ElmTr3 attributesPowerFactory 3-Winding Transformer
Every attribute of the PowerFactory 3-Winding Transformer (ElmTr3): 308 input parameters and 1166 result variables, with units and meaning. Copy a name into GetAttribute or SetAttribute.
What ElmTr3 is
A three-winding transformer with HV, MV and LV terminals; ratings and impedances sit in its type (TypTr3).
- Class
ElmTr3, element class- PowerFactory name
- 3-Winding Transformer
- Type
TypTr3, throughtyp_id- Terminal suffix
:bushvhv-side,:busmvmv-side,:buslvlv-side- Attributes
- 308 input parameters and 1166 result variables, in 7 calculations
Most used ElmTr3 attributes
| Attribute | Unit | Description | Where |
|---|---|---|---|
c:loading | % | Maximum Loadinghighest loading of the three windings | Load flow |
m:P:bushv | MW | Active Power | Load flow |
m:P:busmv | MW | Active Power | Load flow |
m:P:buslv | MW | Active Power | Load flow |
n3tap_h | ยท | Act. PositionHV tap position | input data |
outserv | ยท | Out of Service | input data |
typ_id | ยท | Type | input data |
Read and write ElmTr3 in Python
import powerfactory
app = powerfactory.GetApplication() # GetApplicationExt() from outside PowerFactory
app.GetFromStudyCase("ComLdf").Execute() # results exist after a calculation
for trafo in app.GetCalcRelevantObjects("*.ElmTr3"):
loading = trafo.GetAttribute("c:loading") # Maximum Loading, %
p_bushv = trafo.GetAttribute("m:P:bushv") # Active Power, MW
print(trafo.loc_name, loading, p_bushv)
trafo = app.GetCalcRelevantObjects("*.ElmTr3")[0]
trafo.SetAttribute("outserv", 1) # take the transformer out of service
- A result at a terminal of the 3-winding transformer needs the terminal in its name:
m:P:bushv, notm:P, which raisesAttributeError. - An input parameter is read and written with or without its
e:prefix:GetAttribute("outserv")andGetAttribute("e:outserv")give the same value. - RMS and EMT variables change over time: record them in a results object (
ElmRes) to read the whole curve.GetAttributeafter a run gives the value at the last time step.
- Input parameters308
- Load flow results272
- Short-circuit results295
- RMS simulation results219
- EMT simulation results153
- DC load flow results47
- Modal analysis results33
- Optimal power flow results147
- Basic data12
ElmTr3 input parameters
The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.
| Attribute | Unit | Description |
|---|---|---|
loc_name | ยท | Name |
chr_name | ยท | Characteristic Name |
for_name | ยท | Foreign Key |
dat_src | ยท | Data source |
imldc | ยท | Control Mode |
imldc2 | ยท | Control Mode |
sernum | ยท | Serial Number |
commissionDate | ยท | Commissioning Date |
appr_modby | ยท | Modified by |
outserv | ยท | Out of Service |
iZoneBus | ยท | Zone |
iAreaBus | ยท | Area |
lossAssign | ยท | Loss assignment |
nt3nm | ยท | parallel Transformers |
ntrcn | ยท | Automatic Tap Changing |
ictrlside | ยท | Controller for tap at |
ilcph | ยท | Phase |
t3ldc | ยท | Controlled Node is at |
n3tap_h | ยท | Act. Position |
n3tap_m | ยท | Act. Position |
n3tap_l | ยท | Act. Position |
optaplimit | ยท | Operational limits for tap changer |
optapmin_h | ยท | Minimum Position |
optapmax_h | ยท | Maximum Position |
optapmin_m | ยท | Minimum Position |
optapmax_m | ยท | Maximum Position |
optapmin_l | ยท | Minimum Position |
optapmax_l | ยท | Maximum Position |
ntrcn2 | ยท | Automatic Tap Changing |
ictrlside2 | ยท | Controller for tap at |
ilcph2 | ยท | Phase |
t3ldc2 | ยท | Controlled Node is at |
i_rem | ยท | Remote Control |
i_rem2 | ยท | Remote Control |
i_cont | ยท | Tap Changer |
i_cont2 | ยท | Tap Changer |
uset_mode | ยท | Setpoint |
iPpart | ยท | Active power participation |
uset_mode2 | ยท | Setpoint |
iPpart2 | ยท | Active power participation |
i_auto_hl | ยท | Auto Transformer |
i_neuthv | ยท | Neutral Connection |
i_neutmv | ยท | Neutral Connection |
i_neutlv | ยท | Neutral Connection |
i_eahv | ยท | Phase 2 internally grounded |
i_eamv | ยท | Phase 2 internally grounded |
i_ealv | ยท | Phase 2 internally grounded |
i_hvcon | ยท | Phase 2 connected |
i_mvcon | ยท | Phase 2 connected |
i_lvcon | ยท | Phase 2 connected |
iblock | ยท | Unit Transformer |
ifc | ยท | Forced Cooling Enabled |
constr | ยท | Year of Construction |
appr_status | ยท | Status |
iperfect | ยท | Ideal component |
i_tapopt_l | ยท | Tap Position LV-Side |
i_tapopt_h | ยท | Tap Position HV-Side |
i_tapopt_m | ยท | Tap Position MV-Side |
i_tapoptCont_l | ยท | Control Mode |
i_tapoptCont_h | ยท | Control Mode |
i_tapoptCont_m | ยท | Control Mode |
ionlyPre | ยท | Optimise in DC OPF |
iOPFCload | ยท | Max. loading constraint |
isCtrlTapLV | ยท | Tap Position LV-Side |
isCtrlTapMV | ยท | Tap Position MV-Side |
isCtrlTapHV | ยท | Tap Position HV-Side |
isCtrlTapHVCont | ยท | Control Mode |
isCtrlTapMVCont | ยท | Control Mode |
isCtrlTapLVCont | ยท | Control Mode |
ctrlUsageHV | ยท | Tap Position HV-Side |
curativeLimHV | ยท | Max. curative tap deviation (HV) |
ctrlUsageMV | ยท | Tap Position MV-Side |
curativeLimMV | ยท | Max. curative tap deviation (MV) |
ctrlUsageLV | ยท | Tap Position LV-Side |
curativeLimLV | ยท | Max. curative tap deviation (LV) |
isConstrLoading | ยท | Max. loading constraint for Unit Commitment |
isMaxLoadSoftNlin | ยท | Penalty costs for soft constraints |
allowOutDistFacFilt | ยท | Allow filtering by outage distribution factor |
allowMarginFilt | ยท | Allow filtering by constraint margin |
allowCntConstrFilt | ยท | Allow contingency filtering by number of critical constraints |
isSepCntConstrType | ยท | Separate constraint type |
cntConstrType | ยท | Contingency-constraint type |
isSepCntMaxAllowedLoading | ยท | Separate max. allowed loading |
isConstrLoadingPlacement | ยท | Max. loading constraint for Optimal Equipment Placement |
isCtrlTapLVPlacement | ยท | Tap Position LV-Side |
isCtrlTapMVPlacement | ยท | Tap Position MV-Side |
isCtrlTapHVPlacement | ยท | Tap Position HV-Side |
ildc | ยท | Compensation |
ildc2 | ยท | Compensation |
i_tapini_h | ยท | Estimate Tap Position HV-Side |
i_tapini_m | ยท | Estimate Tap Position MV-Side |
i_tapini_l | ยท | Estimate Tap Position LV-Side |
iIntTapCtrl | ยท | Use Integrated Tap Controller |
icomp | ยท | Compounding |
icomp2 | ยท | Compounding |
iTaps | ยท | According to Measurement Report |
iMeasTap | ยท | for Tap at |
iMeasLoc | ยท | Measured at |
iwinding | ยท | Create Curve for |
ifrqft | ยท | Frequent Fault ( >10(5)/lifetime, Category II(III) ) |
iansish | ยท | ANSI Curve Shift |
drawInr | ยท | Draw Inrush Current |
fr_coldload | ยท | Cold Load Curve |
iopt_hf | ยท | Consider Capacitances |
iAstabint | ยท | A-stable integration algorithm |
iResFlux | ยท | Residual flux |
usetp | p.u. | Voltage Setpoint |
psetp | MW | Active Power Setpoint |
qsetp | Mvar | Reactive Power Setpoint |
usetp2 | p.u. | Voltage Setpoint |
psetp2 | MW | Active Power Setpoint |
qsetp2 | Mvar | Reactive Power Setpoint |
ratfac_h | ยท | HV-Side |
ratfac_m | ยท | MV-Side |
ratfac_l | ยท | LV-Side |
Tctrl | s | Controller Time Constant |
Kqctrl | tap/Mvar | Controller Sensitivity dtap/dQ |
Kpctrl | tap/MW | Controller Sensitivity dtap/dP |
Tctrl2 | s | Controller Time Constant |
Kqctrl2 | tap/Mvar | Controller Sensitivity dtap/dQ |
Kpctrl2 | tap/MW | Controller Sensitivity dtap/dP |
usp_up | p.u. | Upper Voltage Bound |
usp_low | p.u. | Lower Voltage Bound |
psp_up | MW | Upper Active Power Bound |
psp_low | MW | Lower Active Power Bound |
qsp_up | Mvar | Upper Reactive Power Bound |
Ptolerance | MW | Tolerance (+/-) |
qsp_low | Mvar | Lower Reactive Power Bound |
Kpart | ยท | Participation factor |
usp_up2 | p.u. | Upper Voltage Bound |
usp_low2 | p.u. | Lower Voltage Bound |
psp_up2 | MW | Upper Active Power Bound |
psp_low2 | MW | Lower Active Power Bound |
qsp_up2 | Mvar | Upper Reactive Power Bound |
Ptolerance2 | MW | Tolerance (+/-) |
qsp_low2 | Mvar | Lower Reactive Power Bound |
Kpart2 | ยท | Participation factor |
re0h | Ohm | Resistance, Re |
re0m | Ohm | Resistance, Re |
re0l | Ohm | Resistance, Re |
xe0h | Ohm | Reactance, Xe |
xe0m | Ohm | Reactance, Xe |
xe0l | Ohm | Reactance, Xe |
maxload | % | Max. loading |
Vtolerance | % | Tolerance (+/-) |
Vtolerance2 | % | Tolerance (+/-) |
Cg_h | uF | HV-Ground |
Cg_m | uF | MV-Ground |
Cg_l | uF | LV-Ground |
Cc1_lh | uF | LV-HV |
Cc0_lh | uF | LV-HV |
Cc1_hm | uF | HV-MV |
Cc0_hm | uF | HV-MV |
Cc1_ml | uF | MV-LV |
Cc0_ml | uF | MV-LV |
PsiresA | p.u. | Phase A |
PsiresB | p.u. | Phase B |
PsiresC | p.u. | Phase C |
GPSlat | deg | Latitude / Northing |
GPSlon | deg | Longitude / Easting |
scalingFacSoftConstrOpf | ยท | Weighting factor for soft constraint penalty |
curativeCosts | USD | Costs per curative tap deviation |
scalingFacSoftConstrCost | ยท | Cost scaling factor |
cntMaxAllowedLoading | % | Max. allowed loading in Contingencies |
penaltyCosts | USD | Penalty costs per tap deviation |
dpl1 | ยท | dpl1 |
dpl2 | ยท | dpl2 |
dpl3 | ยท | dpl3 |
dpl4 | ยท | dpl4 |
dpl5 | ยท | dpl5 |
appr_modif | ยท | Modified |
mTaps | ยท | Measurement Report |
input_cl | ยท | Values |
cimRdfId | ยท | RDF ID |
desc | ยท | Description |
sOpComment | ยท | Operator Comment |
fold_id | ยท | In Folder |
typ_id | ยท | TypeObject: TypTr3 |
bushv | ยท | HV-SideObject: StaCubic |
busmv | ยท | MV-SideObject: StaCubic |
buslv | ยท | LV-SideObject: StaCubic |
bushvn | ยท | HV-NeutralObject: StaCubic |
busmvn | ยท | MV-NeutralObject: StaCubic |
buslvn | ยท | LV-NeutralObject: StaCubic |
p_rem | ยท | Controlled NodeObject: StaBar,ElmTerm |
p_cub | ยท | Controlled Branch (Cubicle)Object: StaCubic,ElmBoundary |
tapctrl | ยท | Tap ControllerObject: ElmTr3,ElmTr2 |
p_rem2 | ยท | Controlled NodeObject: StaBar,ElmTerm |
p_cub2 | ยท | Controlled Branch (Cubicle)Object: StaCubic,ElmBoundary |
p_pmeas | ยท | P measured atObject: StaCubic,ElmBoundary |
p_pmeas2 | ยท | P measured atObject: StaCubic,ElmBoundary |
doc_id | ยท | Additional Data |
pOwner | ยท | OwnerObject: ElmOwner |
pOperator | ยท | OperatorObject: ElmOperator |
pStoch | StoTyptrf | Element model |
pldc | ยท | External LDCObject: StaLdc |
pldc2 | ยท | External LDCObject: StaLdc |
pVccurve | ยท | V-Control-CurveObject: IntVctrlcurve |
pVccurve2 | ยท | V-Control-CurveObject: IntVctrlcurve |
pRating_h | ยท | HV-SideObject: IntThrating |
pRating_m | ยท | MV-SideObject: IntThrating |
pRating_l | ยท | LV-SideObject: IntThrating |
cpHeadFold | ยท | Head Folder |
bushv_bar | ยท | HV-Side |
busmv_bar | ยท | MV-Side |
buslv_bar | ยท | LV-Side |
bushvn_bar | ยท | HV-Neutral |
busmvn_bar | ยท | MV-Neutral |
buslvn_bar | ยท | LV-Neutral |
cpGrid | ยท | GridObject: ElmNet |
cpZone | ยท | ZoneObject: ElmZone |
cpArea | ยท | AreaObject: ElmArea |
cpFeed | ยท | FeederObject: ElmFeeder |
ciDist | ยท | Distance from infeed in number of buses |
