ElmShnt attributesPowerFactory Shunt/Filter

Every attribute of the PowerFactory Shunt/Filter (ElmShnt): 179 input parameters and 1054 result variables, with units and meaning. Copy a name into GetAttribute or SetAttribute.

What ElmShnt is

A shunt: a capacitor bank, a reactor or a tuned filter, with switchable steps.

Class
ElmShnt, element class
PowerFactory name
Shunt/Filter
Terminal suffix
:bus1 terminal
Attributes
179 input parameters and 1054 result variables, in 7 calculations

Most used ElmShnt attributes

AttributeUnitDescriptionWhere
m:Q:bus1MvarReactive Powerreactive powerLoad flow
shtypeยทShunt TypeR-L, C, R-L-C...input data
qcapnMvarRated Reactive Power, Crated reactive power, capacitiveinput data
qreanMvarRated Reactive Power, Lrated reactive power, inductiveinput data
ncapaยทAct. No. of Stepsteps in serviceinput data
ncapxยทMax. No. of Stepsnumber of stepsinput data
ushnmkVRated Voltageinput data
outservยทOut of Serviceinput data

Read and write ElmShnt in Python

import powerfactory

app = powerfactory.GetApplication()          # GetApplicationExt() from outside PowerFactory
app.GetFromStudyCase("ComLdf").Execute()      # results exist after a calculation

for shunt in app.GetCalcRelevantObjects("*.ElmShnt"):
    q_bus1 = shunt.GetAttribute("m:Q:bus1")       # Reactive Power, Mvar
    print(shunt.loc_name, q_bus1)

shunt = app.GetCalcRelevantObjects("*.ElmShnt")[0]
shunt.SetAttribute("ncapa", 2)                # switch in 2 steps
  • A result at a terminal of the shunt/filter needs the terminal in its name: m:P:bus1, not m:P, which raises AttributeError.
  • An input parameter is read and written with or without its e: prefix: GetAttribute("outserv") and GetAttribute("e:outserv") give the same value.
  • RMS and EMT variables change over time: record them in a results object (ElmRes) to read the whole curve. GetAttribute after a run gives the value at the last time step.

ElmShnt input parameters

The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.

AttributeUnitDescription
loc_nameยทName
chr_nameยทCharacteristic Name
for_nameยทForeign Key
dat_srcยทData source
imldcยทControl Mode
sernumยทSerial Number
manufยทManufacturer
commissionDateยทCommissioning Date
appr_modbyยทModified by
mode_inpยทInput Mode
outservยทOut of Service
iintgndยทN-Connection
ilcphยทPhase
iQorientยทOrientation
ncapxยทMax. No. of Steps
ncapaยทAct. No. of Step
shtypeยทShunt Type
i_optยทUse Controller for OPF optimisation
i_optContยทControl Mode
isCtrlShntยทTap Control for Unit Commitment
isCtrlShntContยทControl Mode
ctrlUsageยทTap Changer
curativeLimยทMax. curative tap deviation
isAllowSwitchingยทAllow control to be switched on/off
minTapยทMin. No. of Steps
itrmtยทType
iFinalSlopeยทSet final slope (peak values)
ksatยทSaturation Exponent
iLimbยทCore
iInterPolยทInterpolation
iFitยทData fitting
iHysterยทModel
iResFluxยทResidual flux
systpยทSystem Type
iZeConfigยทConfiguration
iswitchยทSwitchable
i_contยทTap Changer
constrยทYear of Construction
appr_statusยทStatus
i_remยทRemote Control
pf_recap_mxยทPower Factor
pf_recap_mnยทPower Factor
uset_modeยทSetpoint
iIntTapCtrlยทUse Integrated Tap Controller
iTapsยทAccording to Measurement Report
iperfectยทIdeal component
ushnmkVRated Voltage
qcapnMvarRated Reactive Power, C
qtotnMvarRated Reactive Power, L-C
cucapARated Current, C
cutotARated Current, L-C
bcapuSSusceptance
ccapuFCapacitance
c1uFCapacitance C1
c2uFCapacitance C2
pgrad%Degree
fresHzResonant Frequency
nresยทTuning Order
qreanMvarRated Reactive Power, L
cureaARated Current, L
xreaOhmReactance
rlreamHInductance
greaยทQuality Factor (at fn)
greaf0ยทQuality Factor (at fr)
rreaOhmResistance
rparaOhmParallel Resistance
tandcยทLoss Factor, tan(delta)
gparacuSParallel Conductance
psi0p.u.Knee Flux
xmairp.u.Saturated Reactance
smoothfac%Smoothing Factor
Lwidth%Loop width
PsiresAp.u.Residual flux, ph. A
PsiresBp.u.Residual flux, ph. B
PsiresCp.u.Residual flux, ph. C
BgnSSusceptance to Ground
XeOhmReactance, Xe
ReOhmResistance, Re
X0toX1ยทX0/X1 ratio
R0toR1ยทR0/R1 ratio
B0toB1ยทB0/B1 ratio
G0toG1ยทG0/G1 ratio
acostUSD/aAnnual Cost
TctrlsController Time Constant
Kctrlp.u./%Controller Sensitivity dq/dv
usetp_mxp.u.Upper Voltage Limit
usetp_mnp.u.Lower Voltage Limit
qsetp_mxMvarUpper Reactive Power Limit
qsetp_mnMvarLower Reactive Power Limit
pfsetp_mxยทUpper Power Factor Limit
pfsetp_mnยทLower Power Factor Limit
GPSlatdegLatitude / Northing
GPSlondegLongitude / Easting
penaltyCostsUSDPenalty costs per tap deviation
curativeCostsUSDCosts per curative tap deviation
switchOnCostsUSDSwitch-on costs
switchOffCostsUSDSwitch-off costs
appr_modifยทModified
satcurp.u.Current (peak)
satfluxp.u.Flux (peak)
satcue%Current (RMS)
satvolp.u.Voltage (RMS)
mTapsยทMeasurement Report
cimRdfIdยทRDF ID
descยทDescription
sOpCommentยทOperator Comment
fold_idยทIn Folder
bus1ยทTerminalObject: StaCubic
bus1nยทNeutralObject: StaCubic
fcharLChaPol,ChaVec,ChaMatL(f)
fcharRChaPol,ChaVec,ChaMatRs(f)
fcharCChaPol,ChaVec,ChaMatC(f)
fcharL0ChaPol,ChaVec,ChaMatL0(f)
fcharR0ChaPol,ChaVec,ChaMatRs0(f)
fcharC0ChaPol,ChaVec,ChaMatC0(f)
fcharC1ChaPol,ChaVec,ChaMatC1(f)
fcharC2ChaPol,ChaVec,ChaMatC2(f)
fcharRpChaPol,ChaVec,ChaMatRp(f)
doc_idยทAdditional Data
pOwnerยทOwnerObject: ElmOwner
pOperatorยทOperatorObject: ElmOperator
p_remยทControlled NodeObject: StaBar,ElmTerm
p_cubยทQ Controlled atObject: StaCubic,ElmBoundary
pStochStoTyptrfElement model
cpHeadFoldยทHead Folder
bus1_barยทTerminal
bus1n_barยทNeutral
cpGridยทGridObject: ElmNet
cpZoneยทZoneObject: ElmZone
cpAreaยทAreaObject: ElmArea
cpFeedยทFeederObject: ElmFeeder
ciDistยทDistance from infeed in number of buses
ciLaterยทLateral Index
ciDistRootยทDistance from first infeed in number of buses
ciDistAllยทDistance from infeed in number of buses including switches
ciDistAllRootยทDistance from first infeed in number of buses including switches
cpOwnerยทOwnerObject: ElmOwner
cpOperatorยทOperatorObject: ElmOperator
cpBranchยทBranchObject: ElmBranch
cpSiteยทSiteObject: ElmSite
cpSubstatยทSubstationObject: ElmSubstat,ElmTrfstat
cpMeteostatยทMeteo StationObject: ElmMeteostat
ciOutagedยทPlanned Outage
ciEnergizedยทEnergized
ciEarthedยทEarthed
cDisplayNameยทDisplay Name
cpSupplyTransformerยทSupplying TransformerObject: ElmTr?,ElmTrmult
cpSupplyTrfStationยทSupplying Secondary SubstationObject: ElmTrfstat
cpSupplySubstationยทSupplying SubstationObject: ElmSubstat
cgndยทStar Point
ctechยทTechnology
harmPgeLmHInductance
harmPgeROhmResistance
harmPgeCuFCapacitance
harmPgeL0mHZero-sequence Ind.
harmPgeR0OhmZero-sequence Res.
harmPgeC0uFZero-sequence Cap.
harmPgeC1uFCapacitance 1
harmPgeC2uFCapacitance 2
harmPgeRpOhmParallel Resistance
xreapup.u.Linear Reactance
cPsiresCp.u.Residual flux, ph. C
aFrolichยทFrolich equation coefficient a
bFrolichยทFrolich equation coefficient b
cFrolichยทFrolich equation coefficient c
xsatFrolichยทFrolich equation saturated reactance (p.u.)
mseFrolichยทFrolich equation, mean squared error
cpCtrlNodeยทTarget NodeObject: ElmTerm
c_pstacยทExternal Station ControllerObject: ElmStactrl
c_pctrlยทShunt ControllerObject: ElmShntctrl
qdslCtrlยทQuasi-Dynamic ModelObject: ElmQdsl
QmaxMvarMax. Rated Reactive Power
QactMvarActual Reactive Power
FOR11/aForced Outage Rate
FOEh/aForced Outage Expectancy
FODhForced Outage Duration
CCEarFr1/aFrequency of single earth faults
CCEarRepMuhRepair duration
CCEarProb%Conditional probability of a second earth fault

