Parameters
32, in 3 groups; 23 carry a unit
Read from
PSCAD 5.0.0, 2026-11-07

Read and write master:arrester in Python

import mhi.pscad

pscad = mhi.pscad.connect()              # the PSCAD that is open; launch() starts one
project = pscad.project("my_case")       # a case loaded in the workspace

for comp in project.find_all("master:arrester"):   # the exact definition, namespace first
    params = comp.parameters()           # every parameter, as PSCAD holds it
    print(str(params["VSCAL"]))          # Arrester Voltage Rating, in kV

comp = project.find_all("master:arrester")[0]
comp.parameters(VSCAL="320 [kV]")        # a value that carries a unit is written with it
  • A parameter is named exactly as in the table, letter case included: parameters() gives every one of them in a dictionary, and a name the component does not have is refused.
  • A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (str(...)) or the unit is lost. PSCAD keeps a written unit as it is given: "2500 [mohm]" stays in mohm.
  • A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
  • find_all() takes the exact definition only. A wildcard or a bare name without master: comes back empty; the Builder's px_find walks the pages for those.

The Builder's runtime does the same with the unit handled for you: px_get(comp, "VSCAL") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.

Configuration

ParameterUnitDefaultDescription
CnfgChoice·DEFAULTI-V CharacteristicConfigure to use default characteristics or specified characteristics from a file or tableWritten as DEFAULT (Default), TABLE (User defined (table)), EXTERNAL_DATA_FILE (User defined (external data file))
CurrText··Label for Current [kA]
ENABInteger·1Enable Non-Linear CharacteristicEnter 1 to enable or 0 to disable, or enter a signal name to dynamically change between enable and disableRange -2147483648 to 2147483647
EnergyText··Label for Energy [kJoules]
FileText·datafileFile NameEnter the name of file with the extensionUsed when Cnfg==2
ISCALReal·1.0Number of Parallel Arrester StacksNumber of parallel arresters to be modelledAt least 0
NameText··Arrester Name
NpntsInteger·20Maximum Number of Points in the FileActual number of points may be less than this numberRange 10 to 2147483647Used when (Cnfg==2)
VSCALRealkV160.0Arrester Voltage RatingRater voltage of the arresterAt least 0.001
pathChoice·RELATIVEPath to the Data File is given asSpecify whether filename is given as a relative name or absolute nameWritten as RELATIVE (Relative pathname), ABSOLUTE (Absolute pathname)Used when Cnfg==2

I-V Characteristic (Current)

ParameterUnitDefaultDescription
X1RealkA0.001Point 1 - CurrentAt least 0Used when (Cnfg==1)
X10RealkA2.8Point 10 - CurrentAt least 0Used when (Cnfg==1)
X11RealkA200.0Point 11 - CurrentAt least 0Used when (Cnfg==1)
X2RealkA0.01Point 2 - CurrentAt least 0Used when (Cnfg==1)
X3RealkA0.1Point 3 - CurrentAt least 0Used when (Cnfg==1)
X4RealkA0.2Point 4 - CurrentAt least 0Used when (Cnfg==1)
X5RealkA0.38Point 5 - CurrentAt least 0Used when (Cnfg==1)
X6RealkA0.65Point 6 - CurrentAt least 0Used when (Cnfg==1)
X7RealkA1.11Point 7 - CurrentAt least 0Used when (Cnfg==1)
X8RealkA1.5Point 8 - CurrentAt least 0Used when (Cnfg==1)
X9RealkA2.0Point 9 - CurrentAt least 0Used when (Cnfg==1)

I-V Characteristic (Voltage)

ParameterUnitDefaultDescription
Y1Realpu1.1Point 1 - Voltage in puAt least 0.2Used when (Cnfg==1)
Y10Realpu1.948Point 10 - Voltage in puAt least 0Used when (Cnfg==1)
Y11Realpu3.2Point 11 - Voltage in puAt least 0Used when (Cnfg==1)
Y2Realpu1.6Point 2 - Voltage in puAt least 0Used when (Cnfg==1)
Y3Realpu1.7Point 3 - Voltage in puAt least 0Used when (Cnfg==1)
Y4Realpu1.739Point 4 - Voltage in puAt least 0Used when (Cnfg==1)
Y5Realpu1.777Point 5 - Voltage in puAt least 0Used when (Cnfg==1)
Y6Realpu1.815Point 6 - Voltage in puAt least 0Used when (Cnfg==1)
Y7Realpu1.853Point 7 - Voltage in puAt least 0Used when (Cnfg==1)
Y8Realpu1.881Point 8 - Voltage in puAt least 0Used when (Cnfg==1)
Y9Realpu1.91Point 9 - Voltage in puAt least 0Used when (Cnfg==1)

Related