ElmLodmv attributesPowerFactory MV Load

Every attribute of the PowerFactory MV Load (ElmLodmv): 190 input parameters and 907 result variables, with units and meaning. Copy a name into GetAttribute or SetAttribute.

What ElmLodmv is

An MV load: the load of a distribution transformer, which may also hold embedded generation.

Class
ElmLodmv, element class
PowerFactory name
MV Load
Terminal suffix
:bus1 terminal
Attributes
190 input parameters and 907 result variables, in 7 calculations

Read and write ElmLodmv in Python

import powerfactory

app = powerfactory.GetApplication()          # GetApplicationExt() from outside PowerFactory
app.GetFromStudyCase("ComLdf").Execute()      # results exist after a calculation

for obj in app.GetCalcRelevantObjects("*.ElmLodmv"):
    urnet_bus1 = obj.GetAttribute("m:urnet:bus1") # Voltage, Real Part, referred to network, p.u.
    print(obj.loc_name, urnet_bus1)

obj = app.GetCalcRelevantObjects("*.ElmLodmv")[0]
obj.SetAttribute("outserv", 1)                # take it out of service
  • A result at a terminal of the mv load needs the terminal in its name: m:P:bus1, not m:P, which raises AttributeError.
  • An input parameter is read and written with or without its e: prefix: GetAttribute("outserv") and GetAttribute("e:outserv") give the same value.
  • RMS and EMT variables change over time: record them in a results object (ElmRes) to read the whole curve. GetAttribute after a run gives the value at the last time step.

ElmLodmv input parameters

The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.

AttributeUnitDescription
loc_nameยทName
chr_nameยทCharacteristic Name
for_nameยทForeign Key
dat_srcยทData source
mode_inpยทInput Mode
sernumยทSerial Number
commissionDateยทCommissioning Date
appr_modbyยทModified by
classifยทLoad Classification
outservยทOut of Service
pf_recapยทcos(phi), Load
pfg_recapยทcos(phi), Generation
nntapยทTap Position
pf_recaprยทcos(phi), Load
pfg_recaprยทcos(phi), Generation
pf_recapsยทcos(phi), Load
pfg_recapsยทcos(phi), Generation
pf_recaptยทcos(phi), Load
pfg_recaptยทcos(phi), Generation
i_scaleยทAdjusted by Load Scaling
constrยทYear of Construction
appr_statusยทStatus
NrCustยทNumber of connected customers
i_prtyยทPriority
shedยทShedding steps
iperfectยทIdeal component
iSheddingยทAllow load shedding
isCtrlLdShedยทAllow load shedding
ctrlUsageยทLoad shedding
icurrefยทHarmonic currents referred to
i_csrcยทLoad model
i_pureยทLoad model
iopt_typeยทAllow Load-Ramp Event
i_piniยทEstimate Active Power, Load
i_qiniยทEstimate Reactive Power, Load
i_scaleiniยทEstimate Load Scaling Factor
sliniMVAS, Load
cosliniยทcos(phi), Load
sginiMVAS, Generation
cosginiยทcos(phi), Generation
eliniMWhYearly Energy
slinirMVAS, Load
coslinirยทcos(phi), Load
sginirMVAS, Generation
cosginirยทcos(phi), Generation
slinisMVAS, Load
coslinisยทcos(phi), Load
sginisMVAS, Generation
cosginisยทcos(phi), Generation
slinitMVAS, Load
coslinitยทcos(phi), Load
sginitMVAS, Generation
cosginitยทcos(phi), Generation
scale0ยทLoad Scaling Factor
gscaleยทGeneration Scaling Factor
pcontractMWContracted Active Power
fSCDFยทScaling factor
trans%Transferable
shedcostUSD/MVAhCosts for load shedding
shedmax%Max. load shedding
shedmin%Min. load shedding
SksslodMVA/MWSubtransient Short-Circuit Level
SkslodMVA/MWTransient Short-Circuit Level
SkssgenMVA/MWSubtransient Short-Circuit Level
SksgenMVA/MWTransient Short-Circuit Level
rtoxยทR to X'' ratio
SkssfixMVASubtransient Short-Circuit Level
SksfixMVATransient Short-Circuit Level
SratedMVARated Power
pgrd%QL/QC
r1hmcp.u.Resistance, r1