ElmShnt load flow results

Read after ComLdf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bus1p.u.Voltage, Real Part, referred to network
m:uinet:bus1p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1degPositive-Sequence-Voltage, Angle
m:irnet:bus1p.u.Current, Real Part, referred to network
m:iinet:bus1p.u.Current, Imaginary Part, referred to network
m:inet:bus1p.u.Current, Magnitude, referred to network
m:I:bus1kACurrent, Magnitude
m:phii:bus1degCurrent, Angle
m:i1r:bus1p.u.Positive-Sequence Current, Real Part
m:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:S:bus1MVAApparent Power
m:cosphi:bus1ยทPower Factor
m:tanphi:bus1ยทtan(phi)
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:Ssum:bus1MVATotal Apparent Power
m:cosphisum:bus1ยทTotal Power Factor
m:tanphisum:bus1ยทTotal tan(phi)
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:ur:bus1p.u.Voltage, Real Part
m:ui:bus1p.u.Voltage, Imaginary Part
m:u:bus1p.u.Voltage, Magnitude
m:ir:bus1p.u.Current, Real Part
m:ii:bus1p.u.Current, Imaginary Part
m:i:bus1p.u.Current, Magnitude
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1sFault Clearing Time
m:Brkload:bus1%Breaker Loading
m:Spu:bus1MVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bus1p.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bus1degZero-Sequence-Voltage, Angle
m:u2:bus1p.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bus1degNegative-Sequence-Voltage, Angle
m:irnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part, referred to network
m:iinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part, referred to network
m:inet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude, referred to network
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bus1p.u.Zero-Sequence Current, Real Part
m:i0i:bus1p.u.Zero-Sequence Current, Imaginary Part
m:i0:bus1p.u.Zero-Sequence Current, Magnitude
m:I0:bus1kAZero-Sequence Current, Magnitude
m:I0x3:bus1kA3*I0
m:phii0:bus1degZero-Sequence Current, Angle
m:i2r:bus1p.u.Negative-Sequence Current, Real Part
m:i2i:bus1p.u.Negative-Sequence Current, Imaginary Part
m:i2:bus1p.u.Negative-Sequence Current, Magnitude
m:I2:bus1kANegative-Sequence Current, Magnitude
m:phii2:bus1degNegative-Sequence Current, Angle
m:ubfacI:bus1%Current Unbalance Factor
m:ubfacS:bus1%Power Unbalance Factor
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bus1:Aper phase :A, :B, :C, unbalanced onlyยทPower Factor
m:tanphi:bus1:Aper phase :A, :B, :C, unbalanced onlyยทtan(phi)
m:Pln:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bus1MWPositive Sequence Active Power
m:Q1:bus1MvarPositive Sequence Reactive Power
m:P2:bus1MWNegative Sequence Active Power
m:Q2:bus1MvarNegative Sequence Reactive Power
m:P0:bus1MWZero Sequence Active Power
m:Q0:bus1MvarZero Sequence Reactive Power
m:i2P:bus1p.u.Negative-Sequence Active Current
m:i2Q:bus1p.u.Negative-Sequence Reactive Current
m:I2P:bus1kANegative-Sequence Active Current
m:I2Q:bus1kANegative-Sequence Reactive Current
m:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1degAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bus1degAngle between Voltage and Current in negative sequence system
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bus1:Aper phase :A, :B, :C, unbalanced only%Breaker Loading
c:zp.u.Shunt-Impedance
c:cnยทConnection Mode
c:frnomHzNominal Frequency
c:hpirad/sNominal Angular Frequency
c:rsp.u.Rs
c:gpp.u.Gp
c:xlp.u.Xl
c:bc1p.u.Bc1
c:bc2p.u.Bc2
c:uc1p.u.Voltage across C1
c:uc2p.u.Voltage across C2
c:ucp.u.Voltage across C1 and C2
c:urlp.u.Voltage across Inductor (Rs-L)
c:urpp.u.Voltage across Rp
c:ILACurrent through Inductor L
c:ICACurrent through C2
c:IRpACurrent through Rp
c:PRpkWLosses in Rp
c:PLkWLosses in Inductor (Rs)
c:Uc1kVVoltage across C1
c:Uc2kVVoltage across C2
c:UckVVoltage across C1 and C2
c:UrlkVVoltage across Inductor (Rs-L)
c:UrpkVVoltage across Rp
c:ncapaยทNumber of Stages in Parallel
c:acostยทAnnual Cost
c:ncapxยทMax. No. of Steps
c:nCtrlIterยทNo. of CTRL-iterations
c:TctrlยทController Time Constant
c:Kctrlp.u./%Controller Sensitivity dq/dv
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:b0p.u.sigmaC
c:bcp.u.Bc
c:gpcp.u.Gp(C)
c:y0p.u.Zero Sequence Admittance
c:zep.u.Grounding Impedance
c:uc1ph:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage across Capacitor C1(Phase Value)
c:uc2ph:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage across Capacitor C2(Phase Value)
c:ucph:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage across C1 and C2(Phase Value)
c:ucphp.u.Voltage across Capacitor (Phase Value)
c:urlph:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage across Rs-L (Phase Value)
c:urlphp.u.Voltage across Inductor (Phase Value)
c:urpph:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage across Rp (Phase Value)
c:ILph:Aper phase :A, :B, :C, unbalanced onlyACurrent through Inductor L (Phase Value)
c:ILphACurrent through Inductor L (Phase Value)
c:ICph:Aper phase :A, :B, :C, unbalanced onlyACurrent through C2 (Phase Value)
c:ICphACurrent through Capacitor C (Phase Value)
c:IRpph:Aper phase :A, :B, :C, unbalanced onlyACurrent through Rp (Phase Value)
c:IRpphACurrent through Rp (Phase Value)
c:UstarkVStar-Point Voltage
c:Uc1ph:Aper phase :A, :B, :C, unbalanced onlykVVoltage across Capacitor C1(Phase Value)
c:Uc2ph:Aper phase :A, :B, :C, unbalanced onlykVVoltage across Capacitor C2(Phase Value)
c:Ucph:Aper phase :A, :B, :C, unbalanced onlykVVoltage across C1 and C2(Phase Value)
c:UcphkVVoltage across Capacitor (Phase Value)
c:Urlph:Aper phase :A, :B, :C, unbalanced onlykVVoltage across Rs-L (Phase Value)
c:UrlphkVVoltage across Inductor (Phase Value)
c:Urpph:Aper phase :A, :B, :C, unbalanced onlykVVoltage across Rp (Phase Value)
c:z0p.u.Zero Sequence Impedance
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bus1MWGeneration, Active Power
n:Qgen:bus1MvarGeneration, Reactive Power
n:Pmot:bus1MWMotor Load, Active Power
n:Qmot:bus1MvarMotor Load, Reactive Power
n:Pload:bus1MWGeneral Load, Active Power
n:Qload:bus1MvarGeneral Load, Reactive Power
n:Pcomp:bus1MWCompensation (Losses)
n:Qcomp:bus1MvarCompensation
n:Pnet:bus1MWExternal Networks, Active Power
n:Qnet:bus1MvarExternal Networks, Reactive Power
n:Pflow:bus1MWPower Flow, Active Power
n:Qflow:bus1MvarPower Flow, Reactive Power
n:Pout:bus1MWOutgoing Flow, Active Power
n:Qout:bus1MvarOutgoing Power, Reactive Power
n:Sout:bus1MVAOutgoing Power, Apparent Power
n:cosphiout:bus1ยทOutgoing Power, Power Factor
n:Pbalance:bus1MWActive Power Balance (=0)
n:Qbalance:bus1MvarReactive Power Balance (=0)
n:LossPdown:bus1MWLosses, downstream
n:LossQdown:bus1MvarLosses, downstream (Reactive Power)
n:LossPdownload:bus1MWLoad losses, downstream
n:LossQdownload:bus1MvarLoad losses, downstream
n:LossPdownnoload:bus1MWNo load losses, downstream
n:LossQdownnoload:bus1MvarNo load losses, downstream
n:du_feed:bus1%Difference from voltage at start of feeder
n:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aper phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1kV3*U0
n:phiu0:bus1degZero-Sequence Voltage, Angle
n:U1:bus1kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1degPositive-Sequence Voltage, Angle
n:u2:bus1p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1degNegative-Sequence Voltage, Angle
n:U1l:bus1kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1degNeutral-Ground Voltage, Angle
n:upht:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bus1p.u.Average-Voltage, Magnitude
n:Um:bus1kVAverage-Voltage, Magnitude
n:uphtmin:bus1p.u.Minimum of Phase Technology dependent Voltage, Magnitude
n:uphtmax:bus1p.u.Maximum of Phase Technology dependent Voltage, Magnitude
n:ubfac:bus1%Unbalance Factor
s:ncapainยทNumber of Stages in Parallel, input

