master:xfmr-3p3w2 parametersPSCAD 3 Phase 3 Winding Transformer
Every parameter of the PSCAD 3 Phase 3 Winding Transformer (master:xfmr-3p3w2): 86 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().
What master:xfmr-3p3w2 is
3 Phase 3 Winding Transformer, a component of PSCAD's Master Library, filed under transformers and reactors.
- Definition
master:xfmr-3p3w2- PSCAD name
- 3 Phase 3 Winding Transformer
- Category
- Transformers and reactors
- Parameters
- 86, in 9 groups; 24 carry a unit
- Read from
- PSCAD 5.0.0, 2026-11-07
Read and write master:xfmr-3p3w2 in Python
import mhi.pscad
pscad = mhi.pscad.connect() # the PSCAD that is open; launch() starts one
project = pscad.project("my_case") # a case loaded in the workspace
for comp in project.find_all("master:xfmr-3p3w2"): # the exact definition, namespace first
params = comp.parameters() # every parameter, as PSCAD holds it
print(str(params["Bnom"])) # Nominal Flux Density [T], in T
comp = project.find_all("master:xfmr-3p3w2")[0]
comp.parameters(Bnom="3.4 [T]") # a value that carries a unit is written with it
- A parameter is named exactly as in the table, letter case included:
parameters()gives every one of them in a dictionary, and a name the component does not have is refused. - A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (
str(...)) or the unit is lost. PSCAD keeps a written unit as it is given:"2500 [mohm]"stays in mohm. - A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
find_all()takes the exact definition only. A wildcard or a bare name withoutmaster:comes back empty; the Builder'spx_findwalks the pages for those.
The Builder's runtime does the same with the unit handled for you: px_get(comp, "Bnom") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.
- Monitoring of Magnetic Core:112
- Monitoring of Magnetic Core:212
- Magnetic Characteristics of the Material9
- Saturation14
- Configuration18
- Winding 1 Currents6
- Winding 2 Currents6
- Winding 3 Currents6
- Winding Voltages3
Monitoring of Magnetic Core:1
| Parameter | Unit | Default | Description |
|---|---|---|---|
BA1Text | · | · | Name for Flux Density Phase AUsed when ((Hys==2) &&(Enab==1)) |
BB1Text | · | · | Name for Flux Density Phase BUsed when ((Hys==2) &&(Enab==1)) |
BC1Text | · | · | Name for Flux Density Phase CUsed when ((Hys==2) &&(Enab==1)) |
FLXAText | · | · | Name for Phase A Flux Linkage [kWb-N] |
FLXBText | · | · | Name for Phase B Flux Linkage [kWb-N] |
FLXCText | · | · | Name for Phase C Flux Linkage [kWb-N] |
HA1Text | · | · | Name for Magnetic Field Intensity Phase AUsed when ((Hys==2) &&(Enab==1)) |
HB1Text | · | · | Name for Magnetic Field Intensity Phase BUsed when ((Hys==2) &&(Enab==1)) |
HC1Text | · | · | Name for Magnetic Field Intensity Phase CUsed when ((Hys==2) &&(Enab==1)) |
IMAText | · | · | Name for Phase A Magnetizing Current [kA] |
IMBText | · | · | Name for Phase B Magnetizing Current [kA] |
IMCText | · | · | Name for Phase C Magnetizing Current [kA] |
Monitoring of Magnetic Core:2
| Parameter | Unit | Default | Description |
|---|---|---|---|
BAB1Text | · | · | Name for Flux Density Phase A to BUsed when ((Hys==2) &&(Enab==1)) |
BBC1Text | · | · | Name for Flux Density Phase B to CUsed when ((Hys==2) &&(Enab==1)) |
BCA1Text | · | · | Name for Flux Density Phase C to AUsed when ((Hys==2) &&(Enab==1)) |
FLXABText | · | · | Name for Phase A to B Flux Linkage [kWb-N] |
FLXBCText | · | · | Name for Phase B to C Flux Linkage [kWb-N] |
FLXCAText | · | · | Name for Phase C to A Flux Linkage [kWb-N] |
HAB1Text | · | · | Name for Magnetic Field Intensity Phase A to BUsed when ((Hys==2) &&(Enab==1)) |
HBC1Text | · | · | Name for Magnetic Field Intensity Phase B to CUsed when ((Hys==2) &&(Enab==1)) |
HCA1Text | · | · | Name for Magnetic Field Intensity Phase C to AUsed when ((Hys==2) &&(Enab==1)) |
