master:tpflt parametersPSCAD Three Phase Fault

Every parameter of the PSCAD Three Phase Fault (master:tpflt): 16 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().

What master:tpflt is

The three phase fault: a fault branch between the phases and to ground, drawn into the case. Which phases are faulted and to what is set here; when it is applied comes from the logic wired to it, usually a Timed Fault Logic, because this component has no time parameters of its own.

Definition
master:tpflt
PSCAD name
Three Phase Fault
Category
Faults and switching
Parameters
16, in 5 groups; 3 carry a unit
Read from
PSCAD 5.0.0, 2026-11-07

Most used master:tpflt parameters

ParameterUnitDescription
A·Is Phase A in Fault?phase A in the fault, YES or NO
B·Is Phase B in Fault?
C·Is Phase C in Fault?
G·Is this Fault to Neutral?to ground
RONohmFault ON Resistancethe fault resistance while it is on
Ctype·Fault Type ControlINTERNAL uses A, B, C and G; EXTERNAL takes the phases from a signal

Read and write master:tpflt in Python

import mhi.pscad

pscad = mhi.pscad.connect()              # the PSCAD that is open; launch() starts one
project = pscad.project("my_case")       # a case loaded in the workspace

for comp in project.find_all("master:tpflt"):   # the exact definition, namespace first
    params = comp.parameters()           # every parameter, as PSCAD holds it
    print(str(params["A"]))              # Is Phase A in Fault?

comp = project.find_all("master:tpflt")[0]
comp.parameters(A="NO")                  # a Choice is written as its symbol
  • A parameter is named exactly as in the table, letter case included: parameters() gives every one of them in a dictionary, and a name the component does not have is refused.
  • A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (str(...)) or the unit is lost. PSCAD keeps a written unit as it is given: "2500 [mohm]" stays in mohm.
  • A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
  • find_all() takes the exact definition only. A wildcard or a bare name without master: comes back empty; the Builder's px_find walks the pages for those.

The Builder's runtime does the same with the unit handled for you: px_get(comp, "A") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.

Fault Type

ParameterUnitDefaultDescription
AChoice·YESIs Phase A in Fault?Written as NO (No), YES (Yes)Used when Ctype==0
BChoice·NOIs Phase B in Fault?Written as NO (No), YES (Yes)Used when Ctype==0
CChoice·NOIs Phase C in Fault?Written as NO (No), YES (Yes)Used when Ctype==0
GChoice·YESIs this Fault to Neutral?Written as NO (No), YES (Yes)Used when Ctype==0

Animation

ParameterUnitDefaultDescription
AG1Choice·NORMALAnimation stateWritten as NORMAL (Normal), FAULTED (Faulted)

Configuration

ParameterUnitDefaultDescription
CLVLRealkA0.0Current Chopping LimitUsed when OPCUR==0
CtypeChoice·INTERNALFault Type ControlWritten as INTERNAL (Internal), EXTERNAL (External)
GrndChoice·YESIs the Neutral Grounded?Written as NO (No), YES (Yes)
NameText··NameEnter a name for the component that helps to identify it from others of the same type.
OpCurChoice·NOClear Possible at Any Current?Written as NO (No), YES (Yes)
ViewChoice·SINGLE_LINEGraphics DisplayWritten as 3_PHASE (3 phase view), SINGLE_LINE (Single line view)

Fault Current Names

ParameterUnitDefaultDescription
IflaText··Name for Fault Current, A [kA]
IflbText··Name for Fault Current, B [kA]
IflcText··Name for Fault Current, C [kA]

Fault Resistances

ParameterUnitDefaultDescription
ROFFRealohm1.0E6Fault OFF ResistanceAt least 1
RONRealohm0.01Fault ON ResistanceAt least 0

Related