x1hmcp.u.Reactance, x1
uk%Short Circuit Impedance
PcukWCopper Losses
r2p.u.Resistance r2
x2p.u.Reactance x2
GPSlatdegLatitude / Northing
GPSlondegLongitude / Easting
curativeLim%Max. curative power deviation
curativeCostsUSD/MVAhCosts for curative power deviation
dudropLVfeed%Maximum Voltage Drop (LV Grid)
duriseLVfeed%Maximum Voltage Rise (LV Grid)
dpl1ยทdpl1
dpl2ยทdpl2
dpl3ยทdpl3
dpl4ยทdpl4
dpl5ยทdpl5
appr_modifยทModified
cimRdfIdยทRDF ID
descยทDescription
fold_idยทIn Folder
typ_idยทTypeObject: TypDistrf
bus1ยทTerminalObject: StaCubic
pProfileChaTime,ChaProfileConsumption Profile
doc_idยทAdditional Data
pOwnerยทOwnerObject: ElmOwner
pOperatorยทOperatorObject: ElmOperator
pSCDFยทTariffObject: IntTariffenergy,IntTarifftime
pTransยทAlternative Supply (Load)Object: ElmLod,ElmLodlv,ElmLodmv
pStochStoTyptrfElement model
phmcยทHarmonic CurrentsObject: TypHmccur,TypHmcopcur
fcharr1ChaPol,ChaVec,ChaMatFrequency-Dependence, r1(f)
fcharx1ChaPol,ChaVec,ChaMatFrequency-Dependence, x1(f)
cpHeadFoldยทHead Folder
bus1_barยทTerminal
cpGridยทGridObject: ElmNet
cpZoneยทZoneObject: ElmZone
cpAreaยทAreaObject: ElmArea
cpFeedยทFeederObject: ElmFeeder
ciDistยทDistance from infeed in number of buses
ciLaterยทLateral Index
ciDistRootยทDistance from first infeed in number of buses
ciDistAllยทDistance from infeed in number of buses including switches
ciDistAllRootยทDistance from first infeed in number of buses including switches
cpOwnerยทOwnerObject: ElmOwner
cpOperatorยทOperatorObject: ElmOperator
cpBranchยทBranchObject: ElmBranch
cpSiteยทSiteObject: ElmSite
cpSubstatยทSubstationObject: ElmSubstat,ElmTrfstat
cpMeteostatยทMeteo StationObject: ElmMeteostat
ciOutagedยทPlanned Outage
ciEnergizedยทEnergized
ciEarthedยทEarthed
cDisplayNameยทDisplay Name
cpSupplyTransformerยทSupplying TransformerObject: ElmTr?,ElmTrmult
cpSupplyTrfStationยทSupplying Secondary SubstationObject: ElmTrfstat
cpSupplySubstationยทSupplying SubstationObject: ElmSubstat
pliniMWP, Load
pginiMWP, Generation
cpliniaMWP, Load
qdslCtrlยทQuasi-Dynamic ModelObject: ElmQdsl
plinirMWP, Load
pginirMWP, Generation
plinisMWP, Load
pginisMWP, Generation
plinitMWP, Load
pginitMWP, Generation
phtechยทTechnology
ci_symยทBalanced/Unbalanced
cTrans%Resulting
plini_aMWP(act.)
slini_aMVAS(act.)
coslini_aยทcos(phi)(act.)
scale0_aยทScaling Factor(act.)
gscale_aยทGen. Scaling Factor(act.)
plinir_aMWPh 1
slinir_aMVAPh 1
coslinir_aยทPh 1
plinis_aMWPh 2
slinis_aMVAPh 2
coslinis_aยทPh 2
plinit_aMWPh 3
slinit_aMVAPh 3
coslinit_aยทPh 3
pgini_aMWPgen(act.)
sgini_aMVASgen(act.)
cosgini_aยทcos(phi)(act.), Gen.
pginir_aMWPh 1
sginir_aMVAPh 1
cosginir_aยทPh 1
pginis_aMWPh 2
sginis_aMVAPh 2
cosginis_aยทPh 2
pginit_aMWPh 3
sginit_aMVAPh 3
cosginit_aยทPh 3
FOR11/aForced Complete Outage Rate
FOEh/aForced Outage Expectancy
FODhForced Outage Duration
pTypStochStoTyptrfType model
CCEarFr1/aFrequency of single earth faults
CCEarRepMuhRepair duration
CCEarProb%Conditional probability of a second earth fault
IksslodkA/MWSubtransient Short-Circuit Current
IkslodkA/MWTransient Short-Circuit Current
IkssgenkA/MWSubtransient Short-Circuit Current
IksgenkA/MWTransient Short-Circuit Current
xtorยทX'' to R ratio
IkssfixkASubtransient Short-Circuit Level
IksfixkATransient Short-Circuit Level
ctotSkssMVATotal Subtransient Fault Contribution
ctotSksMVATotal Transient Fault Contribution
ctotIksskATotal Subtransient Fault Contribution
ctotIkskATotal Transient Fault Contribution
InomkANominal Current
cTypHmcยทType of harmonic sources
IratedkARated Current
csratedMVARated Power
qcq%QC/Q
cEstPhasesยทEstimate phases

