ElmTrmult attributesPowerFactory Multi-Winding Transformer

Every attribute of the PowerFactory Multi-Winding Transformer (ElmTrmult): 148 input parameters and 865 result variables, with units and meaning. Copy a name into GetAttribute or SetAttribute.

What ElmTrmult is

A transformer with any number of windings, such as the transformer of a multi-pulse converter.

Class
ElmTrmult, element class
PowerFactory name
Multi-Winding Transformer
Terminal suffix
the name of the terminal, as :busN
Attributes
148 input parameters and 865 result variables, in 7 calculations

Read and write ElmTrmult in Python

import powerfactory

app = powerfactory.GetApplication()          # GetApplicationExt() from outside PowerFactory
app.GetFromStudyCase("ComLdf").Execute()      # results exist after a calculation

for obj in app.GetCalcRelevantObjects("*.ElmTrmult"):
    loading = obj.GetAttribute("c:loading")       # Loading, %
    print(obj.loc_name, loading)

obj = app.GetCalcRelevantObjects("*.ElmTrmult")[0]
obj.SetAttribute("outserv", 1)                # take the transformer out of service
  • A result at a terminal of the multi-winding transformer needs the terminal in its name: m:P:busN, not m:P, which raises AttributeError.
  • An input parameter is read and written with or without its e: prefix: GetAttribute("outserv") and GetAttribute("e:outserv") give the same value.
  • RMS and EMT variables change over time: record them in a results object (ElmRes) to read the whole curve. GetAttribute after a run gives the value at the last time step.

ElmTrmult input parameters

The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.

AttributeUnitDescription
loc_nameยทName
chr_nameยทCharacteristic Name
for_nameยทForeign Key
dat_srcยทData source
imldcยทControl Mode
sernumยทSerial Number
commissionDateยทCommissioning Date
appr_modbyยทModified by
outservยทOut of Service
iZoneBusยทZone
iAreaBusยทArea
nwindingsยทNumber of windings
ntnumยทparallel Transformers
lossAssignยทLoss assignment
tldcยทControlled Node is at
ilcphยทPhase
ntrcnยทAutomatic Tap Changing
ildcยทCompensation
icompยทCompounding
i_remยทRemote Control
i_contยทTap Changer
ntapยทAct. Position
uset_modeยทSetpoint
iPpartยทActive power participation
optaplimitยทOperational limits for tap changer
optapminยทMinimum Position
optapmaxยทMaximum Position
iResFluxยทResidual flux
ifcยทForced Cooling Enabled
constrยทYear of Construction
appr_statusยทStatus
iperfectยทIdeal component
i_tapoptยทTap Changer
ionlyPreยทOptimise in DC OPF
i_tapoptContยทControl Mode
iOPFCloadยทMax. loading constraint
i_tapiniยทEstimate tap position
isCtrlTapยทTap position
isCtrlTapContยทControl mode
isConstrLoadingยทMax. loading constraint for Unit Commitment
isMaxLoadSoftNlinยทPenalty costs for soft constraints
allowOutDistFacFiltยทAllow filtering by outage distribution factor
allowMarginFiltยทAllow filtering by constraint margin
allowCntConstrFiltยทAllow contingency filtering by number of critical constraints
isSepCntConstrTypeยทSeparate constraint type
cntConstrTypeยทContingency-constraint type
isSepCntMaxAllowedLoadingยทSeparate max. allowed loading
ctrlUsageยทTap position
curativeLimยทMax. curative tap deviation
isConstrLoadingPlacementยทMax. loading constraint for Optimal Equipment Placement
isCtrlTapPlacementยทTap position
iAstabintยทA-stable integration algorithm
iIntTapCtrlยทUse Integrated Tap Controller
TctrlsController Time Constant
Kqctrltap/MvarController Sensitivity dtap/dQ
Kpctrltap/MWController Sensitivity dtap/dP
Vtolerance%Tolerance (+/-)
usetpp.u.Voltage Setpoint
psetpMWActive Power Setpoint
qsetpMvarReactive Power Setpoint
usp_upp.u.Upper Voltage Bound
usp_lowp.u.Lower Voltage Bound
psp_upMWUpper Active Power Bound
psp_lowMWLower Active Power Bound
qsp_upMvarUpper Reactive Power Bound
qsp_lowMvarLower Reactive Power Bound
PtoleranceMWTolerance (+/-)
KpartยทParticipation factor
PsiresAp.u.Phase A
PsiresBp.u.Phase B
PsiresCp.u.Phase C
maxload%Max. loading
GPSlatdegLatitude / Northing
GPSlondegLongitude / Easting
scalingFacSoftConstrOpfยทWeighting factor for soft constraint penalty
scalingFacSoftConstrCostยทCost scaling factor
cntMaxAllowedLoading%Max. allowed loading in Contingencies
penaltyCostsUSDPenalty costs per tap deviation
curativeCostsUSDCosts per curative tap deviation
appr_modifยทModified
ratfacยทRating Factor
re0OhmResistance, Re
xe0OhmReactance, Xe
cimRdfIdยทRDF ID
sOpCommentยทOperator Comment
descยทDescription
fold_idยทIn Folder
typ_idยทTypeObject: TypTrmult
pVccurveยทV-Control-CurveObject: IntVctrlcurve
p_remยทControlled NodeObject: StaBar,ElmTerm
p_cubยทControlled Branch (Cubicle)Object: StaCubic
tapctrlยทTap ControllerObject: ElmTrmult,ElmTr2
pldcยทExternal LDCObject: StaLdc
p_pmeasยทP measured atObject: StaCubic*,ElmBoundary
doc_idยทAdditional Data
pOwnerยทOwnerObject: ElmOwner
pOperatorยทOperatorObject: ElmOperator
pStochStoTyptrfElement model
pcubยทTerminalObject: StaCubic
cpHeadFoldยทHead Folder
cpGridยทGridObject: ElmNet
cpZoneยทZoneObject: ElmZone
cpAreaยทAreaObject: ElmArea
cpFeedยทFeederObject: ElmFeeder
ciDistยทDistance from infeed in number of buses
ciLaterยทLateral Index
ciDistRootยทDistance from first infeed in number of buses
ciDistAllยทDistance from infeed in number of buses including switches
ciDistAllRootยทDistance from first infeed in number of buses including switches
cpOwnerยทOwnerObject: ElmOwner
cpOperatorยทOperatorObject: ElmOperator
cpBranchยทBranchObject: ElmBranch
cpSiteยทSiteObject: ElmSite
cpSubstatยทSubstationObject: ElmSubstat,ElmTrfstat
cpMeteostatยทMeteo StationObject: ElmMeteostat
ciOutagedยทPlanned Outage
ciEnergizedยทEnergized
ciEarthedยทEarthed
cDisplayNameยทDisplay Name
cpSupplyTransformerยทSupplying TransformerObject: ElmTr?,ElmTrmult
cpSupplyTrfStationยทSupplying Secondary SubstationObject: ElmTrfstat
cpSupplySubstationยทSupplying SubstationObject: ElmSubstat
pcub_barยทTerminal
pcub_uknomkVNominal Voltage
pcub_statยทSubstationObject: ElmSubstat,ElmTrfstat
cgndยทStar Point
cpeterยทPetersen Coil
vecgrpยทVector group
cPsiresCp.u.Phase C
pTยทVoltage Range
FOR11/aForced Outage Rate
FOEh/aForced Outage Expectancy
FODhForced Outage Duration
pTypStochStoTyptrfType model
CCEarFr1/aFrequency of single earth faults
CCEarRepMuhRepair duration
CCEarProb%Conditional probability of a second earth fault
cCtrlTapContOpfยทControl Mode
cOptOnlyPreยทOptimise in DC OPF
cCtrlTapContยทControl mode
cAllowOutDistFacFiltยทAllow filtering by outage distribution factor
cAllowMarginFiltยทAllow filtering by constraint margin
cAllowCntConstrFiltยทAllow contingency filtering by number of critical constraints
cIsSepCntConstrTypeยทSeparate constraint type
cIsSepCntMaxAllowedLoadingยทSeparate max. allowed loading
cCtrlUsageยทTap position
c_plccยทExternal LCC ControllerObject: StaLdc
cpCtrlNodeยทTarget NodeObject: ElmTerm