ciLater | ยท | Lateral Index |
ciDistRoot | ยท | Distance from first infeed in number of buses |
ciDistAll | ยท | Distance from infeed in number of buses including switches |
ciDistAllRoot | ยท | Distance from first infeed in number of buses including switches |
cpOwner | ยท | OwnerObject: ElmOwner |
cpOperator | ยท | OperatorObject: ElmOperator |
cpBranch | ยท | BranchObject: ElmBranch |
cpSite | ยท | SiteObject: ElmSite |
cpSubstat | ยท | SubstationObject: ElmSubstat,ElmTrfstat |
cpMeteostat | ยท | Meteo StationObject: ElmMeteostat |
ciOutaged | ยท | Planned Outage |
ciEnergized | ยท | Energized |
ciEarthed | ยท | Earthed |
cDisplayName | ยท | Display Name |
cpSupplyTransformer | ยท | Supplying TransformerObject: ElmTr?,ElmTrmult |
cpSupplyTrfStation | ยท | Supplying Secondary SubstationObject: ElmTrfstat |
cpSupplySubstation | ยท | Supplying SubstationObject: ElmSubstat |
Snom_h | MVA | HV-Side, Nominal Power |
Snom_m | MVA | MV-Side, Nominal Power |
Snom_l | MVA | LV-Side, Nominal Power |
Snom_h_a | MVA | HV-Side, Nom.Power (act.) |
Snom_m_a | MVA | MV-Side, Nom.Power (act.) |
Snom_l_a | MVA | LV-Side, Nom.Power (act.) |
cpCtrlNode | ยท | Target NodeObject: ElmTerm |
cpCtrlNode2 | ยท | Target NodeObject: ElmTerm |
cgnd_h | ยท | Star Point |
cgnd_m | ยท | Star Point |
cgnd_l | ยท | Star Point |
cpeter_h | ยท | Petersen Coil |
cpeter_m | ยท | Petersen Coil |
cpeter_l | ยท | Petersen Coil |
neutConfig | ยท | N-Connection |
neutSeparate | ยท | Separate N-connection |
pT_h | ยท | Voltage Range |
pT_m | ยท | Voltage Range |
pT_l | ยท | Voltage Range |
FOR1 | 1/a | Forced Outage Rate |
FOE | h/a | Forced Outage Expectancy |
FOD | h | Forced Outage Duration |
pTypStoch | StoTyptrf | Type model |
CCEarFr | 1/a | Frequency of single earth faults |
CCEarRepMu | h | Repair duration |
CCEarProb | % | Conditional probability of a second earth fault |
cCtrlTapHVContOpf | ยท | Control Mode |
cCtrlTapMVContOpf | ยท | Control Mode |
cCtrlTapLVContOpf | ยท | Control Mode |
cOptOnlyPre | ยท | Optimise in DC OPF |
cCtrlTapHVCont | ยท | Control Mode |
cCtrlTapMVCont | ยท | Control Mode |
cCtrlTapLVCont | ยท | Control Mode |
cCtrlUsageHV | ยท | Tap Position HV-Side |
cCtrlUsageMV | ยท | Tap Position MV-Side |
cCtrlUsageLV | ยท | Tap Position LV-Side |
cAllowOutDistFacFilt | ยท | Allow filtering by outage distribution factor |
cAllowMarginFilt | ยท | Allow filtering by constraint margin |
cAllowCntConstrFilt | ยท | Allow contingency filtering by number of critical constraints |
cIsSepCntConstrType | ยท | Separate constraint type |
cIsSepCntMaxAllowedLoading | ยท | Separate max. allowed loading |
rSbasepu_hm | p.u. | r(HV-MV) (Sbase) |
rSbasepu_ml | p.u. | r(MV-LV) (Sbase) |
rSbasepu_lh | p.u. | r(LV-HV) (Sbase) |
xSbasepu_hm | p.u. | x(HV-MV) (Sbase) |
xSbasepu_ml | p.u. | x(MV-LV) (Sbase) |
xSbasepu_lh | p.u. | x(LV-HV) (Sbase) |
rSbasepu_h | p.u. | r(HV) (Sbase) |
rSbasepu_m | p.u. | r(MV) (Sbase) |
rSbasepu_l | p.u. | r(LV) (Sbase) |
xSbasepu_h | p.u. | x(HV) (Sbase) |
xSbasepu_m | p.u. | x(MV) (Sbase) |
xSbasepu_l | p.u. | x(LV) (Sbase) |
bSbasepu | p.u. | b (Sbase) |
r0Sbasepu_hm | p.u. | r0(HV-MV) (Sbase) |
r0Sbasepu_ml | p.u. | r0(MV-LV) (Sbase) |
r0Sbasepu_lh | p.u. | r0(LV-HV) (Sbase) |
x0Sbasepu_hm | p.u. | x0(HV-MV) (Sbase) |
x0Sbasepu_ml | p.u. | x0(MV-LV) (Sbase) |
x0Sbasepu_lh | p.u. | x0(LV-HV) (Sbase) |
r0Sbasepu_h | p.u. | r0(HV) (Sbase) |
r0Sbasepu_m | p.u. | r0(MV) (Sbase) |
r0Sbasepu_l | p.u. | r0(LV) (Sbase) |
x0Sbasepu_h | p.u. | x0(HV) (Sbase) |
x0Sbasepu_m | p.u. | x0(MV) (Sbase) |
x0Sbasepu_l | p.u. | x0(LV) (Sbase) |
Inom_h | kA | HV-Side, Nominal Current |
Inom_m | kA | MV-Side, Nominal Current |
Inom_l | kA | LV-Side, Nominal Current |
Inom_h_a | kA | HV-Side, Nominal Current (act.) |
Inom_m_a | kA | MV-Side, Nominal Current (act.) |
Inom_l_a | kA | LV-Side, Nominal Current (act.) |
c_pstac | ยท | External Station ControllerObject: ElmStactrl |
c_ptapc | ยท | External Tap ControllerObject: ElmTapctrl |
c_plcc | ยท | External LCC ControllerObject: StaLdc |
qdslCtrl | ยท | Quasi-Dynamic ModelObject: ElmQdsl |
cPsiresC | p.u. | Phase C |
ElmTr3 load flow results
Read after ComLdf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).
| Attribute | Unit | Description |
|---|---|---|
m:urnet:bushvor :busmv, :buslv | p.u. | Voltage, Real Part, referred to network |
m:uinet:bushvor :busmv, :buslv | p.u. | Voltage, Imaginary Part, referred to network |
m:u1r:bushvor :busmv, :buslv | p.u. | Positive-Sequence-Voltage, Real Part |
m:u1i:bushvor :busmv, :buslv | p.u. | Positive-Sequence-Voltage, Imaginary Part |
m:u1:bushvor :busmv, :buslv | p.u. | Positive-Sequence-Voltage, Magnitude |
m:U1:bushvor :busmv, :buslv | kV | Line-Ground Positive-Sequence-Voltage, Magnitude |
m:U1l:bushvor :busmv, :buslv | kV | Line-Line Positive-Sequence-Voltage, Magnitude |
m:phiu1:bushvor :busmv, :buslv | deg | Positive-Sequence-Voltage, Angle |
m:irnet:bushvor :busmv, :buslv | p.u. | Current, Real Part, referred to network |
m:iinet:bushvor :busmv, :buslv | p.u. | Current, Imaginary Part, referred to network |
m:inet:bushvor :busmv, :buslv | p.u. | Current, Magnitude, referred to network |
m:I:bushvor :busmv, :buslv | kA | Current, Magnitude |
m:phii:bushvor :busmv, :buslv | deg | Current, Angle |
m:i1r:bushvor :busmv, :buslv | p.u. | Positive-Sequence Current, Real Part |
m:i1i:bushvor :busmv, :buslv | p.u. | Positive-Sequence Current, Imaginary Part |
m:i1:bushvor :busmv, :buslv | p.u. | Positive-Sequence Current, Magnitude |
m:I1:bushvor :busmv, :buslv | kA | Positive-Sequence Current, Magnitude |
m:phii1:bushvor :busmv, :buslv | deg | Positive-Sequence Current, Angle |
m:P:bushvor :busmv, :buslv | MW | Active Power |
m:Q:bushvor :busmv, :buslv | Mvar | Reactive Power |
m:S:bushvor :busmv, :buslv | MVA | Apparent Power |
m:cosphi:bushvor :busmv, :buslv | ยท | Power Factor |
m:tanphi:bushvor :busmv, :buslv | ยท | tan(phi) |
m:Psum:bushvor :busmv, :buslv | MW | Total Active Power |
m:Qsum:bushvor :busmv, :buslv | Mvar | Total Reactive Power |
m:Ssum:bushvor :busmv, :buslv | MVA | Total Apparent Power |
m:cosphisum:bushvor :busmv, :buslv | ยท | Total Power Factor |
m:tanphisum:bushvor :busmv, :buslv | ยท | Total tan(phi) |
m:i1P:bushvor :busmv, :buslv | p.u. | Positive-Sequence Active Current |
m:i1Q:bushvor :busmv, :buslv | p.u. | Positive-Sequence Reactive Current |
m:I1P:bushvor :busmv, :buslv | kA | Positive-Sequence Active Current |
m:I1Q:bushvor :busmv, :buslv | kA | Positive-Sequence Reactive Current |
m:ur:bushvor :busmv, :buslv | p.u. | Voltage, Real Part |
m:ui:bushvor :busmv, :buslv | p.u. | Voltage, Imaginary Part |
m:u:bushvor :busmv, :buslv | p.u. | Voltage, Magnitude |
m:ir:bushvor :busmv, :buslv | p.u. | Current, Real Part |
m:ii:bushvor :busmv, :buslv | p.u. | Current, Imaginary Part |
m:i:bushvor :busmv, :buslv | p.u. | Current, Magnitude |
m:phiui:bushvor :busmv, :buslv | deg | Angle between Voltage and Current |
m:phiu1i1:bushvor :busmv, :buslv | deg | Angle between Voltage and Current in positive sequence system |
m:Tfct:bushvor :busmv, :buslv | s | Fault Clearing Time |
m:Brkload:bushvor :busmv, :buslv | % | Breaker Loading |
m:Spu:bushvor :busmv, :buslv | MVA/p.u. | Apparent Power per p.u. Voltage |
m:urnet:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Real Part, referred to network |
m:uinet:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Imaginary Part, referred to network |
m:u0:bushvor :busmv, :buslv | p.u. | Zero-Sequence-Voltage, Magnitude |
m:phiu0:bushvor :busmv, :buslv | deg | Zero-Sequence-Voltage, Angle |
m:u2:bushvor :busmv, :buslv | p.u. | Negative-Sequence-Voltage, Magnitude |
m:phiu2:bushvor :busmv, :buslv | deg | Negative-Sequence-Voltage, Angle |
m:irnet:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Real Part, referred to network |
m:iinet:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Imaginary Part, referred to network |
m:inet:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Magnitude, referred to network |
m:I:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kA | Phase Current, Magnitude |
m:phii:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Phase Current, Angle |
m:i0r:bushvor :busmv, :buslv | p.u. | Zero-Sequence Current, Real Part |
m:i0i:bushvor :busmv, :buslv | p.u. | Zero-Sequence Current, Imaginary Part |
m:i0:bushvor :busmv, :buslv | p.u. | Zero-Sequence Current, Magnitude |
m:I0:bushvor :busmv, :buslv | kA | Zero-Sequence Current, Magnitude |
m:I0x3:bushvor :busmv, :buslv | kA | 3*I0 |
m:phii0:bushvor :busmv, :buslv | deg | Zero-Sequence Current, Angle |
m:i2r:bushvor :busmv, :buslv | p.u. | Negative-Sequence Current, Real Part |
m:i2i:bushvor :busmv, :buslv | p.u. | Negative-Sequence Current, Imaginary Part |
m:i2:bushvor :busmv, :buslv | p.u. | Negative-Sequence Current, Magnitude |
m:I2:bushvor :busmv, :buslv | kA | Negative-Sequence Current, Magnitude |
m:phii2:bushvor :busmv, :buslv | deg | Negative-Sequence Current, Angle |
m:ubfacI:bushvor :busmv, :buslv | % | Current Unbalance Factor |
m:ubfacS:bushvor :busmv, :buslv | % | Power Unbalance Factor |
m:P:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | MW | Active Power |
m:Q:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | Mvar | Reactive Power |
m:S:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | MVA | Apparent Power |
m:cosphi:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | ยท | Power Factor |
m:tanphi:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | ยท | tan(phi) |
m:Pln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | MW | Active Power (Line-Neutral) |
m:Qln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | Mvar | Reactive Power (Line-Neutral) |
m:P1:bushvor :busmv, :buslv | MW | Positive Sequence Active Power |
m:Q1:bushvor :busmv, :buslv | Mvar | Positive Sequence Reactive Power |
m:P2:bushvor :busmv, :buslv | MW | Negative Sequence Active Power |
m:Q2:bushvor :busmv, :buslv | Mvar | Negative Sequence Reactive Power |
m:P0:bushvor :busmv, :buslv | MW | Zero Sequence Active Power |
m:Q0:bushvor :busmv, :buslv | Mvar | Zero Sequence Reactive Power |
m:i2P:bushvor :busmv, :buslv | p.u. | Negative-Sequence Active Current |
m:i2Q:bushvor :busmv, :buslv | p.u. | Negative-Sequence Reactive Current |
m:I2P:bushvor :busmv, :buslv | kA | Negative-Sequence Active Current |
m:I2Q:bushvor :busmv, :buslv | kA | Negative-Sequence Reactive Current |
m:ur:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Real Part |
m:ui:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Imaginary Part |
m:u:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Magnitude |
m:ir:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Real Part |
