master:Line_BusWork_3V parametersPSCAD 3 Conductor Vertical Bus Bar
Every parameter of the PSCAD 3 Conductor Vertical Bus Bar (master:Line_BusWork_3V): 12 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().
What master:Line_BusWork_3V is
3 Conductor Vertical Bus Bar (Line Constants 3 Conductor Vertical Bus Bar), a component of PSCAD's Master Library, filed under lines, cables and towers.
- Definition
master:Line_BusWork_3V- PSCAD name
- 3 Conductor Vertical Bus Bar
- Category
- Lines, cables and towers
- Parameters
- 12, in 1 group; 7 carry a unit
- Read from
- PSCAD 5.0.0, 2026-11-07
Read and write master:Line_BusWork_3V in Python
import mhi.pscad
pscad = mhi.pscad.connect() # the PSCAD that is open; launch() starts one
project = pscad.project("my_case") # a case loaded in the workspace
for comp in project.find_all("master:Line_BusWork_3V"): # the exact definition, namespace first
params = comp.parameters() # every parameter, as PSCAD holds it
print(str(params["DCResC"])) # Conductor DC Resistance per unit length, in ohm/km
comp = project.find_all("master:Line_BusWork_3V")[0]
comp.parameters(DCResC="0.14304 [ohm/km]") # a value that carries a unit is written with it
- A parameter is named exactly as in the table, letter case included:
parameters()gives every one of them in a dictionary, and a name the component does not have is refused. - A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (
str(...)) or the unit is lost. PSCAD keeps a written unit as it is given:"2500 [mohm]"stays in mohm. - A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
find_all()takes the exact definition only. A wildcard or a bare name withoutmaster:comes back empty; the Builder'spx_findwalks the pages for those.
The Builder's runtime does the same with the unit handled for you: px_get(comp, "DCResC") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.
Bus Data
| Parameter | Unit | Default | Description |
|---|---|---|---|
BNameText | · | B3V | Bus Name |
DCResCReal | ohm/km | 0.0715198 | Conductor DC Resistance per unit lengthRange 0 to 100 |
NC1Integer | · | 1 | Connection Number for C1Range 1 to 30 |
NC2Integer | · | 2 | Connection Number for C2Range 1 to 30 |
NC3Integer | · | 3 | Connection Number for C3Range 1 to 30 |
PERMCReal | · | 1.0 | Conductor Relative PermeabilityRange 0 to 1 |
RadiusCReal | m | 0.035306 | Conductor Outer RadiusRange 0 to 10 |
ShuntGReal | mho/m | 1.0E-11 | Shunt ConductanceRange 0 to 1 |
XReal | m | 0 | Relative X Position of Bus Centre on Right of WayRange -1e+006 to 1e+006 |
YReal | m | 5 | Bus Height Above GroundRange 0 to 1e+006 |
Y2Real | m | 0.5 | Vertical Spacing Between PhasesRange 0 to 1e+006 |
thicknessReal | m | 0.002921 | Conductor ThicknessRange 0 to 10 |
Related