ElmTrmult load flow results

Read after ComLdf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:busNbusN: the terminalp.u.Voltage, Real Part, referred to network
m:uinet:busNbusN: the terminalp.u.Voltage, Imaginary Part, referred to network
m:u1r:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Real Part
m:u1i:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Magnitude
m:U1:busNbusN: the terminalkVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:busNbusN: the terminalkVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:busNbusN: the terminaldegPositive-Sequence-Voltage, Angle
m:irnet:busNbusN: the terminalp.u.Current, Real Part, referred to network
m:iinet:busNbusN: the terminalp.u.Current, Imaginary Part, referred to network
m:inet:busNbusN: the terminalp.u.Current, Magnitude, referred to network
m:I:busNbusN: the terminalkACurrent, Magnitude
m:phii:busNbusN: the terminaldegCurrent, Angle
m:i1r:busNbusN: the terminalp.u.Positive-Sequence Current, Real Part
m:i1i:busNbusN: the terminalp.u.Positive-Sequence Current, Imaginary Part
m:i1:busNbusN: the terminalp.u.Positive-Sequence Current, Magnitude
m:I1:busNbusN: the terminalkAPositive-Sequence Current, Magnitude
m:phii1:busNbusN: the terminaldegPositive-Sequence Current, Angle
m:P:busNbusN: the terminalMWActive Power
m:Q:busNbusN: the terminalMvarReactive Power
m:S:busNbusN: the terminalMVAApparent Power
m:cosphi:busNbusN: the terminalยทPower Factor
m:tanphi:busNbusN: the terminalยทtan(phi)
m:Psum:busNbusN: the terminalMWTotal Active Power
m:Qsum:busNbusN: the terminalMvarTotal Reactive Power
m:Ssum:busNbusN: the terminalMVATotal Apparent Power
m:cosphisum:busNbusN: the terminalยทTotal Power Factor
m:tanphisum:busNbusN: the terminalยทTotal tan(phi)
m:i1P:busNbusN: the terminalp.u.Positive-Sequence Active Current
m:i1Q:busNbusN: the terminalp.u.Positive-Sequence Reactive Current
m:I1P:busNbusN: the terminalkAPositive-Sequence Active Current
m:I1Q:busNbusN: the terminalkAPositive-Sequence Reactive Current
m:ur:busNbusN: the terminalp.u.Voltage, Real Part
m:ui:busNbusN: the terminalp.u.Voltage, Imaginary Part
m:u:busNbusN: the terminalp.u.Voltage, Magnitude
m:ir:busNbusN: the terminalp.u.Current, Real Part
m:ii:busNbusN: the terminalp.u.Current, Imaginary Part
m:i:busNbusN: the terminalp.u.Current, Magnitude
m:phiui:busNbusN: the terminaldegAngle between Voltage and Current
m:phiu1i1:busNbusN: the terminaldegAngle between Voltage and Current in positive sequence system
m:Tfct:busNbusN: the terminalsFault Clearing Time
m:Brkload:busNbusN: the terminal%Breaker Loading
m:Spu:busNbusN: the terminalMVA/p.u.Apparent Power per p.u. Voltage
m:urnet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:busNbusN: the terminalp.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:busNbusN: the terminaldegZero-Sequence-Voltage, Angle
m:u2:busNbusN: the terminalp.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:busNbusN: the terminaldegNegative-Sequence-Voltage, Angle
m:irnet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part, referred to network
m:iinet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part, referred to network
m:inet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude, referred to network
m:I:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:busNbusN: the terminalp.u.Zero-Sequence Current, Real Part
m:i0i:busNbusN: the terminalp.u.Zero-Sequence Current, Imaginary Part
m:i0:busNbusN: the terminalp.u.Zero-Sequence Current, Magnitude
m:I0:busNbusN: the terminalkAZero-Sequence Current, Magnitude
m:I0x3:busNbusN: the terminalkA3*I0
m:phii0:busNbusN: the terminaldegZero-Sequence Current, Angle
m:i2r:busNbusN: the terminalp.u.Negative-Sequence Current, Real Part
m:i2i:busNbusN: the terminalp.u.Negative-Sequence Current, Imaginary Part
m:i2:busNbusN: the terminalp.u.Negative-Sequence Current, Magnitude
m:I2:busNbusN: the terminalkANegative-Sequence Current, Magnitude
m:phii2:busNbusN: the terminaldegNegative-Sequence Current, Angle
m:ubfacI:busNbusN: the terminal%Current Unbalance Factor
m:ubfacS:busNbusN: the terminal%Power Unbalance Factor
m:P:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyยทPower Factor
m:tanphi:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyยทtan(phi)
m:Pln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:busNbusN: the terminalMWPositive Sequence Active Power
m:Q1:busNbusN: the terminalMvarPositive Sequence Reactive Power
m:P2:busNbusN: the terminalMWNegative Sequence Active Power
m:Q2:busNbusN: the terminalMvarNegative Sequence Reactive Power
m:P0:busNbusN: the terminalMWZero Sequence Active Power
m:Q0:busNbusN: the terminalMvarZero Sequence Reactive Power
m:i2P:busNbusN: the terminalp.u.Negative-Sequence Active Current
m:i2Q:busNbusN: the terminalp.u.Negative-Sequence Reactive Current
m:I2P:busNbusN: the terminalkANegative-Sequence Active Current
m:I2Q:busNbusN: the terminalkANegative-Sequence Reactive Current
m:ur:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:busNbusN: the terminaldegAngle between Voltage and Current in zero-sequence system
