ground
n:Z:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Ground
n:phiz:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Ground
n:Rl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Line
n:Xl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Line
n:Zl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Line
n:phizl:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Line
n:Rln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Neutral
n:Xln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Neutral
n:Zln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Neutral
n:phizln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Neutral
n:Rn:bus1or :bus2OhmNetwork Resistance, Neutral
n:Xn:bus1or :bus2OhmNetwork Reactance, Neutral
n:Zn:bus1or :bus2OhmNetwork Impedance, Neutral
n:phizn:bus1or :bus2degAngle of Network Impedance, Neutral
n:eff:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only·Earth Fault Factor
n:X0toX1:bus1or :bus2·X0/X1
n:In:bus1or :bus2kANeutral Current, Magnitude
n:phiin:bus1or :bus2degNeutral Current, Angle
n:I0:bus1or :bus2kAZero-Sequence Current, Magnitude
n:I0x3:bus1or :bus2kA3*I0
n:phii0:bus1or :bus2degZero-Sequence Current, Angle
n:I1:bus1or :bus2kAPositive-Sequence Current, Magnitude
n:phii1:bus1or :bus2degPositive-Sequence Current, Angle
n:I2:bus1or :bus2kANegative-Sequence Current, Magnitude
n:phii2:bus1or :bus2degNegative-Sequence Current, Angle
n:urpref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Real Part
n:uipref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Imaginary Part
n:upref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Magnitude
n:uprefpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Pre-fault Voltage, Magnitude
n:Upref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegPre-fault Voltage, Angle
n:phiui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
n:phiu1i1:bus1or :bus2degAngle between Voltage and Current in positive sequence system
n:phiu2i2:bus1or :bus2degAngle between Voltage and Current in negative sequence system
n:phiu0i0:bus1or :bus2degAngle between Voltage and Current in zero-sequence system
n:Ik:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykASteady-State Short-Circuit Current
n:in:bus1or :bus2p.u.Neutral Current, Magnitude
n:i0r:bus1or :bus2p.u.Zero-Sequence Current, Real Part
n:i0i:bus1or :bus2p.u.Zero-Sequence Current, Imaginary Part
n:i0:bus1or :bus2p.u.Zero-Sequence Current, Magnitude
n:i1r:bus1or :bus2p.u.Positive-Sequence Current, Real Part
n:i1i:bus1or :bus2p.u.Positive-Sequence Current, Imaginary Part
n:i1:bus1or :bus2p.u.Positive-Sequence Current, Magnitude
n:i2r:bus1or :bus2p.u.Negative-Sequence Current, Real Part
n:i2i:bus1or :bus2p.u.Negative-Sequence Current, Imaginary Part
n:i2:bus1or :bus2p.u.Negative-Sequence Current, Magnitude

