Current Transformer (JA Model) (Current Transformer - JA model), a component of PSCAD's Master Library, filed under transformers and reactors.
- Definition
master:ct_single- PSCAD name
- Current Transformer (JA Model)
- Category
- Transformers and reactors
- Parameters
- 22, in 4 groups; 9 carry a unit
- Read from
- PSCAD 5.0.0, 2026-11-07
Read and write master:ct_single in Python
import mhi.pscad
pscad = mhi.pscad.connect() # the PSCAD that is open; launch() starts one
project = pscad.project("my_case") # a case loaded in the workspace
for comp in project.find_all("master:ct_single"): # the exact definition, namespace first
params = comp.parameters() # every parameter, as PSCAD holds it
print(str(params["Area"])) # Area, in m*m
comp = project.find_all("master:ct_single")[0]
comp.parameters(Area="0.005202 [m*m]") # a value that carries a unit is written with it
- A parameter is named exactly as in the table, letter case included:
parameters()gives every one of them in a dictionary, and a name the component does not have is refused. - A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (
str(...)) or the unit is lost. PSCAD keeps a written unit as it is given:"2500 [mohm]"stays in mohm. - A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
find_all()takes the exact definition only. A wildcard or a bare name withoutmaster:comes back empty; the Builder'spx_findwalks the pages for those.
The Builder's runtime does the same with the unit handled for you: px_get(comp, "Area") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.
Main Data
| Parameter | Unit | Default | Description |
|---|---|---|---|
AreaReal | m*m | 2.601e-3 | AreaCross sectional area of the magnetic materialAt least 0.0001 |
BremnReal | T | 0.0 | Remanent Flux DensityRange -2 to 2 |
NameText | · | · | Name for IdentificationEnter a name for identification |
NpriInteger | · | 20 | Primary TurnsNumber of primary turnsRange 1 to 2147483647 |
NsecInteger | · | 200 | Secondary TurnsNumber of secondary turnsRange 1 to 2147483647 |
PathLReal | m | 0.6377 | Path LengthPath length of the magentic materialAt least 0.01 |
SecLReal | H | 0.8e-3 | Secondary InductanceAt least 0 |
SecRReal | ohm | 0.5 | Secondary ResistanceAt least 0 |
materialChoice | · | MATERIAL_1 | Magnetic MaterialWritten as CUSTOM_MATERIAL (custom material), MATERIAL_1 (material 1) |
Internal Outputs
| Parameter | Unit | Default | Description |
|---|---|---|---|
BText | · | B | Flux Density |
HText | · | H | Magnetomotive Force |
Magneitc Characteristics of the Material
| Parameter | Unit | Default | Description |
|---|---|---|---|
BETAReal | · | 0.96 | Parameter to Adjust K with MRange 0 to 0.98 |
CReal | · | 0.1 | Domain Flexing ParameterRange 0.001 to 0.5 |
F1Real | · | 2730.0 | Coefficient 1 of Anhysteretic CurveAt least 0 |
F2Real | · | 3209.0 | Coefficient 2 of Anhysteretic CurveAt least 0 |
F3Real | · | 20294.0 | Coefficient 3 of Anhysteretic CurveAt least 0 |
FbReal | · | 2.0 | Coefficient 4 of Anhysteretic CurveAt least 1 |
KReal | T | 5.0e-5 | Domain Pinning ParameterAt least 1E-07 |
MsatReal | A/m | 1.72e6 | Saturation Anhysteretic MagnetizationAt least 100000 |
alphaReal | · | 1.325e-05 | Interdomain CouplingAt least 1E-08 |
Burden
| Parameter | Unit | Default | Description |
|---|---|---|---|
BurLReal | H | 0.8e-3 | Burden InductanceAt least 0 |
BurRReal | ohm | 0.5 | Burden ResistanceAt least 0 |
Related