ElmShnt short-circuit results

Read after ComShc with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:I:bus1kAShort-Circuit Current, Magnitude
m:phii:bus1degPhase Current, Angle
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in Positive-Sequence System
m:Tfct:bus1sFault Clearing Time
m:Ikss:bus1kAInitial Short-Circuit Current
m:ikss:bus1p.u.Initial Short-Circuit Current, Magnitude
m:Skss:bus1MVAInitial Short-Circuit Power
m:ip:bus1kAPeak Short-Circuit Current
m:maxIkss:bus1kAMax. Initial Short-Circuit Current
m:maxip:bus1kAMax. Peak Short-Circuit Current
m:maxIth:bus1kAMax. Thermal equivalent Short-Circuit Current
m:maxIb:bus1kAMax. Breaking Current
m:R:bus1OhmFault Impedance, Real Part
m:X:bus1OhmFault Impedance, Imaginary Part
m:Z:bus1OhmFault Impedance, Magnitude
m:phiz:bus1degFault Impedance, Angle
m:Rs:bus1OhmSource Impedance, Real Part
m:Xs:bus1OhmSource Impedance, Imaginary Part
m:Zs:bus1OhmSource Impedance, Magnitude
m:phizs:bus1degSource Impedance, Angle
m:BrkIpload:bus1%Breaker Loading (peak)
m:Ib:bus1kAShort-Circuit Breaking Current
m:Sb:bus1MVAShort-Circuit Breaking Power
m:Ith:bus1kAThermal equivalent Short-Circuit Current
m:zSbase:bus1p.u.Fault Impedance, Magnitude
m:XtoR:bus1ยทX/R ratio
m:cosphiui:bus1ยทcosphi
m:BrkIbload:bus1%Breaker Loading (breaking)
m:BrkmaxIb:bus1kAMax. Breaking Current (breaker time)
m:Ik:bus1kASteady-State Short-Circuit Current
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, Magnitude
m:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:I0:bus1kAZero-Sequence Current, Magnitude
m:I0x3:bus1kA3*I0
m:phii0:bus1degZero-Sequence Current, Angle
m:I2:bus1kANegative-Sequence Current, Magnitude
m:phii2:bus1degNegative-Sequence Current, Angle
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:cosphisum:bus1ยทTotal Power Factor
m:P2:bus1MWP2
m:Q2:bus1MvarQ2
m:P0:bus1MWP0
m:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1degAngle between Voltage and Current in Zero-Sequence System
m:phiu2i2:bus1degAngle between Voltage and Current in Negative-Sequence System
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:Ikss:bus1:Aper phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
m:ikss:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Initial Short-Circuit Current, Magnitude
m:Skss:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
m:Skssx3:bus1:Aper phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
m:ip:bus1:Aper phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
m:Z:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmFault Impedance, Magnitude
m:phiz:bus1:Aper phase :A, :B, :C, unbalanced onlydegFault Impedance, Angle
m:Zl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmLine-Line Fault Impedance, Magnitude
m:phizl:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Fault Impedance, Angle
m:Z0:bus1OhmZero-Sequence Fault Impedance, Magnitude
m:phiz0:bus1degZero-Sequence Fault Impedance, Angle
m:z0Sbase:bus1p.u.Zero-Sequence Fault Impedance, Magnitude
m:cosphiu1i1:bus1ยทPositive-Sequence cosphi
m:I0x3watt:bus1kAEarth-Fault Residual Current
m:I0x3var:bus1kACapacitive Earth-Fault Current
m:Q0cap:bus1MvarQ0 capacitive
m:Rfrel:bus1OhmRelay Impedance, Real Part
m:Xfrel:bus1OhmRelay Impedance, Imaginary Part
m:Zfrel:bus1OhmRelay Impedance, Magnitude
m:phizfrel:bus1degRelay Impedance, Angle
m:Zf:bus1OhmMeas. Fault Impedance, Magnitude
m:phizf:bus1degMeas. Fault Impedance, Angle
c:zp.u.Shunt-Impedance
c:cnยทConnection Mode
c:frnomHzNominal Frequency
c:hpirad/sNominal Angular Frequency
c:rsp.u.Rs
c:gpp.u.Gp
c:xlp.u.Xl
c:uc1p.u.Voltage across C1
c:uc2p.u.Voltage across C2
c:ucp.u.Voltage across C1 and C2
c:urlp.u.Voltage across Inductor (Rs-L)
c:urpp.u.Voltage across Rp
c:ILACurrent through Inductor L
c:ICACurrent through C2
c:IRpACurrent through Rp
c:PRpkWLosses in Rp
c:PLkWLosses in Inductor (Rs)
c:Uc1kVVoltage across C1
c:Uc2kVVoltage across C2
c:UckVVoltage across C1 and C2
c:UrlkVVoltage across Inductor (Rs-L)
c:UrpkVVoltage across Rp
c:ncapaยทNumber of Stages in Parallel
c:b0p.u.Susceptance to Ground
c:uha_c1p.u.Harmonic Voltage (arith.) across C1
c:uhrms_c1p.u.Harmonic Voltage (RMS) across C1
c:ut_c1p.u.Total Voltage (u_fn+uhrms) across C1
c:ufn_c1p.u.Fundamental Frequency Voltage across C1
c:uha_c2p.u.Harmonic Voltage (arith.) across C2
c:uhrms_c2p.u.Harmonic Voltage (RMS) across C2
c:ut_c2p.u.Total Voltage (u_fn+uhrms) across C2
c:ufn_c2p.u.Fundamental Frequency Voltage across C2
c:uha_cp.u.Harmonic Voltage (arith.) across C1 and C2
c:uhrms_cp.u.Harmonic Voltage (RMS) across C1 and C2
c:ut_cp.u.Total Voltage (u_fn+uhrms) across C1 and C2
c:ufn_cp.u.Fundamental Frequency Voltage across C1 and C2
c:uha_rlp.u.Harmonic Voltage (arith.) across Inductor (Rs-L)
c:uhrms_rlp.u.Harmonic Voltage (rms) across Inductor (Rs-L)
c:ut_rlp.u.Total Voltage (u_fn+uhrms) across Inductor (Rs-L)
c:Ihrms_LAHarmonic Current (rms) through Inductor (Rs-L)
c:Irms_LARMS Value of Current through Inductor (Rs-L)
c:Ihrms_RpAHarmonic Current (rms) through Rp
c:Irms_RpARMS Value of Current through Rp
c:Ph_RpkWHarmonic Losses of Rp
c:Pt_RpkWTotal Losses of Rp
c:Ph_LkWHarmonic Losses of Inductor (Rs)
c:Pt_LkWTotal Losses of Inductor