m:ii:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Imaginary Part |
m:i:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Magnitude |
m:phiui:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Angle between Voltage and Current |
m:phiu0i0:bushvor :busmv, :buslv | deg | Angle between Voltage and Current in zero-sequence system |
m:phiu2i2:bushvor :busmv, :buslv | deg | Angle between Voltage and Current in negative sequence system |
m:TfctPh:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | s | Fault Clearing Time |
m:BrkloadPh:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | % | Breaker Loading |
c:loading_h | % | Loading (HV) |
c:loading_m | % | Loading (MV) |
c:loading_l | % | Loading (LV) |
c:loading | % | Maximum Loading |
c:maxload | % | Max. Loading |
c:n3tap_h | ยท | Current Tap Position (HV) |
c:n3tap_m | ยท | Current Tap Position (MV) |
c:n3tap_l | ยท | Current Tap Position (LV) |
c:nntap_int_h | ยท | Tap (HV), relative Position |
c:nntap_int_m | ยท | Tap (MV), relative Position |
c:nntap_int_l | ยท | Tap (LV), relative Position |
c:ym | p.u. | Magnetising Admittance |
c:t_h | ยท | Complex Winding Ratio (HV/S) |
c:t_m | ยท | Complex Winding Ratio (MV/S) |
c:t_l | ยท | Complex Winding Ratio (LV/S) |
c:i_uplim | ยท | Tap at Maximum |
c:i_lowlim | ยท | Tap at Minimum |
c:nCtrlIter | ยท | No. of CTRL-iterations |
c:itrcn | ยท | Flag f. auto. Tap |
c:i3loc | ยท | Position of Magn.ind. |
c:um_1 | ยท | Magnetising Flux |
c:w_0 | ยท | Nominal winding ratio |
c:Gmload | kW | Iron Losses |
c:Xmload | kvar | Magnetising Losses |
c:Ploss | MW | Losses (total) |
c:Qloss | Mvar | Reactive-Losses (total) |
c:Plossld | MW | Losses (load) |
c:Qlossld | Mvar | Reactive-Losses (load) |
c:Plossnld | MW | Losses (no load) |
c:Qlossnld | Mvar | Reactive-Losses (no load) |
c:Pmeas | MW | Measured active power, Controller 1 |
c:i_fixedtap | ยท | Flag |
c:isat | ยท | Saturated Model |
c:Inom_HV | kA | Nominal Current (HV-Side) |
c:Inom_MV | kA | Nominal Current (MV-Side) |
c:Inom_LV | kA | Nominal Current (LV-Side) |
c:zs_h | p.u. | Short Circuit Impedance (HV) |
c:zs_m | p.u. | Short Circuit Impedance (MV) |
c:zs_l | p.u. | Short Circuit Impedance (LV) |
c:Pmeas2 | MW | Measured active power, Controller 2 |
c:ctrl_set | ยท | cc0_ml |
c:ctrl_set2 | ยท | cc0_ml |
c:maxloadpu | p.u. | Max. Loading |
c:u_h | ยท | Internal |
c:u_m | ยท | Internal |
c:u_l | ยท | Internal |
c:dphiu_hm | deg | Voltage Drop Angle (HV-MV) |
c:dphiu_hl | deg | Voltage Drop Angle (HV-LV) |
c:dphiu_ml | deg | Voltage Drop Angle (MV-LV) |
c:yg_hv | p.u. | Parasitic Admittance (HV-Side) |
c:yg_mv | p.u. | Parasitic Admittance (MV-Side) |
c:yg_lv | p.u. | Parasitic Admittance (LV-Side) |
c:yc1_lh | p.u. | LV-HV Coupling-Admittance (normalised on HV-Side) |
c:yc1_hm | p.u. | HV-MV Coupling-Admittance (normalised on HV-Side) |
c:yc1_ml | p.u. | MV-LV Coupling-Admittance (normalised on HV-Side) |
c:loading_st | % | Short Term Loading |
c:dphiu_hm1 | deg | Positive Sequence Voltage Drop Angle (HV-MV) |
c:dphiu_hl1 | deg | Positive Sequence Voltage Drop Angle (HV-LV) |
c:dphiu_ml1 | deg | Positive Sequence Voltage Drop Angle (MV-LV) |
c:i30lc | ยท | Position of 0-Sequ. Magn.ind. |
c:zs0_h | p.u. | 0-Sequ. Short-Circuit Imp (HV) |
c:zs0_m | p.u. | 0-Sequ. Short-Circuit Imp (MV) |
c:zs0_l | p.u. | 0-Sequ. Short-Circuit Imp (LV) |
c:ze0_h | p.u. | Earth Impedance (HV) |
c:ze0_m | p.u. | Earth Impedance (MV) |
c:ze0_l | p.u. | Earth Impedance (LV) |
c:i_star_h | ยท | Flag |
c:i_star_m | ยท | Flag |
c:i_star_l | ยท | Flag |
c:i_earth_h | ยท | Flag |
c:i_earth_m | ยท | Flag |
c:i_earth_l | ยท | Flag |
c:ym0 | p.u. | 0-Sequ. Magn. Admitt. |
c:i_stshort | ยท | Flag |
c:Ustar_h | kV | Star-Point Voltage (HV) |
c:Ustar_m | kV | Star-Point Voltage (MV) |
c:Ustar_l | kV | Star-Point Voltage (LV) |
c:Istar_h | kA | Star-Point Current (HV) |
c:Istar_m | kA | Star-Point Current (MV) |
c:Istar_l | kA | Star-Point Current (LV) |
c:um_2 | p.u. | Magnetising Flux (Imaginary Part) |
c:um_0 | p.u. | Magnetising Flux (0-Sequence) |
c:u1_h | ยท | Internal |
c:u1_m | ยท | Internal |
c:u1_l | ยท | Internal |
c:u2_h | ยท | Internal |
c:u2_m | ยท | Internal |
c:u2_l | ยท | Internal |
c:I0Delta_h | kA | Circulating current in Delta-Winding, Magnitude |
c:I0Delta_m | kA | Circulating current in Delta-Winding, Magnitude |
c:I0Delta_l | kA | Circulating current in Delta-Winding, Magnitude |
c:yc0_lh | p.u. | LV-HV Coupling-Admittance (0-Sys., normalised on HV-Side) |
c:yc0_hm | p.u. | HV-MV Coupling-Admittance (0-Sys., normalised on HV-Side) |
c:yc0_ml | p.u. | MV-LV Coupling-Admittance (0-Sys., normalised on HV-Side) |
n:ur:bushvor :busmv, :buslv | p.u. | Voltage, Real Part |
n:ui:bushvor :busmv, :buslv | p.u. | Voltage, Imaginary Part |
n:u:bushvor :busmv, :buslv | p.u. | Voltage, Magnitude |
n:upc:bushvor :busmv, :buslv | % | Voltage, Magnitude |
n:du:bushvor :busmv, :buslv | % | Voltage Deviation |
n:U:bushvor :busmv, :buslv | kV | Line-Ground Voltage, Magnitude |
n:phiu:bushvor :busmv, :buslv | deg | Voltage, Angle |
n:phiurel:bushvor :busmv, :buslv | deg | Voltage, Relative Angle |
n:Ul:bushvor :busmv, :buslv | kV | Line-Line Voltage, Magnitude |
n:u1:bushvor :busmv, :buslv | p.u. | Voltage, Magnitude |
n:u1pc:bushvor :busmv, :buslv | % | Voltage, Magnitude |
n:u1r:bushvor :busmv, :buslv | p.u. | Positive-Sequence Voltage, Real Part |
n:u1i:bushvor :busmv, :buslv | p.u. | Positive-Sequence Voltage, Imaginary Part |
n:Pgen:bushvor :busmv, :buslv | MW | Generation, Active Power |
n:Qgen:bushvor :busmv, :buslv | Mvar | Generation, Reactive Power |
n:Pmot:bushvor :busmv, :buslv | MW | Motor Load, Active Power |
n:Qmot:bushvor :busmv, :buslv | Mvar | Motor Load, Reactive Power |
n:Pload:bushvor :busmv, :buslv | MW | General Load, Active Power |
n:Qload:bushvor :busmv, :buslv | Mvar | General Load, Reactive Power |
n:Pcomp:bushvor :busmv, :buslv | MW | Compensation (Losses) |
n:Qcomp:bushvor :busmv, :buslv | Mvar | Compensation |
n:Pnet:bushvor :busmv, :buslv | MW | External Networks, Active Power |
n:Qnet:bushvor :busmv, :buslv | Mvar | External Networks, Reactive Power |
n:Pflow:bushvor :busmv, :buslv | MW | Power Flow, Active Power |
n:Qflow:bushvor :busmv, :buslv | Mvar | Power Flow, Reactive Power |
n:Pout:bushvor :busmv, :buslv | MW | Outgoing Flow, Active Power |
n:Qout:bushvor :busmv, :buslv | Mvar | Outgoing Power, Reactive Power |
n:Sout:bushvor :busmv, :buslv | MVA | Outgoing Power, Apparent Power |
n:cosphiout:bushvor :busmv, :buslv | ยท | Outgoing Power, Power Factor |
n:Pbalance:bushvor :busmv, :buslv | MW | Active Power Balance (=0) |
n:Qbalance:bushvor :busmv, :buslv | Mvar | Reactive Power Balance (=0) |
n:LossPdown:bushvor :busmv, :buslv | MW | Losses, downstream |
n:LossQdown:bushvor :busmv, :buslv | Mvar | Losses, downstream (Reactive Power) |
n:LossPdownload:bushvor :busmv, :buslv | MW | Load losses, downstream |
n:LossQdownload:bushvor :busmv, :buslv | Mvar | Load losses, downstream |
n:LossPdownnoload:bushvor :busmv, :buslv | MW | No load losses, downstream |
n:LossQdownnoload:bushvor :busmv, :buslv | Mvar | No load losses, downstream |
n:du_feed:bushvor :busmv, :buslv | % | Difference from voltage at start of feeder |
n:ur:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Real Part |
n:ui:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Imaginary Part |
n:u:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Magnitude |
n:upc:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | % | Line-Ground Voltage, Magnitude |
n:du:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | % | Voltage Deviation |
n:U:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Line-Ground Voltage, Magnitude |
n:phiu:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Line-Ground Voltage, Angle |
n:ul:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Line Voltage, Magnitude |
n:ulpc:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | % | Line-Line Voltage, Magnitude |
n:Ul:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Line-Line Voltage, Magnitude |
n:phiul:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Line-Line Voltage, Angle |
n:u0:bushvor :busmv, :buslv | p.u. | Zero-Sequence Voltage, Magnitude |
n:U0:bushvor :busmv, :buslv | kV | Zero-Sequence Voltage, Magnitude |
n:U0x3:bushvor :busmv, :buslv | kV | 3*U0 |
n:phiu0:bushvor :busmv, :buslv | deg | Zero-Sequence Voltage, Angle |
n:U1:bushvor :busmv, :buslv | kV | Line-Ground Positive-Sequence Voltage, Magnitude |
n:phiu1:bushvor :busmv, :buslv | deg | Positive-Sequence Voltage, Angle |
n:u2:bushvor :busmv, :buslv | p.u. | Negative-Sequence Voltage, Magnitude |
n:U2:bushvor :busmv, :buslv | kV | Line-Ground Negative-Sequence Voltage, Magnitude |
n:phiu2:bushvor :busmv, :buslv | deg | Negative-Sequence Voltage, Angle |
n:U1l:bushvor :busmv, :buslv | kV | Line-Line Positive-Sequence Voltage, Magnitude |
n:U2l:bushvor :busmv, :buslv | kV | Line-Line Negative-Sequence Voltage, Magnitude |
n:uln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Neutral Voltage, Magnitude |
n:Uln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Line-Neutral Voltage, Magnitude |
n:phiuln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Line-Neutral Voltage, Angle |
n:un:bushvor :busmv, :buslv | p.u. | Neutral-Ground Voltage, Magnitude |
n:Un:bushvor :busmv, :buslv | kV | Neutral-Ground Voltage, Magnitude |
n:phiun:bushvor :busmv, :buslv | deg | Neutral-Ground Voltage, Angle |
n:upht:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Technology dependent Voltage, Magnitude |
n:Upht:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Phase Technology dependent Voltage, Magnitude |
n:um:bushvor :busmv, :buslv | p.u. | Average-Voltage, Magnitude |
n:Um:bushvor :busmv, :buslv | kV | Average-Voltage, Magnitude |
n:uphtmin:bushvor :busmv, :buslv | p.u. | Minimum of Phase Technology dependent Voltage, Magnitude |
n:uphtmax:bushvor :busmv, :buslv | p.u. | Maximum of Phase Technology dependent Voltage, Magnitude |
n:ubfac:bushvor :busmv, :buslv | % | Unbalance Factor |
s:nt_in_h | ยท | Tap Position (HV), Input |
s:nt_in_m | ยท | Tap Position (MV), Input |
s:nt_in_l | ยท | Tap Position (LV), Input |
s:du_ldc | ยท | LDC Input |
s:I0rDelta_h | kA | Circulating current in HV-Delta-Winding, Real Part |
s:I0rDelta_m | kA | Circulating current in HV-Delta-Winding, Real Part |
s:I0rDelta_l | kA | Circulating current in LV-Delta-Winding, Real Part |
s:I0iDelta_h | kA | Circulating current in HV-Delta-Winding, Imaginary Part |
s:I0iDelta_m | kA | Circulating current in MV-Delta-Winding, Imaginary Part |
s:I0iDelta_l | kA | Circulating current in LV-Delta-Winding, Imaginary Part |
ElmTr3 short-circuit results
Read after ComShc with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).
