ElmZone attributesPowerFactory Zone

Every attribute of the PowerFactory Zone (ElmZone): 16 input parameters and 314 result variables, with units and meaning. Copy a name into GetAttribute or SetAttribute.

What ElmZone is

A zone: a group of elements for summary results and for scaling loads and generation of one part of the network together.

Class
ElmZone, element class
PowerFactory name
Zone
Attributes
16 input parameters and 314 result variables, in 6 calculations

Read and write ElmZone in Python

import powerfactory

app = powerfactory.GetApplication()          # GetApplicationExt() from outside PowerFactory

for obj in app.GetCalcRelevantObjects("*.ElmZone"):
    print(obj.loc_name, obj.GetAttribute("loc_name")) # Name

obj = app.GetCalcRelevantObjects("*.ElmZone")[0]
obj.SetAttribute("loc_name", "Zone 1")        # rename the zone
  • An input parameter is read and written with or without its e: prefix: GetAttribute("outserv") and GetAttribute("e:outserv") give the same value.
  • RMS and EMT variables change over time: record them in a results object (ElmRes) to read the whole curve. GetAttribute after a run gives the value at the last time step.

ElmZone input parameters

The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.

AttributeUnitDescription
loc_name·Name
chr_name·Characteristic Name
for_name·Foreign Key
dat_src·Data source
appr_modby·Modified by
appr_status·Status
icolor·Colour
iInterChg·Consider Interchange Schedule
isConsSpinReserve·Min. spinning reserve constraint
curscale·Load Scaling Factor
windscale·Wind Generation Scaling Factor
InterPsetMWScheduled Active Power Interchange
spinReserveMWSpinning reserve
appr_modif·Modified
cimRdfId·RDF ID
desc·Description

ElmZone load flow results

Read after ComLdf with GetAttribute. c: calculation parameter.

AttributeUnitDescription
c:n_ele·Number of Elements
c:n_zones·Number of Connected Zones
c:n_volt·Number of Voltage Levels
c:n_bar·No. of Busbars
c:n_term·No. of Terminals
c:n_lne·No. of Lines
c:n_sym·No. of syn. Machines
c:n_asm·No. of asyn. Machines
c:n_stg·No. of Static Generators
c:n_pvs·No. of PV Systems
c:n_lod·No. of Loads
c:n_cust·No. of Customers
c:TotgenPMWTotal Generation, Active Power
c:TotgenQMvarTotal Generation, Reactive Power
c:TotconsPMWTotal Consumption, Active Power
c:TotconsQMvarTotal Consumption, Reactive Power
c:GenPMWGenerators, Active Power
c:GenQMvarGenerators, Reactive Power
c:GenSMVAGenerators, Apparent Power
c:Gencos·Generators, Power Factor
c:GenPnomMWGenerators, Nominal Active Power
c:GenQnomMvarGenerators, Nominal Reactive Power
c:GenSnomMVAGenerators, Nominal Apparent Power
c:GenPdiffMWGenerators, difference between nominal and actual active power
c:GenQdiffMvarGenerators, difference between nominal and actual reactive power
c:Gencosnom·Generators, Nominal Power Factor
c:GenPdispMWGenerators, Dispatch Active Power
c:GenPmismMWGenerators, difference between actual and dispatched active power
c:GenPspinresMWGenerators, difference between maximum and actual active power
c:GenQspinresMvarGenerators, difference between maximum and actual reactive power
c:MotPMWMotor Loads, Active Power
c:MotQMvarMotor Loads, Reactive Power
c:MotSMVAMotor Loads, Apparent Power
c:Motcos·Motor Loads, Power Factor
c:LoadPMWLoads, Active Power
c:LoadQMvarLoads, Reactive Power
c:LoadSMVALoads, Apparent Power
c:Loadcos·Loads, Power Factor
c:LoadPnomMWLoads, Nominal Active Power
c:LoadQnomMvarLoads, Nominal Reactive Power
c:LoadSnomMVALoads, Nominal Apparent Power
c:Loadcosnom·Loads, Nominal Power Factor
c:LoadPdiffMWLoads, difference between nominal and actual active power
c:LoadQdiffMvarLoads, difference between nominal and actual reactive power
c:LoadPdemMWLoads, Active Power Demand
c:LoadPmismMWLoads, difference between actual active power and demand
c:CompPMWCompensation (Losses)
c:CompQMvarCompensation, C
c:ComprQMvarCompensation, L
c:NetPMWExternal Networks, Active Power
c:NetQMvarExternal Networks, Reactive Power
c:NetSMVAExternal Networks, Apparent Power
c:Netcos·External Networks, Power Factor
c:InterPMWInterchange Flow, Active Power
c:InterQMvarInterchange Flow, Reactive Power
c:LossPMWLosses, Active Power
c:LossQMvarLosses, Reactive Power
c:LossPldMWLosses, Active Power (load)
c:LossQldMvarLosses, Reactive Power (load)
c:LossPnldMWLosses, Active Power (no load)
c:LossQnldMvarLosses, Reactive Power (no load)
c:LossPlneMWLine Losses, Active Power
c:LossQlneMvarLine Losses, Reactive Power
c:LossPldlneMWLine Losses, Active Power (load)
c:LossQldlneMvarLine Losses, Reactive Power (load)
c:LossPnldlneMWLine Losses, Active Power (no load)
c:LossQnldlneMvarLine Losses, Reactive Power (no load)
c:LossPtrfMWTransformer Losses, Active Power
c:LossQtrfMvarTransformer Losses, Reactive Power
c:LossPldtrfMWTransformer Losses, Active Power (load)
c:LossQldtrfMvarTransformer Losses, Reactive Power (load)
c:LossPnldtrfMWTransformer Losses, Active Power (no load)
c:LossQnldtrfMvarTransformer Losses, Reactive Power (no load)
c:TotLoadPMWTotal Load, Active Power
c:TotLoadQMvarTotal Load, Reactive Power
c:TotLoadSMVATotal Load, Apparent Power
c:TotLoadcos·Total Load, Power Factor
c:TotPMWTotal Demand
c:UnsupPMWUnsupplied Demand
c:SupPMWSupplied Demand
c:ExportPMWExport, Active Power
c:ExportQMvarExport, Reactive Power
c:ImportPMWImport, Active Power
c:ImportQMvarImport, Reactive Power
c:cst_dispUSD/hTotal Production Costs
c:RUC_LeadMvarUsed Reactive Capacity Lead
c:RUC_LagMvarUsed Reactive Capacity Lag
c:RSC_LeadMvarSpare Reactive Capacity Lead
c:RSC_LagMvarSpare Reactive Capacity Lag
c:Q_shgainMvarReactive Power Shunt Gain
c:ConnMvar_maxMvarConnected MVAR Capacity (max)
c:ConnMvar_minMvarConnected MVAR Capacity (min)
c:NrOvlBranch·Number of overloaded branch components
c:NrTermMin·Number of terminals below their minimum voltage limit
c:NrTermMax·Number of terminals above their maximum voltage limit
c:Maxloading%Maximum Loading
c:NrGenQMax·Number of generators above their maximum reactive power limit
c:NrGenQMin·Number of generators below their minimum reactive power limit
c:uminp.u.Minimum voltage of all terminals
c:umaxp.u.Maximum voltage of all terminals
c:uphtminp.u.Minimum voltage of all terminals
c:uphtmaxp.u.Maximum voltage of all terminals

