master:PUImpedanceBranch parametersPSCAD PU Impedance Branch
Every parameter of the PSCAD PU Impedance Branch (master:PUImpedanceBranch): 6 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().
What master:PUImpedanceBranch is
PU Impedance Branch (RLC branch in per unit values), a component of PSCAD's Master Library, filed under passive branches, loads and filters.
- Definition
master:PUImpedanceBranch- PSCAD name
- PU Impedance Branch
- Category
- Passive branches, loads and filters
- Parameters
- 6, in 1 group; 5 carry a unit
- Read from
- PSCAD 5.0.0, 2026-11-07
Read and write master:PUImpedanceBranch in Python
import mhi.pscad
pscad = mhi.pscad.connect() # the PSCAD that is open; launch() starts one
project = pscad.project("my_case") # a case loaded in the workspace
for comp in project.find_all("master:PUImpedanceBranch"): # the exact definition, namespace first
params = comp.parameters() # every parameter, as PSCAD holds it
print(str(params["Freq1"])) # Base Frequency, in Hz
comp = project.find_all("master:PUImpedanceBranch")[0]
comp.parameters(Freq1="120 [Hz]") # a value that carries a unit is written with it
- A parameter is named exactly as in the table, letter case included:
parameters()gives every one of them in a dictionary, and a name the component does not have is refused. - A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (
str(...)) or the unit is lost. PSCAD keeps a written unit as it is given:"2500 [mohm]"stays in mohm. - A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
find_all()takes the exact definition only. A wildcard or a bare name withoutmaster:comes back empty; the Builder'spx_findwalks the pages for those.
The Builder's runtime does the same with the unit handled for you: px_get(comp, "Freq1") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.
Configuration
| Parameter | Unit | Default | Description |
|---|---|---|---|
Freq1Real | Hz | 60.0 | Base FrequencyAt least 1E-308 |
NameText | · | · | NameName for easy idendificationRange 0 to 0 |
RpuReal | pu | 0.02 | Per unit ResistanceEnter per unit resistance based on specified base values |
Sbase1Real | MVA | 100 | Base MVAAt least 1E-308 |
Vb1Real | kV | 230.00 | Base VoltageAt least 1E-308 |
XpuReal | pu | 0.01 | Per unit ReactanceEnter per unit reactance based on specified base values |
Related
← master:trans_filt Nth Order Butterworth/Chebyshev Filter · master:resistor Resistor →