ElmTr2 attributesPowerFactory 2-Winding Transformer

Every attribute of the PowerFactory 2-Winding Transformer (ElmTr2): 242 input parameters and 1088 result variables, with units and meaning. Copy a name into GetAttribute or SetAttribute.

What ElmTr2 is

A two-winding transformer between an HV and an LV terminal. Rating, impedance and tap changer data sit in its type (TypTr2); the element holds the tap position and the number of parallel units.

Class
ElmTr2, element class
PowerFactory name
2-Winding Transformer
Type
TypTr2, through typ_id
Terminal suffix
:bushv hv-side, :buslv lv-side
Attributes
242 input parameters and 1088 result variables, in 7 calculations

Most used ElmTr2 attributes

AttributeUnitDescriptionWhere
c:loading%LoadingLoad flow
m:P:bushvMWActive Poweractive power at the HV sideLoad flow
m:Q:bushvMvarReactive PowerLoad flow
m:I:buslvkACurrent, Magnitudecurrent at the LV sideLoad flow
c:PlossMWLosses (total)Load flow
nntapยทTap Positiontap position (input)input data
c:nntapยทTap 1, Current Positiontap position after the load flowLoad flow
ntnumยทparallel Transformersinput data
outservยทOut of Serviceinput data
typ_idยทTypeinput data

Read and write ElmTr2 in Python

import powerfactory

app = powerfactory.GetApplication()          # GetApplicationExt() from outside PowerFactory
app.GetFromStudyCase("ComLdf").Execute()      # results exist after a calculation

for trafo in app.GetCalcRelevantObjects("*.ElmTr2"):
    loading = trafo.GetAttribute("c:loading")     # Loading, %
    p_bushv = trafo.GetAttribute("m:P:bushv")     # Active Power, MW
    print(trafo.loc_name, loading, p_bushv)

trafo = app.GetCalcRelevantObjects("*.ElmTr2")[0]
trafo.SetAttribute("nntap", 2)                # move the tap to position 2
  • A result at a terminal of the 2-winding transformer needs the terminal in its name: m:P:bushv, not m:P, which raises AttributeError.
  • An input parameter is read and written with or without its e: prefix: GetAttribute("outserv") and GetAttribute("e:outserv") give the same value.
  • RMS and EMT variables change over time: record them in a results object (ElmRes) to read the whole curve. GetAttribute after a run gives the value at the last time step.

ElmTr2 input parameters

The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.

AttributeUnitDescription
loc_nameยทName
chr_nameยทCharacteristic Name
for_nameยทForeign Key
dat_srcยทData source
imldcยทControl Mode
imldc2ยทControl Mode
sernumยทSerial Number
commissionDateยทCommissioning Date
appr_modbyยทModified by
outservยทOut of Service
iZoneBusยทZone
iAreaBusยทArea
lossAssignยทLoss assignment
ntnumยทparallel Transformers
nntapยทTap Position
optaplimitยทOperational limits for tap changer
optapminยทMinimum Position
optapmaxยทMaximum Position
optap2minยทMinimum Position
optap2maxยทMaximum Position
t2ldcยทControlled Node is at
ilcphยทPhase
ntrcnยทAutomatic Tap Changing
ildcยทCompensation
icompยทCompounding
i_contยทTap Changer
uset_modeยทSetpoint
iPpartยทActive power participation
ntrcn2ยทAutomatic Tap Changing
i_cont2ยทTap Changer
t2ldc2ยทControlled Node is at
i_rem2ยทRemote Control
iopt_hfยทConsider Capacitances
ifcยทForced Cooling Enabled
i_remยทRemote Control
i_autoยทAuto Transformer
i_eahvยทHV-side, phase 2 internally grounded
i_ealvยทLV-side, phase 2 internally grounded
iintgndยทNeutral Connection
i_hvconยทHV-side, phase 2 connected
i_lvconยทLV-side, phase 2 connected
constrยทYear of Construction
appr_statusยทStatus
nntap2ยทTap Position
iperfectยทIdeal component
iTapsยทAccording to Measurement Report
iMeasLocยทMeasured at
i_uoptยทTap Changer 1
ionlyPreยทOptimise in DC OPF
i_uoptContยทControl Mode
iOPFCloadยทMax. loading constraint
isCtrlTapยทTap Changer 1
isCtrlTapContยทControl Mode
isConstrLoadingยทMax. loading constraint for Unit Commitment
isMaxLoadSoftNlinยทPenalty costs for soft constraints
allowOutDistFacFiltยทAllow filtering by outage distribution factor
allowMarginFiltยทAllow filtering by constraint margin
allowCntConstrFiltยทAllow contingency filtering by number of critical constraints
isSepCntConstrTypeยทSeparate constraint type
cntConstrTypeยทContingency-constraint type
isSepCntMaxAllowedLoadingยทSeparate max. allowed loading
ctrlUsageยทTap Changer 1
curativeLimยทMax. curative tap deviation
isConstrLoadingPlacementยทMax. loading constraint for Optimal Equipment Placement
isCtrlTapPlacementยทPosition of tap 1
iblockยทUnit Transformer
ilt_opยทLong-term operating conditions before short-circuit are known
i_tapiniยทEstimate Tap 1 Position
iIntTapCtrlยทUse Integrated Tap Controller
ifrqftยทFrequent Fault ( >10(5)/lifetime, Category II(III) )
iansishยทANSI Curve Shift
drawInrยทDraw Inrush Current
fr_coldloadยทCold load curve
iAstabintยทA-stable integration algorithm
iResFluxยทResidual flux
ldcctACurrent Transformer Rating
ldcptยทVoltage Transformer Ratio
ldcrsVRset
ldcxsVXset
ratfacยทRating Factor
Vtolerance%Tolerance (+/-)
usetpp.u.Voltage Setpoint
psetpMWActive Power Setpoint
qsetpMvarReactive Power Setpoint
usp_upp.u.Upper Voltage Bound
usp_lowp.u.Lower Voltage Bound
psp_upMWUpper Active Power Bound
psp_lowMWLower Active Power Bound
PtoleranceMWTolerance (+/-)
qsp_upMvarUpper Reactive Power Bound