ElmSind rms simulation results

Read after ComInc (RMS) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bus1or :bus2p.u.Voltage, Real Part, referred to network
m:uinet:bus1or :bus2p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1or :bus2p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1or :bus2p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1or :bus2p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1or :bus2kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1or :bus2kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1or :bus2degPositive-Sequence-Voltage, Angle
m:irnet:bus1or :bus2p.u.Current, Real Part, referred to network
m:iinet:bus1or :bus2p.u.Current, Imaginary Part, referred to network
m:inet:bus1or :bus2p.u.Current, Magnitude, referred to network
m:I:bus1or :bus2kACurrent, Magnitude
m:phii:bus1or :bus2degCurrent, Angle
m:i1r:bus1or :bus2p.u.Positive-Sequence Current, Real Part
m:i1i:bus1or :bus2p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1or :bus2p.u.Positive-Sequence Current, Magnitude
m:I1:bus1or :bus2kAPositive-Sequence Current, Magnitude
m:phii1:bus1or :bus2degPositive-Sequence Current, Angle
m:P:bus1or :bus2MWActive Power
m:Q:bus1or :bus2MvarReactive Power
m:S:bus1or :bus2MVAApparent Power
m:cosphi:bus1or :bus2·Power Factor
m:tanphi:bus1or :bus2·tan(phi)
m:Psum:bus1or :bus2MWTotal Active Power
m:Qsum:bus1or :bus2MvarTotal Reactive Power
m:Ssum:bus1or :bus2MVATotal Apparent Power
m:cosphisum:bus1or :bus2·Total Power Factor
m:tanphisum:bus1or :bus2·Total tan(phi)
m:i1P:bus1or :bus2p.u.Positive-Sequence Active Current
m:i1Q:bus1or :bus2p.u.Positive-Sequence Reactive Current
m:I1P:bus1or :bus2kAPositive-Sequence Active Current
m:I1Q:bus1or :bus2kAPositive-Sequence Reactive Current
m:ur:bus1or :bus2p.u.Voltage, Real Part
m:ui:bus1or :bus2p.u.Voltage, Imaginary Part
m:u:bus1or :bus2p.u.Voltage, Magnitude
m:ir:bus1or :bus2p.u.Current, Real Part
m:ii:bus1or :bus2p.u.Current, Imaginary Part
m:i:bus1or :bus2p.u.Current, Magnitude
m:phiui:bus1or :bus2degAngle between Voltage and Current
m:phiu1i1:bus1or :bus2degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1or :bus2sFault Clearing Time
m:Brkload:bus1or :bus2%Breaker Loading
m:Spu:bus1or :bus2MVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bus1or :bus2p.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bus1or :bus2degZero-Sequence-Voltage, Angle
m:u2:bus1or :bus2p.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bus1or :bus2degNegative-Sequence-Voltage, Angle
m:irnet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:iinet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:inet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bus1or :bus2p.u.Zero-Sequence Current, Real Part
m:i0i:bus1or :bus2p.u.Zero-Sequence Current, Imaginary Part
m:i0:bus1or :bus2p.u.Zero-Sequence Current, Magnitude
m:I0:bus1or :bus2kAZero-Sequence Current, Magnitude
m:I0x3:bus1or :bus2kA3*I0
m:phii0:bus1or :bus2degZero-Sequence Current, Angle
m:i2r:bus1or :bus2p.u.Negative-Sequence Current, Real Part
m:i2i:bus1or :bus2p.u.Negative-Sequence Current, Imaginary Part
m:i2:bus1or :bus2p.u.Negative-Sequence Current, Magnitude
m:I2:bus1or :bus2kANegative-Sequence Current, Magnitude
m:phii2:bus1or :bus2degNegative-Sequence Current, Angle
m:P:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only·Power Factor
m:tanphi:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only·tan(phi)
m:Pln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bus1or :bus2MWPositive Sequence Active Power
m:Q1:bus1or :bus2MvarPositive Sequence Reactive Power
m:P2:bus1or :bus2MWNegative Sequence Active Power
m:Q2:bus1or :bus2MvarNegative Sequence Reactive Power
m:P0:bus1or :bus2MWZero Sequence Active Power
m:Q0:bus1or :bus2MvarZero Sequence Reactive Power
m:i2P:bus1or :bus2p.u.Negative-Sequence Active Current
m:i2Q:bus1or :bus2p.u.Negative-Sequence Reactive Current
m:I2P:bus1or :bus2kANegative-Sequence Active Current
m:I2Q:bus1or :bus2kANegative-Sequence Reactive Current
m:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1or :bus2degAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bus1or :bus2degAngle between Voltage and Current in negative sequence system
m:TfctPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Breaker Loading
c:ROhmResistance
c:LHInductance
c:loading%Loading
c:InomkANominal Current
c:Zind_1OhmImpedance
c:Zind_rOhmImpedance, Phase a
c:Zind_sOhmImpedance, Phase b
c:Zind_tOhmImpedance, Phase c
c:Z0OhmZero Sequence Impedance
c:ZindOhmImpedance
n:ur:bus1or :bus2p.u.Voltage, Real Part
n:ui:bus1or :bus2p.u.Voltage, Imaginary Part
n:u:bus1or :bus2p.u.Voltage, Magnitude
n:upc:bus1or :bus2%Voltage, Magnitude
n:du:bus1or :bus2%Voltage Deviation
n:U:bus1or :bus2kVLine-Ground Voltage, Magnitude
n:phiu:bus1or :bus2degVoltage, Angle
n:phiurel:bus1or :bus2degVoltage, Relative Angle
n:Ul:bus1or :bus2kVLine-Line Voltage, Magnitude
n:u1:bus1or :bus2p.u.Voltage, Magnitude
n:u1pc:bus1or :bus2%Voltage, Magnitude
n:u1r:bus1or :bus2p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1or :bus2p.u.Positive-Sequence Voltage, Imaginary Part
n:ishc:bus1or :bus2p.u.Short-Circuit Current, magnitude
n:Ishc:bus1or :bus2kAShort-Circuit Current, magnitude
n:fe:bus1or :bus2p.u.Electrical Frequency
n:dfehz:bus1or :bus2HzDeviation of the El. Frequency
n:fehz:bus1or :bus2HzElectrical Frequency
n:frnom:bus1or :bus2HzNominal Frequency
n:ishcr:bus1or :bus2p.u.Short-Circuit Current, real
n:ishci:bus1or :bus2p.u.Short-Circuit Current, imag
n:dfedt:bus1or :bus2p.u./sDerivative of El. Frequency
n:ur:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1or :bus2p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1or :bus2kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1or :bus2kV3*U0
n:phiu0:bus1or :bus2degZero-Sequence Voltage, Angle
n:U1:bus1or :bus2kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1or :bus2degPositive-Sequence Voltage, Angle
n:u2:bus1or :bus2p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1or :bus2kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1or :bus2degNegative-Sequence Voltage, Angle
n:U1l:bus1or :bus2kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1or :bus2kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1or :bus2p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1or :bus2kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1or :bus2degNeutral-Ground Voltage, Angle
n:upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bus1or :bus2p.u.Average-Voltage, Magnitude
n:Um:bus1or :bus2kVAverage-Voltage, Magnitude
n:ishc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, magnitude
n:Ishc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, magnitude
n:inshc:bus1or :bus2p.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bus1or :bus2kANeutral Short-Circuit Current, magnitude
n:ishcr:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, real
n:ishci:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, imag
s:RinOhmResistance (Input)
s:XinOhmReactance (Input)
s:LinHInductance (Input)

