master:oos_poly68 parametersPSCAD Polygon 68

Every parameter of the PSCAD Polygon 68 (master:oos_poly68): 15 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().

What master:oos_poly68 is

Polygon 68 (Out of step relay - polygon characteristics), a component of PSCAD's Master Library, filed under control blocks.

Definition
master:oos_poly68
PSCAD name
Polygon 68
Category
Control blocks
Parameters
15, in 4 groups; 2 carry a unit
Read from
PSCAD 5.0.0, 2026-11-07

Read and write master:oos_poly68 in Python

import mhi.pscad

pscad = mhi.pscad.connect()              # the PSCAD that is open; launch() starts one
project = pscad.project("my_case")       # a case loaded in the workspace

for comp in project.find_all("master:oos_poly68"):   # the exact definition, namespace first
    params = comp.parameters()           # every parameter, as PSCAD holds it
    print(str(params["TD"]))             # Power Swing Blocking Time delay, in s

comp = project.find_all("master:oos_poly68")[0]
comp.parameters(TD="0.8 [s]")            # a value that carries a unit is written with it
  • A parameter is named exactly as in the table, letter case included: parameters() gives every one of them in a dictionary, and a name the component does not have is refused.
  • A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (str(...)) or the unit is lost. PSCAD keeps a written unit as it is given: "2500 [mohm]" stays in mohm.
  • A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
  • find_all() takes the exact definition only. A wildcard or a bare name without master: comes back empty; the Builder's px_find walks the pages for those.

The Builder's runtime does the same with the unit handled for you: px_get(comp, "TD") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.

Main

ParameterUnitDefaultDescription
EPChoice·DISABLEEnable Power Swing BlockingSelect Enable or DisableWritten as DISABLE (Disable), ENABLE (Enable)
I2SETReal·2.0Restrain Negative CurrentRange 0 to 1000
NameText··Name for IdentificationEnter a name for identification
TDReals0.4Power Swing Blocking Time delayRange 0.008 to 160
TMReals2.0Maximum Blocking TimeRange 0.008 to 160

Internal Timer Output

ParameterUnitDefaultDescription
INTDTText·IntDTPower Swing Blocking Timer
INTMTText·IntMTMaximum Blocking Timer

Zone 5

ParameterUnitDefaultDescription
RL5Real·1.0Left Resistive ReachRange -1000 to 1000
RR5Real·1.0Right Resistive ReachRange -1000 to 1000
XB5Real·1.0Bottom Reactive ReachRange -1000 to 1000
XT5Real·1.0Top Reactive ReachRange -1000 to 1000

Zone 6

ParameterUnitDefaultDescription
RL6Real·1.0Left Resistive ReachRange -1000 to 1000
RR6Real·1.0Right Resistive ReachRange -1000 to 1000
XB6Real·1.0Bottom Reactive ReachRange -1000 to 1000
XT6Real·1.0Top Reactive ReachRange -1000 to 1000

Related

← master:polar_rec Polar Rectangular Coordinate Converter · master:prod_array Product of all elements →