m:phiu2i2:busNbusN: the terminaldegAngle between Voltage and Current in negative sequence system
m:TfctPh:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Breaker Loading
c:loading_w%Loading (Winding)
c:loading%Loading
c:loading_st%Short term loading
c:maxload%Max. loading
c:ratfactยทRating factor
c:um_1p.u.Magnetising flux (Real part)
c:ymp.u.Magnetising admittance
c:tapRatioยทComplex winding ratio
c:ntapยทCurrent tap position
c:ntap_intยทTap, relative position
c:i_uplimยทTap at maximum
c:i_lowlimยทTap at minimum
c:nCtrlIterยทNo. of CTRL-iterations
c:TctrlsController time constant
c:i_fixedtapยทFlag
c:PmeasMWMeasured active power
c:GmloadkWIron losses
c:XmloadkvarMagnetising losses
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:isatยทSaturated model
c:dphiudegVoltage drop angle
c:Inom_wkANominal current
c:maxloadpup.u.Max. loading
c:um_2p.u.Magnetising flux (Imaginary part)
c:um_0p.u.Magnetising flux (0-Sequence)
c:ym0p.u.0-Seq. magn. admitt.
c:UstarkVStar-point voltage
c:IstarkAStar-point current
c:i0Deltap.u.0-Sequence circulating current in Delta-winding
c:I0DeltakA0-Sequence circulating current in Delta-winding, Magnitude
n:ur:busNbusN: the terminalp.u.Voltage, Real Part
n:ui:busNbusN: the terminalp.u.Voltage, Imaginary Part
n:u:busNbusN: the terminalp.u.Voltage, Magnitude
n:upc:busNbusN: the terminal%Voltage, Magnitude
n:du:busNbusN: the terminal%Voltage Deviation
n:U:busNbusN: the terminalkVLine-Ground Voltage, Magnitude
n:phiu:busNbusN: the terminaldegVoltage, Angle
n:phiurel:busNbusN: the terminaldegVoltage, Relative Angle
n:Ul:busNbusN: the terminalkVLine-Line Voltage, Magnitude
n:u1:busNbusN: the terminalp.u.Voltage, Magnitude
n:u1pc:busNbusN: the terminal%Voltage, Magnitude
n:u1r:busNbusN: the terminalp.u.Positive-Sequence Voltage, Real Part
n:u1i:busNbusN: the terminalp.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:busNbusN: the terminalMWGeneration, Active Power
n:Qgen:busNbusN: the terminalMvarGeneration, Reactive Power
n:Pmot:busNbusN: the terminalMWMotor Load, Active Power
n:Qmot:busNbusN: the terminalMvarMotor Load, Reactive Power
n:Pload:busNbusN: the terminalMWGeneral Load, Active Power
n:Qload:busNbusN: the terminalMvarGeneral Load, Reactive Power
n:Pcomp:busNbusN: the terminalMWCompensation (Losses)
n:Qcomp:busNbusN: the terminalMvarCompensation
n:Pnet:busNbusN: the terminalMWExternal Networks, Active Power
n:Qnet:busNbusN: the terminalMvarExternal Networks, Reactive Power
n:Pflow:busNbusN: the terminalMWPower Flow, Active Power
n:Qflow:busNbusN: the terminalMvarPower Flow, Reactive Power
n:Pout:busNbusN: the terminalMWOutgoing Flow, Active Power
n:Qout:busNbusN: the terminalMvarOutgoing Power, Reactive Power
n:Sout:busNbusN: the terminalMVAOutgoing Power, Apparent Power
n:cosphiout:busNbusN: the terminalยทOutgoing Power, Power Factor
n:Pbalance:busNbusN: the terminalMWActive Power Balance (=0)
n:Qbalance:busNbusN: the terminalMvarReactive Power Balance (=0)
n:LossPdown:busNbusN: the terminalMWLosses, downstream
n:LossQdown:busNbusN: the terminalMvarLosses, downstream (Reactive Power)
n:LossPdownload:busNbusN: the terminalMWLoad losses, downstream
n:LossQdownload:busNbusN: the terminalMvarLoad losses, downstream
n:LossPdownnoload:busNbusN: the terminalMWNo load losses, downstream
n:LossQdownnoload:busNbusN: the terminalMvarNo load losses, downstream
n:du_feed:busNbusN: the terminal%Difference from voltage at start of feeder
n:ur:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:busNbusN: the terminalp.u.Zero-Sequence Voltage, Magnitude
n:U0:busNbusN: the terminalkVZero-Sequence Voltage, Magnitude
n:U0x3:busNbusN: the terminalkV3*U0
n:phiu0:busNbusN: the terminaldegZero-Sequence Voltage, Angle
n:U1:busNbusN: the terminalkVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:busNbusN: the terminaldegPositive-Sequence Voltage, Angle
n:u2:busNbusN: the terminalp.u.Negative-Sequence Voltage, Magnitude
n:U2:busNbusN: the terminalkVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:busNbusN: the terminaldegNegative-Sequence Voltage, Angle
n:U1l:busNbusN: the terminalkVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:busNbusN: the terminalkVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:busNbusN: the terminalp.u.Neutral-Ground Voltage, Magnitude
n:Un:busNbusN: the terminalkVNeutral-Ground Voltage, Magnitude
n:phiun:busNbusN: the terminaldegNeutral-Ground Voltage, Angle
n:upht:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:busNbusN: the terminalp.u.Average-Voltage, Magnitude
n:Um:busNbusN: the terminalkVAverage-Voltage, Magnitude
n:uphtmin:busNbusN: the terminalp.u.Minimum of Phase Technology dependent Voltage, Magnitude
n:uphtmax:busNbusN: the terminalp.u.Maximum of Phase Technology dependent Voltage, Magnitude
n:ubfac:busNbusN: the terminal%Unbalance Factor
s:nt_inยทTap, Input
s:I0rDeltakACirculating current in Delta-winding, Real part
s:I0iDeltakACirculating current in Delta-winding, Imaginary part