| Attribute | Unit | Description |
|---|---|---|
m:I:bushvor :busmv, :buslv | kA | Short-Circuit Current, Magnitude |
m:phii:bushvor :busmv, :buslv | deg | Phase Current, Angle |
m:i1:bushvor :busmv, :buslv | p.u. | Positive-Sequence Current, Magnitude |
m:I1:bushvor :busmv, :buslv | kA | Positive-Sequence Current, Magnitude |
m:phii1:bushvor :busmv, :buslv | deg | Positive-Sequence Current, Angle |
m:P:bushvor :busmv, :buslv | MW | Active Power |
m:Q:bushvor :busmv, :buslv | Mvar | Reactive Power |
m:i1P:bushvor :busmv, :buslv | p.u. | Positive-Sequence Active Current |
m:i1Q:bushvor :busmv, :buslv | p.u. | Positive-Sequence Reactive Current |
m:I1P:bushvor :busmv, :buslv | kA | Positive-Sequence Active Current |
m:I1Q:bushvor :busmv, :buslv | kA | Positive-Sequence Reactive Current |
m:phiui:bushvor :busmv, :buslv | deg | Angle between Voltage and Current |
m:phiu1i1:bushvor :busmv, :buslv | deg | Angle between Voltage and Current in Positive-Sequence System |
m:Tfct:bushvor :busmv, :buslv | s | Fault Clearing Time |
m:Ikss:bushvor :busmv, :buslv | kA | Initial Short-Circuit Current |
m:ikss:bushvor :busmv, :buslv | p.u. | Initial Short-Circuit Current, Magnitude |
m:Skss:bushvor :busmv, :buslv | MVA | Initial Short-Circuit Power |
m:ip:bushvor :busmv, :buslv | kA | Peak Short-Circuit Current |
m:maxIkss:bushvor :busmv, :buslv | kA | Max. Initial Short-Circuit Current |
m:maxip:bushvor :busmv, :buslv | kA | Max. Peak Short-Circuit Current |
m:maxIth:bushvor :busmv, :buslv | kA | Max. Thermal equivalent Short-Circuit Current |
m:maxIb:bushvor :busmv, :buslv | kA | Max. Breaking Current |
m:R:bushvor :busmv, :buslv | Ohm | Fault Impedance, Real Part |
m:X:bushvor :busmv, :buslv | Ohm | Fault Impedance, Imaginary Part |
m:Z:bushvor :busmv, :buslv | Ohm | Fault Impedance, Magnitude |
m:phiz:bushvor :busmv, :buslv | deg | Fault Impedance, Angle |
m:Rs:bushvor :busmv, :buslv | Ohm | Source Impedance, Real Part |
m:Xs:bushvor :busmv, :buslv | Ohm | Source Impedance, Imaginary Part |
m:Zs:bushvor :busmv, :buslv | Ohm | Source Impedance, Magnitude |
m:phizs:bushvor :busmv, :buslv | deg | Source Impedance, Angle |
m:BrkIpload:bushvor :busmv, :buslv | % | Breaker Loading (peak) |
m:Ib:bushvor :busmv, :buslv | kA | Short-Circuit Breaking Current |
m:Sb:bushvor :busmv, :buslv | MVA | Short-Circuit Breaking Power |
m:Ith:bushvor :busmv, :buslv | kA | Thermal equivalent Short-Circuit Current |
m:zSbase:bushvor :busmv, :buslv | p.u. | Fault Impedance, Magnitude |
m:XtoR:bushvor :busmv, :buslv | ยท | X/R ratio |
m:cosphiui:bushvor :busmv, :buslv | ยท | cosphi |
m:BrkIbload:bushvor :busmv, :buslv | % | Breaker Loading (breaking) |
m:BrkmaxIb:bushvor :busmv, :buslv | kA | Max. Breaking Current (breaker time) |
m:Ik:bushvor :busmv, :buslv | kA | Steady-State Short-Circuit Current |
m:I:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kA | Short-Circuit Current, Magnitude |
m:phii:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Phase Current, Angle |
m:I0:bushvor :busmv, :buslv | kA | Zero-Sequence Current, Magnitude |
m:I0x3:bushvor :busmv, :buslv | kA | 3*I0 |
m:phii0:bushvor :busmv, :buslv | deg | Zero-Sequence Current, Angle |
m:I2:bushvor :busmv, :buslv | kA | Negative-Sequence Current, Magnitude |
m:phii2:bushvor :busmv, :buslv | deg | Negative-Sequence Current, Angle |
m:P:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | MW | Active Power |
m:Q:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | Mvar | Reactive Power |
m:Psum:bushvor :busmv, :buslv | MW | Total Active Power |
m:Qsum:bushvor :busmv, :buslv | Mvar | Total Reactive Power |
m:cosphisum:bushvor :busmv, :buslv | ยท | Total Power Factor |
m:P2:bushvor :busmv, :buslv | MW | P2 |
m:Q2:bushvor :busmv, :buslv | Mvar | Q2 |
m:P0:bushvor :busmv, :buslv | MW | P0 |
m:phiui:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Angle between Voltage and Current |
m:phiu0i0:bushvor :busmv, :buslv | deg | Angle between Voltage and Current in Zero-Sequence System |
m:phiu2i2:bushvor :busmv, :buslv | deg | Angle between Voltage and Current in Negative-Sequence System |
m:TfctPh:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | s | Fault Clearing Time |
m:Ikss:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kA | Initial Short-Circuit Current |
m:ikss:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Initial Short-Circuit Current, Magnitude |
m:Skss:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | MVA | Initial Short-Circuit Power |
m:Skssx3:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | MVA | 3*Initial Short-Circuit Power |
m:ip:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kA | Peak Short-Circuit Current |
m:Z:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | Ohm | Fault Impedance, Magnitude |
m:phiz:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Fault Impedance, Angle |
m:Zl:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | Ohm | Line-Line Fault Impedance, Magnitude |
m:phizl:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Line-Line Fault Impedance, Angle |
m:Z0:bushvor :busmv, :buslv | Ohm | Zero-Sequence Fault Impedance, Magnitude |
m:phiz0:bushvor :busmv, :buslv | deg | Zero-Sequence Fault Impedance, Angle |
m:z0Sbase:bushvor :busmv, :buslv | p.u. | Zero-Sequence Fault Impedance, Magnitude |
m:cosphiu1i1:bushvor :busmv, :buslv | ยท | Positive-Sequence cosphi |
m:I0x3watt:bushvor :busmv, :buslv | kA | Earth-Fault Residual Current |
m:I0x3var:bushvor :busmv, :buslv | kA | Capacitive Earth-Fault Current |
m:Q0cap:bushvor :busmv, :buslv | Mvar | Q0 capacitive |
m:Rfrel:bushvor :busmv, :buslv | Ohm | Relay Impedance, Real Part |
m:Xfrel:bushvor :busmv, :buslv | Ohm | Relay Impedance, Imaginary Part |
m:Zfrel:bushvor :busmv, :buslv | Ohm | Relay Impedance, Magnitude |
m:phizfrel:bushvor :busmv, :buslv | deg | Relay Impedance, Angle |
m:Zf:bushvor :busmv, :buslv | Ohm | Meas. Fault Impedance, Magnitude |
m:phizf:bushvor :busmv, :buslv | deg | Meas. Fault Impedance, Angle |
c:ntpmn:Aper phase :A, :B, :C, unbalanced only | ยท | Minimum Tap Position |
c:ntpmx:Aper phase :A, :B, :C, unbalanced only | ยท | Maximum Tap Position |
c:nntap0:Aper phase :A, :B, :C, unbalanced only | ยท | Neutral Position |
c:pT:Aper phase :A, :B, :C, unbalanced only | % | Range of Voltage Adjustment |
c:Kt_h | ยท | VDE/IEC Correction Factor, HV-MV |
c:Kt_m | ยท | VDE/IEC Correction Factor, MV-LV |
c:Kt_l | ยท | VDE/IEC Correction Factor, LV-HV |
c:ntagrd:Aper phase :A, :B, :C, unbalanced only | ยท | Phase Shift |
c:zs_h | p.u. | Short Circuit Impedance (HV) |
c:zs_m | p.u. | Short Circuit Impedance (MV) |
c:zs_l | p.u. | Short Circuit Impedance (LV) |
c:yg_hv | p.u. | Parasitic Admittance (HV-Side) |
c:yg_mv | p.u. | Parasitic Admittance (MV-Side) |
c:yg_lv | p.u. | Parasitic Admittance (LV-Side) |
c:yc1_lh | p.u. | LV-HV Coupling-Admittance (normalised on HV-Side) |
c:yc1_hm | p.u. | HV-MV Coupling-Admittance (normalised on HV-Side) |
c:yc1_ml | p.u. | MV-LV Coupling-Admittance (normalised on HV-Side) |
c:i30lc | ยท | Position of 0-Sequ. Magn.ind. |
c:zs0_h | p.u. | 0-Sequ. Short-Circuit Imp (HV) |
c:zs0_m | p.u. | 0-Sequ. Short-Circuit Imp (MV) |
c:zs0_l | p.u. | 0-Sequ. Short-Circuit Imp (LV) |
c:ze0_h | p.u. | Earth Impedance (HV) |
c:ze0_m | p.u. | Earth Impedance (MV) |
c:ze0_l | p.u. | Earth Impedance (LV) |
c:i_star_h | ยท | Flag |
c:i_star_m | ยท | Flag |
c:i_star_l | ยท | Flag |
c:i_earth_h | ยท | Flag |
c:i_earth_m | ยท | Flag |
c:i_earth_l | ยท | Flag |
c:ym0 | p.u. | 0-Sequ. Magn. Admitt. |
c:i_stshort | ยท | Flag |
c:Ustar_h | kV | Star-Point Voltage (HV) |
c:Ustar_m | kV | Star-Point Voltage (MV) |
c:Ustar_l | kV | Star-Point Voltage (LV) |
c:Istar_h | kA | Star-Point Current (HV) |
c:Istar_m | kA | Star-Point Current (MV) |
c:Istar_l | kA | Star-Point Current (LV) |
c:I0Delta_h | kA | Circulating current in HV-Delta-Winding, Magnitude |
c:I0Delta_m | kA | Circulating current in Delta-Winding, Magnitude |
c:I0Delta_l | kA | Circulating current in Delta-Winding, Magnitude |
c:yc0_lh | p.u. | LV-HV Coupling-Admittance (0-Sys., normalised on HV-Side) |
c:yc0_hm | p.u. | HV-MV Coupling-Admittance (0-Sys., normalised on HV-Side) |
c:yc0_ml | p.u. | MV-LV Coupling-Admittance (0-Sys., normalised on HV-Side) |
n:ur:bushvor :busmv, :buslv | p.u. | Voltage, Real Part |
n:ui:bushvor :busmv, :buslv | p.u. | Voltage, Imaginary Part |
n:u:bushvor :busmv, :buslv | p.u. | Voltage, Magnitude |
n:upc:bushvor :busmv, :buslv | % | Voltage, Magnitude |
n:du:bushvor :busmv, :buslv | % | Voltage Deviation |
n:U:bushvor :busmv, :buslv | kV | Line-Ground Voltage, Magnitude |
n:phiu:bushvor :busmv, :buslv | deg | Voltage, Angle |
n:Ul:bushvor :busmv, :buslv | kV | Line-Line Voltage, Magnitude |
n:u1:bushvor :busmv, :buslv | p.u. | Voltage, Magnitude |
n:u1pc:bushvor :busmv, :buslv | % | Voltage, Magnitude |
n:u1r:bushvor :busmv, :buslv | p.u. | Positive-Sequence Voltage, Real Part |
n:u1i:bushvor :busmv, :buslv | p.u. | Positive-Sequence Voltage, Imaginary Part |
n:Ikss:bushvor :busmv, :buslv | kA | Initial Short-Circuit Current |
n:I:bushvor :busmv, :buslv | kA | Short-Circuit Current |
n:phii:bushvor :busmv, :buslv | deg | Phase Current, Angle |
n:Skss:bushvor :busmv, :buslv | MVA | Initial Short-Circuit Power |
n:ip:bushvor :busmv, :buslv | kA | Peak Short-Circuit Current |
n:Ib:bushvor :busmv, :buslv | kA | Short-Circuit Breaking Current |
n:Sb:bushvor :busmv, :buslv | MVA | Short-Circuit Breaking Power |
n:idc:bushvor :busmv, :buslv | kA | Decaying Component |
n:Ith:bushvor :busmv, :buslv | kA | Thermal equivalent Short-Circuit Current |
n:R1toX1:bushvor :busmv, :buslv | ยท | R1/X1 ratio (Zk") |
n:X1toR1:bushvor :busmv, :buslv | ยท | X1/R1 ratio (Zk") |
n:R:bushvor :busmv, :buslv | Ohm | Short-Circuit Impedance, Real Part |
n:X:bushvor :busmv, :buslv | Ohm | Short-Circuit Impedance, Imaginary Part |
n:Z:bushvor :busmv, :buslv | Ohm | Short-Circuit Impedance, Magnitude |
n:phiz:bushvor :busmv, :buslv | deg | Short-Circuit Impedance, Angle |
n:urpref:bushvor :busmv, :buslv | p.u. | Pre-fault Voltage, Real Part |
n:uipref:bushvor :busmv, :buslv | p.u. | Pre-fault Voltage, Imaginary Part |
n:upref:bushvor :busmv, :buslv | p.u. | Pre-fault Voltage, Magnitude |
n:uprefpc:bushvor :busmv, :buslv | % | Pre-fault Voltage, Magnitude |
n:Upref:bushvor :busmv, :buslv | kV | Line-Ground Pre-fault Voltage, Magnitude |
n:Ulpref:bushvor :busmv, :buslv | kV | Line-Line Pre-fault Voltage, Magnitude |
n:phiupref:bushvor :busmv, :buslv | deg | Pre-fault Voltage, Angle |
n:phiui:bushvor :busmv, :buslv | deg | Angle between Voltage and Current |
n:Ithload:bushvor :busmv, :buslv | % | Loading, Thermal equivalent Current |
n:Ipload:bushvor :busmv, :buslv | % | Loading, Peak Short-Circuit Current |
n:Ithrtk:bushvor :busmv, :buslv | kA | Rated Short-Time Current (Tk) |