ElmLodmv load flow results

Read after ComLdf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bus1p.u.Voltage, Real Part, referred to network
m:uinet:bus1p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1degPositive-Sequence-Voltage, Angle
m:irnet:bus1p.u.Current, Real Part, referred to network
m:iinet:bus1p.u.Current, Imaginary Part, referred to network
m:inet:bus1p.u.Current, Magnitude, referred to network
m:I:bus1kACurrent, Magnitude
m:phii:bus1degCurrent, Angle
m:i1r:bus1p.u.Positive-Sequence Current, Real Part
m:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:S:bus1MVAApparent Power
m:cosphi:bus1ยทPower Factor
m:tanphi:bus1ยทtan(phi)
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:Ssum:bus1MVATotal Apparent Power
m:cosphisum:bus1ยทTotal Power Factor
m:tanphisum:bus1ยทTotal tan(phi)
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:ur:bus1p.u.Voltage, Real Part
m:ui:bus1p.u.Voltage, Imaginary Part
m:u:bus1p.u.Voltage, Magnitude
m:ir:bus1p.u.Current, Real Part
m:ii:bus1p.u.Current, Imaginary Part
m:i:bus1p.u.Current, Magnitude
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1sFault Clearing Time
m:Brkload:bus1%Breaker Loading
m:Spu:bus1MVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bus1p.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bus1degZero-Sequence-Voltage, Angle
m:u2:bus1p.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bus1degNegative-Sequence-Voltage, Angle
m:irnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part, referred to network
m:iinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part, referred to network
m:inet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude, referred to network
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bus1p.u.Zero-Sequence Current, Real Part
m:i0i:bus1p.u.Zero-Sequence Current, Imaginary Part
m:i0:bus1p.u.Zero-Sequence Current, Magnitude
m:I0:bus1kAZero-Sequence Current, Magnitude
m:I0x3:bus1kA3*I0
m:phii0:bus1degZero-Sequence Current, Angle
m:i2r:bus1p.u.Negative-Sequence Current, Real Part
m:i2i:bus1p.u.Negative-Sequence Current, Imaginary Part
m:i2:bus1p.u.Negative-Sequence Current, Magnitude
m:I2:bus1kANegative-Sequence Current, Magnitude
m:phii2:bus1degNegative-Sequence Current, Angle
m:ubfacI:bus1%Current Unbalance Factor
m:ubfacS:bus1%Power Unbalance Factor
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bus1:Aper phase :A, :B, :C, unbalanced onlyยทPower Factor
m:tanphi:bus1:Aper phase :A, :B, :C, unbalanced onlyยทtan(phi)
m:Pln:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bus1MWPositive Sequence Active Power
m:Q1:bus1MvarPositive Sequence Reactive Power
m:P2:bus1MWNegative Sequence Active Power
m:Q2:bus1MvarNegative Sequence Reactive Power
m:P0:bus1MWZero Sequence Active Power
m:Q0:bus1MvarZero Sequence Reactive Power
m:i2P:bus1p.u.Negative-Sequence Active Current
m:i2Q:bus1p.u.Negative-Sequence Reactive Current
m:I2P:bus1kANegative-Sequence Active Current
m:I2Q:bus1kANegative-Sequence Reactive Current
m:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1degAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bus1degAngle between Voltage and Current in negative sequence system
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bus1:Aper phase :A, :B, :C, unbalanced only%Breaker Loading
c:sยทComplex Power (P+jQ)
c:frnomHzNominal Frequency
c:hpirad/sNominal angular frequency
c:u0p.u.Nominal Voltage
c:nntapยทCurrent Tap Position
c:ulvp.u.LV Voltage
c:GmloadkWIron Losses
c:ncustยทNumber of Connected Customers
c:scale0ยทInitial Scale Factor
c:zonescaleยทZone Scale Factor
c:gscaleยทGeneration Scale Factor
c:tempscFacยทTemperature dependent load scaling factor
c:kpu0ยทVolt. Dependence I on P
c:kqu0ยทVolt. Dependence I on Q
c:kpu1ยทVolt. Dependence II on P
c:kqu1ยทVolt. Dependence II on Q
c:kpuยทVolt. Dependence III on P
c:kquยทVolt. Dependence III on Q
c:aPยทPercent of Volt. Dep. I on P
c:bPยทPercent of Volt. Dep. II on P
c:aQยทPercent of Volt. Dep. I on Q
c:bQยทPercent of Volt. Dep. II on Q
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:PnomMWNominal Active Power
c:QnomMvarNominal Reactive Power
c:PpeakMWPeak Active Power
c:QpeakMvarPeak Reactive Power
c:piniMWNominal Active Power
c:qiniMvarNominal Reactive Power
c:iRefElementยทReference Element
c:dudropTrf%max. Voltage drop across transformer
c:duriseTrf%max. Voltage rise across transformer
c:pliniMWNominal Active Power
c:qliniMvarNominal Reactive Power
c:ulv:Aper phase :A, :B, :C, unbalanced onlyp.u.LV Voltage
c:PmismMWActive Power Mismatch
c:priniMWNominal Active Power, ph. 1
c:qriniMvarNominal Reactive Power, ph. 1
c:psiniMWNominal Active Power, ph. 2
c:qsiniMvarNominal Reactive Power, ph. 2
c:srMVAComplex Power (P+jQ), ph. 1
c:ssMVAComplex Power (P+jQ), ph. 2
c:ptiniMWNominal Active Power, ph. C
c:qtiniMvarNominal Reactive Power, ph. C
c:stMVAComplex Power (P+jQ), ph. C
c:z0p.u.z0
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bus1MWGeneration, Active Power
n:Qgen:bus1MvarGeneration, Reactive Power
n:Pmot:bus1MWMotor Load, Active Power
n:Qmot:bus1MvarMotor Load, Reactive Power
n:Pload:bus1MWGeneral Load, Active Power
n:Qload:bus1MvarGeneral Load, Reactive Power
n:Pcomp:bus1MWCompensation (Losses)
n:Qcomp:bus1MvarCompensation
n:Pnet:bus1MWExternal Networks, Active Power
n:Qnet:bus1MvarExternal Networks, Reactive Power
n:Pflow:bus1MWPower Flow, Active Power
n:Qflow:bus1MvarPower Flow, Reactive Power
n:Pout:bus1MWOutgoing Flow, Active Power
n:Qout:bus1MvarOutgoing Power, Reactive Power
n:Sout:bus1MVAOutgoing Power, Apparent Power
n:cosphiout:bus1ยทOutgoing Power, Power Factor
n:Pbalance:bus1MWActive Power Balance (=0)
n:Qbalance:bus1MvarReactive Power Balance (=0)
n:LossPdown:bus1MWLosses, downstream
n:LossQdown:bus1MvarLosses, downstream (Reactive Power)
n:LossPdownload:bus1MWLoad losses, downstream
n:LossQdownload:bus1MvarLoad losses, downstream
n:LossPdownnoload:bus1MWNo load losses, downstream
n:LossQdownnoload:bus1MvarNo load losses, downstream
n:du_feed:bus1%Difference from voltage at start of feeder
n:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aper phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1kV3*U0
n:phiu0:bus1degZero-Sequence Voltage, Angle
n:U1:bus1kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1degPositive-Sequence Voltage, Angle
n:u2:bus1p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1degNegative-Sequence Voltage, Angle
n:U1l:bus1kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1degNeutral-Ground Voltage, Angle
n:upht:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bus1p.u.Average-Voltage, Magnitude
n:Um:bus1kVAverage-Voltage, Magnitude
n:uphtmin:bus1p.u.Minimum of Phase Technology dependent Voltage, Magnitude
n:uphtmax:bus1p.u.Maximum of Phase Technology dependent Voltage, Magnitude
n:ubfac:bus1%Unbalance Factor
s:scaleยทScale Factor
s:scalephiradLoad Scaling
s:pini_setยทNominal Active Power
s:qini_setยทNominal Reactive Power
s:prini_setMWActive Power Setpoint, ph. 1
s:qrini_setMvarReactive Power Setpoint, ph. 1
s:psini_setMWActive Power Setpoint, ph. 2
s:qsini_setMvarReactive Power Setpoint, ph. 2
s:scalerยทScale Factor, ph. 1
s:scalesยทScale Factor, ph. 2
s:ptini_setMWActive Power Setpoint, ph. C
s:qtini_setMvarReactive Power Setpoint, ph. C
s:scaletยทScale Factor, ph. C

