master:wind_governor parametersPSCAD Wind Turbine Governor

Every parameter of the PSCAD Wind Turbine Governor (master:wind_governor): 28 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().

What master:wind_governor is

Wind Turbine Governor, a component of PSCAD's Master Library, filed under machines, exciters and governors.

Definition
master:wind_governor
PSCAD name
Wind Turbine Governor
Category
Machines, exciters and governors
Parameters
28, in 6 groups; 17 carry a unit
Read from
PSCAD 5.0.0, 2026-11-07

Read and write master:wind_governor in Python

import mhi.pscad

pscad = mhi.pscad.connect()              # the PSCAD that is open; launch() starts one
project = pscad.project("my_case")       # a case loaded in the workspace

for comp in project.find_all("master:wind_governor"):   # the exact definition, namespace first
    params = comp.parameters()           # every parameter, as PSCAD holds it
    print(str(params["Bll"]))            # Pitch Angle Lower Limit, in deg

comp = project.find_all("master:wind_governor")[0]
comp.parameters(Bll="1 [deg]")           # a value that carries a unit is written with it
  • A parameter is named exactly as in the table, letter case included: parameters() gives every one of them in a dictionary, and a name the component does not have is refused.
  • A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (str(...)) or the unit is lost. PSCAD keeps a written unit as it is given: "2500 [mohm]" stays in mohm.
  • A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
  • find_all() takes the exact definition only. A wildcard or a bare name without master: comes back empty; the Builder's px_find walks the pages for those.

The Builder's runtime does the same with the unit handled for you: px_get(comp, "Bll") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.

Blade Actuator Parameters

ParameterUnitDefaultDescription
ArlChoice·ENABLEDActuator Rate LimitWritten as DISABLED (Disabled), ENABLED (Enabled)Used when Pcnt==1
BllRealdeg0Pitch Angle Lower LimitUsed when (Pcnt==1)&&(Pal==1)
BoRealdeg10Initial Pitch Angle
BulRealdeg25Pitch Angle Upper LimitUsed when (Pcnt==1)&&(Pal==1)
K4Reals0.1Blade Actuator Integral Gain - K4At least 0.01Used when (Pcnt==1)&&(Gov==0)
PalChoice·ENABLEDPitch Angle LimitsWritten as ENABLED (Enabled), DISABLED (Disabled)Used when Pcnt==1
RlRealdeg/s10.0Blade Actuator Rate LimitRange 0 to 100Used when (Pcnt==1)&&(Arl==1)

Filter Parameters

ParameterUnitDefaultDescription
DfReal·0.3Damping RatioUsed when Nf==1
NfChoice·DISABLEDFilter StateWritten as DISABLED (Disabled), ENABLED (Enabled)
TypeChoice·5_MID_REJECT_1Filter TypeWritten as 1_LOW_PASS (1 - Low Pass), 2_HIGH_PASS (2 - High Pass), 3_MID_PASS (3 - Mid Pass), 4_HIGH_REJECT_1 (4 - High Reject -1), 5_MID_REJECT_1 (5 - Mid Reject - 1), 6_LOW_REJECT_1 (6 - Low Reject -1), 7_HIGH_REJECT_2 (7 - High Reject -2), 8_MID_REJECT_2 (8 - Mid Reject - 2), 9_LOW_REJECT_2 (9 - Low Reject -2)Used when Nf==1
WfRealrad/s10.0Characteristic FrequencyUsed when Nf==1

Speed Damping Parameters

ParameterUnitDefaultDescription
DwmRealrad/s0.008Minmum Speed Difference at Gain Crossover
GmulRealdeg/pu30Gain Multiplier - Gm
KsRealdeg/pu46.9Gain - Ks

Configuration

ParameterUnitDefaultDescription
GenChoice·SYNCHRONOUSType of GeneratorWritten as INDUCTION (Induction), SYNCHRONOUS (Synchronous)Used when Pcnt==1
GmvaRealMVA0.25Machine Rated PowerAt least 0Used when Pcnt==1
NameText··Name for IdentificationEnter a name for identification
PcntChoice·ENABLEDVariable Pitch ControlWritten as DISABLED (Disabled), ENABLED (Enabled)
TmvaRealMW0.2Turbine Rated PowerAt least 1E-10Used when Pcnt==1
WratRealrad/s376.99Rated Electrical Frequency of the MachineAt least 0Used when Pcnt==1

Control Settings

ParameterUnitDefaultDescription
GovChoice·MOD2Governor TypeWritten as MOD2, MOD5
GrRealpu90Gear Ratio: Machine/TurbineAt least 0.001
PrefRealMW1Power Demand -Pref [MW]At least 0
WrefRealrad/s376.99Reference Speed -Wref

PI Regulator Parameters

ParameterUnitDefaultDescription
KiRealdeg/pu6.2Integral Gain - Ki
KpRealdeg/pu6.2Proportional Gain - Kp
PillReal·25.0Integrator Lower Limit
PiulReal·90.0Integrator Upper Limit

Related