qsp_lowMvarLower Reactive Power Bound
KpartยทParticipation factor
re0tr_hOhmResistance, Re
xe0tr_hOhmReactance, Xe
re0tr_lOhmResistance, Re
xe0tr_lOhmReactance, Xe
Cg_huFCapacitance HV-Ground
Cg_luFCapacitance LV-Ground
Cc1_hluFCapacitance HV-LV, 1-Sequence
Cc0_hluFCapacitance HV-LV, 0-Sequence
maxload%Max. loading
Ub_lvkVHighest Operating Voltage
Ib_lvkAHighest Operating Current
cosphib_lvยทPower factor
Ubqmin_hvkVMinimum Operating Voltage
TctrlsController Time Constant
Tctrl2sController Time Constant
Kqctrltap/MvarController Sensitivity dtap/dQ
Kpctrltap/MWController Sensitivity dtap/dP
PsiresAp.u.Phase A
PsiresBp.u.Phase B
PsiresCp.u.Phase C
GPSlatdegLatitude / Northing
GPSlondegLongitude / Easting
scalingFacSoftConstrOpfยทWeighting factor for soft constraint penalty
scalingFacSoftConstrCostยทCost scaling factor
cntMaxAllowedLoading%Max. allowed loading in Contingencies
penaltyCostsUSDPenalty costs per tap deviation
curativeCostsUSDCosts per curative tap deviation
dpl1ยทdpl1
dpl2ยทdpl2
dpl3ยทdpl3
dpl4ยทdpl4
dpl5ยทdpl5
appr_modifยทModified
mTapsยทMeasurement Report
coldloadtab2ยทValues
cimRdfIdยทRDF ID
descยทDescription
sOpCommentยทOperator Comment
fold_idยทIn Folder
typ_idยทTypeObject: TypTr2
bushvยทHV-SideObject: StaCubic
buslvยทLV-SideObject: StaCubic
bushvnยทHV-NeutralObject: StaCubic
buslvnยทLV-NeutralObject: StaCubic
pVccurveยทV-Control-CurveObject: IntVctrlcurve
p_pmeasยทP measured atObject: StaCubic,ElmBoundary
p_cub2ยทControlled Branch (Cubicle)Object: StaCubic,ElmBoundary
tapctrlยทTap ControllerObject: ElmTr2*
p_remยทControlled NodeObject: ElmTerm,StaBar
p_cubยทControlled Branch (Cubicle)Object: StaCubic,ElmBoundary
doc_idยทAdditional Data
pOwnerยทOwnerObject: ElmOwner
pOperatorยทOperatorObject: ElmOperator
pStochStoTyptrfElement model
pldcยทExternal LDCObject: StaLdc
pRatingยทThermal RatingObject: IntThrating
cpHeadFoldยทHead Folder
bushv_barยทHV-Side
buslv_barยทLV-Side
bushvn_barยทHV-Neutral
buslvn_barยทLV-Neutral
cpGridยทGridObject: ElmNet
cpZoneยทZoneObject: ElmZone
cpAreaยทAreaObject: ElmArea
cpFeedยทFeederObject: ElmFeeder
ciDistยทDistance from infeed in number of buses
ciLaterยทLateral Index
ciDistRootยทDistance from first infeed in number of buses
ciDistAllยทDistance from infeed in number of buses including switches
ciDistAllRootยทDistance from first infeed in number of buses including switches
cpOwnerยทOwnerObject: ElmOwner
cpOperatorยทOperatorObject: ElmOperator
cpBranchยทBranchObject: ElmBranch
cpSiteยทSiteObject: ElmSite
cpSubstatยทSubstationObject: ElmSubstat,ElmTrfstat
cpMeteostatยทMeteo StationObject: ElmMeteostat
ciOutagedยทPlanned Outage
ciEnergizedยทEnergized
ciEarthedยทEarthed
cDisplayNameยทDisplay Name
cpSupplyTransformerยทSupplying TransformerObject: ElmTr?,ElmTrmult
cpSupplyTrfStationยทSupplying Secondary SubstationObject: ElmTrfstat
cpSupplySubstationยทSupplying SubstationObject: ElmSubstat
cpCtrlNodeยทTarget NodeObject: ElmTerm
cpCtrlNode2ยทTarget NodeObject: ElmTerm
uset_mode2ยทSetpoint
ilcph2ยทPhase
p_rem2ยทControlled NodeObject: ElmTerm,StaBar
iPpart2ยทActive power participation
Kpart2ยทParticipation factor
Ptolerance2MWTolerance (+/-)
p_pmeas2ยทP measured atObject: StaCubic,ElmBoundary
usetp2p.u.Voltage Setpoint
usp_low2p.u.Lower Voltage Bound
usp_up2p.u.Upper Voltage Bound
psetp2MWActive Power Setpoint
psp_low2MWLower Active Power Bound
psp_up2MWUpper Active Power Bound
qsetp2MvarReactive Power Setpoint
qsp_low2MvarLower Reactive Power Bound
qsp_up2MvarUpper Reactive Power Bound
Kqctrl2tap/MvarController Sensitivity dtap/dQ
Kpctrl2tap/MWController Sensitivity dtap/dP
ildc2ยทCompensation
pldc2ยทExternal LDCObject: StaLdc
ldcct2ACurrent Transformer Rating
ldcpt2ยทVoltage Transformer Ratio
ldcrs2VRset
ldcxs2VXset
icomp2ยทCompounding
Vtolerance2%Tolerance (+/-)
pVccurve2ยทV-Control-CurveObject: IntVctrlcurve
cgnd_hยทStar Point
cgnd_lยทStar Point
cpeter_hยทPetersen Coil
cpeter_lยทPetersen Coil
neutConfigยทN-Connection
neutSeparateยทSeparate N-connection
FOR11/aForced Outage Rate
FOEh/aForced Outage Expectancy
FODhForced Outage Duration
pTypStochStoTyptrfType model
rSbasepup.u.r (Sbase)
xSbasepup.u.x (Sbase)
bSbasepup.u.b (Sbase)
r0Sbasepup.u.r0 (Sbase)
x0Sbasepup.u.x0 (Sbase)
Inom_hkAHV-Side, Nominal Current
Inom_lkALV-Side, Nominal Current
Inom_h_akAHV-Side, Nominal Current (act.)
Inom_l_akALV-Side, Nominal Current
SnomMVANominal Power
Snom_aMVANominal Power (act.)
cCtrlTapContOpfยทControl Mode
cOptOnlyPreยทOptimise in DC OPF
cCtrlTapContยทControl Mode
cAllowOutDistFacFiltยทAllow filtering by outage distribution factor
cAllowMarginFiltยทAllow filtering by constraint margin
cAllowCntConstrFiltยทAllow contingency filtering by number of critical constraints
cIsSepCntConstrTypeยทSeparate constraint type
cIsSepCntMaxAllowedLoadingยทSeparate max. allowed loading
cCtrlUsageยทTap Changer 1
CCEarFr1/aFrequency of single earth faults
CCEarRepMuhRepair duration
CCEarProb%Conditional probability of a second earth fault
c_pstacยทExternal Station ControllerObject: ElmStactrl
c_ptapcยทExternal Tap ControllerObject: ElmTapctrl
c_plccยทExternal LCC ControllerObject: StaLdc
qdslCtrlยทQuasi-Dynamic ModelObject: ElmQdsl
cPsiresCp.u.Phase C