ElmLodmv short-circuit results

Read after ComShc with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:I:bus1kAShort-Circuit Current, Magnitude
m:phii:bus1degPhase Current, Angle
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in Positive-Sequence System
m:Tfct:bus1sFault Clearing Time
m:Ikss:bus1kAInitial Short-Circuit Current
m:ikss:bus1p.u.Initial Short-Circuit Current, Magnitude
m:Skss:bus1MVAInitial Short-Circuit Power
m:ip:bus1kAPeak Short-Circuit Current
m:maxIkss:bus1kAMax. Initial Short-Circuit Current
m:maxip:bus1kAMax. Peak Short-Circuit Current
m:maxIth:bus1kAMax. Thermal equivalent Short-Circuit Current
m:maxIb:bus1kAMax. Breaking Current
m:R:bus1OhmFault Impedance, Real Part
m:X:bus1OhmFault Impedance, Imaginary Part
m:Z:bus1OhmFault Impedance, Magnitude
m:phiz:bus1degFault Impedance, Angle
m:Rs:bus1OhmSource Impedance, Real Part
m:Xs:bus1OhmSource Impedance, Imaginary Part
m:Zs:bus1OhmSource Impedance, Magnitude
m:phizs:bus1degSource Impedance, Angle
m:BrkIpload:bus1%Breaker Loading (peak)
m:Ib:bus1kAShort-Circuit Breaking Current
m:Sb:bus1MVAShort-Circuit Breaking Power
m:Ith:bus1kAThermal equivalent Short-Circuit Current
m:zSbase:bus1p.u.Fault Impedance, Magnitude
m:XtoR:bus1ยทX/R ratio
m:cosphiui:bus1ยทcosphi
m:BrkIbload:bus1%Breaker Loading (breaking)
m:BrkmaxIb:bus1kAMax. Breaking Current (breaker time)
m:Ik:bus1kASteady-State Short-Circuit Current
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, Magnitude
m:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:I0:bus1kAZero-Sequence Current, Magnitude
m:I0x3:bus1kA3*I0
m:phii0:bus1degZero-Sequence Current, Angle
m:I2:bus1kANegative-Sequence Current, Magnitude
m:phii2:bus1degNegative-Sequence Current, Angle
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:cosphisum:bus1ยทTotal Power Factor
m:P2:bus1MWP2
m:Q2:bus1MvarQ2
m:P0:bus1MWP0
m:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1degAngle between Voltage and Current in Zero-Sequence System
m:phiu2i2:bus1degAngle between Voltage and Current in Negative-Sequence System
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:Ikss:bus1:Aper phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
m:ikss:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Initial Short-Circuit Current, Magnitude
m:Skss:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
m:Skssx3:bus1:Aper phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
m:ip:bus1:Aper phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
m:Z:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmFault Impedance, Magnitude
m:phiz:bus1:Aper phase :A, :B, :C, unbalanced onlydegFault Impedance, Angle
m:Zl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmLine-Line Fault Impedance, Magnitude
m:phizl:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Fault Impedance, Angle
m:Z0:bus1OhmZero-Sequence Fault Impedance, Magnitude
m:phiz0:bus1degZero-Sequence Fault Impedance, Angle
m:z0Sbase:bus1p.u.Zero-Sequence Fault Impedance, Magnitude
m:cosphiu1i1:bus1ยทPositive-Sequence cosphi
m:I0x3watt:bus1kAEarth-Fault Residual Current
m:I0x3var:bus1kACapacitive Earth-Fault Current
m:Q0cap:bus1MvarQ0 capacitive
m:Rfrel:bus1OhmRelay Impedance, Real Part
m:Xfrel:bus1OhmRelay Impedance, Imaginary Part
m:Zfrel:bus1OhmRelay Impedance, Magnitude
m:phizfrel:bus1degRelay Impedance, Angle
m:Zf:bus1OhmMeas. Fault Impedance, Magnitude
m:phizf:bus1degMeas. Fault Impedance, Angle
c:Rp.u.Resistance
c:Lp.u.Inductance
c:Cp.u.Capacitance
c:i_pureยทPurely inductive/capacitive
c:icsrcยทCurrent Source/Impedance
c:C_lvp.u.LV-Capacitance
c:y1p.u.Admittance
c:i1p.u.Harmonic current
c:z1p.u.Positive-sequence impedance
c:z2p.u.Negative-sequence Impedance
c:cnยทConnection Mode
c:i1iecp.u.Harmonic IEC current
c:RaยทResistance, Phase a
c:RbยทResistance, Phase b
c:LaยทInductance, Phase a
c:LbยทInductance, Phase b
c:CaยทCapacitance, Phase a
c:CbยทCapacitance, Phase b
c:y_aยทAdmittance, Phase a
c:y_bยทAdmittance, Phase b
c:i_abp.u.Harmonic currents
c:i_ab_iecp.u.Harmonic IEC current
c:z0p.u.z0
c:Rcp.u.Resistance, Phase c
c:Lcp.u.Inductance, Phase c
c:Ccp.u.Capacitance, Phase c
c:y_cp.u.Admittance, Phase c
c:Ca_lvp.u.LV-Capacitance, Phase a
c:Cb_lvp.u.LV-Capacitance, Phase b
c:Cc_lvp.u.LV-Capacitance, Phase c
c:i_abcp.u.Harmonic currents
c:i_abc_iecp.u.Harmonic IEC current
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:Ikss:bus1kAInitial Short-Circuit Current
n:I:bus1kAShort-Circuit Current
n:phii:bus1degPhase Current, Angle
n:Skss:bus1MVAInitial Short-Circuit Power
n:ip:bus1kAPeak Short-Circuit Current
n:Ib:bus1kAShort-Circuit Breaking Current
n:Sb:bus1MVAShort-Circuit Breaking Power
n:idc:bus1kADecaying Component
n:Ith:bus1kAThermal equivalent Short-Circuit Current
n:R1toX1:bus1ยทR1/X1 ratio (Zk")
n:X1toR1:bus1ยทX1/R1 ratio (Zk")
n:R:bus1OhmShort-Circuit Impedance, Real Part
n:X:bus1OhmShort-Circuit Impedance, Imaginary Part
n:Z:bus1OhmShort-Circuit Impedance, Magnitude
n:phiz:bus1degShort-Circuit Impedance, Angle
n:urpref:bus1p.u.Pre-fault Voltage, Real Part
n:uipref:bus1p.u.Pre-fault Voltage, Imaginary Part
n:upref:bus1p.u.Pre-fault Voltage, Magnitude
n:uprefpc:bus1%Pre-fault Voltage, Magnitude
n:Upref:bus1kVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bus1kVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bus1degPre-fault Voltage, Angle
n:phiui:bus1degAngle between Voltage and Current
n:Ithload:bus1%Loading, Thermal equivalent Current
n:Ipload:bus1%Loading, Peak Short-Circuit Current
n:Ithrtk:bus1kARated Short-Time Current (Tk)
n:XtoR:bus1ยทX/R ratio (peak)
n:RtoX:bus1ยทR/X ratio (peak)