ElmSind emt simulation results

Read after ComInc (EMT) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:u0:bus1or :bus2p.u.Zero-Sequence-Voltage
m:u1r:bus1or :bus2p.u.Voltage Phasor, Real Part
m:u1i:bus1or :bus2p.u.Voltage Phasor, Imaginary Part
m:u1:bus1or :bus2p.u.Voltage Phasor, Magnitude
m:U1:bus1or :bus2kVLine-Ground Voltage Phasor, Magnitude
m:U1l:bus1or :bus2kVLine-Line Voltage Phasor, Magnitude
m:phiu1:bus1or :bus2degVoltage Phasor, Angle
m:inet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, referred to network
m:I:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAPhase Current
m:i0:bus1or :bus2p.u.Zero-Sequence Current
m:I0:bus1or :bus2kAZero-Sequence Current
m:I0x3:bus1or :bus2kA3*I0
m:i1r:bus1or :bus2p.u.Current Phasor, Real Part
m:i1i:bus1or :bus2p.u.Current Phasor, Imaginary Part
m:i1:bus1or :bus2p.u.Current Phasor, Magnitude
m:I1:bus1or :bus2kACurrent Phasor, Magnitude
m:phii1:bus1or :bus2degCurrent Phasor, Angle
m:P:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Psum:bus1or :bus2MWPower-Phasor, Active Power
m:Qsum:bus1or :bus2MvarPower Phasor, Reactive Part
m:Ssum:bus1or :bus2MVAPower Phasor, Apparent Power
m:i1P:bus1or :bus2p.u.Current Phasor, Active Current
m:i1Q:bus1or :bus2p.u.Current Phasor, Reactive Current
m:I1P:bus1or :bus2kACurrent Phasor, Active Current
m:I1Q:bus1or :bus2kACurrent Phasor, Reactive Current
m:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
m:i:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current
m:phiu1i1:bus1or :bus2degAngle between Voltage and Current Phasor
m:Tfct:bus1or :bus2sFault Clearing Time
m:TfctPh:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:unet:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, referred to network
m:cosphi1:bus1or :bus2·Power-Phasor, Power-Factor
c:IndHInductance
c:RreaOhmResistance
c:ROhmResistance
c:LHInductance
c:Ind_rHInductance, Phase a
c:Ind_sHInductance, Phase b
c:Ind_tHInductance, Phase c
c:Rrea_rOhmResistance, Phase a
c:Rrea_sOhmResistance, Phase b
c:Rrea_tOhmResistance, Phase c
c:phystkWHysteresis losses at rated operation
n:u:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
n:upc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Phase Voltage
n:U:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVPhase Voltage
n:ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage
n:ulpc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced only%Line-Line Voltage
n:Ul:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage
n:u0:bus1or :bus2p.u.Zero-Sequence-Voltage
n:U0:bus1or :bus2kVZero-Sequence-Voltage
n:U0x3:bus1or :bus2kV3*U0
n:u1:bus1or :bus2p.u.Voltage Phasor, Magnitude
n:u1pc:bus1or :bus2%Voltage Phasor, Magnitude
n:u1r:bus1or :bus2p.u.Voltage Phasor, Real Part
n:u1i:bus1or :bus2p.u.Voltage Phasor, Imaginary Part
n:U1:bus1or :bus2kVVoltage Phasor, Magnitude
n:phiu1:bus1or :bus2degVoltage Phasor, Angle
n:U1l:bus1or :bus2kVLine-Line Voltage Phasor, Magnitude
n:uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage
n:Uln:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage
n:un:bus1or :bus2p.u.Neutral-Ground Voltage
n:Un:bus1or :bus2kVNeutral-Ground Voltage
n:ishc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current
n:Ishc:bus1:Aor :bus2; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:inshc:bus1or :bus2p.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bus1or :bus2kANeutral Short-Circuit Current, magnitude
n:fe:bus1or :bus2p.u.Electrical Frequency
n:dfehz:bus1or :bus2HzDeviation of the El. Frequency
n:fehz:bus1or :bus2HzElectrical Frequency
n:frnom:bus1or :bus2HzNominal Frequency
s:RinOhmResistance (Input)
s:XinOhmReactance (Input)
s:LinHInductance (Input)
s:Rin_AOhmResistance (Input)
s:Rin_BOhmResistance (Input)
s:Rin_COhmResistance (Input)
s:Lin_AHInductance (Input)
s:Lin_BHInductance (Input)
s:Lin_CHInductance (Input)
s:psil_dp.u.Flux, d-axis
s:psil_qp.u.Flux, q-axis
s:psil_0p.u.Flux, 0-Sequence
s:psip.u.Flux

