master:g6p200 parametersPSCAD 6 Pulse Bridge
Every parameter of the PSCAD 6 Pulse Bridge (master:g6p200): 25 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().
What master:g6p200 is
6 Pulse Bridge, a component of PSCAD's Master Library, filed under control blocks.
- Definition
master:g6p200- PSCAD name
- 6 Pulse Bridge
- Category
- Control blocks
- Parameters
- 25, in 4 groups; 10 carry a unit
- Read from
- PSCAD 5.0.0, 2026-11-07
Read and write master:g6p200 in Python
import mhi.pscad
pscad = mhi.pscad.connect() # the PSCAD that is open; launch() starts one
project = pscad.project("my_case") # a case loaded in the workspace
for comp in project.find_all("master:g6p200"): # the exact definition, namespace first
params = comp.parameters() # every parameter, as PSCAD holds it
print(str(params["CD"])) # Snubber Capacitance, in uF
comp = project.find_all("master:g6p200")[0]
comp.parameters(CD="0.1 [uF]") # a value that carries a unit is written with it
- A parameter is named exactly as in the table, letter case included:
parameters()gives every one of them in a dictionary, and a name the component does not have is refused. - A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (
str(...)) or the unit is lost. PSCAD keeps a written unit as it is given:"2500 [mohm]"stays in mohm. - A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
find_all()takes the exact definition only. A wildcard or a bare name withoutmaster:comes back empty; the Builder'spx_findwalks the pages for those.
The Builder's runtime does the same with the unit handled for you: px_get(comp, "CD") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.
Valve Data
| Parameter | Unit | Default | Description |
|---|---|---|---|
CDReal | uF | 0.05 | Snubber CapacitanceAt least 0.001Used when (SNUB) |
EBOReal | kV | 1.0E5 | Forward Breakover VoltageAt least 1 |
EFVDReal | kV | 0.0 | Forward Voltage DropRange 0 to 10 |
PFBChoice | · | NO | Protected Against Forward BreakoverIf Yes is selected, the valve group will send a firing pulse just before the Forward Breakover Voltage is exceeded, avoiding permanent failure to the thyristorWritten as NO (No), YES (Yes) |
RDReal | ohm | 5000.0 | Snubber ResistanceAt least 0.001Used when (SNUB) |
ROFFReal | ohm | 1.0E6 | Thyristor OFF ResistanceAt least 1 |
RONReal | ohm | 0.01 | Thyristor ON ResistanceAt least 0 |
RWSAFBChoice | · | SAME_AS_IN_FORWARD_BREAKOVER_VOLTAGE | Reverse Withstand VoltageSelect how to define reverse withstand voltageWritten as SAME_AS_IN_FORWARD_BREAKOVER_VOLTAGE (Same as in Forward Breakover Voltage), SPECIFY (Specify) |
RWVReal | kV | 1.0E5 | Reverse Withstand VoltageAt least 1Used when RWSAFB==1 |
TEXTReal | us | 0.0 | Minimum Extinction TimeThyristors will re-fire if the voltage exceeds Forward Voltage Drop within the this time since last turn offRange 0 to 1000 |
Configuration
| Parameter | Unit | Default | Description |
|---|---|---|---|
FPChoice | · | ANGLE_IN_RADIANS | Firing Order InputWritten as ANGLE_IN_RADIANS (Angle in Radians), ARRAY_OF_6_PULSES (Array of 6 Pulses), 6_PULSES_6_INTERP_TIMES (6 Pulses + 6 Interp. times), ANGLE_IN_DEGREES (Angle in Degrees) |
KVChoice | · | YY_OR_DD | Transformer Phase ConfigurationSelect +30, 0, -30 or 60 degreesWritten as 30_DEG (+30 Deg), YDLEAD (0 Deg (Y-Dlead)), YY_OR_DD (-30 Deg (Y-Y or D-D)), YDLAG (-60 Deg (Y-Dlag)) |
NameText | · | · | Name for IdentificationEnter a name for identificationRange 0 to 0 |
SNUBChoice | · | YES | Use Snubber CircuitSelect Yes or NoWritten as YES (Yes), NO (No) |
TblockReal | s | 0.04 | Unblock TimeThe valve group will be locked until this time has passedAt least 0 |
UPChoice | · | UP | Thyristor DirectionChoose Up or DownWritten as UP (Up), DOWN (Down) |
ViewChoice | · | SINGLE_LINE | Graphics DisplaySelect single line or three phaseWritten as 3_PHASE (3 phase view), SINGLE_LINE (Single line view) |
Internal Outputs
| Parameter | Unit | Default | Description |
|---|---|---|---|
FPNMText | · | · | Firing Pulse ArrayOptional name to monitor firing pulses [6] |
SCurrText | · | · | Snubber Circuit Current ArrayOptional name to monitor snubber circuit currents [6]Used when (SNUB) |
VCurrText | · | · | Valve Current ArrayOptional name to monitor valve currents [6] |
VVoltText | · | · | Valve Voltages ArrayOptional name to monitor valve voltage [6] |
PLO
| Parameter | Unit | Default | Description |
|---|---|---|---|
FRReal | Hz | 60.0 | Rated Frequency |
GIReal | · | 100.0 | PLO Integral Gain |
GPReal | · | 10.0 | PLO Proportional GainAt least 0 |
KPChoice | · | VOLTAGE | PLO Reference VoltageWritten as VOLTAGE (Bus Voltage), VOLTAGE_ZERO_SEQUENCE_REMOVED (Bus Voltage, Zero Sequence Removed) |
Related