n:XtoR_b:bus1ยทX/R ratio (dc)
n:RtoX_b:bus1ยทR/X ratio (dc)
n:fctof_b:bus1ยทEquivalent Frequency fc/f (dc)
n:rSbase:bus1p.u.Short-Circuit Impedance, Real Part
n:xSbase:bus1p.u.Short-Circuit Impedance, Imaginary Part
n:zSbase:bus1p.u.Short-Circuit Impedance, Magnitude
n:Tn:bus1msGrid Time Constant
n:Ik:bus1kASteady-State Short-Circuit Current
n:cfac:bus1ยทVoltage Factor
n:Iasy:bus1kAAsymmetrical Breaking Current
n:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aper phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1kV3*U0
n:phiu0:bus1degZero-Sequence Voltage, Angle
n:U1:bus1kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1degPositive-Sequence Voltage, Angle
n:u2:bus1p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1degNegative-Sequence Voltage, Angle
n:U1l:bus1kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1degNeutral-Ground Voltage, Angle
n:upht:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:Ikss:bus1:Aper phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
n:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
n:Skss:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
n:Skssx3:bus1:Aper phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
n:ip:bus1:Aper phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
n:Ib:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Breaking Current
n:Sb:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAShort-Circuit Breaking Power
n:Ith:bus1:Aper phase :A, :B, :C, unbalanced onlykAThermal equivalent Short-Circuit Current
n:Ithmax:bus1kAMax. Thermal equivalent Short-Circuit Current
n:R0:bus1OhmZero-Sequence Impedance, Real Part
n:X0:bus1OhmZero-Sequence Impedance, Imaginary Part
n:Z0:bus1OhmZero-Sequence Impedance, Magnitude
n:phiz0:bus1degZero-Sequence Impedance, Angle
n:r0Sbase:bus1p.u.Zero-Sequence Impedance, Real Part
n:x0Sbase:bus1p.u.Zero-Sequence Impedance, Imaginary Part
n:z0Sbase:bus1p.u.Zero-Sequence Impedance, Magnitude
n:R1:bus1OhmPositive-Sequence Impedance, Real Part
n:X1:bus1OhmPositive-Sequence Impedance, Imaginary Part
n:Z1:bus1OhmPositive-Sequence Impedance, Magnitude
n:phiz1:bus1degPositive-Sequence Impedance, Angle
n:r1Sbase:bus1p.u.Positive-Sequence Impedance, Real Part
n:x1Sbase:bus1p.u.Positive-Sequence Impedance, Imaginary Part
n:z1Sbase:bus1p.u.Positive-Sequence Impedance, Magnitude
n:R2:bus1OhmNegative-Sequence Impedance, Real Part
n:X2:bus1OhmNegative-Sequence Impedance, Imaginary Part
n:Z2:bus1OhmNegative-Sequence Impedance, Magnitude
n:phiz2:bus1degNegative-Sequence Impedance, Angle
n:r2Sbase:bus1p.u.Negative-Sequence Impedance, Real Part
n:x2Sbase:bus1p.u.Negative-Sequence Impedance, Imaginary Part
n:z2Sbase:bus1p.u.Negative-Sequence Impedance, Magnitude
n:R0toX0:bus1ยทR0/X0 ratio (Zk")
n:X0toR0:bus1ยทX0/R0 ratio (Zk")
n:R2toX2:bus1ยทR2/X2 ratio (Zk")
n:X2toR2:bus1ยทX2/R2 ratio (Zk")
n:R:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Ground
n:X:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Ground
n:Z:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Ground
n:phiz:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Ground
n:Rl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Line
n:Xl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Line
n:Zl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Line
n:phizl:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Line
n:Rln:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Neutral
n:Xln:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Neutral
n:Zln:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Neutral
n:phizln:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Neutral
n:Rn:bus1OhmNetwork Resistance, Neutral
n:Xn:bus1OhmNetwork Reactance, Neutral
n:Zn:bus1OhmNetwork Impedance, Neutral
n:phizn:bus1degAngle of Network Impedance, Neutral
n:eff:bus1:Aper phase :A, :B, :C, unbalanced onlyยทEarth Fault Factor
n:X0toX1:bus1ยทX0/X1
n:In:bus1kANeutral Current, Magnitude
n:phiin:bus1degNeutral Current, Angle
n:I0:bus1kAZero-Sequence Current, Magnitude
n:I0x3:bus1kA3*I0
n:phii0:bus1degZero-Sequence Current, Angle
n:I1:bus1kAPositive-Sequence Current, Magnitude
n:phii1:bus1degPositive-Sequence Current, Angle
n:I2:bus1kANegative-Sequence Current, Magnitude
n:phii2:bus1degNegative-Sequence Current, Angle
n:urpref:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Real Part
n:uipref:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Imaginary Part
n:upref:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Magnitude
n:uprefpc:bus1:Aper phase :A, :B, :C, unbalanced only%Pre-fault Voltage, Magnitude
n:Upref:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bus1:Aper phase :A, :B, :C, unbalanced onlydegPre-fault Voltage, Angle
n:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
n:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
n:phiu2i2:bus1degAngle between Voltage and Current in negative sequence system
n:phiu0i0:bus1degAngle between Voltage and Current in zero-sequence system
n:Ik:bus1:Aper phase :A, :B, :C, unbalanced onlykASteady-State Short-Circuit Current
n:in:bus1p.u.Neutral Current, Magnitude
n:i0r:bus1p.u.Zero-Sequence Current, Real Part
n:i0i:bus1p.u.Zero-Sequence Current, Imaginary Part
n:i0:bus1p.u.Zero-Sequence Current, Magnitude
n:i1r:bus1p.u.Positive-Sequence Current, Real Part
n:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
n:i1:bus1p.u.Positive-Sequence Current, Magnitude
n:i2r:bus1p.u.Negative-Sequence Current, Real Part
n:i2i:bus1p.u.Negative-Sequence Current, Imaginary Part
n:i2:bus1p.u.Negative-Sequence Current, Magnitude