ElmTr2 load flow results

Read after ComLdf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bushvor :buslvp.u.Voltage, Real Part, referred to network
m:uinet:bushvor :buslvp.u.Voltage, Imaginary Part, referred to network
m:u1r:bushvor :buslvp.u.Positive-Sequence-Voltage, Real Part
m:u1i:bushvor :buslvp.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bushvor :buslvp.u.Positive-Sequence-Voltage, Magnitude
m:U1:bushvor :buslvkVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bushvor :buslvkVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bushvor :buslvdegPositive-Sequence-Voltage, Angle
m:irnet:bushvor :buslvp.u.Current, Real Part, referred to network
m:iinet:bushvor :buslvp.u.Current, Imaginary Part, referred to network
m:inet:bushvor :buslvp.u.Current, Magnitude, referred to network
m:I:bushvor :buslvkACurrent, Magnitude
m:phii:bushvor :buslvdegCurrent, Angle
m:i1r:bushvor :buslvp.u.Positive-Sequence Current, Real Part
m:i1i:bushvor :buslvp.u.Positive-Sequence Current, Imaginary Part
m:i1:bushvor :buslvp.u.Positive-Sequence Current, Magnitude
m:I1:bushvor :buslvkAPositive-Sequence Current, Magnitude
m:phii1:bushvor :buslvdegPositive-Sequence Current, Angle
m:P:bushvor :buslvMWActive Power
m:Q:bushvor :buslvMvarReactive Power
m:S:bushvor :buslvMVAApparent Power
m:cosphi:bushvor :buslvยทPower Factor
m:tanphi:bushvor :buslvยทtan(phi)
m:Psum:bushvor :buslvMWTotal Active Power
m:Qsum:bushvor :buslvMvarTotal Reactive Power
m:Ssum:bushvor :buslvMVATotal Apparent Power
m:cosphisum:bushvor :buslvยทTotal Power Factor
m:tanphisum:bushvor :buslvยทTotal tan(phi)
m:i1P:bushvor :buslvp.u.Positive-Sequence Active Current
m:i1Q:bushvor :buslvp.u.Positive-Sequence Reactive Current
m:I1P:bushvor :buslvkAPositive-Sequence Active Current
m:I1Q:bushvor :buslvkAPositive-Sequence Reactive Current
m:ur:bushvor :buslvp.u.Voltage, Real Part
m:ui:bushvor :buslvp.u.Voltage, Imaginary Part
m:u:bushvor :buslvp.u.Voltage, Magnitude
m:ir:bushvor :buslvp.u.Current, Real Part
m:ii:bushvor :buslvp.u.Current, Imaginary Part
m:i:bushvor :buslvp.u.Current, Magnitude
m:phiui:bushvor :buslvdegAngle between Voltage and Current
m:phiu1i1:bushvor :buslvdegAngle between Voltage and Current in positive sequence system
m:Tfct:bushvor :buslvsFault Clearing Time
m:Brkload:bushvor :buslv%Breaker Loading
m:Spu:bushvor :buslvMVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bushvor :buslvp.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bushvor :buslvdegZero-Sequence-Voltage, Angle
m:u2:bushvor :buslvp.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bushvor :buslvdegNegative-Sequence-Voltage, Angle
m:irnet:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part, referred to network
m:iinet:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part, referred to network
m:inet:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude, referred to network
m:I:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bushvor :buslvp.u.Zero-Sequence Current, Real Part
m:i0i:bushvor :buslvp.u.Zero-Sequence Current, Imaginary Part
m:i0:bushvor :buslvp.u.Zero-Sequence Current, Magnitude
m:I0:bushvor :buslvkAZero-Sequence Current, Magnitude
m:I0x3:bushvor :buslvkA3*I0
m:phii0:bushvor :buslvdegZero-Sequence Current, Angle
m:i2r:bushvor :buslvp.u.Negative-Sequence Current, Real Part
m:i2i:bushvor :buslvp.u.Negative-Sequence Current, Imaginary Part
m:i2:bushvor :buslvp.u.Negative-Sequence Current, Magnitude
m:I2:bushvor :buslvkANegative-Sequence Current, Magnitude
m:phii2:bushvor :buslvdegNegative-Sequence Current, Angle
m:ubfacI:bushvor :buslv%Current Unbalance Factor
m:ubfacS:bushvor :buslv%Power Unbalance Factor
m:P:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyยทPower Factor
m:tanphi:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyยทtan(phi)
m:Pln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bushvor :buslvMWPositive Sequence Active Power
m:Q1:bushvor :buslvMvarPositive Sequence Reactive Power
m:P2:bushvor :buslvMWNegative Sequence Active Power
m:Q2:bushvor :buslvMvarNegative Sequence Reactive Power
m:P0:bushvor :buslvMWZero Sequence Active Power
m:Q0:bushvor :buslvMvarZero Sequence Reactive Power
m:i2P:bushvor :buslvp.u.Negative-Sequence Active Current
m:i2Q:bushvor :buslvp.u.Negative-Sequence Reactive Current
m:I2P:bushvor :buslvkANegative-Sequence Active Current
m:I2Q:bushvor :buslvkANegative-Sequence Reactive Current
m:ur:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bushvor :buslvdegAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bushvor :buslvdegAngle between Voltage and Current in negative sequence system
m:TfctPh:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced only%Breaker Loading
c:loading_h%Loading (HV)
c:loading_l%Loading (LV)
c:loading%Loading
c:maxload%Max. Loading
c:nntapยทTap 1, Current Position
c:ntpmnยทTap 1, Min. Position
c:ntpmxยทTap 1, Max. Position
c:dutยทTap 1
c:phitrrdradTap 1
c:nt2agrdradPhase Angle
c:ratfacยทRating Factor
c:snomMVARated Power
c:zshvp.u.Leakage Impedance (HV-Side)
c:zslvp.u.Leakage Impedance (LV-Side)
c:ymp.u.Magnetising Admittance
c:thvยทComplex Winding Ratio HV
c:tlvยทComplex Winding Ratio LV
c:tap_sideยท0
c:tap_side2ยท0
c:nntap2ยทTap 2, Current Position
c:ntpmn2ยทTap 2, Min. Position
c:ntpmx2ยทTap 2, Max. Position
c:dut2ยทTap 2
c:phitrrd2radTap 2
c:PmeasMWMeasured active power
c:du_ldcp.u.LDC Input
c:ctrl_setยทSetpoint
c:i_uplimยทTap 1 at Maximum
c:i_lowlimยทTap 1 at Minimum
c:i_uplim2ยทTap 2 at Maximum
c:i_lowlim2ยทTap 2 at Minimum
c:nCtrlIterยทNo. of CTRL-iterations
c:w_0ยทNominal winding ratio
c:GmloadkWIron Losses
c:XmloadkvarMagnetising Losses
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:TctrlsController Time Constant
c:i_fixedtapยทFlag
c:isatยทSaturated Model
c:Inom_HVkANominal Current (HV-Side)
c:Inom_LVkANominal Current (LV-Side)
c:dup.u.Voltage Drop
c:dupc%Voltage Drop
c:dphiudegVoltage Drop Angle
c:du1p.u.Positive Sequence Voltage Drop
c:du1pc%Positive Sequence Voltage Drop
c:dphiu1degPositive Sequence Voltage Drop Angle
c:maxloadpup.u.Max. Loading
c:yg_hvp.u.Parasitic Admittance (HV-Side)
c:yg_lvp.u.Parasitic Admittance (LV-Side)
c:yc1p.u.Coupling-Admittance (normalised on HV-Side)
c:i_ea_hยทFlag
c:i_ea_lยทFlag
c:i_star_hยทFlag
c:i_star_lยทFlag
c:zs0hvp.u.Zero sequence short circuit imp. (HV)
c:zs0lvp.u.Zero sequence short circuit imp. (LV)
c:ym0p.u.Zero Sequence Magnetising Admittance
c:Ustar_hkVStar-Point Voltage (HV)
c:Ustar_lkVStar-Point Voltage (LV)
c:Istar_hkAStar-Point Current (HV)
c:Istar_lkAStar-Point Current (LV)
c:loading_st%Short Term Loading
c:du:Aper phase :A, :B, :C, unbalanced onlyp.u.Voltage Drop
c:dupc:Aper phase :A, :B, :C, unbalanced only%Voltage Drop
c:dphiu:Aper phase :A, :B, :C, unbalanced onlydegVoltage Drop Angle
c:tยทWinding Ratio
c:yc0p.u.Coupling-Admittance (0-Sys., normalised on HV-Side)
n:ur:bushvor :buslvp.u.Voltage, Real Part
n:ui:bushvor :buslvp.u.Voltage, Imaginary Part
n:u:bushvor :buslvp.u.Voltage, Magnitude
n:upc:bushvor :buslv%Voltage, Magnitude
n:du:bushvor :buslv%Voltage Deviation
n:U:bushvor :buslvkVLine-Ground Voltage, Magnitude
n:phiu:bushvor :buslvdegVoltage, Angle
n:phiurel:bushvor :buslvdegVoltage, Relative Angle
n:Ul:bushvor :buslvkVLine-Line Voltage, Magnitude
n:u1:bushvor :buslvp.u.Voltage, Magnitude
n:u1pc:bushvor :buslv%Voltage, Magnitude
n:u1r:bushvor :buslvp.u.Positive-Sequence Voltage, Real Part
n:u1i:bushvor :buslvp.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bushvor :buslvMWGeneration, Active Power
n:Qgen:bushvor :buslvMvarGeneration, Reactive Power
n:Pmot:bushvor :buslvMWMotor Load, Active Power
n:Qmot:bushvor :buslvMvarMotor Load, Reactive Power
n:Pload:bushvor :buslvMWGeneral Load, Active Power
n:Qload:bushvor :buslvMvarGeneral Load, Reactive Power
n:Pcomp:bushvor :buslvMWCompensation (Losses)
n:Qcomp:bushvor :buslvMvarCompensation
n:Pnet:bushvor :buslvMWExternal Networks, Active Power
n:Qnet:bushvor :buslvMvarExternal Networks, Reactive Power
n:Pflow:bushvor :buslvMWPower Flow, Active Power
n:Qflow:bushvor :buslvMvarPower Flow, Reactive Power
n:Pout:bushvor :buslvMWOutgoing Flow, Active Power
n:Qout:bushvor :buslvMvarOutgoing Power, Reactive Power
n:Sout:bushvor :buslvMVAOutgoing Power, Apparent Power
n:cosphiout:bushvor :buslvยทOutgoing Power, Power Factor
n:Pbalance:bushvor :buslvMWActive Power Balance (=0)
n:Qbalance:bushvor :buslvMvarReactive Power Balance (=0)
n:LossPdown:bushvor :buslvMWLosses, downstream
n:LossQdown:bushvor :buslvMvarLosses, downstream (Reactive Power)
n:LossPdownload:bushvor :buslvMWLoad losses, downstream
n:LossQdownload:bushvor :buslvMvarLoad losses, downstream
n:LossPdownnoload:bushvor :buslvMWNo load losses, downstream
n:LossQdownnoload:bushvor :buslvMvarNo load losses, downstream
n:du_feed:bushvor :buslv%Difference from voltage at start of feeder
n:ur:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bushvor :buslvp.u.Zero-Sequence Voltage, Magnitude
n:U0:bushvor :buslvkVZero-Sequence Voltage, Magnitude
n:U0x3:bushvor :buslvkV3*U0
n:phiu0:bushvor :buslvdegZero-Sequence Voltage, Angle
n:U1:bushvor :buslvkVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bushvor :buslvdegPositive-Sequence Voltage, Angle
n:u2:bushvor :buslvp.u.Negative-Sequence Voltage, Magnitude
n:U2:bushvor :buslvkVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bushvor :buslvdegNegative-Sequence Voltage, Angle
n:U1l:bushvor :buslvkVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bushvor :buslvkVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bushvor :buslvp.u.Neutral-Ground Voltage, Magnitude
n:Un:bushvor :buslvkVNeutral-Ground Voltage, Magnitude
n:phiun:bushvor :buslvdegNeutral-Ground Voltage, Angle
n:upht:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bushvor :buslvp.u.Average-Voltage, Magnitude
n:Um:bushvor :buslvkVAverage-Voltage, Magnitude
n:uphtmin:bushvor :buslvp.u.Minimum of Phase Technology dependent Voltage, Magnitude
n:uphtmax:bushvor :buslvp.u.Maximum of Phase Technology dependent Voltage, Magnitude
n:ubfac:bushvor :buslv%Unbalance Factor
s:nt_inยทTap 1, Input
s:nt2_inยทTap 2, Input

