master:pi_double_cct parametersPSCAD Double Circuit Pi section

Every parameter of the PSCAD Double Circuit Pi section (master:pi_double_cct): 66 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().

What master:pi_double_cct is

Double Circuit Pi section (Double Circuit Pi Section), a component of PSCAD's Master Library, filed under lines, cables and towers.

Definition
master:pi_double_cct
PSCAD name
Double Circuit Pi section
Category
Lines, cables and towers
Parameters
66, in 8 groups; 54 carry a unit
Read from
PSCAD 5.0.0, 2026-11-07

Read and write master:pi_double_cct in Python

import mhi.pscad

pscad = mhi.pscad.connect()              # the PSCAD that is open; launch() starts one
project = pscad.project("my_case")       # a case loaded in the workspace

for comp in project.find_all("master:pi_double_cct"):   # the exact definition, namespace first
    params = comp.parameters()           # every parameter, as PSCAD holds it
    print(str(params["BPUP1"]))          # Positive Sequence Capacitive Susceptance, in pu/m

comp = project.find_all("master:pi_double_cct")[0]
comp.parameters(BPUP1="0.00000346147 [pu/m]") # a value that carries a unit is written with it
  • A parameter is named exactly as in the table, letter case included: parameters() gives every one of them in a dictionary, and a name the component does not have is refused.
  • A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (str(...)) or the unit is lost. PSCAD keeps a written unit as it is given: "2500 [mohm]" stays in mohm.
  • A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
  • find_all() takes the exact definition only. A wildcard or a bare name without master: comes back empty; the Builder's px_find walks the pages for those.

The Builder's runtime does the same with the unit handled for you: px_get(comp, "BPUP1") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.

Per Unit Data

ParameterUnitDefaultDescription
BPUP1Realpu/m1.73073458E-6Positive Sequence Capacitive SusceptanceAt least 1E-307Used when PU==0
BPUZ1Realpu/m1.23404897E-6Zero Sequence Capacitive SusceptanceAt least 1E-307Used when (PU==0)&&(Estim==0)
BPUZmRealpu/m4.89777347e-8Zero Sequence Mutual Capacitive SusceptanceAt least 1E-307Used when (PU==0)&&(EstimM==0)
MVARealMVA100.0MVA for All PhasesAt least 1E-307
RPUP1Realpu/m6.86967845E-8Positive Sequence ResistanceAt least 1E-307
RPUZ1Realpu/m7.22669229E-7Zero Sequence ResistanceAt least 1E-307Used when Estim==0
RPUZmRealpu/m5.96870325e-7Zero Sequence Mutual ResistanceAt least 1E-307Used when Estim==0
VRRealkV230.0Rated Voltage L-LAt least 1E-307
XCPUP1Realpu*m5.77789346E5Positive Sequence Capacitive ReactanceAt least 1E-307Used when PU==1
XCPUZ1Realpu*m8.10340612E5Zero Sequence Capacitive ReactanceAt least 1E-307Used when (PU==1)&&(Estim==0)
XCPUZmRealpu*m2.041744E7Zero Sequence Mutual Capacitive ReactanceAt least 1E-307Used when (PU==1)&&(EstimM==0)
XLPUP1Realpu/m9.61469669E-7Positive Sequence Inductive ReactanceAt least 1E-307
XLPUZ1Realpu/m2.37992559E-6Zero Sequence Inductive ReactanceAt least 1E-307Used when Estim==0
XLPUZmRealpu/m8.07394866e-7Zero Sequence Mutual Inductive ReactanceAt least 1E-307Used when EstimM==0

Per Unit Data - 2nd Circuit

ParameterUnitDefaultDescription
BPUP2Realpu/m1.73073458E-6Positive Sequence Capacitive SusceptanceAt least 1E-307Used when PU==0
BPUZ2Realpu/m1.23404897E-6Zero Sequence Capacitive SusceptanceAt least 1E-307Used when (PU==0)&&(Estim==0)
RPUP2Realpu/m6.86967845E-8Positive Sequence ResistanceAt least 1E-307
RPUZ2Realpu/m7.22669229E-7Zero Sequence ResistanceAt least 1E-307Used when Estim==0
XCPUP2Realpu*m5.77789346E5Positive Sequence Capacitive ReactanceAt least 1E-307Used when PU==1
XCPUZ2Realpu*m8.10340612E5Zero Sequence Capacitive ReactanceAt least 1E-307Used when (PU==1)&&(Estim==0)
XLPUP2Realpu/m9.61469669E-7Positive Sequence Inductive ReactanceAt least 1E-307
XLPUZ2Realpu/m2.37992559E-6Zero Sequence Inductive ReactanceAt least 1E-307Used when Estim==0