ElmLodmv rms simulation results

Read after ComInc (RMS) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bus1p.u.Voltage, Real Part, referred to network
m:uinet:bus1p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1degPositive-Sequence-Voltage, Angle
m:irnet:bus1p.u.Current, Real Part, referred to network
m:iinet:bus1p.u.Current, Imaginary Part, referred to network
m:inet:bus1p.u.Current, Magnitude, referred to network
m:I:bus1kACurrent, Magnitude
m:phii:bus1degCurrent, Angle
m:i1r:bus1p.u.Positive-Sequence Current, Real Part
m:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:S:bus1MVAApparent Power
m:cosphi:bus1ยทPower Factor
m:tanphi:bus1ยทtan(phi)
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:Ssum:bus1MVATotal Apparent Power
m:cosphisum:bus1ยทTotal Power Factor
m:tanphisum:bus1ยทTotal tan(phi)
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:ur:bus1p.u.Voltage, Real Part
m:ui:bus1p.u.Voltage, Imaginary Part
m:u:bus1p.u.Voltage, Magnitude
m:ir:bus1p.u.Current, Real Part
m:ii:bus1p.u.Current, Imaginary Part
m:i:bus1p.u.Current, Magnitude
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1sFault Clearing Time
m:Brkload:bus1%Breaker Loading
m:Spu:bus1MVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bus1p.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bus1degZero-Sequence-Voltage, Angle
m:u2:bus1p.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bus1degNegative-Sequence-Voltage, Angle
m:irnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:iinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:inet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bus1p.u.Zero-Sequence Current, Real Part
m:i0i:bus1p.u.Zero-Sequence Current, Imaginary Part
m:i0:bus1p.u.Zero-Sequence Current, Magnitude
m:I0:bus1kAZero-Sequence Current, Magnitude
m:I0x3:bus1kA3*I0
m:phii0:bus1degZero-Sequence Current, Angle
m:i2r:bus1p.u.Negative-Sequence Current, Real Part
m:i2i:bus1p.u.Negative-Sequence Current, Imaginary Part
m:i2:bus1p.u.Negative-Sequence Current, Magnitude
m:I2:bus1kANegative-Sequence Current, Magnitude
m:phii2:bus1degNegative-Sequence Current, Angle
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bus1:Aper phase :A, :B, :C, unbalanced onlyยทPower Factor
m:tanphi:bus1:Aper phase :A, :B, :C, unbalanced onlyยทtan(phi)
m:Pln:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bus1MWPositive Sequence Active Power
m:Q1:bus1MvarPositive Sequence Reactive Power
m:P2:bus1MWNegative Sequence Active Power
m:Q2:bus1MvarNegative Sequence Reactive Power
m:P0:bus1MWZero Sequence Active Power
m:Q0:bus1MvarZero Sequence Reactive Power
m:i2P:bus1p.u.Negative-Sequence Active Current
m:i2Q:bus1p.u.Negative-Sequence Reactive Current
m:I2P:bus1kANegative-Sequence Active Current
m:I2Q:bus1kANegative-Sequence Reactive Current
m:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1degAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bus1degAngle between Voltage and Current in negative sequence system
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bus1:Aper phase :A, :B, :C, unbalanced only%Breaker Loading
c:cnยทConnection Mode
c:srMVAComplex Power (P+jQ), ph. 1
c:ssMVAComplex Power (P+jQ), ph. 2
c:yrp.u.Load Admittance, ph. 1
c:ysp.u.Load Admittance, ph. 2
c:yr0p.u.Load Admittance, ph. 1
c:ys0p.u.Load Admittance, ph. 2
c:stMWComplex Power (P+jQ), ph. C
c:z0p.u.z0
c:ytp.u.Load Admittance, ph. C
c:yt0p.u.Load Admittance, ph. C
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:ishc:bus1p.u.Short-Circuit Current, magnitude
n:Ishc:bus1kAShort-Circuit Current, magnitude
n:fe:bus1p.u.Electrical Frequency
n:dfehz:bus1HzDeviation of the El. Frequency
n:fehz:bus1HzElectrical Frequency
n:frnom:bus1HzNominal Frequency
n:ishcr:bus1p.u.Short-Circuit Current, real
n:ishci:bus1p.u.Short-Circuit Current, imag
n:dfedt:bus1p.u./sDerivative of El. Frequency
n:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aper phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1kV3*U0
n:phiu0:bus1degZero-Sequence Voltage, Angle
n:U1:bus1kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1degPositive-Sequence Voltage, Angle
n:u2:bus1p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1degNegative-Sequence Voltage, Angle
n:U1l:bus1kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1degNeutral-Ground Voltage, Angle
n:upht:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bus1p.u.Average-Voltage, Magnitude
n:Um:bus1kVAverage-Voltage, Magnitude
n:ishc:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, magnitude
n:Ishc:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, magnitude
n:inshc:bus1p.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bus1kANeutral Short-Circuit Current, magnitude
n:ishcr:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, real
n:ishci:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, imag
s:PextMWLoad
s:QextMvarLoad
s:igenp.u.Generation
s:phiuigenradGeneration
s:igenap.u.Generation
s:igenbp.u.Generation
s:phiuigenaradGeneration
s:phiuigenbradGeneration
s:igencp.u.Generation
s:phiuigencradGeneration