ElmTrmult short-circuit results

Read after ComShc with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:I:busNbusN: the terminalkAShort-Circuit Current, Magnitude
m:phii:busNbusN: the terminaldegPhase Current, Angle
m:i1:busNbusN: the terminalp.u.Positive-Sequence Current, Magnitude
m:I1:busNbusN: the terminalkAPositive-Sequence Current, Magnitude
m:phii1:busNbusN: the terminaldegPositive-Sequence Current, Angle
m:P:busNbusN: the terminalMWActive Power
m:Q:busNbusN: the terminalMvarReactive Power
m:i1P:busNbusN: the terminalp.u.Positive-Sequence Active Current
m:i1Q:busNbusN: the terminalp.u.Positive-Sequence Reactive Current
m:I1P:busNbusN: the terminalkAPositive-Sequence Active Current
m:I1Q:busNbusN: the terminalkAPositive-Sequence Reactive Current
m:phiui:busNbusN: the terminaldegAngle between Voltage and Current
m:phiu1i1:busNbusN: the terminaldegAngle between Voltage and Current in Positive-Sequence System
m:Tfct:busNbusN: the terminalsFault Clearing Time
m:Ikss:busNbusN: the terminalkAInitial Short-Circuit Current
m:ikss:busNbusN: the terminalp.u.Initial Short-Circuit Current, Magnitude
m:Skss:busNbusN: the terminalMVAInitial Short-Circuit Power
m:ip:busNbusN: the terminalkAPeak Short-Circuit Current
m:maxIkss:busNbusN: the terminalkAMax. Initial Short-Circuit Current
m:maxip:busNbusN: the terminalkAMax. Peak Short-Circuit Current
m:maxIth:busNbusN: the terminalkAMax. Thermal equivalent Short-Circuit Current
m:maxIb:busNbusN: the terminalkAMax. Breaking Current
m:R:busNbusN: the terminalOhmFault Impedance, Real Part
m:X:busNbusN: the terminalOhmFault Impedance, Imaginary Part
m:Z:busNbusN: the terminalOhmFault Impedance, Magnitude
m:phiz:busNbusN: the terminaldegFault Impedance, Angle
m:Rs:busNbusN: the terminalOhmSource Impedance, Real Part
m:Xs:busNbusN: the terminalOhmSource Impedance, Imaginary Part
m:Zs:busNbusN: the terminalOhmSource Impedance, Magnitude
m:phizs:busNbusN: the terminaldegSource Impedance, Angle
m:BrkIpload:busNbusN: the terminal%Breaker Loading (peak)
m:Ib:busNbusN: the terminalkAShort-Circuit Breaking Current
m:Sb:busNbusN: the terminalMVAShort-Circuit Breaking Power
m:Ith:busNbusN: the terminalkAThermal equivalent Short-Circuit Current
m:zSbase:busNbusN: the terminalp.u.Fault Impedance, Magnitude
m:XtoR:busNbusN: the terminalยทX/R ratio
m:cosphiui:busNbusN: the terminalยทcosphi
m:BrkIbload:busNbusN: the terminal%Breaker Loading (breaking)
m:BrkmaxIb:busNbusN: the terminalkAMax. Breaking Current (breaker time)
m:Ik:busNbusN: the terminalkASteady-State Short-Circuit Current
m:I:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, Magnitude
m:phii:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:I0:busNbusN: the terminalkAZero-Sequence Current, Magnitude
m:I0x3:busNbusN: the terminalkA3*I0
m:phii0:busNbusN: the terminaldegZero-Sequence Current, Angle
m:I2:busNbusN: the terminalkANegative-Sequence Current, Magnitude
m:phii2:busNbusN: the terminaldegNegative-Sequence Current, Angle
m:P:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:Psum:busNbusN: the terminalMWTotal Active Power
m:Qsum:busNbusN: the terminalMvarTotal Reactive Power
m:cosphisum:busNbusN: the terminalยทTotal Power Factor
m:P2:busNbusN: the terminalMWP2
m:Q2:busNbusN: the terminalMvarQ2
m:P0:busNbusN: the terminalMWP0
m:phiui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:busNbusN: the terminaldegAngle between Voltage and Current in Zero-Sequence System
m:phiu2i2:busNbusN: the terminaldegAngle between Voltage and Current in Negative-Sequence System
m:TfctPh:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:Ikss:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
m:ikss:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Initial Short-Circuit Current, Magnitude
m:Skss:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
m:Skssx3:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
m:ip:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
m:Z:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmFault Impedance, Magnitude
m:phiz:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegFault Impedance, Angle
m:Zl:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmLine-Line Fault Impedance, Magnitude
m:phizl:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Line Fault Impedance, Angle
m:Z0:busNbusN: the terminalOhmZero-Sequence Fault Impedance, Magnitude
m:phiz0:busNbusN: the terminaldegZero-Sequence Fault Impedance, Angle
m:z0Sbase:busNbusN: the terminalp.u.Zero-Sequence Fault Impedance, Magnitude
m:cosphiu1i1:busNbusN: the terminalยทPositive-Sequence cosphi
m:I0x3watt:busNbusN: the terminalkAEarth-Fault Residual Current
m:I0x3var:busNbusN: the terminalkACapacitive Earth-Fault Current
m:Q0cap:busNbusN: the terminalMvarQ0 capacitive
m:Rfrel:busNbusN: the terminalOhmRelay Impedance, Real Part
m:Xfrel:busNbusN: the terminalOhmRelay Impedance, Imaginary Part
m:Zfrel:busNbusN: the terminalOhmRelay Impedance, Magnitude
m:phizfrel:busNbusN: the terminaldegRelay Impedance, Angle
m:Zf:busNbusN: the terminalOhmMeas. Fault Impedance, Magnitude
m:phizf:busNbusN: the terminaldegMeas. Fault Impedance, Angle
c:pT%Range of voltage adjustment
c:Kt_vdeยทVDE/IEC Correction Factor
c:UstarkVStar-point voltage
c:IstarkAStar-point current
c:i0Deltap.u.0-Sequence circulating current in Delta-winding
c:I0DeltakA0-Sequence circulating current in Delta-winding, Magnitude
n:ur:busNbusN: the terminalp.u.Voltage, Real Part
n:ui:busNbusN: the terminalp.u.Voltage, Imaginary Part
n:u:busNbusN: the terminalp.u.Voltage, Magnitude
n:upc:busNbusN: the terminal%Voltage, Magnitude
n:du:busNbusN: the terminal%Voltage Deviation
n:U:busNbusN: the terminalkVLine-Ground Voltage, Magnitude
n:phiu:busNbusN: the terminaldegVoltage, Angle
n:Ul:busNbusN: the terminalkVLine-Line Voltage, Magnitude
n:u1:busNbusN: the terminalp.u.Voltage, Magnitude
n:u1pc:busNbusN: the terminal%Voltage, Magnitude
n:u1r:busNbusN: the terminalp.u.Positive-Sequence Voltage, Real Part
n:u1i:busNbusN: the terminalp.u.Positive-Sequence Voltage, Imaginary Part
n:Ikss:busNbusN: the terminalkAInitial Short-Circuit Current
n:I:busNbusN: the terminalkAShort-Circuit Current
n:phii:busNbusN: the terminaldegPhase Current, Angle
n:Skss:busNbusN: the terminalMVAInitial Short-Circuit Power
n:ip:busNbusN: the terminalkAPeak Short-Circuit Current
n:Ib:busNbusN: the terminalkAShort-Circuit Breaking Current
n:Sb:busNbusN: the terminalMVAShort-Circuit Breaking Power
n:idc:busNbusN: the terminalkADecaying Component
n:Ith:busNbusN: the terminalkAThermal equivalent Short-Circuit Current
n:R1toX1:busNbusN: the terminalยทR1/X1 ratio (Zk")
n:X1toR1:busNbusN: the terminalยทX1/R1 ratio (Zk")
n:R:busNbusN: the terminalOhmShort-Circuit Impedance, Real Part
n:X:busNbusN: the terminalOhmShort-Circuit Impedance, Imaginary Part
n:Z:busNbusN: the terminalOhmShort-Circuit Impedance, Magnitude
n:phiz:busNbusN: the terminaldegShort-Circuit Impedance, Angle
n:urpref:busNbusN: the terminalp.u.Pre-fault Voltage, Real Part
n:uipref:busNbusN: the terminalp.u.Pre-fault Voltage, Imaginary Part
n:upref:busNbusN: the terminalp.u.Pre-fault Voltage, Magnitude
n:uprefpc:busNbusN: the terminal%Pre-fault Voltage, Magnitude
n:Upref:busNbusN: the terminalkVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:busNbusN: the terminalkVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:busNbusN: the terminaldegPre-fault Voltage, Angle
n:phiui:busNbusN: the terminaldegAngle between Voltage and Current
n:Ithload:busNbusN: the terminal%Loading, Thermal equivalent Current
n:Ipload:busNbusN: the terminal%Loading, Peak Short-Circuit Current