n:XtoR:bushvor :busmv, :buslv | ยท | X/R ratio (peak) |
n:RtoX:bushvor :busmv, :buslv | ยท | R/X ratio (peak) |
n:XtoR_b:bushvor :busmv, :buslv | ยท | X/R ratio (dc) |
n:RtoX_b:bushvor :busmv, :buslv | ยท | R/X ratio (dc) |
n:fctof_b:bushvor :busmv, :buslv | ยท | Equivalent Frequency fc/f (dc) |
n:rSbase:bushvor :busmv, :buslv | p.u. | Short-Circuit Impedance, Real Part |
n:xSbase:bushvor :busmv, :buslv | p.u. | Short-Circuit Impedance, Imaginary Part |
n:zSbase:bushvor :busmv, :buslv | p.u. | Short-Circuit Impedance, Magnitude |
n:Tn:bushvor :busmv, :buslv | ms | Grid Time Constant |
n:Ik:bushvor :busmv, :buslv | kA | Steady-State Short-Circuit Current |
n:cfac:bushvor :busmv, :buslv | ยท | Voltage Factor |
n:Iasy:bushvor :busmv, :buslv | kA | Asymmetrical Breaking Current |
n:ur:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Real Part |
n:ui:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Imaginary Part |
n:u:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Magnitude |
n:upc:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | % | Line-Ground Voltage, Magnitude |
n:du:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | % | Voltage Deviation |
n:U:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Line-Ground Voltage, Magnitude |
n:phiu:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Line-Ground Voltage, Angle |
n:ul:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Line Voltage, Magnitude |
n:ulpc:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | % | Line-Line Voltage, Magnitude |
n:Ul:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Line-Line Voltage, Magnitude |
n:phiul:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Line-Line Voltage, Angle |
n:u0:bushvor :busmv, :buslv | p.u. | Zero-Sequence Voltage, Magnitude |
n:U0:bushvor :busmv, :buslv | kV | Zero-Sequence Voltage, Magnitude |
n:U0x3:bushvor :busmv, :buslv | kV | 3*U0 |
n:phiu0:bushvor :busmv, :buslv | deg | Zero-Sequence Voltage, Angle |
n:U1:bushvor :busmv, :buslv | kV | Line-Ground Positive-Sequence Voltage, Magnitude |
n:phiu1:bushvor :busmv, :buslv | deg | Positive-Sequence Voltage, Angle |
n:u2:bushvor :busmv, :buslv | p.u. | Negative-Sequence Voltage, Magnitude |
n:U2:bushvor :busmv, :buslv | kV | Line-Ground Negative-Sequence Voltage, Magnitude |
n:phiu2:bushvor :busmv, :buslv | deg | Negative-Sequence Voltage, Angle |
n:U1l:bushvor :busmv, :buslv | kV | Line-Line Positive-Sequence Voltage, Magnitude |
n:U2l:bushvor :busmv, :buslv | kV | Line-Line Negative-Sequence Voltage, Magnitude |
n:uln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Neutral Voltage, Magnitude |
n:Uln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Line-Neutral Voltage, Magnitude |
n:phiuln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Line-Neutral Voltage, Angle |
n:un:bushvor :busmv, :buslv | p.u. | Neutral-Ground Voltage, Magnitude |
n:Un:bushvor :busmv, :buslv | kV | Neutral-Ground Voltage, Magnitude |
n:phiun:bushvor :busmv, :buslv | deg | Neutral-Ground Voltage, Angle |
n:upht:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Technology dependent Voltage, Magnitude |
n:Upht:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Phase Technology dependent Voltage, Magnitude |
n:Ikss:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kA | Initial Short-Circuit Current |
n:I:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kA | Short-Circuit Current |
n:phii:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Phase Current, Angle |
n:Skss:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | MVA | Initial Short-Circuit Power |
n:Skssx3:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | MVA | 3*Initial Short-Circuit Power |
n:ip:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kA | Peak Short-Circuit Current |
n:Ib:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kA | Short-Circuit Breaking Current |
n:Sb:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | MVA | Short-Circuit Breaking Power |
n:Ith:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kA | Thermal equivalent Short-Circuit Current |
n:Ithmax:bushvor :busmv, :buslv | kA | Max. Thermal equivalent Short-Circuit Current |
n:R0:bushvor :busmv, :buslv | Ohm | Zero-Sequence Impedance, Real Part |
n:X0:bushvor :busmv, :buslv | Ohm | Zero-Sequence Impedance, Imaginary Part |
n:Z0:bushvor :busmv, :buslv | Ohm | Zero-Sequence Impedance, Magnitude |
n:phiz0:bushvor :busmv, :buslv | deg | Zero-Sequence Impedance, Angle |
n:r0Sbase:bushvor :busmv, :buslv | p.u. | Zero-Sequence Impedance, Real Part |
n:x0Sbase:bushvor :busmv, :buslv | p.u. | Zero-Sequence Impedance, Imaginary Part |
n:z0Sbase:bushvor :busmv, :buslv | p.u. | Zero-Sequence Impedance, Magnitude |
n:R1:bushvor :busmv, :buslv | Ohm | Positive-Sequence Impedance, Real Part |
n:X1:bushvor :busmv, :buslv | Ohm | Positive-Sequence Impedance, Imaginary Part |
n:Z1:bushvor :busmv, :buslv | Ohm | Positive-Sequence Impedance, Magnitude |
n:phiz1:bushvor :busmv, :buslv | deg | Positive-Sequence Impedance, Angle |
n:r1Sbase:bushvor :busmv, :buslv | p.u. | Positive-Sequence Impedance, Real Part |
n:x1Sbase:bushvor :busmv, :buslv | p.u. | Positive-Sequence Impedance, Imaginary Part |
n:z1Sbase:bushvor :busmv, :buslv | p.u. | Positive-Sequence Impedance, Magnitude |
n:R2:bushvor :busmv, :buslv | Ohm | Negative-Sequence Impedance, Real Part |
n:X2:bushvor :busmv, :buslv | Ohm | Negative-Sequence Impedance, Imaginary Part |
n:Z2:bushvor :busmv, :buslv | Ohm | Negative-Sequence Impedance, Magnitude |
n:phiz2:bushvor :busmv, :buslv | deg | Negative-Sequence Impedance, Angle |
n:r2Sbase:bushvor :busmv, :buslv | p.u. | Negative-Sequence Impedance, Real Part |
n:x2Sbase:bushvor :busmv, :buslv | p.u. | Negative-Sequence Impedance, Imaginary Part |
n:z2Sbase:bushvor :busmv, :buslv | p.u. | Negative-Sequence Impedance, Magnitude |
n:R0toX0:bushvor :busmv, :buslv | ยท | R0/X0 ratio (Zk") |
n:X0toR0:bushvor :busmv, :buslv | ยท | X0/R0 ratio (Zk") |
n:R2toX2:bushvor :busmv, :buslv | ยท | R2/X2 ratio (Zk") |
n:X2toR2:bushvor :busmv, :buslv | ยท | X2/R2 ratio (Zk") |
n:R:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | Ohm | Network Resistance, Line-Ground |
n:X:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | Ohm | Network Reactance, Line-Ground |
n:Z:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | Ohm | Network Impedance, Line-Ground |
n:phiz:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Angle of Network Impedance, Line-Ground |
n:Rl:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | Ohm | Network Resistance, Line-Line |
n:Xl:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | Ohm | Network Reactance, Line-Line |
n:Zl:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | Ohm | Network Impedance, Line-Line |
n:phizl:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Angle of Network Impedance, Line-Line |
n:Rln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | Ohm | Network Resistance, Line-Neutral |
n:Xln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | Ohm | Network Reactance, Line-Neutral |
n:Zln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | Ohm | Network Impedance, Line-Neutral |
n:phizln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Angle of Network Impedance, Line-Neutral |
n:Rn:bushvor :busmv, :buslv | Ohm | Network Resistance, Neutral |
n:Xn:bushvor :busmv, :buslv | Ohm | Network Reactance, Neutral |
n:Zn:bushvor :busmv, :buslv | Ohm | Network Impedance, Neutral |
n:phizn:bushvor :busmv, :buslv | deg | Angle of Network Impedance, Neutral |
n:eff:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | ยท | Earth Fault Factor |
n:X0toX1:bushvor :busmv, :buslv | ยท | X0/X1 |
n:In:bushvor :busmv, :buslv | kA | Neutral Current, Magnitude |
n:phiin:bushvor :busmv, :buslv | deg | Neutral Current, Angle |
n:I0:bushvor :busmv, :buslv | kA | Zero-Sequence Current, Magnitude |
n:I0x3:bushvor :busmv, :buslv | kA | 3*I0 |
n:phii0:bushvor :busmv, :buslv | deg | Zero-Sequence Current, Angle |
n:I1:bushvor :busmv, :buslv | kA | Positive-Sequence Current, Magnitude |
n:phii1:bushvor :busmv, :buslv | deg | Positive-Sequence Current, Angle |
n:I2:bushvor :busmv, :buslv | kA | Negative-Sequence Current, Magnitude |
n:phii2:bushvor :busmv, :buslv | deg | Negative-Sequence Current, Angle |
n:urpref:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Pre-fault Voltage, Real Part |
n:uipref:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Pre-fault Voltage, Imaginary Part |
n:upref:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Pre-fault Voltage, Magnitude |
n:uprefpc:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | % | Pre-fault Voltage, Magnitude |
n:Upref:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Line-Ground Pre-fault Voltage, Magnitude |
n:Ulpref:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Line-Line Pre-fault Voltage, Magnitude |
n:phiupref:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Pre-fault Voltage, Angle |
n:phiui:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Angle between Voltage and Current |
n:phiu1i1:bushvor :busmv, :buslv | deg | Angle between Voltage and Current in positive sequence system |
n:phiu2i2:bushvor :busmv, :buslv | deg | Angle between Voltage and Current in negative sequence system |
n:phiu0i0:bushvor :busmv, :buslv | deg | Angle between Voltage and Current in zero-sequence system |
n:Ik:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kA | Steady-State Short-Circuit Current |
n:in:bushvor :busmv, :buslv | p.u. | Neutral Current, Magnitude |
n:i0r:bushvor :busmv, :buslv | p.u. | Zero-Sequence Current, Real Part |
n:i0i:bushvor :busmv, :buslv | p.u. | Zero-Sequence Current, Imaginary Part |
n:i0:bushvor :busmv, :buslv | p.u. | Zero-Sequence Current, Magnitude |
n:i1r:bushvor :busmv, :buslv | p.u. | Positive-Sequence Current, Real Part |
n:i1i:bushvor :busmv, :buslv | p.u. | Positive-Sequence Current, Imaginary Part |
n:i1:bushvor :busmv, :buslv | p.u. | Positive-Sequence Current, Magnitude |
n:i2r:bushvor :busmv, :buslv | p.u. | Negative-Sequence Current, Real Part |
n:i2i:bushvor :busmv, :buslv | p.u. | Negative-Sequence Current, Imaginary Part |
n:i2:bushvor :busmv, :buslv | p.u. | Negative-Sequence Current, Magnitude |
s:I0rDelta_h | kA | Circulating current in HV-Delta-Winding, Real Part |
s:I0rDelta_m | kA | Circulating current in HV-Delta-Winding, Real Part |
s:I0rDelta_l | kA | Circulating current in LV-Delta-Winding, Real Part |
s:I0iDelta_h | kA | Circulating current in HV-Delta-Winding, Imaginary Part |
s:I0iDelta_m | kA | Circulating current in MV-Delta-Winding, Imaginary Part |
s:I0iDelta_l | kA | Circulating current in LV-Delta-Winding, Imaginary Part |
ElmTr3 rms simulation results
Read after ComInc (RMS) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).