c:ufn_rlp.u.Fundamental Frequency Voltage across Inductor (Rs-L)
c:Ifn_RpAFundamental Frequency Current through Rp
c:Ifn_LAFundamental Frequency Current through Inductor (Rs-L)
c:Pfn_LkWFundamental Frequency Losses of Inductor
c:Pfn_RpkWFundamental Frequency Losses of Rp
c:Ifn_cAFundamental Frequency Current through Capacitor C2
c:Ihrms_cAHarmonic Current (rms) through Capacitor C2
c:Irms_cARMS Value of Current through Capacitor C2
c:C1uFAuxiliary Capacitance C1
c:C2uFMain Capacitance C2
c:LmHInductance L
c:RpOhmParallel-Resistance Rp
c:RsOhmResistance Rs
c:Uha_c1kVHarmonic Voltage (arith.) across C1
c:Uhrms_c1kVHarmonic Voltage (RMS) across C1
c:Ut_c1kVTotal Voltage (U_fn+Uhrms) across C1
c:Ufn_c1kVFundamental Frequency Voltage across C1
c:Uha_c2kVHarmonic Voltage (arith.) across C2
c:Uhrms_c2kVHarmonic Voltage (RMS) across C2
c:Ut_c2kVTotal Voltage (U_fn+Uhrms) across C2
c:Ufn_c2kVFundamental Frequency Voltage across C2
c:Uha_ckVHarmonic Voltage (arith.) across C1 and C2
c:Uhrms_ckVHarmonic Voltage (RMS) across C1 and C2
c:Ut_ckVTotal Voltage (U_fn+Uhrms) across C1 and C2
c:Ufn_ckVFundamental Frequency Voltage across C1 and C2
c:Uha_rlkVHarmonic Voltage (arith.) across Inductor (Rs-L)
c:Uhrms_rlkVHarmonic Voltage (rms) across Inductor (Rs-L)
c:Ut_rlkVTotal Voltage (U_fn+Uhrms) across Inductor (Rs-L)
c:Ufn_rlkVFundamental Frequency Voltage across Inductor (Rs-L)
c:bcp.u.Bc
c:gpcp.u.Gp(C)
c:CuFCapacitance C
c:y0p.u.Zero Sequence Admittance
c:zep.u.Grounding Impedance
c:uc1ph:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage across C1 (Phase Value)
c:uc2ph:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage across C2 (Phase Value)
c:ucph:Aper phase :A, :B, :C, unbalanced onlyp.u.uc1
c:ucphp.u.Voltage across Capacitor (Phase Value)
c:urlph:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage across Inductor (Phase Value)
c:urlphp.u.Voltage across Inductor (Phase Value)
c:urpph:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage across Rp (Phase Value)
c:ILph:Aper phase :A, :B, :C, unbalanced onlyACurrent through Inductor (Phase Value)
c:ILphACurrent through Inductor (Phase Value)
c:ICph:Aper phase :A, :B, :C, unbalanced onlyACurrent through C2 (Phase Value)
c:ICphACurrent through Capacitor C(Phase Value)
c:IRpph:Aper phase :A, :B, :C, unbalanced onlyACurrent through Rp (Phase Value)
c:IRpphACurrent through Rp (Phase Value)
c:UstarkVStar-Point Voltage
c:Uc1ph:Aper phase :A, :B, :C, unbalanced onlykVVoltage across C1 (Phase Value)
c:Uc2ph:Aper phase :A, :B, :C, unbalanced onlykVVoltage across C2 (Phase Value)
c:Ucph:Aper phase :A, :B, :C, unbalanced onlykVUrl
c:UcphkVVoltage across Capacitor (Phase Value)
c:Urlph:Aper phase :A, :B, :C, unbalanced onlykVVoltage across Inductor (Phase Value)
c:UrlphkVVoltage across Inductor (Phase Value)
c:Urpph:Aper phase :A, :B, :C, unbalanced onlykVVoltage across Rp (Phase Value)
c:ncapxยทMax. No. of Steps
c:i_earthยทInternal
c:Uhaph_c1:Aper phase :A, :B, :C, unbalanced onlykVsigmaC
c:Ufnph_c1:Aper phase :A, :B, :C, unbalanced onlykVsigmaC
c:Uhaph_c2:Aper phase :A, :B, :C, unbalanced onlykVsigmaC
c:Ufnph_c2:Aper phase :A, :B, :C, unbalanced onlykVsigmaC
c:Uhaph_c:Aper phase :A, :B, :C, unbalanced onlykVsigmaC
c:Uhaph_ckVsigmaC
c:Ufnph_c:Aper phase :A, :B, :C, unbalanced onlykVsigmaC
c:Ufnph_ckVsigmaC
c:Uhaph_rl:Aper phase :A, :B, :C, unbalanced onlykVsigmaC
c:Uhaph_rlkVsigmaC
c:Ufnph_rl:Aper phase :A, :B, :C, unbalanced onlykVsigmaC
c:Ufnph_rlkVsigmaC
c:z0p.u.Zero Sequence Impedance
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:Ikss:bus1kAInitial Short-Circuit Current
n:I:bus1kAShort-Circuit Current
n:phii:bus1degPhase Current, Angle
n:Skss:bus1MVAInitial Short-Circuit Power
n:ip:bus1kAPeak Short-Circuit Current
n:Ib:bus1kAShort-Circuit Breaking Current
n:Sb:bus1MVAShort-Circuit Breaking Power
n:idc:bus1kADecaying Component
n:Ith:bus1kAThermal equivalent Short-Circuit Current
n:R1toX1:bus1ยทR1/X1 ratio (Zk")
n:X1toR1:bus1ยทX1/R1 ratio (Zk")
n:R:bus1OhmShort-Circuit Impedance, Real Part
n:X:bus1OhmShort-Circuit Impedance, Imaginary Part
n:Z:bus1OhmShort-Circuit Impedance, Magnitude
n:phiz:bus1degShort-Circuit Impedance, Angle
n:urpref:bus1p.u.Pre-fault Voltage, Real Part
n:uipref:bus1p.u.Pre-fault Voltage, Imaginary Part
n:upref:bus1p.u.Pre-fault Voltage, Magnitude
n:uprefpc:bus1%Pre-fault Voltage, Magnitude
n:Upref:bus1kVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bus1kVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bus1degPre-fault Voltage, Angle
n:phiui:bus1degAngle between Voltage and Current
n:Ithload:bus1%Loading, Thermal equivalent Current
n:Ipload:bus1%Loading, Peak Short-Circuit Current
n:Ithrtk:bus1kARated Short-Time Current (Tk)
n:XtoR:bus1ยทX/R ratio (peak)
n:RtoX:bus1ยทR/X ratio (peak)
n:XtoR_b:bus1ยทX/R ratio (dc)
n:RtoX_b:bus1ยทR/X ratio (dc)
n:fctof_b:bus1ยทEquivalent Frequency fc/f (dc)
n:rSbase:bus1p.u.Short-Circuit Impedance, Real Part
n:xSbase:bus1p.u.Short-Circuit Impedance, Imaginary Part
n:zSbase:bus1p.u.Short-Circuit Impedance, Magnitude
n:Tn:bus1msGrid Time Constant
n:Ik:bus1kASteady-State Short-Circuit Current
n:cfac:bus1ยทVoltage Factor