n:Ithrtk:busNbusN: the terminalkARated Short-Time Current (Tk)
n:XtoR:busNbusN: the terminalยทX/R ratio (peak)
n:RtoX:busNbusN: the terminalยทR/X ratio (peak)
n:XtoR_b:busNbusN: the terminalยทX/R ratio (dc)
n:RtoX_b:busNbusN: the terminalยทR/X ratio (dc)
n:fctof_b:busNbusN: the terminalยทEquivalent Frequency fc/f (dc)
n:rSbase:busNbusN: the terminalp.u.Short-Circuit Impedance, Real Part
n:xSbase:busNbusN: the terminalp.u.Short-Circuit Impedance, Imaginary Part
n:zSbase:busNbusN: the terminalp.u.Short-Circuit Impedance, Magnitude
n:Tn:busNbusN: the terminalmsGrid Time Constant
n:Ik:busNbusN: the terminalkASteady-State Short-Circuit Current
n:cfac:busNbusN: the terminalยทVoltage Factor
n:Iasy:busNbusN: the terminalkAAsymmetrical Breaking Current
n:ur:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:busNbusN: the terminalp.u.Zero-Sequence Voltage, Magnitude
n:U0:busNbusN: the terminalkVZero-Sequence Voltage, Magnitude
n:U0x3:busNbusN: the terminalkV3*U0
n:phiu0:busNbusN: the terminaldegZero-Sequence Voltage, Angle
n:U1:busNbusN: the terminalkVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:busNbusN: the terminaldegPositive-Sequence Voltage, Angle
n:u2:busNbusN: the terminalp.u.Negative-Sequence Voltage, Magnitude
n:U2:busNbusN: the terminalkVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:busNbusN: the terminaldegNegative-Sequence Voltage, Angle
n:U1l:busNbusN: the terminalkVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:busNbusN: the terminalkVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:busNbusN: the terminalp.u.Neutral-Ground Voltage, Magnitude
n:Un:busNbusN: the terminalkVNeutral-Ground Voltage, Magnitude
n:phiun:busNbusN: the terminaldegNeutral-Ground Voltage, Angle
n:upht:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:Ikss:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
n:I:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:phii:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
n:Skss:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
n:Skssx3:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
n:ip:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
n:Ib:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Breaking Current
n:Sb:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMVAShort-Circuit Breaking Power
n:Ith:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAThermal equivalent Short-Circuit Current
n:Ithmax:busNbusN: the terminalkAMax. Thermal equivalent Short-Circuit Current
n:R0:busNbusN: the terminalOhmZero-Sequence Impedance, Real Part
n:X0:busNbusN: the terminalOhmZero-Sequence Impedance, Imaginary Part
n:Z0:busNbusN: the terminalOhmZero-Sequence Impedance, Magnitude
n:phiz0:busNbusN: the terminaldegZero-Sequence Impedance, Angle
n:r0Sbase:busNbusN: the terminalp.u.Zero-Sequence Impedance, Real Part
n:x0Sbase:busNbusN: the terminalp.u.Zero-Sequence Impedance, Imaginary Part
n:z0Sbase:busNbusN: the terminalp.u.Zero-Sequence Impedance, Magnitude
n:R1:busNbusN: the terminalOhmPositive-Sequence Impedance, Real Part
n:X1:busNbusN: the terminalOhmPositive-Sequence Impedance, Imaginary Part
n:Z1:busNbusN: the terminalOhmPositive-Sequence Impedance, Magnitude
n:phiz1:busNbusN: the terminaldegPositive-Sequence Impedance, Angle
n:r1Sbase:busNbusN: the terminalp.u.Positive-Sequence Impedance, Real Part
n:x1Sbase:busNbusN: the terminalp.u.Positive-Sequence Impedance, Imaginary Part
n:z1Sbase:busNbusN: the terminalp.u.Positive-Sequence Impedance, Magnitude
n:R2:busNbusN: the terminalOhmNegative-Sequence Impedance, Real Part
n:X2:busNbusN: the terminalOhmNegative-Sequence Impedance, Imaginary Part
n:Z2:busNbusN: the terminalOhmNegative-Sequence Impedance, Magnitude
n:phiz2:busNbusN: the terminaldegNegative-Sequence Impedance, Angle
n:r2Sbase:busNbusN: the terminalp.u.Negative-Sequence Impedance, Real Part
n:x2Sbase:busNbusN: the terminalp.u.Negative-Sequence Impedance, Imaginary Part
n:z2Sbase:busNbusN: the terminalp.u.Negative-Sequence Impedance, Magnitude
n:R0toX0:busNbusN: the terminalยทR0/X0 ratio (Zk")
n:X0toR0:busNbusN: the terminalยทX0/R0 ratio (Zk")
n:R2toX2:busNbusN: the terminalยทR2/X2 ratio (Zk")
n:X2toR2:busNbusN: the terminalยทX2/R2 ratio (Zk")
n:R:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Ground
n:X:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Ground
n:Z:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Ground
n:phiz:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Ground
n:Rl:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Line
n:Xl:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Line
n:Zl:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Line
n:phizl:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Line
n:Rln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Neutral
n:Xln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Neutral
n:Zln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Neutral
n:phizln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Neutral
n:Rn:busNbusN: the terminalOhmNetwork Resistance, Neutral
n:Xn:busNbusN: the terminalOhmNetwork Reactance, Neutral
n:Zn:busNbusN: the terminalOhmNetwork Impedance, Neutral
n:phizn:busNbusN: the terminaldegAngle of Network Impedance, Neutral
n:eff:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyยทEarth Fault Factor
n:X0toX1:busNbusN: the terminalยทX0/X1
n:In:busNbusN: the terminalkANeutral Current, Magnitude
n:phiin:busNbusN: the terminaldegNeutral Current, Angle
n:I0:busNbusN: the terminalkAZero-Sequence Current, Magnitude
n:I0x3:busNbusN: the terminalkA3*I0
n:phii0:busNbusN: the terminaldegZero-Sequence Current, Angle
n:I1:busNbusN: the terminalkAPositive-Sequence Current, Magnitude
n:phii1:busNbusN: the terminaldegPositive-Sequence Current, Angle
n:I2:busNbusN: the terminalkANegative-Sequence Current, Magnitude
n:phii2:busNbusN: the terminaldegNegative-Sequence Current, Angle
n:urpref:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Real Part
n:uipref:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Imaginary Part
n:upref:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Magnitude
n:uprefpc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Pre-fault Voltage, Magnitude
n:Upref:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegPre-fault Voltage, Angle
n:phiui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
n:phiu1i1:busNbusN: the terminaldegAngle between Voltage and Current in positive sequence system
n:phiu2i2:busNbusN: the terminaldegAngle between Voltage and Current in negative sequence system
n:phiu0i0:busNbusN: the terminaldegAngle between Voltage and Current in zero-sequence system
n:Ik:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykASteady-State Short-Circuit Current
n:in:busNbusN: the terminalp.u.Neutral Current, Magnitude
n:i0r:busNbusN: the terminalp.u.Zero-Sequence Current, Real Part
n:i0i:busNbusN: the terminalp.u.Zero-Sequence Current, Imaginary Part
n:i0:busNbusN: the terminalp.u.Zero-Sequence Current, Magnitude
n:i1r:busNbusN: the terminalp.u.Positive-Sequence Current, Real Part
n:i1i:busNbusN: the terminalp.u.Positive-Sequence Current, Imaginary Part
n:i1:busNbusN: the terminalp.u.Positive-Sequence Current, Magnitude
n:i2r:busNbusN: the terminalp.u.Negative-Sequence Current, Real Part
n:i2i:busNbusN: the terminalp.u.Negative-Sequence Current, Imaginary Part
n:i2:busNbusN: the terminalp.u.Negative-Sequence Current, Magnitude
s:I0rDeltakACirculating current in Delta-winding, Real part
s:I0iDeltakACirculating current in Delta-winding, Imaginary part

