master:oos_mho68 parametersPSCAD Mho 68

Every parameter of the PSCAD Mho 68 (master:oos_mho68): 14 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().

What master:oos_mho68 is

Mho 68 (Out of step relay - mho characteristics), a component of PSCAD's Master Library, filed under control blocks.

Definition
master:oos_mho68
PSCAD name
Mho 68
Category
Control blocks
Parameters
14, in 4 groups; 3 carry a unit
Read from
PSCAD 5.0.0, 2026-11-07

Read and write master:oos_mho68 in Python

import mhi.pscad

pscad = mhi.pscad.connect()              # the PSCAD that is open; launch() starts one
project = pscad.project("my_case")       # a case loaded in the workspace

for comp in project.find_all("master:oos_mho68"):   # the exact definition, namespace first
    params = comp.parameters()           # every parameter, as PSCAD holds it
    print(str(params["TM"]))             # Maximum Blocking Time, in s

comp = project.find_all("master:oos_mho68")[0]
comp.parameters(TM="4 [s]")              # a value that carries a unit is written with it
  • A parameter is named exactly as in the table, letter case included: parameters() gives every one of them in a dictionary, and a name the component does not have is refused.
  • A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (str(...)) or the unit is lost. PSCAD keeps a written unit as it is given: "2500 [mohm]" stays in mohm.
  • A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
  • find_all() takes the exact definition only. A wildcard or a bare name without master: comes back empty; the Builder's px_find walks the pages for those.

The Builder's runtime does the same with the unit handled for you: px_get(comp, "TM") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.

Main

ParameterUnitDefaultDescription
EPChoice·DISABLEEnable Power Swing BlockingSelect Enable or DisableWritten as DISABLE (Disable), ENABLE (Enable)
NameText··Name for IdentificationEnter a name for identification
TMReals2.0Maximum Blocking TimeRange -1000 to 1000
TZ6Reals0.04Power Swing Blocking Time delayRange 0.03 to 0.08

Internal Timer Output

ParameterUnitDefaultDescription
INTDTText·IntDTPower Swing Blocking Timer
Z5Text·Z5Zone 5 Output
Z6Text·Z6Zone 6 Output

Configuration

ParameterUnitDefaultDescription
R5Real·1.0Zone 5 RadiusAt least 1E-307
R6Real·2.0Zone 6 RadiusAt least 1E-307
XYChoice·X_YCoordinates of the CirclesSelect Cartesian or Polar coordinatesWritten as X_Y ((X,Y)), Z_THETA ((Z,theta))

Coordinates of the Centre

ParameterUnitDefaultDescription
X1Real·0.0XUsed when xy==0
Y1Real·0.0YUsed when xy==0
ZReal·0.0ZUsed when xy==1
thetaRealrad0.0ThetaUsed when xy==1

Related