n:Iasy:bus1kAAsymmetrical Breaking Current
n:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aper phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1kV3*U0
n:phiu0:bus1degZero-Sequence Voltage, Angle
n:U1:bus1kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1degPositive-Sequence Voltage, Angle
n:u2:bus1p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1degNegative-Sequence Voltage, Angle
n:U1l:bus1kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1degNeutral-Ground Voltage, Angle
n:upht:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:Ikss:bus1:Aper phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
n:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
n:Skss:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
n:Skssx3:bus1:Aper phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
n:ip:bus1:Aper phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
n:Ib:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Breaking Current
n:Sb:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAShort-Circuit Breaking Power
n:Ith:bus1:Aper phase :A, :B, :C, unbalanced onlykAThermal equivalent Short-Circuit Current
n:Ithmax:bus1kAMax. Thermal equivalent Short-Circuit Current
n:R0:bus1OhmZero-Sequence Impedance, Real Part
n:X0:bus1OhmZero-Sequence Impedance, Imaginary Part
n:Z0:bus1OhmZero-Sequence Impedance, Magnitude
n:phiz0:bus1degZero-Sequence Impedance, Angle
n:r0Sbase:bus1p.u.Zero-Sequence Impedance, Real Part
n:x0Sbase:bus1p.u.Zero-Sequence Impedance, Imaginary Part
n:z0Sbase:bus1p.u.Zero-Sequence Impedance, Magnitude
n:R1:bus1OhmPositive-Sequence Impedance, Real Part
n:X1:bus1OhmPositive-Sequence Impedance, Imaginary Part
n:Z1:bus1OhmPositive-Sequence Impedance, Magnitude
n:phiz1:bus1degPositive-Sequence Impedance, Angle
n:r1Sbase:bus1p.u.Positive-Sequence Impedance, Real Part
n:x1Sbase:bus1p.u.Positive-Sequence Impedance, Imaginary Part
n:z1Sbase:bus1p.u.Positive-Sequence Impedance, Magnitude
n:R2:bus1OhmNegative-Sequence Impedance, Real Part
n:X2:bus1OhmNegative-Sequence Impedance, Imaginary Part
n:Z2:bus1OhmNegative-Sequence Impedance, Magnitude
n:phiz2:bus1degNegative-Sequence Impedance, Angle
n:r2Sbase:bus1p.u.Negative-Sequence Impedance, Real Part
n:x2Sbase:bus1p.u.Negative-Sequence Impedance, Imaginary Part
n:z2Sbase:bus1p.u.Negative-Sequence Impedance, Magnitude
n:R0toX0:bus1ยทR0/X0 ratio (Zk")
n:X0toR0:bus1ยทX0/R0 ratio (Zk")
n:R2toX2:bus1ยทR2/X2 ratio (Zk")
n:X2toR2:bus1ยทX2/R2 ratio (Zk")
n:R:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Ground
n:X:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Ground
n:Z:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Ground
n:phiz:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Ground
n:Rl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Line
n:Xl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Line
n:Zl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Line
n:phizl:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Line
n:Rln:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Neutral
n:Xln:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Neutral
n:Zln:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Neutral
n:phizln:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Neutral
n:Rn:bus1OhmNetwork Resistance, Neutral
n:Xn:bus1OhmNetwork Reactance, Neutral
n:Zn:bus1OhmNetwork Impedance, Neutral
n:phizn:bus1degAngle of Network Impedance, Neutral
n:eff:bus1:Aper phase :A, :B, :C, unbalanced onlyยทEarth Fault Factor
n:X0toX1:bus1ยทX0/X1
n:In:bus1kANeutral Current, Magnitude
n:phiin:bus1degNeutral Current, Angle
n:I0:bus1kAZero-Sequence Current, Magnitude
n:I0x3:bus1kA3*I0
n:phii0:bus1degZero-Sequence Current, Angle
n:I1:bus1kAPositive-Sequence Current, Magnitude
n:phii1:bus1degPositive-Sequence Current, Angle
n:I2:bus1kANegative-Sequence Current, Magnitude
n:phii2:bus1degNegative-Sequence Current, Angle
n:urpref:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Real Part
n:uipref:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Imaginary Part
n:upref:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Magnitude
n:uprefpc:bus1:Aper phase :A, :B, :C, unbalanced only%Pre-fault Voltage, Magnitude
n:Upref:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bus1:Aper phase :A, :B, :C, unbalanced onlydegPre-fault Voltage, Angle
n:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
n:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
n:phiu2i2:bus1degAngle between Voltage and Current in negative sequence system
n:phiu0i0:bus1degAngle between Voltage and Current in zero-sequence system
n:Ik:bus1:Aper phase :A, :B, :C, unbalanced onlykASteady-State Short-Circuit Current
n:in:bus1p.u.Neutral Current, Magnitude
n:i0r:bus1p.u.Zero-Sequence Current, Real Part
n:i0i:bus1p.u.Zero-Sequence Current, Imaginary Part
n:i0:bus1p.u.Zero-Sequence Current, Magnitude
n:i1r:bus1p.u.Positive-Sequence Current, Real Part
n:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
n:i1:bus1p.u.Positive-Sequence Current, Magnitude
n:i2r:bus1p.u.Negative-Sequence Current, Real Part
n:i2i:bus1p.u.Negative-Sequence Current, Imaginary Part
n:i2:bus1p.u.Negative-Sequence Current, Magnitude

