master:statistical_breaker parametersPSCAD Statistical breaker
Every parameter of the PSCAD Statistical breaker (master:statistical_breaker): 6 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().
What master:statistical_breaker is
Statistical breaker (Breaker close signal generation with statistical distribution), a component of PSCAD's Master Library, filed under faults and switching.
- Definition
master:statistical_breaker- PSCAD name
- Statistical breaker
- Category
- Faults and switching
- Parameters
- 6, in 1 group; 2 carry a unit
- Read from
- PSCAD 5.0.0, 2026-11-07
Read and write master:statistical_breaker in Python
import mhi.pscad
pscad = mhi.pscad.connect() # the PSCAD that is open; launch() starts one
project = pscad.project("my_case") # a case loaded in the workspace
for comp in project.find_all("master:statistical_breaker"): # the exact definition, namespace first
params = comp.parameters() # every parameter, as PSCAD holds it
print(str(params["T_max"])) # Maximum Time Delay, in s
comp = project.find_all("master:statistical_breaker")[0]
comp.parameters(T_max="0.03 [s]") # a value that carries a unit is written with it
- A parameter is named exactly as in the table, letter case included:
parameters()gives every one of them in a dictionary, and a name the component does not have is refused. - A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (
str(...)) or the unit is lost. PSCAD keeps a written unit as it is given:"2500 [mohm]"stays in mohm. - A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
find_all()takes the exact definition only. A wildcard or a bare name withoutmaster:comes back empty; the Builder'spx_findwalks the pages for those.
The Builder's runtime does the same with the unit handled for you: px_get(comp, "T_max") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.
Configuration
| Parameter | Unit | Default | Description |
|---|---|---|---|
N_sigmaReal | · | 2 | Number of Standard Deviations in the IntervalNumber of standard deviations in the defined intervalRange 1 to 4 |
NameText | · | · | Name for IdentificationEnter a name for identification |
T_maxReal | s | 15.0e-3 | Maximum Time DelayMaximum time delay for individual breaker close signalsAt least 0 |
T_minReal | s | 9.0e-3 | Minimum Time DelayMinimum time delay for individual breaker close signalsAt least 0 |
seedInteger | · | 0 | Initial Seed ValueSeed used for random number variation, Enter 0 for auto generationRange 0 to 2147483647 |
seedoutText | · | · | Seed Value UsedSeed value used for generating random variation |
Related