ElmTr2 short-circuit results

Read after ComShc with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:I:bushvor :buslvkAShort-Circuit Current, Magnitude
m:phii:bushvor :buslvdegPhase Current, Angle
m:i1:bushvor :buslvp.u.Positive-Sequence Current, Magnitude
m:I1:bushvor :buslvkAPositive-Sequence Current, Magnitude
m:phii1:bushvor :buslvdegPositive-Sequence Current, Angle
m:P:bushvor :buslvMWActive Power
m:Q:bushvor :buslvMvarReactive Power
m:i1P:bushvor :buslvp.u.Positive-Sequence Active Current
m:i1Q:bushvor :buslvp.u.Positive-Sequence Reactive Current
m:I1P:bushvor :buslvkAPositive-Sequence Active Current
m:I1Q:bushvor :buslvkAPositive-Sequence Reactive Current
m:phiui:bushvor :buslvdegAngle between Voltage and Current
m:phiu1i1:bushvor :buslvdegAngle between Voltage and Current in Positive-Sequence System
m:Tfct:bushvor :buslvsFault Clearing Time
m:Ikss:bushvor :buslvkAInitial Short-Circuit Current
m:ikss:bushvor :buslvp.u.Initial Short-Circuit Current, Magnitude
m:Skss:bushvor :buslvMVAInitial Short-Circuit Power
m:ip:bushvor :buslvkAPeak Short-Circuit Current
m:maxIkss:bushvor :buslvkAMax. Initial Short-Circuit Current
m:maxip:bushvor :buslvkAMax. Peak Short-Circuit Current
m:maxIth:bushvor :buslvkAMax. Thermal equivalent Short-Circuit Current
m:maxIb:bushvor :buslvkAMax. Breaking Current
m:R:bushvor :buslvOhmFault Impedance, Real Part
m:X:bushvor :buslvOhmFault Impedance, Imaginary Part
m:Z:bushvor :buslvOhmFault Impedance, Magnitude
m:phiz:bushvor :buslvdegFault Impedance, Angle
m:Rs:bushvor :buslvOhmSource Impedance, Real Part
m:Xs:bushvor :buslvOhmSource Impedance, Imaginary Part
m:Zs:bushvor :buslvOhmSource Impedance, Magnitude
m:phizs:bushvor :buslvdegSource Impedance, Angle
m:BrkIpload:bushvor :buslv%Breaker Loading (peak)
m:Ib:bushvor :buslvkAShort-Circuit Breaking Current
m:Sb:bushvor :buslvMVAShort-Circuit Breaking Power
m:Ith:bushvor :buslvkAThermal equivalent Short-Circuit Current
m:zSbase:bushvor :buslvp.u.Fault Impedance, Magnitude
m:XtoR:bushvor :buslvยทX/R ratio
m:cosphiui:bushvor :buslvยทcosphi
m:BrkIbload:bushvor :buslv%Breaker Loading (breaking)
m:BrkmaxIb:bushvor :buslvkAMax. Breaking Current (breaker time)
m:Ik:bushvor :buslvkASteady-State Short-Circuit Current
m:I:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, Magnitude
m:phii:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:I0:bushvor :buslvkAZero-Sequence Current, Magnitude
m:I0x3:bushvor :buslvkA3*I0
m:phii0:bushvor :buslvdegZero-Sequence Current, Angle
m:I2:bushvor :buslvkANegative-Sequence Current, Magnitude
m:phii2:bushvor :buslvdegNegative-Sequence Current, Angle
m:P:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:Psum:bushvor :buslvMWTotal Active Power
m:Qsum:bushvor :buslvMvarTotal Reactive Power
m:cosphisum:bushvor :buslvยทTotal Power Factor
m:P2:bushvor :buslvMWP2
m:Q2:bushvor :buslvMvarQ2
m:P0:bushvor :buslvMWP0
m:phiui:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bushvor :buslvdegAngle between Voltage and Current in Zero-Sequence System
m:phiu2i2:bushvor :buslvdegAngle between Voltage and Current in Negative-Sequence System
m:TfctPh:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:Ikss:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
m:ikss:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Initial Short-Circuit Current, Magnitude
m:Skss:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
m:Skssx3:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
m:ip:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
m:Z:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyOhmFault Impedance, Magnitude
m:phiz:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegFault Impedance, Angle
m:Zl:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyOhmLine-Line Fault Impedance, Magnitude
m:phizl:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegLine-Line Fault Impedance, Angle
m:Z0:bushvor :buslvOhmZero-Sequence Fault Impedance, Magnitude
m:phiz0:bushvor :buslvdegZero-Sequence Fault Impedance, Angle
m:z0Sbase:bushvor :buslvp.u.Zero-Sequence Fault Impedance, Magnitude
m:cosphiu1i1:bushvor :buslvยทPositive-Sequence cosphi
m:I0x3watt:bushvor :buslvkAEarth-Fault Residual Current
m:I0x3var:bushvor :buslvkACapacitive Earth-Fault Current
m:Q0cap:bushvor :buslvMvarQ0 capacitive
m:Rfrel:bushvor :buslvOhmRelay Impedance, Real Part
m:Xfrel:bushvor :buslvOhmRelay Impedance, Imaginary Part
m:Zfrel:bushvor :buslvOhmRelay Impedance, Magnitude
m:phizfrel:bushvor :buslvdegRelay Impedance, Angle
m:Zf:bushvor :buslvOhmMeas. Fault Impedance, Magnitude
m:phizf:bushvor :buslvdegMeas. Fault Impedance, Angle
c:nt2agrdradPhase Angle
c:snomMVARated Power
c:zshvp.u.Leakage Impedance (HV-Side)
c:zslvp.u.Leakage Impedance (LV-Side)
c:tap_sideยท0
c:tap_side2ยท0
c:xs1p.u.Leakage Reactance
c:oltcยทOn-load Tap Changer
c:pT%Range of Voltage Adjustment
c:Ubqmin_hvkVMinimum Operating Voltage
c:ilt_opยทLong-term operating condition before short-circuit are known
c:yg_hvp.u.Parasitic Admittance (HV-Side)
c:yg_lvp.u.Parasitic Admittance (LV-Side)
c:yc1p.u.Coupling-Admittance (1-Sequ., normalised on HV-Side)
c:ntpmnยทtap_side2
c:ntpmxยทzs0hv
c:ratfacยทRating Factor
c:zs0hvp.u.Zero sequence short circuit imp. (HV)
c:zs0lvp.u.Zero sequence short circuit imp. (LV)
c:ym0p.u.Zero Sequence Magnetising Admittance
c:Ustar_hkVStar-Point Voltage (HV)
c:Ustar_lkVStar-Point Voltage (LV)
c:Istar_hkAStar-Point Current (HV)
c:Istar_lkAStar-Point Current (LV)
c:yc0p.u.Coupling-Admittance (0-Sequ., normalised on HV-Side)
n:ur:bushvor :buslvp.u.Voltage, Real Part
n:ui:bushvor :buslvp.u.Voltage, Imaginary Part
n:u:bushvor :buslvp.u.Voltage, Magnitude
n:upc:bushvor :buslv%Voltage, Magnitude
n:du:bushvor :buslv%Voltage Deviation
n:U:bushvor :buslvkVLine-Ground Voltage, Magnitude
n:phiu:bushvor :buslvdegVoltage, Angle
n:Ul:bushvor :buslvkVLine-Line Voltage, Magnitude
n:u1:bushvor :buslvp.u.Voltage, Magnitude
n:u1pc:bushvor :buslv%Voltage, Magnitude
n:u1r:bushvor :buslvp.u.Positive-Sequence Voltage, Real Part
n:u1i:bushvor :buslvp.u.Positive-Sequence Voltage, Imaginary Part
n:Ikss:bushvor :buslvkAInitial Short-Circuit Current
n:I:bushvor :buslvkAShort-Circuit Current
n:phii:bushvor :buslvdegPhase Current, Angle
n:Skss:bushvor :buslvMVAInitial Short-Circuit Power
n:ip:bushvor :buslvkAPeak Short-Circuit Current
n:Ib:bushvor :buslvkAShort-Circuit Breaking Current
n:Sb:bushvor :buslvMVAShort-Circuit Breaking Power
n:idc:bushvor :buslvkADecaying Component
n:Ith:bushvor :buslvkAThermal equivalent Short-Circuit Current
n:R1toX1:bushvor :buslvยทR1/X1 ratio (Zk")
n:X1toR1:bushvor :buslvยทX1/R1 ratio (Zk")
n:R:bushvor :buslvOhmShort-Circuit Impedance, Real Part
n:X:bushvor :buslvOhmShort-Circuit Impedance, Imaginary Part
n:Z:bushvor :buslvOhmShort-Circuit Impedance, Magnitude
n:phiz:bushvor :buslvdegShort-Circuit Impedance, Angle
n:urpref:bushvor :buslvp.u.Pre-fault Voltage, Real Part
n:uipref:bushvor :buslvp.u.Pre-fault Voltage, Imaginary Part
n:upref:bushvor :buslvp.u.Pre-fault Voltage, Magnitude
n:uprefpc:bushvor :buslv%Pre-fault Voltage, Magnitude