ElmShnt rms simulation results

Read after ComInc (RMS) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bus1p.u.Voltage, Real Part, referred to network
m:uinet:bus1p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1degPositive-Sequence-Voltage, Angle
m:irnet:bus1p.u.Current, Real Part, referred to network
m:iinet:bus1p.u.Current, Imaginary Part, referred to network
m:inet:bus1p.u.Current, Magnitude, referred to network
m:I:bus1kACurrent, Magnitude
m:phii:bus1degCurrent, Angle
m:i1r:bus1p.u.Positive-Sequence Current, Real Part
m:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:S:bus1MVAApparent Power
m:cosphi:bus1ยทPower Factor
m:tanphi:bus1ยทtan(phi)
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:Ssum:bus1MVATotal Apparent Power
m:cosphisum:bus1ยทTotal Power Factor
m:tanphisum:bus1ยทTotal tan(phi)
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:ur:bus1p.u.Voltage, Real Part
m:ui:bus1p.u.Voltage, Imaginary Part
m:u:bus1p.u.Voltage, Magnitude
m:ir:bus1p.u.Current, Real Part
m:ii:bus1p.u.Current, Imaginary Part
m:i:bus1p.u.Current, Magnitude
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1sFault Clearing Time
m:Brkload:bus1%Breaker Loading
m:Spu:bus1MVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bus1p.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bus1degZero-Sequence-Voltage, Angle
m:u2:bus1p.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bus1degNegative-Sequence-Voltage, Angle
m:irnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:iinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:inet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bus1p.u.Zero-Sequence Current, Real Part
m:i0i:bus1p.u.Zero-Sequence Current, Imaginary Part
m:i0:bus1p.u.Zero-Sequence Current, Magnitude
m:I0:bus1kAZero-Sequence Current, Magnitude
m:I0x3:bus1kA3*I0
m:phii0:bus1degZero-Sequence Current, Angle
m:i2r:bus1p.u.Negative-Sequence Current, Real Part
m:i2i:bus1p.u.Negative-Sequence Current, Imaginary Part
m:i2:bus1p.u.Negative-Sequence Current, Magnitude
m:I2:bus1kANegative-Sequence Current, Magnitude
m:phii2:bus1degNegative-Sequence Current, Angle
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bus1:Aper phase :A, :B, :C, unbalanced onlyยทPower Factor
m:tanphi:bus1:Aper phase :A, :B, :C, unbalanced onlyยทtan(phi)
m:Pln:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bus1MWPositive Sequence Active Power
m:Q1:bus1MvarPositive Sequence Reactive Power
m:P2:bus1MWNegative Sequence Active Power
m:Q2:bus1MvarNegative Sequence Reactive Power
m:P0:bus1MWZero Sequence Active Power
m:Q0:bus1MvarZero Sequence Reactive Power
m:i2P:bus1p.u.Negative-Sequence Active Current
m:i2Q:bus1p.u.Negative-Sequence Reactive Current
m:I2P:bus1kANegative-Sequence Active Current
m:I2Q:bus1kANegative-Sequence Reactive Current
m:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1degAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bus1degAngle between Voltage and Current in negative sequence system
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bus1:Aper phase :A, :B, :C, unbalanced only%Breaker Loading
c:zp.u.Shunt-Impedance
c:cnยทConnection Mode
c:frnomHzNominal Frequency
c:hpirad/sNominal Angular Frequency
c:ncapaยทNumber of Stages in Parallel
c:ncapxยทMax. No. of Steps
c:b0p.u.sigmaC
c:shtypeยทType
c:LHInductance
c:RsOhmSeries-Resistance
c:QmaxMvarMax. Rated Reactive Power
c:CFCapacitance
c:GpSParallel-Conductance
c:y0p.u.Zero Sequence Admittance
c:zep.u.Grounding Impedance
c:UstarkVStar-Point Voltage
c:i_earthยทInternal
c:z0p.u.Zero Sequence Impedance
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:ishc:bus1p.u.Short-Circuit Current, magnitude
n:Ishc:bus1kAShort-Circuit Current, magnitude
n:fe:bus1p.u.Electrical Frequency
n:dfehz:bus1HzDeviation of the El. Frequency
n:fehz:bus1HzElectrical Frequency
n:frnom:bus1HzNominal Frequency
n:ishcr:bus1p.u.Short-Circuit Current, real
n:ishci:bus1p.u.Short-Circuit Current, imag
n:dfedt:bus1p.u./sDerivative of El. Frequency
n:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aper phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1kV3*U0
n:phiu0:bus1degZero-Sequence Voltage, Angle
n:U1:bus1kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1degPositive-Sequence Voltage, Angle
n:u2:bus1p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1degNegative-Sequence Voltage, Angle
n:U1l:bus1kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1degNeutral-Ground Voltage, Angle
n:upht:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bus1p.u.Average-Voltage, Magnitude
n:Um:bus1kVAverage-Voltage, Magnitude
n:ishc:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, magnitude
n:Ishc:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, magnitude
n:inshc:bus1p.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bus1kANeutral Short-Circuit Current, magnitude
n:ishcr:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, real
n:ishci:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, imag
s:u_rp.u.Voltage, Real Part
s:u_ip.u.Voltage, Imaginary Part
s:i_rp.u.Current, Real Part
s:i_ip.u.Current, Imaginary Part
s:IRLkACurrent through Inductance
s:UCkVVoltage at Capacitance