IMABText | · | · | Name for Phase A to B Magnetizing Current [kA] |
IMBCText | · | · | Name for Phase B to C Magnetizing Current [kA] |
IMCAText | · | · | Name for Phase C to A Magnetizing Current [kA] |
Magnetic Characteristics of the Material
| Parameter | Unit | Default | Description |
|---|---|---|---|
BETAReal | · | 0.96 | Parameter to Adjust K with MThis parameter adjusts domian pinning parameter with magnetization for better representation of shoulder areaRange 0 to 0.98 |
CReal | · | 0.1 | Domain Flexing ParameterThis parameter represents the contribution of reversible magnetization processRange 0.001 to 0.5 |
F1Real | · | 2730.0 | Coefficient 1 of Anhysteretic CurveAt least 0 |
F2Real | · | 3209.0 | Coefficient 2 of Anhysteretic CurveAt least 0 |
F3Real | · | 20294.0 | Coefficient 3 of Anhysteretic CurveAt least 0 |
FbReal | · | 2.0 | Coefficient 4 of Anhysteretic CurveAt least 1 |
KReal | A/m | 5.0e-5 | Domain Pinning ParameterThis parameter has a direct impact on the width of the loopAt least 1E-07 |
MsatReal | A/m | 1.72e6 | Saturated Anhysteretic MagnetizationAt least 100000 |
alphaReal | · | 1.325e-05 | Interdomain CouplingAt least 1E-08 |
Saturation
| Parameter | Unit | Default | Description |
|---|---|---|---|
BnomReal | T | 1.7 | Nominal Flux Density [T]Enter the nominal flux density corresponding to saturation curveAt least 1E-307Used when (Hys==2) |
EnabChoice | · | NO | Saturation EnabledSelect Yes or No to enable or disable the core saturation routineWritten as NO (No), YES (Yes) |
Fremn1Real | pu | 0.0 | Remanent Flux Core 1Enter the remanent flux as a per unit value of the peak flux at rated voltageRange -1.5 to 1.5Used when (Hys!=0) |
Fremn2Real | pu | 0.0 | Remanent Flux Core 2Enter the remanent flux as a per unit value of the peak flux at rated voltageRange -1.5 to 1.5Used when (Hys!=0) |
Fremn3Real | pu | 0.0 | Remanent Flux Core 3Enter the remanent flux as a per unit value of the peak flux at rated voltageRange -1.5 to 1.5Used when (Hys!=0) |
HysChoice | · | NONE | HysteresisWritten as NONE (None), BASIC_MODEL (Basic model), JILES_ATHERTON (Jiles_Atherton) |
Im1Real | % | 0.4 | Magnetizing CurrentEnter the magnetizing current as a percentage of base currentRange 0.0001 to 50 |
LW2Real | % | 10 | Loop WidthEnter the loop width as a percentage of magnetizing currentRange 0 to 100Used when (Hys==1) |
SatChoice | · | MIDDLE | Place Saturation on WindingSelect the winding # on which to place the magnetization branchWritten as MIDDLE (Middle), _1 (#1), _2 (#2), _3 (#3) |
TdcReal | s | 0.0 | Inrush Decay Time ConstantFictitious damping of inrush can be enabled by using a non-zero time constantAt least 0Used when Hys==0 |
TxkReal | s | 0.0 | Time to Release Flux ClippingThis could be used to reduce start-up transientsRange 0 to 1000000Used when Hys==0 |
XairReal | pu | 0.2 | Air Core ReactanceEnter the air core reactance based on transformer base impedanceRange 0.001 to 10 |
XkneeReal | pu | 1.17 | Knee VoltageEnter the knee point voltage corresponding to saturation curveAt least 1E-307Used when (Hys!=2) |
materialChoice | · | DEFAULT | Magnetic MaterialWritten as CUSTOM_MATERIAL (custom material), DEFAULT (default)Used when (Hys==2) |
Configuration
| Parameter | Unit | Default | Description |
|---|---|---|---|
CuL12Real | pu | 0.0 | Copper Losses (#1-#2)Enter the copper losses based on transformer ratingRange 0 to 1 |
CuL13Real | pu | 0.0 | Copper Losses (#1-#3)Enter the copper losses based on transformer ratingRange 0 to 1 |
CuL23Real | pu | 0.0 | Copper Losses (#2-#3)Enter the copper losses based on transformer ratingRange 0 to 1 |
DtlsChoice | · | NO | Display Details?Select Yes or No to display transformer details on canvasWritten as NO (No), YES (Yes)Used when View!=0 |
