master:hgov90defn parametersPSCAD hgov90defn
Every parameter of the PSCAD hgov90defn (master:hgov90defn): 25 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().
What master:hgov90defn is
hgov90defn (Hydro Governor), a component of PSCAD's Master Library, filed under machines, exciters and governors.
- Definition
master:hgov90defn- PSCAD name
- hgov90defn
- Category
- Machines, exciters and governors
- Parameters
- 25, in 4 groups; 12 carry a unit
- Read from
- PSCAD 5.0.0, 2026-11-07
Read and write master:hgov90defn in Python
import mhi.pscad
pscad = mhi.pscad.connect() # the PSCAD that is open; launch() starts one
project = pscad.project("my_case") # a case loaded in the workspace
for comp in project.find_all("master:hgov90defn"): # the exact definition, namespace first
params = comp.parameters() # every parameter, as PSCAD holds it
print(str(params["C1"])) # Inverse Gate Velocity Limit, in s/pu
comp = project.find_all("master:hgov90defn")[0]
comp.parameters(C1="9.6 [s/pu]") # a value that carries a unit is written with it
- A parameter is named exactly as in the table, letter case included:
parameters()gives every one of them in a dictionary, and a name the component does not have is refused. - A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (
str(...)) or the unit is lost. PSCAD keeps a written unit as it is given:"2500 [mohm]"stays in mohm. - A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
find_all()takes the exact definition only. A wildcard or a bare name withoutmaster:comes back empty; the Builder'spx_findwalks the pages for those.
The Builder's runtime does the same with the unit handled for you: px_get(comp, "C1") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.
Governor Parameters
| Parameter | Unit | Default | Description |
|---|---|---|---|
C1Real | s/pu | 4.8 | Inverse Gate Velocity LimitAt least 0.001 |
C2Real | s | 0.1 | Gate Velocity Time ConstantAt least 0.001 |
C3Real | · | 0.04 | Permanent Droop GainAt least 0.001 |
C4Real | pu/s | 0.22 | Gate Position Control Rate LimitAt least 0.001 |
C5Real | · | 0.0 | Temporary Droop GainAt least 0 |
C6Real | s | 1.0 | Temporary Droop Time ConstantAt least 0.001 |
T1Real | · | 0.88 | Controller Derivative GainAt least 0 |
T2Real | · | 3.7 | Controller Proportional GainAt least 0.001 |
T3Real | · | 0.44 | Controller Integral GainAt least 0.001 |
T4Real | s | 0.02 | Controller Real Pole Time ConstAt least 0.001 |
T5Real | s | 0.8 | Turbine Lead Time ConstantAt least 0.001 |
T6Real | s | 0.4 | Turbine Lag Time ConstantAt least 0.001 |
TSReal | s | 0.05 | Governor Time ConstantAt least 0.001 |
TmaxReal | pu | 0.957 | Maximum Mechanical TorqueAt least 0.001 |
fReal | Hz | 60.0 | Base FrequencyAt least 0.001 |
Monitoring Internal Variables
| Parameter | Unit | Default | Description |
|---|---|---|---|
Chn1Text | · | · | Name for 1st monitored STOR |
Chn2Text | · | · | Name for 2nd monitored STOR |
Mon1Integer | · | 1 | Monitor internal storage NEXC +Range 1 to 25 |
Mon2Integer | · | 1 | Monitor internal storage NEXC +Range 1 to 25 |
Configuration
| Parameter | Unit | Default | Description |
|---|---|---|---|
IandInteger | · | 1 | No of activating and-gate inputs [1-2]Range 1 to 2 |
IshnmInteger | · | 0 | Show units for icon inputs ? [0-1]Range 0 to 1 |
ItrqiInteger | · | 1 | Icon Input: Initializing torque [0-1]Range 0 to 1 |
ItrqrInteger | · | 0 | Icon Input: Torque reference [0-1]Range 0 to 1 |
Operation Settings
| Parameter | Unit | Default | Description |
|---|---|---|---|
TrqiReal | pu | 0.0 | Initial Mechanical TorqueRange 0 to 10Used when (Itrqr==0)||(Itrqi==0) |
TrqrReal | pu | 0.0 | Torque Ref. (offsets droop)Range 0 to 10Used when (Itrqr==0)||(Itrqi==0) |
Related
← master:exci35defn exci35defn · master:hy_gov Hydro Governor →