Main Configuration

ParameterUnitDefaultDescription
ConfigChoice·IDENTICAL2 Circuits areIdential or DifferentWritten as IDENTICAL (Identical), DIFFERENT (Different)
EstimChoice·ENTEREnter 0 Sequence Data, or Estimate:Enter zero sequence data or estimate using given factorsWritten as ENTER (Enter), ESTIMATE (Estimate)
EstimMChoice·ENTEREnter 0 Sequence Mutual Data, or Estimate:Enter exact data or estimate using given factorsWritten as ENTER (Enter), ESTIMATE (Estimate)
FRealHz60.0Line Rated FrequencyAt least 1E-307
NameText·LineT-LINE NAME
PUChoice·R_X_B_PUEnter Impedance/Admittance Data in:Select one of the data formatsWritten as R_X_B_PU (R,X,B (P.U.)), R_XL_XC_PU (R,Xl,Xc (P.U.)), R_XL_XC_OHMS (R,Xl,Xc (Ohms)), ZSURGE_TAU (Zsurge,Tau..)
ViewChoice·SINGLE_LINEGraphics DisplaySelect graphical view single line or 3 phase viewWritten as 3_PHASE (3 phase view), SINGLE_LINE (Single line view)
lenRealm1.0E5Line LengthAt least 1E-307

Zero Sequence Estimation Parameters

ParameterUnitDefaultDescription
REstReal·10.520 Sequence R / Positive Sequence RAt least 1Used when Estim==1
REstMReal·0.8260 Sequence Mutual R / 0 Sequence R (C. 1)At least 1E-307Used when EstimM==1
TEstReal·1.32850 Sequence Travel Time / Positive Sequence TAUAt least 1Used when Estim==1
TEstMReal·0.1160 Seqence Mutual Travel Time / 0 Sequence Travel Time (C. 1)At least 1E-307Used when EstimM==1
ZEstReal·1.8630 Sequence Z / Positive Sequence ZAt least 1Used when Estim==1
ZEstMReal·2.9240 Sequence Mutual Z / 0 Sequence Z (C. 1)At least 1E-307Used when EstimM==1

Surge Impedance,Travel Time Data

ParameterUnitDefaultDescription
RTP1Realohm/m3.6340599E-5Positive Sequence ResistanceAt least 1E-307
RTZ1Realohm/m3.82292022E-4Zero Sequence ResistanceAt least 1E-307Used when Estim==0
RTZmRealohm/m3.15744402E-4Zero Sequence Mutual ResistanceAt least 1E-307Used when EstimM==0
TTP1Realms0.34217786Positive Sequence Travel TimeAt least 1E-307
TTZ1Realms0.4545867Zero Sequence Travel TimeAt least 1E-307Used when Estim==0
TTZmRealms0.0527486Zero Sequence Mutual Travel TimeAt least 1E-307Used when EstimM==0
ZTP1Realohm394.28316Positive Sequence Surge ImpedanceAt least 1E-307
ZTZ1Realohm734.6342Zero Sequence Surge ImpedanceAt least 1E-307Used when Estim==0
ZTZmRealohm2147.827Zero Sequence Mutual Surge ImpedanceAt least 1E-307Used when EstimM==0

Surge Impedance,Travel Time Data - 2nd Circuit

ParameterUnitDefaultDescription
RTP2Realohm/m3.6340599E-5Positive Sequence ResistanceAt least 1E-307
RTZ2Realohm/m3.82292022E-4Zero Sequence ResistanceAt least 1E-307Used when Estim==0
TTP2Realms0.34217786Positive Sequence Travel TimeAt least 1E-307
TTZ2Realms0.4545867Zero Sequence Travel TimeAt least 1E-307Used when Estim==0
ZTP2Realohm394.28316Positive Sequence Surge ImpedanceAt least 1E-307
ZTZ2Realohm734.6342Zero Sequence Surge ImpedanceAt least 1E-307Used when Estim==0

R, Xl, Xc Data (ohms)

ParameterUnitDefaultDescription
Rp1Realohm/m3.6340599E-5Positive Sequence ResistanceAt least 1E-307
Rz1Realohm/m3.82292022E-4Zero Sequence ResistanceAt least 1E-307Used when Estim==0
Rzm1Realohm/m3.15744402E-4Zero Sequence Mutual ResistanceAt least 1E-307Used when EstimM==0
XCp1RealMohm*m305.65056427Positive Sequence Capacitive ReactanceAt least 1E-307
XCz1RealMohm*m428.67018377Zero Sequence Capacitive ReactanceAt least 1E-307Used when Estim==0
XCzmRealMohm*m10800.8262Zero Sequence Mutual Capacitive ReactanceAt least 1E-307Used when EstimM==0
XLp1Realohm/m5.08617455E-4Positive Sequence Inductive ReactanceAt least 1E-307
XLz1Realohm/m1.258980635E-3Zero Sequence Inductive ReactanceAt least 1E-307Used when Estim==0
XLzmRealohm/m4.27111884E-4Zero Sequence Mutual Inductive ReactanceAt least 1E-307Used when EstimM==0

R, Xl, Xc Data (ohms) - 2nd Circuit

ParameterUnitDefaultDescription
Rp2Realohm/m3.6340599E-5Positive Sequence ResistanceAt least 1E-307
Rz2Realohm/m3.82292022E-4Zero Sequence ResistanceAt least 1E-307Used when Estim==0
XCp2RealMohm*m305.65056427Positive Sequence Capacitive ReactanceAt least 1E-307
XCz2RealMohm*m428.67018377Zero Sequence Capacitive ReactanceAt least 1E-307Used when Estim==0
XLp2Realohm/m5.08617455E-4Positive Sequence Inductive ReactanceAt least 1E-307
XLz2Realohm/m1.258980635E-3Zero Sequence Inductive ReactanceAt least 1E-307Used when Estim==0

Related

← master:newpi Coupled PI Section · master:Line_FreDep_Options Frequency Dependent (Mode) Model →