ElmTrmult rms simulation results

Read after ComInc (RMS) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:busNbusN: the terminalp.u.Voltage, Real Part, referred to network
m:uinet:busNbusN: the terminalp.u.Voltage, Imaginary Part, referred to network
m:u1r:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Real Part
m:u1i:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Magnitude
m:U1:busNbusN: the terminalkVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:busNbusN: the terminalkVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:busNbusN: the terminaldegPositive-Sequence-Voltage, Angle
m:irnet:busNbusN: the terminalp.u.Current, Real Part, referred to network
m:iinet:busNbusN: the terminalp.u.Current, Imaginary Part, referred to network
m:inet:busNbusN: the terminalp.u.Current, Magnitude, referred to network
m:I:busNbusN: the terminalkACurrent, Magnitude
m:phii:busNbusN: the terminaldegCurrent, Angle
m:i1r:busNbusN: the terminalp.u.Positive-Sequence Current, Real Part
m:i1i:busNbusN: the terminalp.u.Positive-Sequence Current, Imaginary Part
m:i1:busNbusN: the terminalp.u.Positive-Sequence Current, Magnitude
m:I1:busNbusN: the terminalkAPositive-Sequence Current, Magnitude
m:phii1:busNbusN: the terminaldegPositive-Sequence Current, Angle
m:P:busNbusN: the terminalMWActive Power
m:Q:busNbusN: the terminalMvarReactive Power
m:S:busNbusN: the terminalMVAApparent Power
m:cosphi:busNbusN: the terminalยทPower Factor
m:tanphi:busNbusN: the terminalยทtan(phi)
m:Psum:busNbusN: the terminalMWTotal Active Power
m:Qsum:busNbusN: the terminalMvarTotal Reactive Power
m:Ssum:busNbusN: the terminalMVATotal Apparent Power
m:cosphisum:busNbusN: the terminalยทTotal Power Factor
m:tanphisum:busNbusN: the terminalยทTotal tan(phi)
m:i1P:busNbusN: the terminalp.u.Positive-Sequence Active Current
m:i1Q:busNbusN: the terminalp.u.Positive-Sequence Reactive Current
m:I1P:busNbusN: the terminalkAPositive-Sequence Active Current
m:I1Q:busNbusN: the terminalkAPositive-Sequence Reactive Current
m:ur:busNbusN: the terminalp.u.Voltage, Real Part
m:ui:busNbusN: the terminalp.u.Voltage, Imaginary Part
m:u:busNbusN: the terminalp.u.Voltage, Magnitude
m:ir:busNbusN: the terminalp.u.Current, Real Part
m:ii:busNbusN: the terminalp.u.Current, Imaginary Part
m:i:busNbusN: the terminalp.u.Current, Magnitude
m:phiui:busNbusN: the terminaldegAngle between Voltage and Current
m:phiu1i1:busNbusN: the terminaldegAngle between Voltage and Current in positive sequence system
m:Tfct:busNbusN: the terminalsFault Clearing Time
m:Brkload:busNbusN: the terminal%Breaker Loading
m:Spu:busNbusN: the terminalMVA/p.u.Apparent Power per p.u. Voltage
m:urnet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:busNbusN: the terminalp.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:busNbusN: the terminaldegZero-Sequence-Voltage, Angle
m:u2:busNbusN: the terminalp.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:busNbusN: the terminaldegNegative-Sequence-Voltage, Angle
m:irnet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:iinet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:inet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:I:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:busNbusN: the terminalp.u.Zero-Sequence Current, Real Part
m:i0i:busNbusN: the terminalp.u.Zero-Sequence Current, Imaginary Part
m:i0:busNbusN: the terminalp.u.Zero-Sequence Current, Magnitude
m:I0:busNbusN: the terminalkAZero-Sequence Current, Magnitude
m:I0x3:busNbusN: the terminalkA3*I0
m:phii0:busNbusN: the terminaldegZero-Sequence Current, Angle
m:i2r:busNbusN: the terminalp.u.Negative-Sequence Current, Real Part
m:i2i:busNbusN: the terminalp.u.Negative-Sequence Current, Imaginary Part
m:i2:busNbusN: the terminalp.u.Negative-Sequence Current, Magnitude
m:I2:busNbusN: the terminalkANegative-Sequence Current, Magnitude
m:phii2:busNbusN: the terminaldegNegative-Sequence Current, Angle
m:P:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyยทPower Factor
m:tanphi:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyยทtan(phi)
m:Pln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:busNbusN: the terminalMWPositive Sequence Active Power
m:Q1:busNbusN: the terminalMvarPositive Sequence Reactive Power
m:P2:busNbusN: the terminalMWNegative Sequence Active Power
m:Q2:busNbusN: the terminalMvarNegative Sequence Reactive Power
m:P0:busNbusN: the terminalMWZero Sequence Active Power
m:Q0:busNbusN: the terminalMvarZero Sequence Reactive Power
m:i2P:busNbusN: the terminalp.u.Negative-Sequence Active Current
m:i2Q:busNbusN: the terminalp.u.Negative-Sequence Reactive Current
m:I2P:busNbusN: the terminalkANegative-Sequence Active Current
m:I2Q:busNbusN: the terminalkANegative-Sequence Reactive Current
m:ur:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:busNbusN: the terminaldegAngle between Voltage and Current in zero-sequence system
m:phiu2i2:busNbusN: the terminaldegAngle between Voltage and Current in negative sequence system
m:TfctPh:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Breaker Loading
c:loading_w%Loading (Winding)
c:loading%Loading
c:ratfactยทRating factor
c:um_1p.u.Magnetising flux (Real part)
c:ymp.u.Magnetising admittance
c:tapRatioยทComplex winding ratio
c:ntapยทCurrent tap position
c:ntap_intยทTap, relative position
c:isatยทSaturated model
c:Inom_wkANominal current
c:um_2p.u.Magnetising flux (Imaginary part)
c:um_0p.u.Magnetising flux (0-Sequence)
c:ym0p.u.0-Seq. magn. admitt.
c:UstarkVStar-point voltage
c:IstarkAStar-point current
c:i0Deltap.u.0-Sequence circulating current in Delta-winding
c:I0DeltakA0-Sequence circulating current in Delta-Winding, Magnitude
n:ur:busNbusN: the terminalp.u.Voltage, Real Part
n:ui:busNbusN: the terminalp.u.Voltage, Imaginary Part
n:u:busNbusN: the terminalp.u.Voltage, Magnitude
n:upc:busNbusN: the terminal%Voltage, Magnitude
n:du:busNbusN: the terminal%Voltage Deviation
n:U:busNbusN: the terminalkVLine-Ground Voltage, Magnitude
n:phiu:busNbusN: the terminaldegVoltage, Angle
n:phiurel:busNbusN: the terminaldegVoltage, Relative Angle
n:Ul:busNbusN: the terminalkVLine-Line Voltage, Magnitude
n:u1:busNbusN: the terminalp.u.Voltage, Magnitude
n:u1pc:busNbusN: the terminal%Voltage, Magnitude
n:u1r:busNbusN: the terminalp.u.Positive-Sequence Voltage, Real Part
n:u1i:busNbusN: the terminalp.u.Positive-Sequence Voltage, Imaginary Part
n:ishc:busNbusN: the terminalp.u.Short-Circuit Current, magnitude
n:Ishc:busNbusN: the terminalkAShort-Circuit Current, magnitude
n:fe:busNbusN: the terminalp.u.Electrical Frequency
n:dfehz:busNbusN: the terminalHzDeviation of the El. Frequency
n:fehz:busNbusN: the terminalHzElectrical Frequency
n:frnom:busNbusN: the terminalHzNominal Frequency
n:ishcr:busNbusN: the terminalp.u.Short-Circuit Current, real
n:ishci:busNbusN: the terminalp.u.Short-Circuit Current, imag
n:dfedt:busNbusN: the terminalp.u./sDerivative of El. Frequency
n:ur:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:busNbusN: the terminalp.u.Zero-Sequence Voltage, Magnitude
n:U0:busNbusN: the terminalkVZero-Sequence Voltage, Magnitude
n:U0x3:busNbusN: the terminalkV3*U0
n:phiu0:busNbusN: the terminaldegZero-Sequence Voltage, Angle
n:U1:busNbusN: the terminalkVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:busNbusN: the terminaldegPositive-Sequence Voltage, Angle
n:u2:busNbusN: the terminalp.u.Negative-Sequence Voltage, Magnitude
n:U2:busNbusN: the terminalkVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:busNbusN: the terminaldegNegative-Sequence Voltage, Angle
n:U1l:busNbusN: the terminalkVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:busNbusN: the terminalkVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:busNbusN: the terminalp.u.Neutral-Ground Voltage, Magnitude
n:Un:busNbusN: the terminalkVNeutral-Ground Voltage, Magnitude
n:phiun:busNbusN: the terminaldegNeutral-Ground Voltage, Angle
n:upht:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:busNbusN: the terminalp.u.Average-Voltage, Magnitude
n:Um:busNbusN: the terminalkVAverage-Voltage, Magnitude
n:ishc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, magnitude
n:Ishc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, magnitude
n:inshc:busNbusN: the terminalp.u.Neutral Short-Circuit Current, magnitude
n:Inshc:busNbusN: the terminalkANeutral Short-Circuit Current, magnitude
n:ishcr:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, real
n:ishci:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, imag
s:nntapinยทTap, Controller input
s:I0rDeltakACirculating current in Delta-Winding, Real part
s:I0iDeltakACirculating current in Delta-Winding, Imaginary part