ElmSind dc load flow results

Read after ComLdf (DC) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:P:bus1or :bus2MWActive Power
m:Q:bus1or :bus2MvarReactive Power
c:ROhmResistance
c:loading%Loading
c:maxload%Max. Loading
c:dphiudegVoltage Drop Angle
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:Zind_1OhmImpedance
n:u:bus1or :bus2p.u.Voltage, Magnitude
n:upc:bus1or :bus2%Voltage, Magnitude
n:U:bus1or :bus2kVLine-Ground Voltage, Magnitude
n:phiu:bus1or :bus2degVoltage, Angle
n:phiurel:bus1or :bus2degVoltage, Relative Angle
n:Ul:bus1or :bus2kVLine-Line Voltage, Magnitude
n:u1:bus1or :bus2p.u.Voltage, Magnitude
n:Pgen:bus1or :bus2MWGeneration, Active Power
n:Pmot:bus1or :bus2MWMotor Load, Active Power
n:Pload:bus1or :bus2MWGeneral Load, Active Power
n:Pcomp:bus1or :bus2MWCompensation (Losses)
n:Pnet:bus1or :bus2MWExternal Networks, Active Power
n:Pflow:bus1or :bus2MWPower Flow, Active Power

Read after ComMod with GetAttribute. c: calculation parameter, s: signal (state or model variable).

AttributeUnitDescription
c:ROhmResistance
c:LHInductance
c:loading%Loading
c:InomkANominal Current
c:Zind_1OhmImpedance
s:RinOhmResistance (Input)
s:XinOhmReactance (Input)
s:LinHInductance (Input)