ElmZone rms simulation results

Read after ComInc (RMS) with GetAttribute. c: calculation parameter.

AttributeUnitDescription
c:PgenMWGenerators, Active Power
c:QgenMvarGenerators, Reactive Power
c:SgenMVAGenerators, Apparent Power
c:cosgen·Generators, Power Factor
c:PmotMWMotor Loads, Active Power
c:QmotMvarMotor Loads, Reactive Power
c:SmotMVAMotor Loads, Apparent Power
c:cosmot·Motor Loads, Power Factor
c:PloadMWLoads, Active Power
c:QloadMvarLoads, Reactive Power
c:SloadMVALoads, Apparent Power
c:cosload·Loads, Power Factor
c:PcompMWCompensation (Losses)
c:QcompMvarCompensation, C
c:QcomprMvarCompensation, L
c:PnetMWExternal Networks, Active Power
c:QnetMvarExternal Networks, Reactive Power
c:SnetMVAExternal Networks, Apparent Power
c:cosnet·External Networks, Power Factor
c:PinterMWInterchange Flow, Active Power
c:QinterMvarInterchange Flow, Reactive Power
c:PlossMWLosses, Active Power
c:QlossMvarLosses, Reactive Power
c:PtMWTurbine Power
c:PresMWAvailable-Reserve

ElmZone emt simulation results

Read after ComInc (EMT) with GetAttribute. c: calculation parameter.

AttributeUnitDescription
c:PgenMWGenerators, Active Power
c:QgenMvarGenerators, Reactive Power
c:SgenMVAGenerators, Apparent Power
c:cosgen·Generators, Power Factor
c:PmotMWMotor Loads, Active Power
c:QmotMvarMotor Loads, Reactive Power
c:SmotMVAMotor Loads, Apparent Power
c:cosmot·Motor Loads, Power Factor
c:PloadMWLoads, Active Power
c:QloadMvarLoads, Reactive Power
c:SloadMVALoads, Apparent Power
c:cosload·Loads, Power Factor
c:PcompMWCompensation (Losses)
c:QcompMvarCompensation, C
c:QcomprMvarCompensation, L
c:PnetMWExternal Networks, Active Power
c:QnetMvarExternal Networks, Reactive Power
c:SnetMVAExternal Networks, Apparent Power
c:cosnet·External Networks, Power Factor
c:PinterMWInterchange Flow, Active Power
c:QinterMvarInterchange Flow, Reactive Power
c:PlossMWLosses, Active Power
c:QlossMvarLosses, Reactive Power
c:PtMWTurbine Power
c:PresMWAvailable Reserve

ElmZone dc load flow results

Read after ComLdf (DC) with GetAttribute. c: calculation parameter.

