master:oos_poly68 parametersPSCAD Polygon 68
Every parameter of the PSCAD Polygon 68 (master:oos_poly68): 15 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().
What master:oos_poly68 is
Polygon 68 (Out of step relay - polygon characteristics), a component of PSCAD's Master Library, filed under control blocks.
- Definition
master:oos_poly68- PSCAD name
- Polygon 68
- Category
- Control blocks
- Parameters
- 15, in 4 groups; 2 carry a unit
- Read from
- PSCAD 5.0.0, 2026-11-07
Read and write master:oos_poly68 in Python
import mhi.pscad
pscad = mhi.pscad.connect() # the PSCAD that is open; launch() starts one
project = pscad.project("my_case") # a case loaded in the workspace
for comp in project.find_all("master:oos_poly68"): # the exact definition, namespace first
params = comp.parameters() # every parameter, as PSCAD holds it
print(str(params["TD"])) # Power Swing Blocking Time delay, in s
comp = project.find_all("master:oos_poly68")[0]
comp.parameters(TD="0.8 [s]") # a value that carries a unit is written with it
- A parameter is named exactly as in the table, letter case included:
parameters()gives every one of them in a dictionary, and a name the component does not have is refused. - A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (
str(...)) or the unit is lost. PSCAD keeps a written unit as it is given:"2500 [mohm]"stays in mohm. - A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
find_all()takes the exact definition only. A wildcard or a bare name withoutmaster:comes back empty; the Builder'spx_findwalks the pages for those.
The Builder's runtime does the same with the unit handled for you: px_get(comp, "TD") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.
Main
| Parameter | Unit | Default | Description |
|---|---|---|---|
EPChoice | · | DISABLE | Enable Power Swing BlockingSelect Enable or DisableWritten as DISABLE (Disable), ENABLE (Enable) |
I2SETReal | · | 2.0 | Restrain Negative CurrentRange 0 to 1000 |
NameText | · | · | Name for IdentificationEnter a name for identification |
TDReal | s | 0.4 | Power Swing Blocking Time delayRange 0.008 to 160 |
TMReal | s | 2.0 | Maximum Blocking TimeRange 0.008 to 160 |
Internal Timer Output
| Parameter | Unit | Default | Description |
|---|---|---|---|
INTDTText | · | IntDT | Power Swing Blocking Timer |
INTMTText | · | IntMT | Maximum Blocking Timer |
Zone 5
| Parameter | Unit | Default | Description |
|---|---|---|---|
RL5Real | · | 1.0 | Left Resistive ReachRange -1000 to 1000 |
RR5Real | · | 1.0 | Right Resistive ReachRange -1000 to 1000 |
XB5Real | · | 1.0 | Bottom Reactive ReachRange -1000 to 1000 |
XT5Real | · | 1.0 | Top Reactive ReachRange -1000 to 1000 |
Zone 6
| Parameter | Unit | Default | Description |
|---|---|---|---|
RL6Real | · | 1.0 | Left Resistive ReachRange -1000 to 1000 |
RR6Real | · | 1.0 | Right Resistive ReachRange -1000 to 1000 |
XB6Real | · | 1.0 | Bottom Reactive ReachRange -1000 to 1000 |
XT6Real | · | 1.0 | Top Reactive ReachRange -1000 to 1000 |
Related
← master:polar_rec Polar Rectangular Coordinate Converter · master:prod_array Product of all elements →