ElmTrmult emt simulation results

Read after ComInc (EMT) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:u0:busNbusN: the terminalp.u.Zero-Sequence-Voltage
m:u1r:busNbusN: the terminalp.u.Voltage Phasor, Real Part
m:u1i:busNbusN: the terminalp.u.Voltage Phasor, Imaginary Part
m:u1:busNbusN: the terminalp.u.Voltage Phasor, Magnitude
m:U1:busNbusN: the terminalkVLine-Ground Voltage Phasor, Magnitude
m:U1l:busNbusN: the terminalkVLine-Line Voltage Phasor, Magnitude
m:phiu1:busNbusN: the terminaldegVoltage Phasor, Angle
m:inet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, referred to network
m:I:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAPhase Current
m:i0:busNbusN: the terminalp.u.Zero-Sequence Current
m:I0:busNbusN: the terminalkAZero-Sequence Current
m:I0x3:busNbusN: the terminalkA3*I0
m:i1r:busNbusN: the terminalp.u.Current Phasor, Real Part
m:i1i:busNbusN: the terminalp.u.Current Phasor, Imaginary Part
m:i1:busNbusN: the terminalp.u.Current Phasor, Magnitude
m:I1:busNbusN: the terminalkACurrent Phasor, Magnitude
m:phii1:busNbusN: the terminaldegCurrent Phasor, Angle
m:P:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Psum:busNbusN: the terminalMWPower-Phasor, Active Power
m:Qsum:busNbusN: the terminalMvarPower Phasor, Reactive Part
m:Ssum:busNbusN: the terminalMVAPower Phasor, Apparent Power
m:i1P:busNbusN: the terminalp.u.Current Phasor, Active Current
m:i1Q:busNbusN: the terminalp.u.Current Phasor, Reactive Current
m:I1P:busNbusN: the terminalkACurrent Phasor, Active Current
m:I1Q:busNbusN: the terminalkACurrent Phasor, Reactive Current
m:u:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
m:i:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current
m:phiu1i1:busNbusN: the terminaldegAngle between Voltage and Current Phasor
m:Tfct:busNbusN: the terminalsFault Clearing Time
m:TfctPh:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:unet:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, referred to network
m:cosphi1:busNbusN: the terminalยทPower-Phasor, Power-Factor
c:tapRatioยทComplex winding ratio
c:ntapยทCurrent tap position
c:ntap_intยทTap, relative position
c:imaglocยทPosition of magn.ind.
c:UstarkVStar-point voltage
c:IstarkAStar-point current
c:I0DeltakACirculating current in Delta-winding, Magnitude
c:bmp.u.Magnetising inductance
c:gmp.u.Magnetising conductance
c:rep.u.Earth resistance
c:lep.u.Earth inductance
c:bm0p.u.0-Seq. magn. inductance
c:rm0p.u.0-Seq. magn. resistance
c:hpirad/sAngular frequency
c:i_satยทSaturated model
c:im_ap.u.Magnetising current, Phase a
c:im_bp.u.Magnetising current, Phase b
c:im_cp.u.Magnetising current, Phase c
c:phystkWHysteresis losses at rated operation
n:u:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
n:upc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Phase Voltage
n:U:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVPhase Voltage
n:ul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage
n:ulpc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced only%Line-Line Voltage
n:Ul:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage
n:u0:busNbusN: the terminalp.u.Zero-Sequence-Voltage
n:U0:busNbusN: the terminalkVZero-Sequence-Voltage
n:U0x3:busNbusN: the terminalkV3*U0
n:u1:busNbusN: the terminalp.u.Voltage Phasor, Magnitude
n:u1pc:busNbusN: the terminal%Voltage Phasor, Magnitude
n:u1r:busNbusN: the terminalp.u.Voltage Phasor, Real Part
n:u1i:busNbusN: the terminalp.u.Voltage Phasor, Imaginary Part
n:U1:busNbusN: the terminalkVVoltage Phasor, Magnitude
n:phiu1:busNbusN: the terminaldegVoltage Phasor, Angle
n:U1l:busNbusN: the terminalkVLine-Line Voltage Phasor, Magnitude
n:uln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage
n:Uln:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage
n:un:busNbusN: the terminalp.u.Neutral-Ground Voltage
n:Un:busNbusN: the terminalkVNeutral-Ground Voltage
n:ishc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current
n:Ishc:busN:AbusN: the terminal; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:inshc:busNbusN: the terminalp.u.Neutral Short-Circuit Current, magnitude
n:Inshc:busNbusN: the terminalkANeutral Short-Circuit Current, magnitude
n:fe:busNbusN: the terminalp.u.Electrical Frequency
n:dfehz:busNbusN: the terminalHzDeviation of the El. Frequency
n:fehz:busNbusN: the terminalHzElectrical Frequency
n:frnom:busNbusN: the terminalHzNominal Frequency
s:nntapinยทTap, Controller input
s:psim_rp.u.Magnetising flux (real part)
s:psim_ip.u.Magnetising flux (imaginary part)
s:psim_0p.u.Magnetising flux (0-sequence)
s:i0Deltap.u.0-Seq. current in Delta-winding
s:psim_ap.u.Magnetising flux
s:psim_bp.u.Magnetising flux
s:psim_cp.u.Magnetising flux