IdealChoice | · | NO | Ideal Transformer ModelSelect Yes or NoWritten as NO (No), YES (Yes) |
LeadChoice | · | LAGS | Delta Lags or Leads YSelect whether Delta connected winding is leading or lagging the Y connected windingWritten as LAGS (Lags), LEADS (Leads)Used when !((YD1+YD2+YD3==0)||(YD1+YD2+YD3==3)) |
NLLReal | pu | 0.0 | Eddy Current LossesEnter the eddy current loss portion of no load losses based on transformer rating, hysteresis loss may also be added here if hysteresis is not modelledRange 0 to 1 |
NameText | · | T33 | Transformer NameEnter an optional name for easy identification |
TapChoice | · | NONE | Tap Changer on WindingSelect the winding number on which to place the on-line tap changerWritten as NONE (None), _1 (#1), _2 (#2), _3 (#3) |
TmvaReal | MVA | 100.0 | 3 Phase Transformer MVAEnter the apparent power rating of the transformerAt least 1E-06 |
ViewChoice | · | CIRCLES | Graphics DisplaySelect the preferred view of graphicsWritten as 3_PHASE_VIEW (3 phase view), CIRCLES (Single line (circles)), WINDINGS (Single line (windings)) |
Xl12Real | pu | 0.1 | Positive Sequence Leakage Reactance (#1-#2)Enter the leakge reactance based on transformer base impedanceAt least 1E-307 |
Xl13Real | pu | 0.1 | Positive Sequence Leakage Reactance (#1-#3)Enter the leakge reactance based on transformer base impedanceAt least 1E-307 |
Xl23Real | pu | 0.1 | Positive Sequence Leakage Reactance (#2-#3)Enter the leakge reactance based on transformer base impedanceAt least 1E-307 |
YD1Choice | · | Y | Winding #1 TypeSelect whether winding type is Y or DeltaWritten as Y, DELTA (Delta) |
YD2Choice | · | DELTA | Winding #2 TypeSelect whether winding type is Y or DeltaWritten as Y, DELTA (Delta) |
YD3Choice | · | Y | Winding #3 TypeSelect whether winding type is Y or DeltaWritten as Y, DELTA (Delta) |
fReal | Hz | 60.0 | Base Operation FrequencyEnter the base frequencyAt least 0.0001 |
Winding 1 Currents
| Parameter | Unit | Default | Description |
|---|---|---|---|
IAB1Text | · | · | Name for A to B Winding Current [kA]Used when (YD1) |
IBC1Text | · | · | Name for B to C Winding Current [kA]Used when (YD1) |
ICA1Text | · | · | Name for C to A Winding Current [kA]Used when (YD1) |
ILA1Text | · | · | Name for Phase A Current (+in)[kA] |
ILB1Text | · | · | Name for Phase B Current (+in)[kA] |
ILC1Text | · | · | Name for Phase C Current (+in)[kA] |
Winding 2 Currents
| Parameter | Unit | Default | Description |
|---|---|---|---|
IAB2Text | · | · | Name for A to B Winding Current [kA]Used when (YD2) |
IBC2Text | · | · | Name for B to C Winding Current [kA]Used when (YD2) |
ICA2Text | · | · | Name for C to A Winding Current [kA]Used when (YD2) |
ILA2Text | · | · | Name for Phase A Current (+in)[kA] |
ILB2Text | · | · | Name for Phase B Current (+in)[kA] |
ILC2Text | · | · | Name for Phase C Current (+in)[kA] |
Winding 3 Currents
| Parameter | Unit | Default | Description |
|---|---|---|---|
IAB3Text | · | · | Name for A to B Winding Current [kA]Used when (YD3) |
IBC3Text | · | · | Name for B to C Winding Current [kA]Used when (YD3) |
ICA3Text | · | · | Name for C to A Winding Current [kA]Used when (YD3) |
ILA3Text | · | · | Name for Phase A Current (+in)[kA] |
ILB3Text | · | · | Name for Phase B Current (+in)[kA] |
ILC3Text | · | · | Name for Phase C Current (+in)[kA] |
Winding Voltages
| Parameter | Unit | Default | Description |
|---|---|---|---|
V1Real | kV | 230.0 | Winding 1 Line to Line Voltage (RMS)Enter the RMS voltage rating of winding 1At least 0.0001 |
V2Real | kV | 230.0 | Winding 2 Line to Line Voltage (RMS)Enter the RMS voltage rating of winding 2At least 0.0001 |
V3Real | kV | 230.0 | Winding 3 Line to Line Voltage (RMS)Enter the RMS voltage rating of winding 3At least 0.0001 |
Related
← master:xfmr-3p3w 3 Phase 3 Winding Transformer · master:xfmr-3p4w 3 Phase 4 Winding Transformer →