n:Upref:bushvor :buslvkVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bushvor :buslvkVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bushvor :buslvdegPre-fault Voltage, Angle
n:phiui:bushvor :buslvdegAngle between Voltage and Current
n:Ithload:bushvor :buslv%Loading, Thermal equivalent Current
n:Ipload:bushvor :buslv%Loading, Peak Short-Circuit Current
n:Ithrtk:bushvor :buslvkARated Short-Time Current (Tk)
n:XtoR:bushvor :buslvยทX/R ratio (peak)
n:RtoX:bushvor :buslvยทR/X ratio (peak)
n:XtoR_b:bushvor :buslvยทX/R ratio (dc)
n:RtoX_b:bushvor :buslvยทR/X ratio (dc)
n:fctof_b:bushvor :buslvยทEquivalent Frequency fc/f (dc)
n:rSbase:bushvor :buslvp.u.Short-Circuit Impedance, Real Part
n:xSbase:bushvor :buslvp.u.Short-Circuit Impedance, Imaginary Part
n:zSbase:bushvor :buslvp.u.Short-Circuit Impedance, Magnitude
n:Tn:bushvor :buslvmsGrid Time Constant
n:Ik:bushvor :buslvkASteady-State Short-Circuit Current
n:cfac:bushvor :buslvยทVoltage Factor
n:Iasy:bushvor :buslvkAAsymmetrical Breaking Current
n:ur:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bushvor :buslvp.u.Zero-Sequence Voltage, Magnitude
n:U0:bushvor :buslvkVZero-Sequence Voltage, Magnitude
n:U0x3:bushvor :buslvkV3*U0
n:phiu0:bushvor :buslvdegZero-Sequence Voltage, Angle
n:U1:bushvor :buslvkVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bushvor :buslvdegPositive-Sequence Voltage, Angle
n:u2:bushvor :buslvp.u.Negative-Sequence Voltage, Magnitude
n:U2:bushvor :buslvkVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bushvor :buslvdegNegative-Sequence Voltage, Angle
n:U1l:bushvor :buslvkVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bushvor :buslvkVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bushvor :buslvp.u.Neutral-Ground Voltage, Magnitude
n:Un:bushvor :buslvkVNeutral-Ground Voltage, Magnitude
n:phiun:bushvor :buslvdegNeutral-Ground Voltage, Angle
n:upht:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:Ikss:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
n:I:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:phii:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
n:Skss:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
n:Skssx3:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
n:ip:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
n:Ib:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Breaking Current
n:Sb:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMVAShort-Circuit Breaking Power
n:Ith:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykAThermal equivalent Short-Circuit Current
n:Ithmax:bushvor :buslvkAMax. Thermal equivalent Short-Circuit Current
n:R0:bushvor :buslvOhmZero-Sequence Impedance, Real Part
n:X0:bushvor :buslvOhmZero-Sequence Impedance, Imaginary Part
n:Z0:bushvor :buslvOhmZero-Sequence Impedance, Magnitude
n:phiz0:bushvor :buslvdegZero-Sequence Impedance, Angle
n:r0Sbase:bushvor :buslvp.u.Zero-Sequence Impedance, Real Part
n:x0Sbase:bushvor :buslvp.u.Zero-Sequence Impedance, Imaginary Part
n:z0Sbase:bushvor :buslvp.u.Zero-Sequence Impedance, Magnitude
n:R1:bushvor :buslvOhmPositive-Sequence Impedance, Real Part
n:X1:bushvor :buslvOhmPositive-Sequence Impedance, Imaginary Part
n:Z1:bushvor :buslvOhmPositive-Sequence Impedance, Magnitude
n:phiz1:bushvor :buslvdegPositive-Sequence Impedance, Angle
n:r1Sbase:bushvor :buslvp.u.Positive-Sequence Impedance, Real Part
n:x1Sbase:bushvor :buslvp.u.Positive-Sequence Impedance, Imaginary Part
n:z1Sbase:bushvor :buslvp.u.Positive-Sequence Impedance, Magnitude
n:R2:bushvor :buslvOhmNegative-Sequence Impedance, Real Part
n:X2:bushvor :buslvOhmNegative-Sequence Impedance, Imaginary Part
n:Z2:bushvor :buslvOhmNegative-Sequence Impedance, Magnitude
n:phiz2:bushvor :buslvdegNegative-Sequence Impedance, Angle
n:r2Sbase:bushvor :buslvp.u.Negative-Sequence Impedance, Real Part
n:x2Sbase:bushvor :buslvp.u.Negative-Sequence Impedance, Imaginary Part
n:z2Sbase:bushvor :buslvp.u.Negative-Sequence Impedance, Magnitude
n:R0toX0:bushvor :buslvยทR0/X0 ratio (Zk")
n:X0toR0:bushvor :buslvยทX0/R0 ratio (Zk")
n:R2toX2:bushvor :buslvยทR2/X2 ratio (Zk")
n:X2toR2:bushvor :buslvยทX2/R2 ratio (Zk")
n:R:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Ground
n:X:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Ground
n:Z:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Ground
n:phiz:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Ground
n:Rl:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Line
n:Xl:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Line
n:Zl:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Line
n:phizl:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Line
n:Rln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Neutral
n:Xln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Neutral
n:Zln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Neutral
n:phizln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Neutral
n:Rn:bushvor :buslvOhmNetwork Resistance, Neutral
n:Xn:bushvor :buslvOhmNetwork Reactance, Neutral
n:Zn:bushvor :buslvOhmNetwork Impedance, Neutral
n:phizn:bushvor :buslvdegAngle of Network Impedance, Neutral
n:eff:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyยทEarth Fault Factor
n:X0toX1:bushvor :buslvยทX0/X1
n:In:bushvor :buslvkANeutral Current, Magnitude
n:phiin:bushvor :buslvdegNeutral Current, Angle
n:I0:bushvor :buslvkAZero-Sequence Current, Magnitude
n:I0x3:bushvor :buslvkA3*I0
n:phii0:bushvor :buslvdegZero-Sequence Current, Angle
n:I1:bushvor :buslvkAPositive-Sequence Current, Magnitude
n:phii1:bushvor :buslvdegPositive-Sequence Current, Angle
n:I2:bushvor :buslvkANegative-Sequence Current, Magnitude
n:phii2:bushvor :buslvdegNegative-Sequence Current, Angle
n:urpref:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Real Part
n:uipref:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Imaginary Part
n:upref:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Magnitude
n:uprefpc:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced only%Pre-fault Voltage, Magnitude
n:Upref:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegPre-fault Voltage, Angle
n:phiui:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
n:phiu1i1:bushvor :buslvdegAngle between Voltage and Current in positive sequence system
n:phiu2i2:bushvor :buslvdegAngle between Voltage and Current in negative sequence system
n:phiu0i0:bushvor :buslvdegAngle between Voltage and Current in zero-sequence system
n:Ik:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykASteady-State Short-Circuit Current
n:in:bushvor :buslvp.u.Neutral Current, Magnitude
n:i0r:bushvor :buslvp.u.Zero-Sequence Current, Real Part
n:i0i:bushvor :buslvp.u.Zero-Sequence Current, Imaginary Part
n:i0:bushvor :buslvp.u.Zero-Sequence Current, Magnitude
n:i1r:bushvor :buslvp.u.Positive-Sequence Current, Real Part
n:i1i:bushvor :buslvp.u.Positive-Sequence Current, Imaginary Part
n:i1:bushvor :buslvp.u.Positive-Sequence Current, Magnitude
n:i2r:bushvor :buslvp.u.Negative-Sequence Current, Real Part
n:i2i:bushvor :buslvp.u.Negative-Sequence Current, Imaginary Part
n:i2:bushvor :buslvp.u.Negative-Sequence Current, Magnitude