| Attribute | Unit | Description |
|---|---|---|
m:urnet:bushvor :busmv, :buslv | p.u. | Voltage, Real Part, referred to network |
m:uinet:bushvor :busmv, :buslv | p.u. | Voltage, Imaginary Part, referred to network |
m:u1r:bushvor :busmv, :buslv | p.u. | Positive-Sequence-Voltage, Real Part |
m:u1i:bushvor :busmv, :buslv | p.u. | Positive-Sequence-Voltage, Imaginary Part |
m:u1:bushvor :busmv, :buslv | p.u. | Positive-Sequence-Voltage, Magnitude |
m:U1:bushvor :busmv, :buslv | kV | Line-Ground Positive-Sequence-Voltage, Magnitude |
m:U1l:bushvor :busmv, :buslv | kV | Line-Line Positive-Sequence-Voltage, Magnitude |
m:phiu1:bushvor :busmv, :buslv | deg | Positive-Sequence-Voltage, Angle |
m:irnet:bushvor :busmv, :buslv | p.u. | Current, Real Part, referred to network |
m:iinet:bushvor :busmv, :buslv | p.u. | Current, Imaginary Part, referred to network |
m:inet:bushvor :busmv, :buslv | p.u. | Current, Magnitude, referred to network |
m:I:bushvor :busmv, :buslv | kA | Current, Magnitude |
m:phii:bushvor :busmv, :buslv | deg | Current, Angle |
m:i1r:bushvor :busmv, :buslv | p.u. | Positive-Sequence Current, Real Part |
m:i1i:bushvor :busmv, :buslv | p.u. | Positive-Sequence Current, Imaginary Part |
m:i1:bushvor :busmv, :buslv | p.u. | Positive-Sequence Current, Magnitude |
m:I1:bushvor :busmv, :buslv | kA | Positive-Sequence Current, Magnitude |
m:phii1:bushvor :busmv, :buslv | deg | Positive-Sequence Current, Angle |
m:P:bushvor :busmv, :buslv | MW | Active Power |
m:Q:bushvor :busmv, :buslv | Mvar | Reactive Power |
m:S:bushvor :busmv, :buslv | MVA | Apparent Power |
m:cosphi:bushvor :busmv, :buslv | ยท | Power Factor |
m:tanphi:bushvor :busmv, :buslv | ยท | tan(phi) |
m:Psum:bushvor :busmv, :buslv | MW | Total Active Power |
m:Qsum:bushvor :busmv, :buslv | Mvar | Total Reactive Power |
m:Ssum:bushvor :busmv, :buslv | MVA | Total Apparent Power |
m:cosphisum:bushvor :busmv, :buslv | ยท | Total Power Factor |
m:tanphisum:bushvor :busmv, :buslv | ยท | Total tan(phi) |
m:i1P:bushvor :busmv, :buslv | p.u. | Positive-Sequence Active Current |
m:i1Q:bushvor :busmv, :buslv | p.u. | Positive-Sequence Reactive Current |
m:I1P:bushvor :busmv, :buslv | kA | Positive-Sequence Active Current |
m:I1Q:bushvor :busmv, :buslv | kA | Positive-Sequence Reactive Current |
m:ur:bushvor :busmv, :buslv | p.u. | Voltage, Real Part |
m:ui:bushvor :busmv, :buslv | p.u. | Voltage, Imaginary Part |
m:u:bushvor :busmv, :buslv | p.u. | Voltage, Magnitude |
m:ir:bushvor :busmv, :buslv | p.u. | Current, Real Part |
m:ii:bushvor :busmv, :buslv | p.u. | Current, Imaginary Part |
m:i:bushvor :busmv, :buslv | p.u. | Current, Magnitude |
m:phiui:bushvor :busmv, :buslv | deg | Angle between Voltage and Current |
m:phiu1i1:bushvor :busmv, :buslv | deg | Angle between Voltage and Current in positive sequence system |
m:Tfct:bushvor :busmv, :buslv | s | Fault Clearing Time |
m:Brkload:bushvor :busmv, :buslv | % | Breaker Loading |
m:Spu:bushvor :busmv, :buslv | MVA/p.u. | Apparent Power per p.u. Voltage |
m:urnet:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Real Part, referred to network |
m:uinet:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Imaginary Part, referred to network |
m:u0:bushvor :busmv, :buslv | p.u. | Zero-Sequence-Voltage, Magnitude |
m:phiu0:bushvor :busmv, :buslv | deg | Zero-Sequence-Voltage, Angle |
m:u2:bushvor :busmv, :buslv | p.u. | Negative-Sequence-Voltage, Magnitude |
m:phiu2:bushvor :busmv, :buslv | deg | Negative-Sequence-Voltage, Angle |
m:irnet:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Real Part |
m:iinet:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Imaginary Part |
m:inet:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Magnitude |
m:I:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kA | Phase Current, Magnitude |
m:phii:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Phase Current, Angle |
m:i0r:bushvor :busmv, :buslv | p.u. | Zero-Sequence Current, Real Part |
m:i0i:bushvor :busmv, :buslv | p.u. | Zero-Sequence Current, Imaginary Part |
m:i0:bushvor :busmv, :buslv | p.u. | Zero-Sequence Current, Magnitude |
m:I0:bushvor :busmv, :buslv | kA | Zero-Sequence Current, Magnitude |
m:I0x3:bushvor :busmv, :buslv | kA | 3*I0 |
m:phii0:bushvor :busmv, :buslv | deg | Zero-Sequence Current, Angle |
m:i2r:bushvor :busmv, :buslv | p.u. | Negative-Sequence Current, Real Part |
m:i2i:bushvor :busmv, :buslv | p.u. | Negative-Sequence Current, Imaginary Part |
m:i2:bushvor :busmv, :buslv | p.u. | Negative-Sequence Current, Magnitude |
m:I2:bushvor :busmv, :buslv | kA | Negative-Sequence Current, Magnitude |
m:phii2:bushvor :busmv, :buslv | deg | Negative-Sequence Current, Angle |
m:P:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | MW | Active Power |
m:Q:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | Mvar | Reactive Power |
m:S:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | MVA | Apparent Power |
m:cosphi:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | ยท | Power Factor |
m:tanphi:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | ยท | tan(phi) |
m:Pln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | MW | Active Power (Line-Neutral) |
m:Qln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | Mvar | Reactive Power (Line-Neutral) |
m:P1:bushvor :busmv, :buslv | MW | Positive Sequence Active Power |
m:Q1:bushvor :busmv, :buslv | Mvar | Positive Sequence Reactive Power |
m:P2:bushvor :busmv, :buslv | MW | Negative Sequence Active Power |
m:Q2:bushvor :busmv, :buslv | Mvar | Negative Sequence Reactive Power |
m:P0:bushvor :busmv, :buslv | MW | Zero Sequence Active Power |
m:Q0:bushvor :busmv, :buslv | Mvar | Zero Sequence Reactive Power |
m:i2P:bushvor :busmv, :buslv | p.u. | Negative-Sequence Active Current |
m:i2Q:bushvor :busmv, :buslv | p.u. | Negative-Sequence Reactive Current |
m:I2P:bushvor :busmv, :buslv | kA | Negative-Sequence Active Current |
m:I2Q:bushvor :busmv, :buslv | kA | Negative-Sequence Reactive Current |
m:ur:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Real Part |
m:ui:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Imaginary Part |
m:u:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, Magnitude |
m:ir:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Real Part |
m:ii:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Imaginary Part |
m:i:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, Magnitude |
m:phiui:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Angle between Voltage and Current |
m:phiu0i0:bushvor :busmv, :buslv | deg | Angle between Voltage and Current in zero-sequence system |
m:phiu2i2:bushvor :busmv, :buslv | deg | Angle between Voltage and Current in negative sequence system |
m:TfctPh:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | s | Fault Clearing Time |
m:BrkloadPh:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | % | Breaker Loading |
c:loading_h | % | Loading (HV) |
c:loading_m | % | Loading (MV) |
c:loading_l | % | Loading (LV) |
c:loading | % | Maximum Loading |
c:n3tap_h | ยท | Current Tap Position (HV) |
c:n3tap_m | ยท | Current Tap Position (MV) |
c:n3tap_l | ยท | Current Tap Position (LV) |
c:nntap_int_h | ยท | Tap (HV), relative Position |
c:nntap_int_m | ยท | Tap (MV), relative Position |
c:nntap_int_l | ยท | Tap (LV), relative Position |
c:ym | p.u. | Magnetising Admittance |
c:t_h | ยท | Complex Winding Ratio (HV/S) |
c:t_m | ยท | Complex Winding Ratio (MV/S) |
c:t_l | ยท | Complex Winding Ratio (LV/S) |
c:i3loc | ยท | Position of Magn.ind. |
c:w_0 | ยท | Nominal winding ratio |
c:isat | ยท | Saturated Model |
c:Inom_HV | kA | Nominal Current (HV-Side) |
c:Inom_MV | kA | Nominal Current (MV-Side) |
c:Inom_LV | kA | Nominal Current (LV-Side) |
c:iAutoTap | ยท | Controller Mode |
c:zs_h | p.u. | Short Circuit Impedance (HV) |
c:zs_m | p.u. | Short Circuit Impedance (MV) |
c:zs_l | p.u. | Short Circuit Impedance (LV) |
c:yg_hv | p.u. | Parasitic Admittance (HV-Side) |
c:yg_mv | p.u. | Parasitic Admittance (MV-Side) |
c:yg_lv | p.u. | Parasitic Admittance (LV-Side) |
c:yc1_lh | p.u. | LV-HV Coupling-Admittance (normalised on HV-Side) |
c:yc1_hm | p.u. | HV-MV Coupling-Admittance (normalised on HV-Side) |
c:yc1_ml | p.u. | MV-LV Coupling-Admittance (normalised on HV-Side) |
c:i30lc | ยท | Position of 0-Sequ. Magn.ind. |
c:zs0_h | p.u. | 0-Sequ. Short-Circuit Imp (HV) |
c:zs0_m | p.u. | 0-Sequ. Short-Circuit Imp (MV) |
c:zs0_l | p.u. | 0-Sequ. Short-Circuit Imp (LV) |
c:ze0_h | p.u. | Earth Impedance (HV) |
c:ze0_m | p.u. | Earth Impedance (MV) |
c:ze0_l | p.u. | Earth Impedance (LV) |
c:i_star_h | ยท | Flag |
c:i_star_m | ยท | Flag |
c:i_star_l | ยท | Flag |
c:i_earth_h | ยท | Flag |
c:i_earth_m | ยท | Flag |
c:i_earth_l | ยท | Flag |
c:ym0 | p.u. | 0-Sequ. Magn. Admitt. |
c:i_stshort | ยท | Flag |
c:Ustar_h | kV | Star-Point Voltage (HV) |
c:Ustar_m | kV | Star-Point Voltage (MV) |
c:Ustar_l | kV | Star-Point Voltage (LV) |
c:Istar_h | kA | Star-Point Current (HV) |
c:Istar_m | kA | Star-Point Current (MV) |
c:Istar_l | kA | Star-Point Current (LV) |
c:I0Delta_h | kA | Circulating current in HV-D-Winding |
c:I0Delta_m | kA | Circulating current in MV-D-Winding |
c:I0Delta_l | kA | Circulating current in LV-D-Winding |
c:yc0_lh | p.u. | LV-HV Coupling-Admittance (0-Sys., normalised on HV-Side) |
c:yc0_hm | p.u. | HV-MV Coupling-Admittance (0-Sys., normalised on HV-Side) |
c:yc0_ml | p.u. | MV-LV Coupling-Admittance (0-Sys., normalised on HV-Side) |
n:ur:bushvor :busmv, :buslv | p.u. | Voltage, Real Part |
n:ui:bushvor :busmv, :buslv | p.u. | Voltage, Imaginary Part |
n:u:bushvor :busmv, :buslv | p.u. | Voltage, Magnitude |
n:upc:bushvor :busmv, :buslv | % | Voltage, Magnitude |
n:du:bushvor :busmv, :buslv | % | Voltage Deviation |
n:U:bushvor :busmv, :buslv | kV | Line-Ground Voltage, Magnitude |
n:phiu:bushvor :busmv, :buslv | deg | Voltage, Angle |
n:phiurel:bushvor :busmv, :buslv | deg | Voltage, Relative Angle |
n:Ul:bushvor :busmv, :buslv | kV | Line-Line Voltage, Magnitude |
n:u1:bushvor :busmv, :buslv | p.u. | Voltage, Magnitude |
n:u1pc:bushvor :busmv, :buslv | % | Voltage, Magnitude |
n:u1r:bushvor :busmv, :buslv | p.u. | Positive-Sequence Voltage, Real Part |
n:u1i:bushvor :busmv, :buslv | p.u. | Positive-Sequence Voltage, Imaginary Part |
n:ishc:bushvor :busmv, :buslv | p.u. | Short-Circuit Current, magnitude |
n:Ishc:bushvor :busmv, :buslv | kA | Short-Circuit Current, magnitude |
n:fe:bushvor :busmv, :buslv | p.u. | Electrical Frequency |
n:dfehz:bushvor :busmv, :buslv | Hz | Deviation of the El. Frequency |
n:fehz:bushvor :busmv, :buslv | Hz | Electrical Frequency |
n:frnom:bushvor :busmv, :buslv | Hz | Nominal Frequency |
n:ishcr:bushvor :busmv, :buslv | p.u. | Short-Circuit Current, real |
n:ishci:bushvor :busmv, :buslv | p.u. | Short-Circuit Current, imag |
n:dfedt:bushvor :busmv, :buslv | p.u./s | Derivative of El. Frequency |
n:ur:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Real Part |
n:ui:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Imaginary Part |
n:u:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Ground Voltage, Magnitude |
n:upc:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | % | Line-Ground Voltage, Magnitude |
n:du:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | % | Voltage Deviation |
n:U:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Line-Ground Voltage, Magnitude |
n:phiu:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Line-Ground Voltage, Angle |
n:ul:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Line Voltage, Magnitude |
n:ulpc:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | % | Line-Line Voltage, Magnitude |
n:Ul:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Line-Line Voltage, Magnitude |
n:phiul:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Line-Line Voltage, Angle |
n:u0:bushvor :busmv, :buslv | p.u. | Zero-Sequence Voltage, Magnitude |
n:U0:bushvor :busmv, :buslv | kV | Zero-Sequence Voltage, Magnitude |
n:U0x3:bushvor :busmv, :buslv | kV | 3*U0 |
n:phiu0:bushvor :busmv, :buslv | deg | Zero-Sequence Voltage, Angle |
n:U1:bushvor :busmv, :buslv | kV | Line-Ground Positive-Sequence Voltage, Magnitude |
n:phiu1:bushvor :busmv, :buslv | deg | Positive-Sequence Voltage, Angle |
n:u2:bushvor :busmv, :buslv | p.u. | Negative-Sequence Voltage, Magnitude |
n:U2:bushvor :busmv, :buslv | kV | Line-Ground Negative-Sequence Voltage, Magnitude |
n:phiu2:bushvor :busmv, :buslv | deg | Negative-Sequence Voltage, Angle |
n:U1l:bushvor :busmv, :buslv | kV | Line-Line Positive-Sequence Voltage, Magnitude |
n:U2l:bushvor :busmv, :buslv | kV | Line-Line Negative-Sequence Voltage, Magnitude |
n:uln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Neutral Voltage, Magnitude |
n:Uln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Line-Neutral Voltage, Magnitude |
n:phiuln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | deg | Line-Neutral Voltage, Angle |
n:un:bushvor :busmv, :buslv | p.u. | Neutral-Ground Voltage, Magnitude |
n:Un:bushvor :busmv, :buslv | kV | Neutral-Ground Voltage, Magnitude |
n:phiun:bushvor :busmv, :buslv | deg | Neutral-Ground Voltage, Angle |
n:upht:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Technology dependent Voltage, Magnitude |
n:Upht:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Phase Technology dependent Voltage, Magnitude |
n:um:bushvor :busmv, :buslv | p.u. | Average-Voltage, Magnitude |
n:Um:bushvor :busmv, :buslv | kV | Average-Voltage, Magnitude |
n:ishc:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Short-Circuit Current, magnitude |
n:Ishc:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kA | Short-Circuit Current, magnitude |
n:inshc:bushvor :busmv, :buslv | p.u. | Neutral Short-Circuit Current, magnitude |
n:Inshc:bushvor :busmv, :buslv | kA | Neutral Short-Circuit Current, magnitude |
n:ishcr:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Short-Circuit Current, real |
n:ishci:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Short-Circuit Current, imag |
s:nntapin_h | ยท | Tap (HV), Controller Input |
s:nntapin_m | ยท | Tap (MV), Controller Input |
s:nntapin_l | ยท | Tap (LV), Controller Input |
s:I0rDelta_h | kA | Circulating current in HV-Delta-Winding, Real Part |
s:I0rDelta_m | kA | Circulating current in HV-Delta-Winding, Real Part |
s:I0rDelta_l | kA | Circulating current in LV-Delta-Winding, Real Part |
s:I0iDelta_h | kA | Circulating current in HV-Delta-Winding, Imaginary Part |
s:I0iDelta_m | kA | Circulating current in MV-Delta-Winding, Imaginary Part |
s:I0iDelta_l | kA | Circulating current in LV-Delta-Winding, Imaginary Part |
ElmTr3 emt simulation results
Read after ComInc (EMT) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).