AttributeUnitDescription
c:n_ele·Number of Elements
c:n_zones·Number of Connected Zones
c:n_volt·Number of Voltage Levels
c:n_bar·No. of Busbars
c:n_term·No. of Terminals
c:n_lne·No. of Lines
c:n_sym·No. of syn. Machines
c:n_asm·No. of asyn. Machines
c:n_stg·No. of Static Generators
c:n_pvs·No. of PV Systems
c:n_lod·No. of Loads
c:n_cust·Number of Customers
c:TotgenPMWTotal Generation, Active Power
c:TotconsPMWTotal Consumption, Active Power
c:GenPMWGenerators, Active Power
c:GenPnomMWGenerators, Nominal Active Power
c:GenPdiffMWGenerators, difference between nominal and actual active power
c:GenPdispMWGenerators, Dispatch Active Power
c:GenPmismMWGenerators, difference between actual and dispatched active power
c:GenPspinresMWGenerators, difference between maximum and actual active power
c:MotPMWMotor Loads, Active Power
c:LoadPMWLoads, Active Power
c:LoadPnomMWLoads, Nominal Active Power
c:LoadPdiffMWLoads, difference between nominal and actual active power
c:LoadPdemMWLoads, Active Power Demand
c:LoadPmismMWLoads, difference between actual active power and demand
c:NetPMWExternal Networks, Active Power
c:InterPMWInterchange Flow, Active Power
c:TotLoadPMWTotal Load, Active Power
c:TotPMWTotal Demand
c:UnsupPMWUnsupplied Demand
c:SupPMWSupplied Demand
c:ExportPMWExport, Active Power
c:ImportPMWImport, Active Power
c:cst_dispUSD/hTotal Production Costs
c:NrOvlBranch·Number of overloaded branch components
c:Maxloading%Maximum Loading

Read after ComMod with GetAttribute. c: calculation parameter.

AttributeUnitDescription
c:PgenMWGenerators, Active Power
c:QgenMvarGenerators, Reactive Power
c:SgenMVAGenerators, Apparent Power
c:cosgen·Generators, Power Factor
c:PmotMWMotor Loads, Active Power
c:QmotMvarMotor Loads, Reactive Power
c:SmotMVAMotor Loads, Apparent Power
c:cosmot·Motor Loads, Power Factor
c:PloadMWLoads, Active Power
c:QloadMvarLoads, Reactive Power
c:SloadMVALoads, Apparent Power
c:cosload·Loads, Power Factor
c:PcompMWCompensation (Losses)
c:QcompMvarCompensation, C
c:QcomprMvarCompensation, L
c:PnetMWExternal Networks, Active Power
c:QnetMvarExternal Networks, Reactive Power
c:SnetMVAExternal Networks, Apparent Power
c:cosnet·External Networks, Power Factor
c:PinterMWInterchange Flow, Active Power
c:QinterMvarInterchange Flow, Reactive Power
c:PlossMWLosses, Active Power
c:QlossMvarLosses, Reactive Power
c:PtMWTurbine Power
c:PresMWAvailable-Reserve

ElmZone optimal power flow results

Read after ComOpf with GetAttribute. c: calculation parameter.

