master:hydro_gov parametersPSCAD Hydro Governor/Turbine

Every parameter of the PSCAD Hydro Governor/Turbine (master:hydro_gov): 18 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().

What master:hydro_gov is

Hydro Governor/Turbine, a component of PSCAD's Master Library, filed under machines, exciters and governors.

Definition
master:hydro_gov
PSCAD name
Hydro Governor/Turbine
Category
Machines, exciters and governors
Parameters
18, in 1 group; 10 carry a unit
Read from
PSCAD 5.0.0, 2026-11-07

Read and write master:hydro_gov in Python

import mhi.pscad

pscad = mhi.pscad.connect()              # the PSCAD that is open; launch() starts one
project = pscad.project("my_case")       # a case loaded in the workspace

for comp in project.find_all("master:hydro_gov"):   # the exact definition, namespace first
    params = comp.parameters()           # every parameter, as PSCAD holds it
    print(str(params["C1"]))             # Inverse Gate Velocity Limit, in s/pu

comp = project.find_all("master:hydro_gov")[0]
comp.parameters(C1="9.6 [s/pu]")         # a value that carries a unit is written with it
  • A parameter is named exactly as in the table, letter case included: parameters() gives every one of them in a dictionary, and a name the component does not have is refused.
  • A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (str(...)) or the unit is lost. PSCAD keeps a written unit as it is given: "2500 [mohm]" stays in mohm.
  • A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
  • find_all() takes the exact definition only. A wildcard or a bare name without master: comes back empty; the Builder's px_find walks the pages for those.

The Builder's runtime does the same with the unit handled for you: px_get(comp, "C1") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.

Parameters

ParameterUnitDefaultDescription
C1Reals/pu4.8Inverse Gate Velocity Limit
C2Reals0.1Gate Velocity Time Constant
C3Real·0.04Permanent Droop Gain
C4Realpu/s0.22Gate Position Control Rate Limit
C5Real·0.0Temporary Droop Gain
C6Reals1.0Temporary Droop Time Constant
EnabInteger·1Initialization SwitchType=Integer, Symbol=Enab, Content=Variable, 0 for initialization, 1 for normal operationRange -2147483648 to 2147483647
NameText··Name for IdentificationEnter a name for identification
T1Real·0.88Controller Real Pole Gain
T2Real·3.7Controller Proportional Gain
T3Real·0.44Controller Integral Gain
T4Reals0.02Controller Real Pole Time Constant
T5Reals0.8Turbine Lead Time Constant
T6Reals0.4Turbine Lag Time Constant
TSReals0.05Governor Time Constant
Tm0sReals0.02Time Constant for Smoothing Tm0Range 0.001 to 0.05
TmaxReal·0.957Conversion Constant
fRealHz60.0Base Frequency

Related