| Attribute | Unit | Description |
|---|---|---|
m:u0:bushvor :busmv, :buslv | p.u. | Zero-Sequence-Voltage |
m:u1r:bushvor :busmv, :buslv | p.u. | Voltage Phasor, Real Part |
m:u1i:bushvor :busmv, :buslv | p.u. | Voltage Phasor, Imaginary Part |
m:u1:bushvor :busmv, :buslv | p.u. | Voltage Phasor, Magnitude |
m:U1:bushvor :busmv, :buslv | kV | Line-Ground Voltage Phasor, Magnitude |
m:U1l:bushvor :busmv, :buslv | kV | Line-Line Voltage Phasor, Magnitude |
m:phiu1:bushvor :busmv, :buslv | deg | Voltage Phasor, Angle |
m:inet:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current, referred to network |
m:I:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kA | Phase Current |
m:i0:bushvor :busmv, :buslv | p.u. | Zero-Sequence Current |
m:I0:bushvor :busmv, :buslv | kA | Zero-Sequence Current |
m:I0x3:bushvor :busmv, :buslv | kA | 3*I0 |
m:i1r:bushvor :busmv, :buslv | p.u. | Current Phasor, Real Part |
m:i1i:bushvor :busmv, :buslv | p.u. | Current Phasor, Imaginary Part |
m:i1:bushvor :busmv, :buslv | p.u. | Current Phasor, Magnitude |
m:I1:bushvor :busmv, :buslv | kA | Current Phasor, Magnitude |
m:phii1:bushvor :busmv, :buslv | deg | Current Phasor, Angle |
m:P:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | MW | Active Power |
m:Psum:bushvor :busmv, :buslv | MW | Power-Phasor, Active Power |
m:Qsum:bushvor :busmv, :buslv | Mvar | Power Phasor, Reactive Part |
m:Ssum:bushvor :busmv, :buslv | MVA | Power Phasor, Apparent Power |
m:i1P:bushvor :busmv, :buslv | p.u. | Current Phasor, Active Current |
m:i1Q:bushvor :busmv, :buslv | p.u. | Current Phasor, Reactive Current |
m:I1P:bushvor :busmv, :buslv | kA | Current Phasor, Active Current |
m:I1Q:bushvor :busmv, :buslv | kA | Current Phasor, Reactive Current |
m:u:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage |
m:i:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Current |
m:phiu1i1:bushvor :busmv, :buslv | deg | Angle between Voltage and Current Phasor |
m:Tfct:bushvor :busmv, :buslv | s | Fault Clearing Time |
m:TfctPh:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | s | Fault Clearing Time |
m:unet:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage, referred to network |
m:cosphi1:bushvor :busmv, :buslv | ยท | Power-Phasor, Power-Factor |
c:n3tap_h | ยท | Current Tap Position (HV) |
c:n3tap_m | ยท | Current Tap Position (MV) |
c:n3tap_l | ยท | Current Tap Position (LV) |
c:nntap_int_h | ยท | Tap (HV), relative Position |
c:nntap_int_m | ยท | Tap (MV), relative Position |
c:nntap_int_l | ยท | Tap (LV), relative Position |
c:t_h | ยท | Complex Winding Ratio (HV/S) |
c:t_m | ยท | Complex Winding Ratio (MV/S) |
c:t_l | ยท | Complex Winding Ratio (LV/S) |
c:i3loc | ยท | Position of Magn.ind. |
c:w_0 | ยท | Nominal winding ratio |
c:hpi | rad/s | Nominal angular frequency |
c:bm | p.u. | Magnetising Susceptance |
c:gm | p.u. | Magnetising Conductance |
c:i_sat | ยท | Saturated Model |
c:i_five | ยท | Five Limb Design |
c:im | p.u. | Magnetising current |
c:im0 | p.u. | Magnetising current, zero-sequence |
c:bmsat | p.u. | Saturated Magnetising Susceptance |
c:ksat | ยท | Saturation Exponent |
c:psimknee | p.u. | Knee Flux |
c:physt | kW | Hysteresis losses at rated operation |
c:i30lc | ยท | Position of 0-Sequ. Magn.ind. |
c:i_star_h | ยท | Flag |
c:i_star_m | ยท | Flag |
c:i_star_l | ยท | Flag |
c:i_earth_h | ยท | Flag |
c:i_earth_m | ยท | Flag |
c:i_earth_l | ยท | Flag |
c:i_stshort | ยท | Flag |
c:Ustar_h | kV | Star-Point Voltage (HV) |
c:Ustar_m | kV | Star-Point Voltage (MV) |
c:Ustar_l | kV | Star-Point Voltage (LV) |
c:Istar_h | kA | Star-Point Current (HV) |
c:Istar_m | kA | Star-Point Current (MV) |
c:Istar_l | kA | Star-Point Current (LV) |
c:rs_h | p.u. | Short Circuit Resistance (HV) |
c:rs_m | p.u. | Short Circuit Resistance (MV) |
c:rs_l | p.u. | Short Circuit Resistance (LV) |
c:ls_h | p.u. | Short Circuit Inductance (HV) |
c:ls_m | p.u. | Short Circuit Inductance (MV) |
c:ls_l | p.u. | Short Circuit Inductance (LV) |
c:rs0_h | p.u. | 0-Sequ. Short-Circuit Imp (HV) |
c:rs0_m | p.u. | 0-Sequ. Short-Circuit Imp (MV) |
c:rs0_l | p.u. | 0-Sequ. Short-Circuit Imp (LV) |
c:re0_h | p.u. | Earth Impedance (HV) |
c:re0_m | p.u. | Earth Impedance (MV) |
c:re0_l | p.u. | Earth Impedance (LV) |
c:ls0_h | p.u. | 0-Sequ. Short-Circuit Imp (HV) |
c:ls0_m | p.u. | 0-Sequ. Short-Circuit Imp (MV) |
c:ls0_l | p.u. | 0-Sequ. Short-Circuit Imp (LV) |
c:le0_h | p.u. | Earth Impedance (HV) |
c:le0_m | p.u. | Earth Impedance (MV) |
c:le0_l | p.u. | Earth Impedance (LV) |
c:bm0 | p.u. | 0-Sequ. Magn. Inductance |
c:rm0 | p.u. | 0-Sequ. Magn. Resistance |
c:im_a | p.u. | Magnetising Current, Phase a |
c:im_b | p.u. | Magnetising Current, Phase b |
c:im_c | p.u. | Magnetising Current, Phase c |
c:cg_hv | p.u. | Parasitic Capacitance (HV-Side) |
c:cg_mv | p.u. | Parasitic Capacitance (MV-Side) |
c:cg_lv | p.u. | Parasitic Capacitance (LV-Side) |
c:cc1_lh | p.u. | LV-HV Coupling-Capacitance (normalised on HV-Side) |
c:cc1_hm | p.u. | HV-MV Coupling-Capacitance (normalised on HV-Side) |
c:cc1_ml | p.u. | MV-LV Coupling-Capacitance (normalised on HV-Side) |
c:cc0_lh | p.u. | LV-HV Coupling-Capacitance (0-Sys., normalised on HV-Side) |
c:cc0_hm | p.u. | HV-MV Coupling-Capacitance (0-Sys., normalised on HV-Side) |
c:cc0_ml | p.u. | MV-LV Coupling-Capacitance (0-Sys., normalised on HV-Side) |
n:u:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Phase Voltage |
n:upc:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | % | Phase Voltage |
n:U:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Phase Voltage |
n:ul:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Line Voltage |
n:ulpc:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | % | Line-Line Voltage |
n:Ul:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Line-Line Voltage |
n:u0:bushvor :busmv, :buslv | p.u. | Zero-Sequence-Voltage |
n:U0:bushvor :busmv, :buslv | kV | Zero-Sequence-Voltage |
n:U0x3:bushvor :busmv, :buslv | kV | 3*U0 |
n:u1:bushvor :busmv, :buslv | p.u. | Voltage Phasor, Magnitude |
n:u1pc:bushvor :busmv, :buslv | % | Voltage Phasor, Magnitude |
n:u1r:bushvor :busmv, :buslv | p.u. | Voltage Phasor, Real Part |
n:u1i:bushvor :busmv, :buslv | p.u. | Voltage Phasor, Imaginary Part |
n:U1:bushvor :busmv, :buslv | kV | Voltage Phasor, Magnitude |
n:phiu1:bushvor :busmv, :buslv | deg | Voltage Phasor, Angle |
n:U1l:bushvor :busmv, :buslv | kV | Line-Line Voltage Phasor, Magnitude |
n:uln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Line-Neutral Voltage |
n:Uln:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kV | Line-Neutral Voltage |
n:un:bushvor :busmv, :buslv | p.u. | Neutral-Ground Voltage |
n:Un:bushvor :busmv, :buslv | kV | Neutral-Ground Voltage |
n:ishc:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | p.u. | Short-Circuit Current |
n:Ishc:bushv:Aor :busmv, :buslv; per phase :A, :B, :C, unbalanced only | kA | Short-Circuit Current |
n:inshc:bushvor :busmv, :buslv | p.u. | Neutral Short-Circuit Current, magnitude |
n:Inshc:bushvor :busmv, :buslv | kA | Neutral Short-Circuit Current, magnitude |
n:fe:bushvor :busmv, :buslv | p.u. | Electrical Frequency |
n:dfehz:bushvor :busmv, :buslv | Hz | Deviation of the El. Frequency |
n:fehz:bushvor :busmv, :buslv | Hz | Electrical Frequency |
n:frnom:bushvor :busmv, :buslv | Hz | Nominal Frequency |
s:nntapin_h | ยท | Tap (HV), Controller Input |
s:nntapin_m | ยท | Tap (MV), Controller Input |
s:nntapin_l | ยท | Tap (LV), Controller Input |
s:psim | p.u. | Magnetising flux |
s:psim_0 | p.u. | Magnetising flux, zero-sequence |
s:i0_h | p.u. | 0-Current in Delta-Winding (HV) |
s:i0_m | p.u. | 0-Current in Delta-Winding (MV) |
s:i0_l | p.u. | 0-Current in Delta-Winding (LV) |
s:psim_r | p.u. | Magnetising Flux (Real Part) |
s:psim_i | p.u. | Magnetising Flux (Imaginary Part) |
s:I0Delta_h | kA | Circulating current in HV-D-Winding |
s:I0Delta_m | kA | Circulating current in MV-D-Winding |
s:I0Delta_l | kA | Circulating current in LV-D-Winding |
s:psim_a | p.u. | Magnetising Flux |
s:psim_b | p.u. | Magnetising Flux |
s:psim_c | p.u. | Magnetising Flux |
s:iha | p.u. | Inductive Current, HV |
s:ihb | p.u. | Inductive Current, HV |
s:ih0 | p.u. | Inductive Current, HV |
s:ima | p.u. | Inductive Current, MV |
s:imb | p.u. | Inductive Current, MV |
s:im0 | p.u. | Inductive Current, MV |
s:ila | p.u. | Inductive Current, LV |
s:ilb | p.u. | Inductive Current, LV |
s:il0 | p.u. | Inductive Current, LV |
ElmTr3 dc load flow results
Read after ComLdf (DC) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).
| Attribute | Unit | Description |
|---|---|---|
m:P:bushvor :busmv, :buslv | MW | Active Power |
m:Q:bushvor :busmv, :buslv | Mvar | Reactive Power |
c:loading_h | % | Loading (HV) |
c:loading_m | % | Loading (MV) |
c:loading_l | % | Loading (LV) |
c:loading | % | Maximum Loading |
c:maxload | % | Max. Loading |
c:n3tap_h | ยท | Current Tap Position (HV) |
c:n3tap_m | ยท | Current Tap Position (MV) |
c:n3tap_l | ยท | Current Tap Position (LV) |
c:nntap_int_h | ยท | Tap (HV), relative Position |
c:nntap_int_m | ยท | Tap (MV), relative Position |
c:nntap_int_l | ยท | Tap (LV), relative Position |
c:t_h | ยท | Complex Winding Ratio (HV/S) |
c:t_m | ยท | Complex Winding Ratio (MV/S) |
c:t_l | ยท | Complex Winding Ratio (LV/S) |
c:i_uplim | ยท | Tap at Maximum |
c:i_lowlim | ยท | Tap at Minimum |
c:w_0 | ยท | Nominal winding ratio |
c:Ploss | MW | Losses (total) |
c:Qloss | Mvar | Reactive-Losses (total) |
c:Pmeas | MW | Measured active power, Controller 1 |
c:i_fixedtap | ยท | Flag |
c:zs_h | p.u. | Short Circuit Impedance (HV) |
c:zs_m | p.u. | Short Circuit Impedance (MV) |
c:zs_l | p.u. | Short Circuit Impedance (LV) |
c:Pmeas2 | MW | Measured active power, Controller 2 |
c:maxloadpu | p.u. | Max. Loading |
c:dphiu_hm | deg | Voltage Drop Angle (HV-MV) |
c:dphiu_hl | deg | Voltage Drop Angle (HV-LV) |
c:dphiu_ml | deg | Voltage Drop Angle (MV-LV) |
n:u:bushvor :busmv, :buslv | p.u. | Voltage, Magnitude |
n:upc:bushvor :busmv, :buslv | % | Voltage, Magnitude |
n:U:bushvor :busmv, :buslv | kV | Line-Ground Voltage, Magnitude |
n:phiu:bushvor :busmv, :buslv | deg | Voltage, Angle |
n:phiurel:bushvor :busmv, :buslv | deg | Voltage, Relative Angle |
n:Ul:bushvor :busmv, :buslv | kV | Line-Line Voltage, Magnitude |
n:u1:bushvor :busmv, :buslv | p.u. | Voltage, Magnitude |
n:Pgen:bushvor :busmv, :buslv | MW | Generation, Active Power |
n:Pmot:bushvor :busmv, :buslv | MW | Motor Load, Active Power |
n:Pload:bushvor :busmv, :buslv | MW | General Load, Active Power |
n:Pcomp:bushvor :busmv, :buslv | MW | Compensation (Losses) |
n:Pnet:bushvor :busmv, :buslv | MW | External Networks, Active Power |
n:Pflow:bushvor :busmv, :buslv | MW | Power Flow, Active Power |
s:nt_in_h | ยท | Tap Position (HV), Input |
s:nt_in_m | ยท | Tap Position (MV), Input |
s:nt_in_l | ยท | Tap Position (LV), Input |
ElmTr3 modal analysis results
Read after ComMod with GetAttribute. c: calculation parameter, s: signal (state or model variable).