ElmShnt emt simulation results

Read after ComInc (EMT) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:u0:bus1p.u.Zero-Sequence-Voltage
m:u1r:bus1p.u.Voltage Phasor, Real Part
m:u1i:bus1p.u.Voltage Phasor, Imaginary Part
m:u1:bus1p.u.Voltage Phasor, Magnitude
m:U1:bus1kVLine-Ground Voltage Phasor, Magnitude
m:U1l:bus1kVLine-Line Voltage Phasor, Magnitude
m:phiu1:bus1degVoltage Phasor, Angle
m:inet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, referred to network
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAPhase Current
m:i0:bus1p.u.Zero-Sequence Current
m:I0:bus1kAZero-Sequence Current
m:I0x3:bus1kA3*I0
m:i1r:bus1p.u.Current Phasor, Real Part
m:i1i:bus1p.u.Current Phasor, Imaginary Part
m:i1:bus1p.u.Current Phasor, Magnitude
m:I1:bus1kACurrent Phasor, Magnitude
m:phii1:bus1degCurrent Phasor, Angle
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Psum:bus1MWPower-Phasor, Active Power
m:Qsum:bus1MvarPower Phasor, Reactive Part
m:Ssum:bus1MVAPower Phasor, Apparent Power
m:i1P:bus1p.u.Current Phasor, Active Current
m:i1Q:bus1p.u.Current Phasor, Reactive Current
m:I1P:bus1kACurrent Phasor, Active Current
m:I1Q:bus1kACurrent Phasor, Reactive Current
m:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
m:i:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current
m:phiu1i1:bus1degAngle between Voltage and Current Phasor
m:Tfct:bus1sFault Clearing Time
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:unet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, referred to network
m:cosphi1:bus1ยทPower-Phasor, Power-Factor
c:cnยทConnection Mode
c:frnomHzNominal Frequency
c:hpirad/sNominal Angular Frequency
c:rsp.u.Series-Resistance
c:gpp.u.Parallel-Resistance
c:uc1ph:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage across C1 (Phase Value)
c:uc2ph:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage across C2 (Phase Value)
c:ucph:Aper phase :A, :B, :C, unbalanced onlyp.u.Uc1ph
c:ucphp.u.Voltage across Capacitor (Phase Value)
c:urlph:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage across Inductor (Phase Value)
c:urlphp.u.Voltage across Inductor (Phase Value)
c:urpph:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage across Rp (Phase Value)
c:ILph:Aper phase :A, :B, :C, unbalanced onlyACurrent through Inductor L (Phase Value)
c:ILphACurrent through Inductor L (Phase Value)
c:ICph:Aper phase :A, :B, :C, unbalanced onlyACurrent through Capacitor C2 (Phase Value)
c:ICphACurrent through Capacitor C (Phase Value)
c:IRpph:Aper phase :A, :B, :C, unbalanced onlyACurrent through Rp (Phase Value)
c:IRpphACurrent through Rp (Phase Value)
c:UstarkVStar-Point Voltage
c:Uc1ph:Aper phase :A, :B, :C, unbalanced onlykVVoltage across Capacitor C1(Phase Value)
c:Uc2ph:Aper phase :A, :B, :C, unbalanced onlykVVoltage across Capacitor C2(Phase Value)
c:Ucph:Aper phase :A, :B, :C, unbalanced onlykVVoltage across C1 and C2(Phase Value)
c:UcphkVVoltage across Capacitor (Phase Value)
c:Urlph:Aper phase :A, :B, :C, unbalanced onlykVVoltage across Rs-L (Phase Value)
c:UrlphkVVoltage across Inductor (Phase Value)
c:Urpph:Aper phase :A, :B, :C, unbalanced onlykVVoltage across Rp (Phase Value)
c:ncapaยทNumber of Stages in Parallel
c:ncapxยทMax. No. of Steps
c:i_earthยทInternal
c:lp.u.Inductance
c:cp.u.Capacitance
c:lep.u.Grounding Inductance
c:rep.u.Grounding Resistance
c:c0p.u.Parasitic Capacitance
c:c1p.u.Capacitance C1
c:c2p.u.Capacitance C2
c:UnomkVNominal Voltage
c:SnomMVANominal Power
c:shtypeยทType
c:iRL:Aper phase :A, :B, :C, unbalanced onlyp.u.Current through Inductance
c:iRLp.u.Current through Inductance
c:LHInductance
c:RsOhmSeries-Resistance
c:QmaxMvarMax. Rated Reactive Power
c:rs0p.u.Zero Sequence Series-Resistance
c:l0p.u.Zero Sequence Inductance
c:phystkWHysteresis losses at rated operation
c:CFCapacitance
c:GpSParallel-Conductance
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Phase Voltage
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Voltage
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage
n:u0:bus1p.u.Zero-Sequence-Voltage
n:U0:bus1kVZero-Sequence-Voltage
n:U0x3:bus1kV3*U0
n:u1:bus1p.u.Voltage Phasor, Magnitude
n:u1pc:bus1%Voltage Phasor, Magnitude
n:u1r:bus1p.u.Voltage Phasor, Real Part
n:u1i:bus1p.u.Voltage Phasor, Imaginary Part
n:U1:bus1kVVoltage Phasor, Magnitude
n:phiu1:bus1degVoltage Phasor, Angle
n:U1l:bus1kVLine-Line Voltage Phasor, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage
n:un:bus1p.u.Neutral-Ground Voltage
n:Un:bus1kVNeutral-Ground Voltage
n:ishc:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current
n:Ishc:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:inshc:bus1p.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bus1kANeutral Short-Circuit Current, magnitude
n:fe:bus1p.u.Electrical Frequency
n:dfehz:bus1HzDeviation of the El. Frequency
n:fehz:bus1HzElectrical Frequency
n:frnom:bus1HzNominal Frequency
s:psil_dp.u.Flux, alpha-component
s:psil_qp.u.Flux, beta-component
s:psil_0p.u.Flux, gamma-component
s:uC1_ap.u.Voltage C1, Phase a
s:uC1_bp.u.Voltage C1, Phase b
s:uC1_cp.u.Voltage C1, Phase c
s:uC2_ap.u.Voltage C2, Phase a
s:uC2_bp.u.Voltage C2, Phase b
s:uC2_cp.u.Voltage C2, Phase c
s:psil_ap.u.Flux, Phase a
s:psil_bp.u.Flux, Phase b
s:psil_cp.u.Flux, Phase c
s:uC_ap.u.Voltage at Capacitance, Phase a
s:uC_bp.u.Voltage at Capacitance, Phase b
s:uC_cp.u.Voltage at Capacitance, Phase c
s:IRLkACurrent through Inductance
s:UCkVVoltage at Capacitance