ElmTr2 rms simulation results

Read after ComInc (RMS) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bushvor :buslvp.u.Voltage, Real Part, referred to network
m:uinet:bushvor :buslvp.u.Voltage, Imaginary Part, referred to network
m:u1r:bushvor :buslvp.u.Positive-Sequence-Voltage, Real Part
m:u1i:bushvor :buslvp.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bushvor :buslvp.u.Positive-Sequence-Voltage, Magnitude
m:U1:bushvor :buslvkVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bushvor :buslvkVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bushvor :buslvdegPositive-Sequence-Voltage, Angle
m:irnet:bushvor :buslvp.u.Current, Real Part, referred to network
m:iinet:bushvor :buslvp.u.Current, Imaginary Part, referred to network
m:inet:bushvor :buslvp.u.Current, Magnitude, referred to network
m:I:bushvor :buslvkACurrent, Magnitude
m:phii:bushvor :buslvdegCurrent, Angle
m:i1r:bushvor :buslvp.u.Positive-Sequence Current, Real Part
m:i1i:bushvor :buslvp.u.Positive-Sequence Current, Imaginary Part
m:i1:bushvor :buslvp.u.Positive-Sequence Current, Magnitude
m:I1:bushvor :buslvkAPositive-Sequence Current, Magnitude
m:phii1:bushvor :buslvdegPositive-Sequence Current, Angle
m:P:bushvor :buslvMWActive Power
m:Q:bushvor :buslvMvarReactive Power
m:S:bushvor :buslvMVAApparent Power
m:cosphi:bushvor :buslvยทPower Factor
m:tanphi:bushvor :buslvยทtan(phi)
m:Psum:bushvor :buslvMWTotal Active Power
m:Qsum:bushvor :buslvMvarTotal Reactive Power
m:Ssum:bushvor :buslvMVATotal Apparent Power
m:cosphisum:bushvor :buslvยทTotal Power Factor
m:tanphisum:bushvor :buslvยทTotal tan(phi)
m:i1P:bushvor :buslvp.u.Positive-Sequence Active Current
m:i1Q:bushvor :buslvp.u.Positive-Sequence Reactive Current
m:I1P:bushvor :buslvkAPositive-Sequence Active Current
m:I1Q:bushvor :buslvkAPositive-Sequence Reactive Current
m:ur:bushvor :buslvp.u.Voltage, Real Part
m:ui:bushvor :buslvp.u.Voltage, Imaginary Part
m:u:bushvor :buslvp.u.Voltage, Magnitude
m:ir:bushvor :buslvp.u.Current, Real Part
m:ii:bushvor :buslvp.u.Current, Imaginary Part
m:i:bushvor :buslvp.u.Current, Magnitude
m:phiui:bushvor :buslvdegAngle between Voltage and Current
m:phiu1i1:bushvor :buslvdegAngle between Voltage and Current in positive sequence system
m:Tfct:bushvor :buslvsFault Clearing Time
m:Brkload:bushvor :buslv%Breaker Loading
m:Spu:bushvor :buslvMVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bushvor :buslvp.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bushvor :buslvdegZero-Sequence-Voltage, Angle
m:u2:bushvor :buslvp.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bushvor :buslvdegNegative-Sequence-Voltage, Angle
m:irnet:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:iinet:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:inet:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:I:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bushvor :buslvp.u.Zero-Sequence Current, Real Part
m:i0i:bushvor :buslvp.u.Zero-Sequence Current, Imaginary Part
m:i0:bushvor :buslvp.u.Zero-Sequence Current, Magnitude
m:I0:bushvor :buslvkAZero-Sequence Current, Magnitude
m:I0x3:bushvor :buslvkA3*I0
m:phii0:bushvor :buslvdegZero-Sequence Current, Angle
m:i2r:bushvor :buslvp.u.Negative-Sequence Current, Real Part
m:i2i:bushvor :buslvp.u.Negative-Sequence Current, Imaginary Part
m:i2:bushvor :buslvp.u.Negative-Sequence Current, Magnitude
m:I2:bushvor :buslvkANegative-Sequence Current, Magnitude
m:phii2:bushvor :buslvdegNegative-Sequence Current, Angle
m:P:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyยทPower Factor
m:tanphi:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyยทtan(phi)
m:Pln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bushvor :buslvMWPositive Sequence Active Power
m:Q1:bushvor :buslvMvarPositive Sequence Reactive Power
m:P2:bushvor :buslvMWNegative Sequence Active Power
m:Q2:bushvor :buslvMvarNegative Sequence Reactive Power
m:P0:bushvor :buslvMWZero Sequence Active Power
m:Q0:bushvor :buslvMvarZero Sequence Reactive Power
m:i2P:bushvor :buslvp.u.Negative-Sequence Active Current
m:i2Q:bushvor :buslvp.u.Negative-Sequence Reactive Current
m:I2P:bushvor :buslvkANegative-Sequence Active Current
m:I2Q:bushvor :buslvkANegative-Sequence Reactive Current
m:ur:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bushvor :buslvdegAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bushvor :buslvdegAngle between Voltage and Current in negative sequence system
m:TfctPh:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced only%Breaker Loading
c:loading_h%Loading (HV)
c:loading_l%Loading (LV)
c:loading%Loading
c:nntapยทTap 1, Current Position
c:nntap_intยทTap 1, relative Position
c:ntpmnยทTap 1, Min. Position
c:ntpmxยทTap 1, Max. Position
c:dutยทTap 1
c:phitrrdradTap 1
c:nt2agrdradPhase Angle
c:ratfacยทRating Factor
c:snomMVARated Power
c:zshvp.u.Leakage Impedance (HV-Side)
c:zslvp.u.Leakage Impedance (LV-Side)
c:ymp.u.Magnetising Admittance
c:thvยทComplex Winding Ratio HV
c:tlvยทComplex Winding Ratio LV
c:tap_sideยท0
c:tap_side2ยท0
c:nntap2ยทTap 2, Current Position
c:ntpmn2ยทTap 2, Min. Position
c:ntpmx2ยทTap 2, Max. Position
c:dut2ยทTap 2
c:phitrrd2radTap 2
c:PmeasMWMeasured active power
c:du_ldcp.u.LDC Input
c:ctrl_setยทSetpoint
c:w_0ยทNominal winding ratio
c:isatยทSaturated Model
c:Inom_HVkANominal Current (HV-Side)
c:Inom_LVkANominal Current (LV-Side)
c:iAutoTapยทController Mode
c:yg_hvp.u.Parasitic Admittance (HV-Side)
c:yg_lvp.u.Parasitic Admittance (LV-Side)
c:yc1p.u.Coupling-Admittance (1-Sequ., normalised on HV-Side)
c:i_ea_hยทFlag
c:i_ea_lยทFlag
c:i_star_hยทFlag
c:i_star_lยทFlag
c:zs0hvp.u.Zero sequence short circuit imp. (HV)
c:zs0lvp.u.Zero sequence short circuit imp. (LV)
c:ym0p.u.Zero Sequence Magnetising Admittance
c:Ustar_hkVStar-Point Voltage (HV)
c:Ustar_lkVStar-Point Voltage (LV)
c:Istar_hkAStar-Point Current (HV)
c:Istar_lkAStar-Point Current (LV)
c:tยทWinding Ratio
c:yc0p.u.Coupling-Admittance (0-Sys., normalised on HV-Side)
n:ur:bushvor :buslvp.u.Voltage, Real Part
n:ui:bushvor :buslvp.u.Voltage, Imaginary Part
n:u:bushvor :buslvp.u.Voltage, Magnitude
n:upc:bushvor :buslv%Voltage, Magnitude
n:du:bushvor :buslv%Voltage Deviation
n:U:bushvor :buslvkVLine-Ground Voltage, Magnitude
n:phiu:bushvor :buslvdegVoltage, Angle
n:phiurel:bushvor :buslvdegVoltage, Relative Angle
n:Ul:bushvor :buslvkVLine-Line Voltage, Magnitude
n:u1:bushvor :buslvp.u.Voltage, Magnitude
n:u1pc:bushvor :buslv%Voltage, Magnitude
n:u1r:bushvor :buslvp.u.Positive-Sequence Voltage, Real Part
n:u1i:bushvor :buslvp.u.Positive-Sequence Voltage, Imaginary Part
n:ishc:bushvor :buslvp.u.Short-Circuit Current, magnitude
n:Ishc:bushvor :buslvkAShort-Circuit Current, magnitude
n:fe:bushvor :buslvp.u.Electrical Frequency
n:dfehz:bushvor :buslvHzDeviation of the El. Frequency
n:fehz:bushvor :buslvHzElectrical Frequency
n:frnom:bushvor :buslvHzNominal Frequency
n:ishcr:bushvor :buslvp.u.Short-Circuit Current, real
n:ishci:bushvor :buslvp.u.Short-Circuit Current, imag
n:dfedt:bushvor :buslvp.u./sDerivative of El. Frequency
n:ur:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bushvor :buslvp.u.Zero-Sequence Voltage, Magnitude
n:U0:bushvor :buslvkVZero-Sequence Voltage, Magnitude
n:U0x3:bushvor :buslvkV3*U0
n:phiu0:bushvor :buslvdegZero-Sequence Voltage, Angle
n:U1:bushvor :buslvkVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bushvor :buslvdegPositive-Sequence Voltage, Angle
n:u2:bushvor :buslvp.u.Negative-Sequence Voltage, Magnitude
n:U2:bushvor :buslvkVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bushvor :buslvdegNegative-Sequence Voltage, Angle
n:U1l:bushvor :buslvkVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bushvor :buslvkVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bushvor :buslvp.u.Neutral-Ground Voltage, Magnitude
n:Un:bushvor :buslvkVNeutral-Ground Voltage, Magnitude
n:phiun:bushvor :buslvdegNeutral-Ground Voltage, Angle
n:upht:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bushvor :buslvp.u.Average-Voltage, Magnitude
n:Um:bushvor :buslvkVAverage-Voltage, Magnitude
n:ishc:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, magnitude
n:Ishc:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, magnitude
n:inshc:bushvor :buslvp.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bushvor :buslvkANeutral Short-Circuit Current, magnitude
n:ishcr:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, real
n:ishci:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, imag
s:nntapinยทTap 1, Controller Input
s:nntapin2ยทTap 2, Controller Input
s:uremr_ap.u.Control Voltage (Real)
s:uremi_ap.u.Control Voltage (Imaginary)
s:uremr_bp.u.Control Voltage (Real)
s:uremi_bp.u.Control Voltage (Imaginary)
s:uremr_cp.u.Control Voltage (Real)
s:uremi_cp.u.Control Voltage (Imaginary)
s:iremr_ap.u.Control Current (Real)
s:iremi_ap.u.Control Current (Imaginary)
s:iremr_bp.u.Control Current (Real)
s:iremi_bp.u.Control Current (Imaginary)
s:iremr_cp.u.Control Current (Real)
s:iremi_cp.u.Control Current (Imaginary)
s:du_ldcp.u.LDC Input

