master:phasorimp parametersPSCAD Harmonic Impedance

Every parameter of the PSCAD Harmonic Impedance (master:phasorimp): 11 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().

What master:phasorimp is

Harmonic Impedance (Interface to Harmonic Impedance Solution), a component of PSCAD's Master Library, filed under meters and output.

Definition
master:phasorimp
PSCAD name
Harmonic Impedance
Category
Meters and output
Parameters
11, in 1 group; 3 carry a unit
Read from
PSCAD 5.0.0, 2026-11-07

Read and write master:phasorimp in Python

import mhi.pscad

pscad = mhi.pscad.connect()              # the PSCAD that is open; launch() starts one
project = pscad.project("my_case")       # a case loaded in the workspace

for comp in project.find_all("master:phasorimp"):   # the exact definition, namespace first
    params = comp.parameters()           # every parameter, as PSCAD holds it
    print(str(params["Finc"]))           # Frequency Increment, in Hz

comp = project.find_all("master:phasorimp")[0]
comp.parameters(Finc="20 [Hz]")          # a value that carries a unit is written with it
  • A parameter is named exactly as in the table, letter case included: parameters() gives every one of them in a dictionary, and a name the component does not have is refused.
  • A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (str(...)) or the unit is lost. PSCAD keeps a written unit as it is given: "2500 [mohm]" stays in mohm.
  • A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
  • find_all() takes the exact definition only. A wildcard or a bare name without master: comes back empty; the Builder's px_find walks the pages for those.

The Builder's runtime does the same with the unit handled for you: px_get(comp, "Finc") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.

Main Configuration

ParameterUnitDefaultDescription
FNameText·Harm.outOutput FilenameRange 0 to 0
FTypeChoice·LINEAR_SCALEFrequency Increment TypeWritten as LINEAR_SCALE (Linear Scale), LOG_SCALE (Log Scale)
FUnitsChoice·HZFrequency Output UnitsWritten as HZ (Hz), RADIANS_SEC (Radians/Sec), LOG10_HZ (LOG10(Hz)), LOG10_RADIANS_SEC (LOG10(Radians/Sec))
FincRealHz10Frequency IncrementAt least 0Used when FType==0
FmaxRealHz2000Maximum FrequencyAt least 0
FminRealHz0Minimum FrequencyAt least 0
HTypeChoice·SEQUENCEImpedance Output TypeWritten as SEQUENCE (Sequence Impedances), PHASE (Phase Impedances)
HUnitsChoice·DEGImpedance Output UnitsWritten as DEG (Magnitude and Phase (Deg)), OHMS (Real, Imaginary (ohms))
NameText··Name for identificationEnter a name for identificationRange 0 to 0
NumFInteger·1000Number of FrequenciesRange 0 to 2147483647Used when FType==1
ViewChoice·DEFAULTViewSelect the desired graphical displayWritten as DEFAULT (Default), COMPACT (Compact)