| Attribute | Unit | Description |
|---|---|---|
c:loading_h | % | Loading (HV) |
c:loading_m | % | Loading (MV) |
c:loading_l | % | Loading (LV) |
c:loading | % | Maximum Loading |
c:n3tap_h | ยท | Current Tap Position (HV) |
c:n3tap_m | ยท | Current Tap Position (MV) |
c:n3tap_l | ยท | Current Tap Position (LV) |
c:nntap_int_h | ยท | Tap (HV), relative Position |
c:nntap_int_m | ยท | Tap (MV), relative Position |
c:nntap_int_l | ยท | Tap (LV), relative Position |
c:ym | p.u. | Magnetising Admittance |
c:t_h | ยท | Complex Winding Ratio (HV/S) |
c:t_m | ยท | Complex Winding Ratio (MV/S) |
c:t_l | ยท | Complex Winding Ratio (LV/S) |
c:i3loc | ยท | Position of Magn.ind. |
c:w_0 | ยท | Nominal winding ratio |
c:isat | ยท | Saturated Model |
c:Inom_HV | kA | Nominal Current (HV-Side) |
c:Inom_MV | kA | Nominal Current (MV-Side) |
c:Inom_LV | kA | Nominal Current (LV-Side) |
c:iAutoTap | ยท | Controller Mode |
c:zs_h | p.u. | Short Circuit Impedance (HV) |
c:zs_m | p.u. | Short Circuit Impedance (MV) |
c:zs_l | p.u. | Short Circuit Impedance (LV) |
c:yg_hv | p.u. | Parasitic Admittance (HV-Side) |
c:yg_mv | p.u. | Parasitic Admittance (MV-Side) |
c:yg_lv | p.u. | Parasitic Admittance (LV-Side) |
c:yc1_lh | p.u. | LV-HV Coupling-Admittance (normalised on HV-Side) |
c:yc1_hm | p.u. | HV-MV Coupling-Admittance (normalised on HV-Side) |
c:yc1_ml | p.u. | MV-LV Coupling-Admittance (normalised on HV-Side) |
s:nntapin_h | ยท | Tap (HV), Controller Input |
s:nntapin_m | ยท | Tap (MV), Controller Input |
s:nntapin_l | ยท | Tap (LV), Controller Input |
ElmTr3 optimal power flow results
Read after ComOpf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.
| Attribute | Unit | Description |
|---|---|---|
m:urnet:bushvor :busmv, :buslv | p.u. | Voltage, Real Part, referred to network |
m:uinet:bushvor :busmv, :buslv | p.u. | Voltage, Imaginary Part, referred to network |
m:u1r:bushvor :busmv, :buslv | p.u. | Positive-Sequence-Voltage, Real Part |
m:u1i:bushvor :busmv, :buslv | p.u. | Positive-Sequence-Voltage, Imaginary Part |
m:u1:bushvor :busmv, :buslv | p.u. | Positive-Sequence-Voltage, Magnitude |
m:U1:bushvor :busmv, :buslv | kV | Line-Ground Positive-Sequence-Voltage, Magnitude |
m:U1l:bushvor :busmv, :buslv | kV | Line-Line Positive-Sequence-Voltage, Magnitude |
m:phiu1:bushvor :busmv, :buslv | deg | Positive-Sequence-Voltage, Angle |
m:irnet:bushvor :busmv, :buslv | p.u. | Current, Real Part, referred to network |
m:iinet:bushvor :busmv, :buslv | p.u. | Current, Imaginary Part, referred to network |
m:inet:bushvor :busmv, :buslv | p.u. | Current, Magnitude, referred to network |
m:I:bushvor :busmv, :buslv | kA | Current, Magnitude |
m:phii:bushvor :busmv, :buslv | deg | Current, Angle |
m:i1r:bushvor :busmv, :buslv | p.u. | Positive-Sequence Current, Real Part |
m:i1i:bushvor :busmv, :buslv | p.u. | Positive-Sequence Current, Imaginary Part |
m:i1:bushvor :busmv, :buslv | p.u. | Positive-Sequence Current, Magnitude |
m:I1:bushvor :busmv, :buslv | kA | Positive-Sequence Current, Magnitude |
m:phii1:bushvor :busmv, :buslv | deg | Positive-Sequence Current, Angle |
m:P:bushvor :busmv, :buslv | MW | Active Power |
m:Q:bushvor :busmv, :buslv | Mvar | Reactive Power |
m:S:bushvor :busmv, :buslv | MVA | Apparent Power |
m:cosphi:bushvor :busmv, :buslv | ยท | Power Factor |
m:tanphi:bushvor :busmv, :buslv | ยท | tan(phi) |
m:Psum:bushvor :busmv, :buslv | MW | Total Active Power |
m:Qsum:bushvor :busmv, :buslv | Mvar | Total Reactive Power |
m:Ssum:bushvor :busmv, :buslv | MVA | Total Apparent Power |
m:cosphisum:bushvor :busmv, :buslv | ยท | Total Power Factor |
m:tanphisum:bushvor :busmv, :buslv | ยท | Total tan(phi) |
m:i1P:bushvor :busmv, :buslv | p.u. | Positive-Sequence Active Current |
m:i1Q:bushvor :busmv, :buslv | p.u. | Positive-Sequence Reactive Current |
m:I1P:bushvor :busmv, :buslv | kA | Positive-Sequence Active Current |
m:I1Q:bushvor :busmv, :buslv | kA | Positive-Sequence Reactive Current |
m:ur:bushvor :busmv, :buslv | p.u. | Voltage, Real Part |
m:ui:bushvor :busmv, :buslv | p.u. | Voltage, Imaginary Part |
m:u:bushvor :busmv, :buslv | p.u. | Voltage, Magnitude |
m:ir:bushvor :busmv, :buslv | p.u. | Current, Real Part |
m:ii:bushvor :busmv, :buslv | p.u. | Current, Imaginary Part |
m:i:bushvor :busmv, :buslv | p.u. | Current, Magnitude |
m:phiui:bushvor :busmv, :buslv | deg | Angle between Voltage and Current |
m:phiu1i1:bushvor :busmv, :buslv | deg | Angle between Voltage and Current in positive sequence system |
m:Tfct:bushvor :busmv, :buslv | s | Fault Clearing Time |
m:Brkload:bushvor :busmv, :buslv | % | Breaker Loading |
m:Spu:bushvor :busmv, :buslv | MVA/p.u. | Apparent Power per p.u. Voltage |
c:loading_h | % | Loading (HV) |
c:loading_m | % | Loading (MV) |
c:loading_l | % | Loading (LV) |
c:loading | % | Maximum Loading |
c:maxload | % | Max. Loading |
c:n3tap_h | ยท | Current Tap Position (HV) |
c:n3tap_m | ยท | Current Tap Position (MV) |
c:n3tap_l | ยท | Current Tap Position (LV) |
c:nntap_int_h | ยท | Tap (HV), relative Position |
c:nntap_int_m | ยท | Tap (MV), relative Position |
c:nntap_int_l | ยท | Tap (LV), relative Position |
c:ym | p.u. | Magnetising Admittance |
c:t_h | ยท | Complex Winding Ratio (HV/S) |
c:t_m | ยท | Complex Winding Ratio (MV/S) |
c:t_l | ยท | Complex Winding Ratio (LV/S) |
c:i_uplim | ยท | Tap at Maximum |
c:i_lowlim | ยท | Tap at Minimum |
c:nCtrlIter | ยท | No. of CTRL-iterations |
c:itrcn | ยท | Flag f. auto. Tap |
c:i3loc | ยท | Position of Magn.ind. |
c:um_1 | ยท | Magnetising Flux |
c:w_0 | ยท | Nominal winding ratio |
c:Gmload | kW | Iron Losses |
c:Xmload | kvar | Magnetising Losses |
c:Ploss | MW | Losses (total) |
c:Qloss | Mvar | Reactive-Losses (total) |
c:Plossld | MW | Losses (load) |
c:Qlossld | Mvar | Reactive-Losses (load) |
c:Plossnld | MW | Losses (no load) |
c:Qlossnld | Mvar | Reactive-Losses (no load) |
c:Pmeas | MW | Measured active power, Controller 1 |
c:i_fixedtap | ยท | Flag |
c:isat | ยท | Saturated Model |
c:Inom_HV | kA | Nominal Current (HV-Side) |
c:Inom_MV | kA | Nominal Current (MV-Side) |
c:Inom_LV | kA | Nominal Current (LV-Side) |
c:zs_h | p.u. | Short Circuit Impedance (HV) |
c:zs_m | p.u. | Short Circuit Impedance (MV) |
c:zs_l | p.u. | Short Circuit Impedance (LV) |
c:Pmeas2 | MW | Measured active power, Controller 2 |
c:ctrl_set | ยท | cc0_ml |
c:ctrl_set2 | ยท | cc0_ml |
c:maxloadpu | p.u. | Max. Loading |
c:u_h | ยท | Internal |
c:u_m | ยท | Internal |
c:u_l | ยท | Internal |
c:dphiu_hm | deg | Voltage Drop Angle (HV-MV) |
c:dphiu_hl | deg | Voltage Drop Angle (HV-LV) |
c:dphiu_ml | deg | Voltage Drop Angle (MV-LV) |
c:tapHvTarget | ยท | Tap - target value (HV) |
c:tapMvTarget | ยท | Tap - target value (MV) |
c:tapLvTarget | ยท | Tap - target value (LV) |
c:totPenaltyCosts | USD | Total penalty costs |
c:totTapDeviation | ยท | Total tap deviation |
c:totPenaltyCostsHV | USD | Total penalty costs (HV) |
c:totPenaltyCostsMV | USD | Total penalty costs (MV) |
c:totPenaltyCostsLV | USD | Total penalty costs (LV) |
c:totTapDeviationHV | ยท | Total tap deviation (HV) |
c:totTapDeviationMV | ยท | Total tap deviation (MV) |
c:totTapDeviationLV | ยท | Total tap deviation (LV) |
c:yg_hv | p.u. | Parasitic Admittance (HV-Side) |
c:yg_mv | p.u. | Parasitic Admittance (MV-Side) |
c:yg_lv | p.u. | Parasitic Admittance (LV-Side) |
c:yc1_lh | p.u. | LV-HV Coupling-Admittance (normalised on HV-Side) |
c:yc1_hm | p.u. | HV-MV Coupling-Admittance (normalised on HV-Side) |
c:yc1_ml | p.u. | MV-LV Coupling-Admittance (normalised on HV-Side) |
n:ur:bushvor :busmv, :buslv | p.u. | Voltage, Real Part |
n:ui:bushvor :busmv, :buslv | p.u. | Voltage, Imaginary Part |
n:u:bushvor :busmv, :buslv | p.u. | Voltage, Magnitude |
n:upc:bushvor :busmv, :buslv | % | Voltage, Magnitude |
n:du:bushvor :busmv, :buslv | % | Voltage Deviation |
n:U:bushvor :busmv, :buslv | kV | Line-Ground Voltage, Magnitude |
n:phiu:bushvor :busmv, :buslv | deg | Voltage, Angle |
n:phiurel:bushvor :busmv, :buslv | deg | Voltage, Relative Angle |
n:Ul:bushvor :busmv, :buslv | kV | Line-Line Voltage, Magnitude |
n:u1:bushvor :busmv, :buslv | p.u. | Voltage, Magnitude |
n:u1pc:bushvor :busmv, :buslv | % | Voltage, Magnitude |
n:u1r:bushvor :busmv, :buslv | p.u. | Positive-Sequence Voltage, Real Part |
n:u1i:bushvor :busmv, :buslv | p.u. | Positive-Sequence Voltage, Imaginary Part |
n:Pgen:bushvor :busmv, :buslv | MW | Generation, Active Power |
n:Qgen:bushvor :busmv, :buslv | Mvar | Generation, Reactive Power |
n:Pmot:bushvor :busmv, :buslv | MW | Motor Load, Active Power |
n:Qmot:bushvor :busmv, :buslv | Mvar | Motor Load, Reactive Power |
n:Pload:bushvor :busmv, :buslv | MW | General Load, Active Power |
n:Qload:bushvor :busmv, :buslv | Mvar | General Load, Reactive Power |
n:Pcomp:bushvor :busmv, :buslv | MW | Compensation (Losses) |
n:Qcomp:bushvor :busmv, :buslv | Mvar | Compensation |
n:Pnet:bushvor :busmv, :buslv | MW | External Networks, Active Power |
n:Qnet:bushvor :busmv, :buslv | Mvar | External Networks, Reactive Power |
n:Pflow:bushvor :busmv, :buslv | MW | Power Flow, Active Power |
n:Qflow:bushvor :busmv, :buslv | Mvar | Power Flow, Reactive Power |
n:Pout:bushvor :busmv, :buslv | MW | Outgoing Flow, Active Power |
n:Qout:bushvor :busmv, :buslv | Mvar | Outgoing Power, Reactive Power |
n:Sout:bushvor :busmv, :buslv | MVA | Outgoing Power, Apparent Power |
n:cosphiout:bushvor :busmv, :buslv | ยท | Outgoing Power, Power Factor |
n:Pbalance:bushvor :busmv, :buslv | MW | Active Power Balance (=0) |
n:Qbalance:bushvor :busmv, :buslv | Mvar | Reactive Power Balance (=0) |
n:LossPdown:bushvor :busmv, :buslv | MW | Losses, downstream |
n:LossQdown:bushvor :busmv, :buslv | Mvar | Losses, downstream (Reactive Power) |
n:LossPdownload:bushvor :busmv, :buslv | MW | Load losses, downstream |
n:LossQdownload:bushvor :busmv, :buslv | Mvar | Load losses, downstream |
n:LossPdownnoload:bushvor :busmv, :buslv | MW | No load losses, downstream |
n:LossQdownnoload:bushvor :busmv, :buslv | Mvar | No load losses, downstream |
n:du_feed:bushvor :busmv, :buslv | % | Difference from voltage at start of feeder |
ElmTr3 basic data
b: values are worked out from the input data. Read them; they are not set.
| Attribute | Unit | Description |
|---|---|---|
b:loc_name | ยท | Name |
b:nt2ag | ยท | Rel.Phase Displacement |
b:ntrcn | ยท | Automatic Tap-Changer on/off |
b:i_cont | ยท | Continuous Tap |
b:itrcn:Aper phase :A, :B, :C, unbalanced only | ยท | isat |
b:icont:Aper phase :A, :B, :C, unbalanced only | ยท | nt3ag_h |
b:iExtCtrl:Aper phase :A, :B, :C, unbalanced only | ยท | External Controlled |
b:isat | ยท | ipsu |
b:nt3ag_h | ยท | Rel.Phase Displacement |
b:nt3ag_m | ยท | Rel.Phase Displacement |
b:nt3ag_l | ยท | Rel.Phase Displacement |
b:ipsu:Aper phase :A, :B, :C, unbalanced only | ยท | Power Station Unit |