ElmLodmv emt simulation results

Read after ComInc (EMT) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:u0:bus1p.u.Zero-Sequence-Voltage
m:u1r:bus1p.u.Voltage Phasor, Real Part
m:u1i:bus1p.u.Voltage Phasor, Imaginary Part
m:u1:bus1p.u.Voltage Phasor, Magnitude
m:U1:bus1kVLine-Ground Voltage Phasor, Magnitude
m:U1l:bus1kVLine-Line Voltage Phasor, Magnitude
m:phiu1:bus1degVoltage Phasor, Angle
m:inet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, referred to network
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAPhase Current
m:i0:bus1p.u.Zero-Sequence Current
m:I0:bus1kAZero-Sequence Current
m:I0x3:bus1kA3*I0
m:i1r:bus1p.u.Current Phasor, Real Part
m:i1i:bus1p.u.Current Phasor, Imaginary Part
m:i1:bus1p.u.Current Phasor, Magnitude
m:I1:bus1kACurrent Phasor, Magnitude
m:phii1:bus1degCurrent Phasor, Angle
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Psum:bus1MWPower-Phasor, Active Power
m:Qsum:bus1MvarPower Phasor, Reactive Part
m:Ssum:bus1MVAPower Phasor, Apparent Power
m:i1P:bus1p.u.Current Phasor, Active Current
m:i1Q:bus1p.u.Current Phasor, Reactive Current
m:I1P:bus1kACurrent Phasor, Active Current
m:I1Q:bus1kACurrent Phasor, Reactive Current
m:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
m:i:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current
m:phiu1i1:bus1degAngle between Voltage and Current Phasor
m:Tfct:bus1sFault Clearing Time
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:unet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, referred to network
m:cosphi1:bus1ยทPower-Phasor, Power-Factor
c:frnomHzNominal Frequency
c:hpirad/sNominal angular frequency
c:ROhmResistance
c:LmHInductance
c:CuFCapacitance
c:RaOhmResistance
c:RbOhmResistance
c:LamHInductance
c:LbmHInductance
c:CauFCapacitance
c:CbuFCapacitance
c:RcOhmResistance
c:LcmHInductance
c:CcuFCapacitance
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Phase Voltage
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Voltage
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage
n:u0:bus1p.u.Zero-Sequence-Voltage
n:U0:bus1kVZero-Sequence-Voltage
n:U0x3:bus1kV3*U0
n:u1:bus1p.u.Voltage Phasor, Magnitude
n:u1pc:bus1%Voltage Phasor, Magnitude
n:u1r:bus1p.u.Voltage Phasor, Real Part
n:u1i:bus1p.u.Voltage Phasor, Imaginary Part
n:U1:bus1kVVoltage Phasor, Magnitude
n:phiu1:bus1degVoltage Phasor, Angle
n:U1l:bus1kVLine-Line Voltage Phasor, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage
n:un:bus1p.u.Neutral-Ground Voltage
n:Un:bus1kVNeutral-Ground Voltage
n:ishc:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current
n:Ishc:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:inshc:bus1p.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bus1kANeutral Short-Circuit Current, magnitude
n:fe:bus1p.u.Electrical Frequency
n:dfehz:bus1HzDeviation of the El. Frequency
n:fehz:bus1HzElectrical Frequency
n:frnom:bus1HzNominal Frequency