ElmSind optimal power flow results

Read after ComOpf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:bus1or :bus2p.u.Voltage, Real Part, referred to network
m:uinet:bus1or :bus2p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1or :bus2p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1or :bus2p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1or :bus2p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1or :bus2kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1or :bus2kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1or :bus2degPositive-Sequence-Voltage, Angle
m:irnet:bus1or :bus2p.u.Current, Real Part, referred to network
m:iinet:bus1or :bus2p.u.Current, Imaginary Part, referred to network
m:inet:bus1or :bus2p.u.Current, Magnitude, referred to network
m:I:bus1or :bus2kACurrent, Magnitude
m:phii:bus1or :bus2degCurrent, Angle
m:i1r:bus1or :bus2p.u.Positive-Sequence Current, Real Part
m:i1i:bus1or :bus2p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1or :bus2p.u.Positive-Sequence Current, Magnitude
m:I1:bus1or :bus2kAPositive-Sequence Current, Magnitude
m:phii1:bus1or :bus2degPositive-Sequence Current, Angle
m:P:bus1or :bus2MWActive Power
m:Q:bus1or :bus2MvarReactive Power
m:S:bus1or :bus2MVAApparent Power
m:cosphi:bus1or :bus2·Power Factor
m:tanphi:bus1or :bus2·tan(phi)
m:Psum:bus1or :bus2MWTotal Active Power
m:Qsum:bus1or :bus2MvarTotal Reactive Power
m:Ssum:bus1or :bus2MVATotal Apparent Power
m:cosphisum:bus1or :bus2·Total Power Factor
m:tanphisum:bus1or :bus2·Total tan(phi)
m:i1P:bus1or :bus2p.u.Positive-Sequence Active Current
m:i1Q:bus1or :bus2p.u.Positive-Sequence Reactive Current
m:I1P:bus1or :bus2kAPositive-Sequence Active Current
m:I1Q:bus1or :bus2kAPositive-Sequence Reactive Current
m:ur:bus1or :bus2p.u.Voltage, Real Part
m:ui:bus1or :bus2p.u.Voltage, Imaginary Part
m:u:bus1or :bus2p.u.Voltage, Magnitude
m:ir:bus1or :bus2p.u.Current, Real Part
m:ii:bus1or :bus2p.u.Current, Imaginary Part
m:i:bus1or :bus2p.u.Current, Magnitude
m:phiui:bus1or :bus2degAngle between Voltage and Current
m:phiu1i1:bus1or :bus2degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1or :bus2sFault Clearing Time
m:Brkload:bus1or :bus2%Breaker Loading
m:Spu:bus1or :bus2MVA/p.u.Apparent Power per p.u. Voltage
c:ROhmResistance
c:loading%Loading
c:maxload%Max. Loading
c:dup.u.Voltage Drop
c:dupc%Voltage Drop
c:dphiudegVoltage Drop Angle
c:du1p.u.Positive Sequence Voltage Drop
c:du1pc%Positive Sequence Voltage Drop
c:dphiu1degPositive Sequence Voltage Drop Angle
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:Zind_1OhmImpedance
c:dUkVVoltage Drop
n:ur:bus1or :bus2p.u.Voltage, Real Part
n:ui:bus1or :bus2p.u.Voltage, Imaginary Part
n:u:bus1or :bus2p.u.Voltage, Magnitude
n:upc:bus1or :bus2%Voltage, Magnitude
n:du:bus1or :bus2%Voltage Deviation
n:U:bus1or :bus2kVLine-Ground Voltage, Magnitude
n:phiu:bus1or :bus2degVoltage, Angle
n:phiurel:bus1or :bus2degVoltage, Relative Angle
n:Ul:bus1or :bus2kVLine-Line Voltage, Magnitude
n:u1:bus1or :bus2p.u.Voltage, Magnitude
n:u1pc:bus1or :bus2%Voltage, Magnitude
n:u1r:bus1or :bus2p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1or :bus2p.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bus1or :bus2MWGeneration, Active Power
n:Qgen:bus1or :bus2MvarGeneration, Reactive Power
n:Pmot:bus1or :bus2MWMotor Load, Active Power
n:Qmot:bus1or :bus2MvarMotor Load, Reactive Power
n:Pload:bus1or :bus2MWGeneral Load, Active Power
n:Qload:bus1or :bus2MvarGeneral Load, Reactive Power
n:Pcomp:bus1or :bus2MWCompensation (Losses)
n:Qcomp:bus1or :bus2MvarCompensation
n:Pnet:bus1or :bus2MWExternal Networks, Active Power
n:Qnet:bus1or :bus2MvarExternal Networks, Reactive Power
n:Pflow:bus1or :bus2MWPower Flow, Active Power
n:Qflow:bus1or :bus2MvarPower Flow, Reactive Power
n:Pout:bus1or :bus2MWOutgoing Flow, Active Power
n:Qout:bus1or :bus2MvarOutgoing Power, Reactive Power
n:Sout:bus1or :bus2MVAOutgoing Power, Apparent Power
n:cosphiout:bus1or :bus2·Outgoing Power, Power Factor
n:Pbalance:bus1or :bus2MWActive Power Balance (=0)
n:Qbalance:bus1or :bus2MvarReactive Power Balance (=0)
n:LossPdown:bus1or :bus2MWLosses, downstream
n:LossQdown:bus1or :bus2MvarLosses, downstream (Reactive Power)
n:LossPdownload:bus1or :bus2MWLoad losses, downstream
n:LossQdownload:bus1or :bus2MvarLoad losses, downstream
n:LossPdownnoload:bus1or :bus2MWNo load losses, downstream
n:LossQdownnoload:bus1or :bus2MvarNo load losses, downstream
n:du_feed:bus1or :bus2%Difference from voltage at start of feeder

ElmSind basic data

b: values are worked out from the input data. Read them; they are not set.

AttributeUnitDescription
b:loc_name·Name

Related

← ElmLnesec Line Sub-Section · ElmTow Line Couplings →