ElmTr2 emt simulation results

Read after ComInc (EMT) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:u0:bushvor :buslvp.u.Zero-Sequence-Voltage
m:u1r:bushvor :buslvp.u.Voltage Phasor, Real Part
m:u1i:bushvor :buslvp.u.Voltage Phasor, Imaginary Part
m:u1:bushvor :buslvp.u.Voltage Phasor, Magnitude
m:U1:bushvor :buslvkVLine-Ground Voltage Phasor, Magnitude
m:U1l:bushvor :buslvkVLine-Line Voltage Phasor, Magnitude
m:phiu1:bushvor :buslvdegVoltage Phasor, Angle
m:inet:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, referred to network
m:I:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykAPhase Current
m:i0:bushvor :buslvp.u.Zero-Sequence Current
m:I0:bushvor :buslvkAZero-Sequence Current
m:I0x3:bushvor :buslvkA3*I0
m:i1r:bushvor :buslvp.u.Current Phasor, Real Part
m:i1i:bushvor :buslvp.u.Current Phasor, Imaginary Part
m:i1:bushvor :buslvp.u.Current Phasor, Magnitude
m:I1:bushvor :buslvkACurrent Phasor, Magnitude
m:phii1:bushvor :buslvdegCurrent Phasor, Angle
m:P:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Psum:bushvor :buslvMWPower-Phasor, Active Power
m:Qsum:bushvor :buslvMvarPower Phasor, Reactive Part
m:Ssum:bushvor :buslvMVAPower Phasor, Apparent Power
m:i1P:bushvor :buslvp.u.Current Phasor, Active Current
m:i1Q:bushvor :buslvp.u.Current Phasor, Reactive Current
m:I1P:bushvor :buslvkACurrent Phasor, Active Current
m:I1Q:bushvor :buslvkACurrent Phasor, Reactive Current
m:u:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
m:i:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current
m:phiu1i1:bushvor :buslvdegAngle between Voltage and Current Phasor
m:Tfct:bushvor :buslvsFault Clearing Time
m:TfctPh:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:unet:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, referred to network
m:cosphi1:bushvor :buslvยทPower-Phasor, Power-Factor
c:nntapยทTap 1, Current Position
c:nntap_intยทTap 1, relative Position
c:ntpmnยทTap 1, Min. Position
c:ntpmxยทTap 1, Max. Position
c:dutยทTap 1
c:phitrrdradTap 1
c:nt2agrdradPhase Angle
c:thvยทComplex Winding Ratio HV
c:tlvยทComplex Winding Ratio LV
c:tap_sideยท0
c:tap_side2ยท0
c:nntap2ยทTap 2, Current Position
c:ntpmn2ยทTap 2, Min. Position
c:ntpmx2ยทTap 2, Max. Position
c:dut2ยทTap 2
c:phitrrd2radTap 2
c:i_ea_hยทFlag
c:i_ea_lยทFlag
c:i_star_hยทFlag
c:i_star_lยทFlag
c:Ustar_hkVStar-Point Voltage (HV)
c:Ustar_lkVStar-Point Voltage (LV)
c:Istar_hkAStar-Point Current (HV)
c:Istar_lkAStar-Point Current (LV)
c:w_0ยทNominal winding ratio
c:uhp.u.Aux.-value
c:rshvp.u.Leakage Resistance (HV-Side)
c:lshvp.u.Leakage Inductance (HV-Side)
c:rslvp.u.Leakage Resistance (LV-Side)
c:lslvp.u.Leakage Inductance (LV-Side)
c:bmp.u.Magnetising Susceptance
c:gmp.u.Magnetising Conductance
c:rs0hvp.u.Leakage Resistance (HV-Side)
c:ls0hvp.u.Leakage Inductance (HV-Side)
c:rs0lvp.u.Leakage Resistance (LV-Side)
c:ls0lvp.u.Leakage Inductance (LV-Side)
c:bm0p.u.Zero Sequence Magnetising Admittance
c:hpirad/sAngular frequency
c:psimkneep.u.Knee Flux
c:bmsatp.u.Saturated Magnetising Susceptance
c:i_satยทSaturated Model
c:im_ap.u.Magnetising Current, Phase a
c:im_bp.u.Magnetising Current, Phase b
c:im_cp.u.Magnetising Current, Phase c
c:ksatยทSaturation Exponent
c:i_fiveยทFive Limb Design
c:phystkWHysteresis losses at rated operation
c:tยทWinding Ratio
c:imp.u.Magnetising current
c:im0p.u.Magnetising current, zero-sequence
c:us_hvp.u.HV Star Point Voltage
c:us_lvp.u.LV Star Point Voltage
n:u:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
n:upc:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced only%Phase Voltage
n:U:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVPhase Voltage
n:ul:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage
n:ulpc:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced only%Line-Line Voltage
n:Ul:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage
n:u0:bushvor :buslvp.u.Zero-Sequence-Voltage
n:U0:bushvor :buslvkVZero-Sequence-Voltage
n:U0x3:bushvor :buslvkV3*U0
n:u1:bushvor :buslvp.u.Voltage Phasor, Magnitude
n:u1pc:bushvor :buslv%Voltage Phasor, Magnitude
n:u1r:bushvor :buslvp.u.Voltage Phasor, Real Part
n:u1i:bushvor :buslvp.u.Voltage Phasor, Imaginary Part
n:U1:bushvor :buslvkVVoltage Phasor, Magnitude
n:phiu1:bushvor :buslvdegVoltage Phasor, Angle
n:U1l:bushvor :buslvkVLine-Line Voltage Phasor, Magnitude
n:uln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage
n:Uln:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage
n:un:bushvor :buslvp.u.Neutral-Ground Voltage
n:Un:bushvor :buslvkVNeutral-Ground Voltage
n:ishc:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current
n:Ishc:bushv:Aor :buslv; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:inshc:bushvor :buslvp.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bushvor :buslvkANeutral Short-Circuit Current, magnitude
n:fe:bushvor :buslvp.u.Electrical Frequency
n:dfehz:bushvor :buslvHzDeviation of the El. Frequency
n:fehz:bushvor :buslvHzElectrical Frequency
n:frnom:bushvor :buslvHzNominal Frequency
s:nntapinยทTap 1, Controller Input
s:psimdp.u.Magnetising Flux, alpha-component
s:psimqp.u.Magnetising Flux, beta-component
s:psim0p.u.Magnetising Flux, gamma-component
s:psim_ap.u.Magnetising Flux
s:psim_bp.u.Magnetising Flux
s:psim_cp.u.Magnetising Flux
s:gm_ap.u.Magnetising Conductance
s:gm_bp.u.Magnetising Conductance
s:gm_cp.u.Magnetising Conductance
s:psimp.u.Magnetising flux
s:ihap.u.Inductive Current, HV
s:ihbp.u.Inductive Current, HV
s:ih0p.u.Inductive Current, HV
s:ilap.u.Inductive Current, LV
s:ilbp.u.Inductive Current, LV
s:il0p.u.Inductive Current, LV

ElmTr2 dc load flow results

Read after ComLdf (DC) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:P:bushvor :buslvMWActive Power
m:Q:bushvor :buslvMvarReactive Power
c:loading_h%Loading (HV)
c:loading_l%Loading (LV)
c:loading%Loading
c:maxload%Max. Loading
c:nntapยทTap 1, Current Position
c:ntpmnยทTap 1, Min. Position
c:ntpmxยทTap 1, Max. Position
c:dutยทTap 1
c:phitrrdradTap 1
c:nt2agrdradPhase Angle
c:ratfacยทRating Factor
c:snomMVARated Power
c:zshvp.u.Leakage Impedance (HV-Side)
c:zslvp.u.Leakage Impedance (LV-Side)
c:ymp.u.Magnetising Admittance
c:thvยทComplex Winding Ratio HV
c:tlvยทComplex Winding Ratio LV
c:tap_sideยท0
c:tap_side2ยท0
c:nntap2ยทTap 2, Current Position
c:ntpmn2ยทTap 2, Min. Position
c:ntpmx2ยทTap 2, Max. Position
c:dut2ยทTap 2
c:phitrrd2radTap 2
c:PmeasMWMeasured active power
c:i_uplimยทTap at Maximum
c:i_lowlimยทTap at Minimum
c:i_uplim2ยทTap 2 at Maximum
c:i_lowlim2ยทTap 2 at Minimum
c:w_0ยทNominal winding ratio
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:TctrlsController Time Constant
c:i_fixedtapยทFlag
c:dphiudegVoltage Drop Angle
c:maxloadpup.u.Max. Loading
n:u:bushvor :buslvp.u.Voltage, Magnitude
n:upc:bushvor :buslv%Voltage, Magnitude
n:U:bushvor :buslvkVLine-Ground Voltage, Magnitude
n:phiu:bushvor :buslvdegVoltage, Angle
n:phiurel:bushvor :buslvdegVoltage, Relative Angle
n:Ul:bushvor :buslvkVLine-Line Voltage, Magnitude
n:u1:bushvor :buslvp.u.Voltage, Magnitude
n:Pgen:bushvor :buslvMWGeneration, Active Power
n:Pmot:bushvor :buslvMWMotor Load, Active Power
n:Pload:bushvor :buslvMWGeneral Load, Active Power
n:Pcomp:bushvor :buslvMWCompensation (Losses)
n:Pnet:bushvor :buslvMWExternal Networks, Active Power
n:Pflow:bushvor :buslvMWPower Flow, Active Power
s:nt_inยทTap 1, Input
s:nt2_inยทTap 2, Input

Read after ComMod with GetAttribute. c: calculation parameter, s: signal (state or model variable).