ElmLodmv dc load flow results

Read after ComLdf (DC) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
c:ncustยทNumber of Connected Customers
c:scale0ยทInitial Scale Factor
c:zonescaleยทZone Scale Factor
c:gscaleยทGeneration Scale Factor
c:tempscFacยทTemperature dependent load scaling factor
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PnomMWNominal Active Power
c:PpeakMWPeak Active Power
c:piniMWNominal Active Power
c:iRefElementยทReference Element
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:Pgen:bus1MWGeneration, Active Power
n:Pmot:bus1MWMotor Load, Active Power
n:Pload:bus1MWGeneral Load, Active Power
n:Pcomp:bus1MWCompensation (Losses)
n:Pnet:bus1MWExternal Networks, Active Power
n:Pflow:bus1MWPower Flow, Active Power
s:scaleยทScale Factor
s:pini_setยทNominal Active Power

Read after ComMod with GetAttribute. s: signal (state or model variable).

AttributeUnitDescription
s:PextMWLoad
s:QextMvarLoad
s:igenp.u.Generation
s:phiuigenradGeneration

ElmLodmv optimal power flow results

Read after ComOpf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:bus1p.u.Voltage, Real Part, referred to network
m:uinet:bus1p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1degPositive-Sequence-Voltage, Angle
m:irnet:bus1p.u.Current, Real Part, referred to network
m:iinet:bus1p.u.Current, Imaginary Part, referred to network
m:inet:bus1p.u.Current, Magnitude, referred to network
m:I:bus1kACurrent, Magnitude
m:phii:bus1degCurrent, Angle
m:i1r:bus1p.u.Positive-Sequence Current, Real Part
m:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:S:bus1MVAApparent Power
m:cosphi:bus1ยทPower Factor
m:tanphi:bus1ยทtan(phi)
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:Ssum:bus1MVATotal Apparent Power
m:cosphisum:bus1ยทTotal Power Factor
m:tanphisum:bus1ยทTotal tan(phi)
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:ur:bus1p.u.Voltage, Real Part
m:ui:bus1p.u.Voltage, Imaginary Part
m:u:bus1p.u.Voltage, Magnitude
m:ir:bus1p.u.Current, Real Part
m:ii:bus1p.u.Current, Imaginary Part
m:i:bus1p.u.Current, Magnitude
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1sFault Clearing Time
m:Brkload:bus1%Breaker Loading
m:Spu:bus1MVA/p.u.Apparent Power per p.u. Voltage
c:sยทComplex Power (P+jQ)
c:frnomHzNominal Frequency
c:hpirad/sNominal angular frequency
c:u0p.u.Nominal Voltage
c:nntapยทCurrent Tap Position
c:ulvp.u.LV Voltage
c:GmloadkWIron Losses
c:ncustยทNumber of Connected Customers
c:scale0ยทInitial Scale Factor
c:zonescaleยทZone Scale Factor
c:gscaleยทGeneration Scale Factor
c:tempscFacยทTemperature dependent load scaling factor
c:kpu0ยทVolt. Dependence I on P
c:kqu0ยทVolt. Dependence I on Q
c:kpu1ยทVolt. Dependence II on P
c:kqu1ยทVolt. Dependence II on Q
c:kpuยทVolt. Dependence III on P
c:kquยทVolt. Dependence III on Q
c:aPยทPercent of Volt. Dep. I on P
c:bPยทPercent of Volt. Dep. II on P
c:aQยทPercent of Volt. Dep. I on Q
c:bQยทPercent of Volt. Dep. II on Q
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:PnomMWNominal Active Power
c:QnomMvarNominal Reactive Power
c:PpeakMWPeak Active Power
c:QpeakMvarPeak Reactive Power
c:piniMWNominal Active Power
c:qiniMvarNominal Reactive Power
c:iRefElementยทReference Element
c:dudropTrf%max. Voltage drop across transformer
c:duriseTrf%max. Voltage rise across transformer
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bus1MWGeneration, Active Power
n:Qgen:bus1MvarGeneration, Reactive Power
n:Pmot:bus1MWMotor Load, Active Power
n:Qmot:bus1MvarMotor Load, Reactive Power
n:Pload:bus1MWGeneral Load, Active Power
n:Qload:bus1MvarGeneral Load, Reactive Power
n:Pcomp:bus1MWCompensation (Losses)
n:Qcomp:bus1MvarCompensation
n:Pnet:bus1MWExternal Networks, Active Power
n:Qnet:bus1MvarExternal Networks, Reactive Power
n:Pflow:bus1MWPower Flow, Active Power
n:Qflow:bus1MvarPower Flow, Reactive Power
n:Pout:bus1MWOutgoing Flow, Active Power
n:Qout:bus1MvarOutgoing Power, Reactive Power
n:Sout:bus1MVAOutgoing Power, Apparent Power
n:cosphiout:bus1ยทOutgoing Power, Power Factor
n:Pbalance:bus1MWActive Power Balance (=0)
n:Qbalance:bus1MvarReactive Power Balance (=0)
n:LossPdown:bus1MWLosses, downstream
n:LossQdown:bus1MvarLosses, downstream (Reactive Power)
n:LossPdownload:bus1MWLoad losses, downstream
n:LossQdownload:bus1MvarLoad losses, downstream
n:LossPdownnoload:bus1MWNo load losses, downstream
n:LossQdownnoload:bus1MvarNo load losses, downstream
n:du_feed:bus1%Difference from voltage at start of feeder

ElmLodmv basic data

b: values are worked out from the input data. Read them; they are not set.

AttributeUnitDescription
b:loc_nameยทName

Related

โ† ElmLodlv Low-Voltage Load ยท ElmShnt Shunt/Filter โ†’