AttributeUnitDescription
c:n_ele·Number of Elements
c:n_zones·Number of Connected Zones
c:n_volt·Number of Voltage Levels
c:n_bar·No. of Busbars
c:n_term·No. of Terminals
c:n_lne·No. of Lines
c:n_sym·No. of syn. Machines
c:n_asm·No. of asyn. Machines
c:n_stg·No. of Static Generators
c:n_pvs·No. of PV Systems
c:n_lod·No. of Loads
c:n_cust·No. of Customers
c:TotgenPMWTotal Generation, Active Power
c:TotgenQMvarTotal Generation, Reactive Power
c:TotconsPMWTotal Consumption, Active Power
c:TotconsQMvarTotal Consumption, Reactive Power
c:GenPMWGenerators, Active Power
c:GenQMvarGenerators, Reactive Power
c:GenSMVAGenerators, Apparent Power
c:Gencos·Generators, Power Factor
c:GenPnomMWGenerators, Nominal Active Power
c:GenQnomMvarGenerators, Nominal Reactive Power
c:GenSnomMVAGenerators, Nominal Apparent Power
c:GenPdiffMWGenerators, difference between nominal and actual active power
c:GenQdiffMvarGenerators, difference between nominal and actual reactive power
c:Gencosnom·Generators, Nominal Power Factor
c:GenPdispMWGenerators, Dispatch Active Power
c:GenPmismMWGenerators, difference between actual and dispatched active power
c:GenPspinresMWGenerators, difference between maximum and actual active power
c:GenQspinresMvarGenerators, difference between maximum and actual reactive power
c:MotPMWMotor Loads, Active Power
c:MotQMvarMotor Loads, Reactive Power
c:MotSMVAMotor Loads, Apparent Power
c:Motcos·Motor Loads, Power Factor
c:LoadPMWLoads, Active Power
c:LoadQMvarLoads, Reactive Power
c:LoadSMVALoads, Apparent Power
c:Loadcos·Loads, Power Factor
c:LoadPnomMWLoads, Nominal Active Power
c:LoadQnomMvarLoads, Nominal Reactive Power
c:LoadSnomMVALoads, Nominal Apparent Power
c:Loadcosnom·Loads, Nominal Power Factor
c:LoadPdiffMWLoads, difference between nominal and actual active power
c:LoadQdiffMvarLoads, difference between nominal and actual reactive power
c:LoadPdemMWLoads, Active Power Demand
c:LoadPmismMWLoads, difference between actual active power and demand
c:CompPMWCompensation (Losses)
c:CompQMvarCompensation, C
c:ComprQMvarCompensation, L
c:NetPMWExternal Networks, Active Power
c:NetQMvarExternal Networks, Reactive Power
c:NetSMVAExternal Networks, Apparent Power
c:Netcos·External Networks, Power Factor
c:InterPMWInterchange Flow, Active Power
c:InterQMvarInterchange Flow, Reactive Power
c:LossPMWLosses, Active Power
c:LossQMvarLosses, Reactive Power
c:LossPldMWLosses, Active Power (load)
c:LossQldMvarLosses, Reactive Power (load)
c:LossPnldMWLosses, Active Power (no load)
c:LossQnldMvarLosses, Reactive Power (no load)
c:LossPlneMWLine Losses, Active Power
c:LossQlneMvarLine Losses, Reactive Power
c:LossPldlneMWLine Losses, Active Power (load)
c:LossQldlneMvarLine Losses, Reactive Power (load)
c:LossPnldlneMWLine Losses, Active Power (no load)
c:LossQnldlneMvarLine Losses, Reactive Power (no load)
c:LossPtrfMWTransformer Losses, Active Power
c:LossQtrfMvarTransformer Losses, Reactive Power
c:LossPldtrfMWTransformer Losses, Active Power (load)
c:LossQldtrfMvarTransformer Losses, Reactive Power (load)
c:LossPnldtrfMWTransformer Losses, Active Power (no load)
c:LossQnldtrfMvarTransformer Losses, Reactive Power (no load)
c:TotLoadPMWTotal Load, Active Power
c:TotLoadQMvarTotal Load, Reactive Power
c:TotLoadSMVATotal Load, Apparent Power
c:TotLoadcos·Total Load, Power Factor
c:TotPMWTotal Demand
c:UnsupPMWUnsupplied Demand
c:SupPMWSupplied Demand
c:ExportPMWExport, Active Power
c:ExportQMvarExport, Reactive Power
c:ImportPMWImport, Active Power
c:ImportQMvarImport, Reactive Power
c:cst_dispUSD/hTotal Production Costs
c:RUC_LeadMvarUsed Reactive Capacity Lead
c:RUC_LagMvarUsed Reactive Capacity Lag
c:RSC_LeadMvarSpare Reactive Capacity Lead
c:RSC_LagMvarSpare Reactive Capacity Lag
c:Q_shgainMvarReactive Power Shunt Gain
c:ConnMvar_maxMvarConnected MVAR Capacity (max)
c:ConnMvar_minMvarConnected MVAR Capacity (min)
c:NrOvlBranch·Number of overloaded branch components
c:NrTermMin·Number of terminals below their minimum voltage limit
c:NrTermMax·Number of terminals above their maximum voltage limit
c:Maxloading%Maximum Loading
c:NrGenQMax·Number of generators above their maximum reactive power limit
c:NrGenQMin·Number of generators below their minimum reactive power limit
c:uminp.u.Minimum voltage of all terminals
c:umaxp.u.Maximum voltage of all terminals

ElmZone basic data

b: values are worked out from the input data. Read them; they are not set.

AttributeUnitDescription
b:loc_name·Name
b:n_ele·Number of Elements
b:n_zones·Number of Connected Zones
b:scale·Load Scaling Factor
b:scaleWind·Wind Generation Scaling Factor

Related

← ElmTrfstat Secondary Substation · ElmFile Measurement File →