AttributeUnitDescription
c:loading_h%Loading (HV)
c:loading_l%Loading (LV)
c:loading%Loading
c:nntapยทTap 1, Current Position
c:nntap_intยทTap 1, relative Position
c:ntpmnยทTap 1, Min. Position
c:ntpmxยทTap 1, Max. Position
c:dutยทTap 1
c:phitrrdradTap 1
c:nt2agrdradPhase Angle
c:ratfacยทRating Factor
c:snomMVARated Power
c:zshvp.u.Leakage Impedance (HV-Side)
c:zslvp.u.Leakage Impedance (LV-Side)
c:ymp.u.Magnetising Admittance
c:thvยทComplex Winding Ratio HV
c:tlvยทComplex Winding Ratio LV
c:tap_sideยท0
c:tap_side2ยท0
c:nntap2ยทTap 2, Current Position
c:ntpmn2ยทTap 2, Min. Position
c:ntpmx2ยทTap 2, Max. Position
c:dut2ยทTap 2
c:phitrrd2radTap 2
c:PmeasMWMeasured active power
c:du_ldcp.u.LDC Input
c:ctrl_setยทSetpoint
c:w_0ยทNominal winding ratio
c:isatยทSaturated Model
c:Inom_HVkANominal Current (HV-Side)
c:Inom_LVkANominal Current (LV-Side)
c:iAutoTapยทController Mode
c:yg_hvp.u.Parasitic Admittance (HV-Side)
c:yg_lvp.u.Parasitic Admittance (LV-Side)
c:yc1p.u.Coupling-Admittance (1-Sequ., normalised on HV-Side)
s:nntapinยทTap 1, Controller Input
s:nntapin2ยทTap 2, Controller Input

ElmTr2 optimal power flow results

Read after ComOpf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:bushvor :buslvp.u.Voltage, Real Part, referred to network
m:uinet:bushvor :buslvp.u.Voltage, Imaginary Part, referred to network
m:u1r:bushvor :buslvp.u.Positive-Sequence-Voltage, Real Part
m:u1i:bushvor :buslvp.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bushvor :buslvp.u.Positive-Sequence-Voltage, Magnitude
m:U1:bushvor :buslvkVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bushvor :buslvkVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bushvor :buslvdegPositive-Sequence-Voltage, Angle
m:irnet:bushvor :buslvp.u.Current, Real Part, referred to network
m:iinet:bushvor :buslvp.u.Current, Imaginary Part, referred to network
m:inet:bushvor :buslvp.u.Current, Magnitude, referred to network
m:I:bushvor :buslvkACurrent, Magnitude
m:phii:bushvor :buslvdegCurrent, Angle
m:i1r:bushvor :buslvp.u.Positive-Sequence Current, Real Part
m:i1i:bushvor :buslvp.u.Positive-Sequence Current, Imaginary Part
m:i1:bushvor :buslvp.u.Positive-Sequence Current, Magnitude
m:I1:bushvor :buslvkAPositive-Sequence Current, Magnitude
m:phii1:bushvor :buslvdegPositive-Sequence Current, Angle
m:P:bushvor :buslvMWActive Power
m:Q:bushvor :buslvMvarReactive Power
m:S:bushvor :buslvMVAApparent Power
m:cosphi:bushvor :buslvยทPower Factor
m:tanphi:bushvor :buslvยทtan(phi)
m:Psum:bushvor :buslvMWTotal Active Power
m:Qsum:bushvor :buslvMvarTotal Reactive Power
m:Ssum:bushvor :buslvMVATotal Apparent Power
m:cosphisum:bushvor :buslvยทTotal Power Factor
m:tanphisum:bushvor :buslvยทTotal tan(phi)
m:i1P:bushvor :buslvp.u.Positive-Sequence Active Current
m:i1Q:bushvor :buslvp.u.Positive-Sequence Reactive Current
m:I1P:bushvor :buslvkAPositive-Sequence Active Current
m:I1Q:bushvor :buslvkAPositive-Sequence Reactive Current
m:ur:bushvor :buslvp.u.Voltage, Real Part
m:ui:bushvor :buslvp.u.Voltage, Imaginary Part
m:u:bushvor :buslvp.u.Voltage, Magnitude
m:ir:bushvor :buslvp.u.Current, Real Part
m:ii:bushvor :buslvp.u.Current, Imaginary Part
m:i:bushvor :buslvp.u.Current, Magnitude
m:phiui:bushvor :buslvdegAngle between Voltage and Current
m:phiu1i1:bushvor :buslvdegAngle between Voltage and Current in positive sequence system
m:Tfct:bushvor :buslvsFault Clearing Time
m:Brkload:bushvor :buslv%Breaker Loading
m:Spu:bushvor :buslvMVA/p.u.Apparent Power per p.u. Voltage
c:loading_h%Loading (HV)
c:loading_l%Loading (LV)
c:loading%Loading
c:maxload%Max. Loading
c:nntapยทTap 1, Current Position
c:ntpmnยทTap 1, Min. Position
c:ntpmxยทTap 1, Max. Position
c:dutยทTap 1
c:phitrrdradTap 1
c:nt2agrdradPhase Angle
c:ratfacยทRating Factor
c:snomMVARated Power
c:zshvp.u.Leakage Impedance (HV-Side)
c:zslvp.u.Leakage Impedance (LV-Side)
c:ymp.u.Magnetising Admittance
c:thvยทComplex Winding Ratio HV
c:tlvยทComplex Winding Ratio LV
c:tap_sideยท0
c:tap_side2ยท0
c:nntap2ยทTap 2, Current Position
c:ntpmn2ยทTap 2, Min. Position
c:ntpmx2ยทTap 2, Max. Position
c:dut2ยทTap 2
c:phitrrd2radTap 2
c:PmeasMWMeasured active power
c:du_ldcp.u.LDC Input
c:ctrl_setยทSetpoint
c:i_uplimยทTap 1 at Maximum
c:i_lowlimยทTap 1 at Minimum
c:i_uplim2ยทTap 2 at Maximum
c:i_lowlim2ยทTap 2 at Minimum
c:nCtrlIterยทNo. of CTRL-iterations
c:w_0ยทNominal winding ratio
c:GmloadkWIron Losses
c:XmloadkvarMagnetising Losses
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:TctrlsController Time Constant
c:i_fixedtapยทFlag
c:isatยทSaturated Model
c:Inom_HVkANominal Current (HV-Side)
c:Inom_LVkANominal Current (LV-Side)
c:dup.u.Voltage Drop
c:dupc%Voltage Drop
c:dphiudegVoltage Drop Angle
c:du1p.u.Positive Sequence Voltage Drop
c:du1pc%Positive Sequence Voltage Drop
c:dphiu1degPositive Sequence Voltage Drop Angle
c:maxloadpup.u.Max. Loading
c:nntapTargetยทTap 1 - target value
c:totPenaltyCostsUSDTotal penalty costs
c:totTapDeviationยทTotal tap deviation
c:yg_hvp.u.Parasitic Admittance (HV-Side)
c:yg_lvp.u.Parasitic Admittance (LV-Side)
c:yc1p.u.Coupling-Admittance (normalised on HV-Side)
n:ur:bushvor :buslvp.u.Voltage, Real Part
n:ui:bushvor :buslvp.u.Voltage, Imaginary Part
n:u:bushvor :buslvp.u.Voltage, Magnitude
n:upc:bushvor :buslv%Voltage, Magnitude
n:du:bushvor :buslv%Voltage Deviation
n:U:bushvor :buslvkVLine-Ground Voltage, Magnitude
n:phiu:bushvor :buslvdegVoltage, Angle
n:phiurel:bushvor :buslvdegVoltage, Relative Angle
n:Ul:bushvor :buslvkVLine-Line Voltage, Magnitude
n:u1:bushvor :buslvp.u.Voltage, Magnitude
n:u1pc:bushvor :buslv%Voltage, Magnitude
n:u1r:bushvor :buslvp.u.Positive-Sequence Voltage, Real Part
n:u1i:bushvor :buslvp.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bushvor :buslvMWGeneration, Active Power
n:Qgen:bushvor :buslvMvarGeneration, Reactive Power
n:Pmot:bushvor :buslvMWMotor Load, Active Power
n:Qmot:bushvor :buslvMvarMotor Load, Reactive Power
n:Pload:bushvor :buslvMWGeneral Load, Active Power
n:Qload:bushvor :buslvMvarGeneral Load, Reactive Power
n:Pcomp:bushvor :buslvMWCompensation (Losses)
n:Qcomp:bushvor :buslvMvarCompensation
n:Pnet:bushvor :buslvMWExternal Networks, Active Power
n:Qnet:bushvor :buslvMvarExternal Networks, Reactive Power
n:Pflow:bushvor :buslvMWPower Flow, Active Power
n:Qflow:bushvor :buslvMvarPower Flow, Reactive Power
n:Pout:bushvor :buslvMWOutgoing Flow, Active Power
n:Qout:bushvor :buslvMvarOutgoing Power, Reactive Power
n:Sout:bushvor :buslvMVAOutgoing Power, Apparent Power
n:cosphiout:bushvor :buslvยทOutgoing Power, Power Factor
n:Pbalance:bushvor :buslvMWActive Power Balance (=0)
n:Qbalance:bushvor :buslvMvarReactive Power Balance (=0)
n:LossPdown:bushvor :buslvMWLosses, downstream
n:LossQdown:bushvor :buslvMvarLosses, downstream (Reactive Power)
n:LossPdownload:bushvor :buslvMWLoad losses, downstream
n:LossQdownload:bushvor :buslvMvarLoad losses, downstream
n:LossPdownnoload:bushvor :buslvMWNo load losses, downstream
n:LossQdownnoload:bushvor :buslvMvarNo load losses, downstream
n:du_feed:bushvor :buslv%Difference from voltage at start of feeder

ElmTr2 basic data

b: values are worked out from the input data. Read them; they are not set.

AttributeUnitDescription
b:loc_nameยทName
b:KfยทCorrection Factor (Short-Circuit)
b:UgnยทRated Voltage of Generator (for PSU)
b:ipsuยทPower Station Unit
b:nt2agยทRel.Phase Displacement
b:ntrcnยทAutomatic Tap Changer on/off
b:i_contยทContinuous Tap
b:iExtCtrlยทExternal Controlled
b:isatยทSaturated Model