ElmShnt dc load flow results

Read after ComLdf (DC) with GetAttribute. m: currents, voltages and powers, n: bus result at a terminal.

AttributeUnitDescription
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:Pgen:bus1MWGeneration, Active Power
n:Pmot:bus1MWMotor Load, Active Power
n:Pload:bus1MWGeneral Load, Active Power
n:Pcomp:bus1MWCompensation (Losses)
n:Pnet:bus1MWExternal Networks, Active Power
n:Pflow:bus1MWPower Flow, Active Power

Read after ComMod with GetAttribute. c: calculation parameter, s: signal (state or model variable).

AttributeUnitDescription
c:zp.u.Shunt-Impedance
c:cnยทConnection Mode
c:frnomHzNominal Frequency
c:hpirad/sNominal Angular Frequency
c:ncapaยทNumber of Stages in Parallel
c:ncapxยทMax. No. of Steps
c:b0p.u.sigmaC
c:shtypeยทType
c:LHInductance
c:RsOhmSeries-Resistance
c:QmaxMvarMax. Rated Reactive Power
c:CFCapacitance
c:GpSParallel-Conductance
s:u_rp.u.Voltage, Real Part
s:u_ip.u.Voltage, Imaginary Part
s:i_rp.u.Current, Real Part
s:i_ip.u.Current, Imaginary Part
s:IRLkACurrent through Inductance
s:UCkVVoltage at Capacitance

ElmShnt optimal power flow results

Read after ComOpf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:bus1p.u.Voltage, Real Part, referred to network
m:uinet:bus1p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1degPositive-Sequence-Voltage, Angle
m:irnet:bus1p.u.Current, Real Part, referred to network
m:iinet:bus1p.u.Current, Imaginary Part, referred to network
m:inet:bus1p.u.Current, Magnitude, referred to network
m:I:bus1kACurrent, Magnitude
m:phii:bus1degCurrent, Angle
m:i1r:bus1p.u.Positive-Sequence Current, Real Part
m:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:S:bus1MVAApparent Power
m:cosphi:bus1ยทPower Factor
m:tanphi:bus1ยทtan(phi)
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:Ssum:bus1MVATotal Apparent Power
m:cosphisum:bus1ยทTotal Power Factor
m:tanphisum:bus1ยทTotal tan(phi)
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:ur:bus1p.u.Voltage, Real Part
m:ui:bus1p.u.Voltage, Imaginary Part
m:u:bus1p.u.Voltage, Magnitude
m:ir:bus1p.u.Current, Real Part
m:ii:bus1p.u.Current, Imaginary Part
m:i:bus1p.u.Current, Magnitude
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1sFault Clearing Time
m:Brkload:bus1%Breaker Loading
m:Spu:bus1MVA/p.u.Apparent Power per p.u. Voltage
c:zp.u.Shunt-Impedance
c:cnยทConnection Mode
c:frnomHzNominal Frequency
c:hpirad/sNominal Angular Frequency
c:rsp.u.Rs
c:gpp.u.Gp
c:xlp.u.Xl
c:bc1p.u.Bc1
c:bc2p.u.Bc2
c:uc1p.u.Voltage across C1
c:uc2p.u.Voltage across C2
c:ucp.u.Voltage across C1 and C2
c:urlp.u.Voltage across Inductor (Rs-L)
c:urpp.u.Voltage across Rp
c:ILACurrent through Inductor L
c:ICACurrent through C2
c:IRpACurrent through Rp
c:PRpkWLosses in Rp
c:PLkWLosses in Inductor (Rs)
c:Uc1kVVoltage across C1
c:Uc2kVVoltage across C2
c:UckVVoltage across C1 and C2
c:UrlkVVoltage across Inductor (Rs-L)
c:UrpkVVoltage across Rp
c:ncapaยทNumber of Stages in Parallel
c:acostยทAnnual Cost
c:ncapxยทMax. No. of Steps
c:nCtrlIterยทNo. of CTRL-iterations
c:TctrlยทController Time Constant
c:Kctrlp.u./%Controller Sensitivity dq/dv
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:b0p.u.sigmaC
c:ncapaTargetยทNumber of Stages in Parallel - target value
c:totPenaltyCostsUSDTotal penalty costs
c:totTapDeviationยทTotal tap deviation
c:bcp.u.Bc
c:gpcp.u.Gp(C)
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bus1MWGeneration, Active Power
n:Qgen:bus1MvarGeneration, Reactive Power
n:Pmot:bus1MWMotor Load, Active Power
n:Qmot:bus1MvarMotor Load, Reactive Power
n:Pload:bus1MWGeneral Load, Active Power
n:Qload:bus1MvarGeneral Load, Reactive Power
n:Pcomp:bus1MWCompensation (Losses)
n:Qcomp:bus1MvarCompensation
n:Pnet:bus1MWExternal Networks, Active Power
n:Qnet:bus1MvarExternal Networks, Reactive Power
n:Pflow:bus1MWPower Flow, Active Power
n:Qflow:bus1MvarPower Flow, Reactive Power
n:Pout:bus1MWOutgoing Flow, Active Power
n:Qout:bus1MvarOutgoing Power, Reactive Power
n:Sout:bus1MVAOutgoing Power, Apparent Power
n:cosphiout:bus1ยทOutgoing Power, Power Factor
n:Pbalance:bus1MWActive Power Balance (=0)
n:Qbalance:bus1MvarReactive Power Balance (=0)
n:LossPdown:bus1MWLosses, downstream
n:LossQdown:bus1MvarLosses, downstream (Reactive Power)
n:LossPdownload:bus1MWLoad losses, downstream
n:LossQdownload:bus1MvarLoad losses, downstream
n:LossPdownnoload:bus1MWNo load losses, downstream
n:LossQdownnoload:bus1MvarNo load losses, downstream
n:du_feed:bus1%Difference from voltage at start of feeder

ElmShnt basic data

b: values are worked out from the input data. Read them; they are not set.

AttributeUnitDescription
b:loc_nameยทName

Related

โ† ElmLodmv MV Load ยท ElmSvs Static Var System โ†’