master:vdvocr parametersPSCAD CCCM controller for rectifier
Every parameter of the PSCAD CCCM controller for rectifier (master:vdvocr): 5 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().
What master:vdvocr is
CCCM controller for rectifier, a component of PSCAD's Master Library, filed under other components.
- Definition
master:vdvocr- PSCAD name
- CCCM controller for rectifier
- Category
- Other components
- Parameters
- 5, in 1 group; 4 carry a unit
- Read from
- PSCAD 5.0.0, 2026-11-07
Read and write master:vdvocr in Python
import mhi.pscad
pscad = mhi.pscad.connect() # the PSCAD that is open; launch() starts one
project = pscad.project("my_case") # a case loaded in the workspace
for comp in project.find_all("master:vdvocr"): # the exact definition, namespace first
params = comp.parameters() # every parameter, as PSCAD holds it
print(str(params["CI"])) # Maximum Current Capability, in pu
comp = project.find_all("master:vdvocr")[0]
comp.parameters(CI="2 [pu]") # a value that carries a unit is written with it
- A parameter is named exactly as in the table, letter case included:
parameters()gives every one of them in a dictionary, and a name the component does not have is refused. - A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (
str(...)) or the unit is lost. PSCAD keeps a written unit as it is given:"2500 [mohm]"stays in mohm. - A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
find_all()takes the exact definition only. A wildcard or a bare name withoutmaster:comes back empty; the Builder'spx_findwalks the pages for those.
The Builder's runtime does the same with the unit handled for you: px_get(comp, "CI") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.
Rectifier Parameters
| Parameter | Unit | Default | Description |
|---|---|---|---|
CIReal | pu | 1.0 | Maximum Current CapabilityAt least 0 |
CPUReal | pu | 0.3 | Minimum Current LevelAt least 0 |
NameText | · | · | Name for IdentificationEnter a name for identification |
VOFFReal | pu | 0.8 | Voltage Above Which VDCOL is OFFAt least 0 |
VONReal | pu | 0.3 | Voltage When VDCOL is Fully ONAt least 0 |
Related