ElmTrmult dc load flow results

Read after ComLdf (DC) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:P:busNbusN: the terminalMWActive Power
m:Q:busNbusN: the terminalMvarReactive Power
c:loading_w%Loading (Winding)
c:loading%Loading
c:maxload%Max. loading
c:tapRatioยทComplex winding ratio
c:ntapยทCurrent tap position
c:ntap_intยทTap, relative position
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:dphiudegVoltage drop angle
c:maxloadpup.u.Max. loading
n:u:busNbusN: the terminalp.u.Voltage, Magnitude
n:upc:busNbusN: the terminal%Voltage, Magnitude
n:U:busNbusN: the terminalkVLine-Ground Voltage, Magnitude
n:phiu:busNbusN: the terminaldegVoltage, Angle
n:phiurel:busNbusN: the terminaldegVoltage, Relative Angle
n:Ul:busNbusN: the terminalkVLine-Line Voltage, Magnitude
n:u1:busNbusN: the terminalp.u.Voltage, Magnitude
n:Pgen:busNbusN: the terminalMWGeneration, Active Power
n:Pmot:busNbusN: the terminalMWMotor Load, Active Power
n:Pload:busNbusN: the terminalMWGeneral Load, Active Power
n:Pcomp:busNbusN: the terminalMWCompensation (Losses)
n:Pnet:busNbusN: the terminalMWExternal Networks, Active Power
n:Pflow:busNbusN: the terminalMWPower Flow, Active Power
s:nt_inยทTap, Input

Read after ComMod with GetAttribute. c: calculation parameter, s: signal (state or model variable).

AttributeUnitDescription
c:loading_w%Loading (Winding)
c:loading%Loading
c:ratfactยทRating factor
c:um_1p.u.Magnetising flux (Real part)
c:ymp.u.Magnetising admittance
c:tapRatioยทComplex winding ratio
c:ntapยทCurrent tap position
c:ntap_intยทTap, relative position
c:isatยทSaturated model
c:Inom_wkANominal current
s:nntapinยทTap, Controller input

ElmTrmult optimal power flow results

Read after ComOpf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:busNbusN: the terminalp.u.Voltage, Real Part, referred to network
m:uinet:busNbusN: the terminalp.u.Voltage, Imaginary Part, referred to network
m:u1r:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Real Part
m:u1i:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:busNbusN: the terminalp.u.Positive-Sequence-Voltage, Magnitude
m:U1:busNbusN: the terminalkVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:busNbusN: the terminalkVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:busNbusN: the terminaldegPositive-Sequence-Voltage, Angle
m:irnet:busNbusN: the terminalp.u.Current, Real Part, referred to network
m:iinet:busNbusN: the terminalp.u.Current, Imaginary Part, referred to network
m:inet:busNbusN: the terminalp.u.Current, Magnitude, referred to network
m:I:busNbusN: the terminalkACurrent, Magnitude
m:phii:busNbusN: the terminaldegCurrent, Angle
m:i1r:busNbusN: the terminalp.u.Positive-Sequence Current, Real Part
m:i1i:busNbusN: the terminalp.u.Positive-Sequence Current, Imaginary Part
m:i1:busNbusN: the terminalp.u.Positive-Sequence Current, Magnitude
m:I1:busNbusN: the terminalkAPositive-Sequence Current, Magnitude
m:phii1:busNbusN: the terminaldegPositive-Sequence Current, Angle
m:P:busNbusN: the terminalMWActive Power
m:Q:busNbusN: the terminalMvarReactive Power
m:S:busNbusN: the terminalMVAApparent Power
m:cosphi:busNbusN: the terminalยทPower Factor
m:tanphi:busNbusN: the terminalยทtan(phi)
m:Psum:busNbusN: the terminalMWTotal Active Power
m:Qsum:busNbusN: the terminalMvarTotal Reactive Power
m:Ssum:busNbusN: the terminalMVATotal Apparent Power
m:cosphisum:busNbusN: the terminalยทTotal Power Factor
m:tanphisum:busNbusN: the terminalยทTotal tan(phi)
m:i1P:busNbusN: the terminalp.u.Positive-Sequence Active Current
m:i1Q:busNbusN: the terminalp.u.Positive-Sequence Reactive Current
m:I1P:busNbusN: the terminalkAPositive-Sequence Active Current
m:I1Q:busNbusN: the terminalkAPositive-Sequence Reactive Current
m:ur:busNbusN: the terminalp.u.Voltage, Real Part
m:ui:busNbusN: the terminalp.u.Voltage, Imaginary Part
m:u:busNbusN: the terminalp.u.Voltage, Magnitude
m:ir:busNbusN: the terminalp.u.Current, Real Part
m:ii:busNbusN: the terminalp.u.Current, Imaginary Part
m:i:busNbusN: the terminalp.u.Current, Magnitude
m:phiui:busNbusN: the terminaldegAngle between Voltage and Current
m:phiu1i1:busNbusN: the terminaldegAngle between Voltage and Current in positive sequence system
m:Tfct:busNbusN: the terminalsFault Clearing Time
m:Brkload:busNbusN: the terminal%Breaker Loading
m:Spu:busNbusN: the terminalMVA/p.u.Apparent Power per p.u. Voltage
c:loading_w%Loading (Winding)
c:loading%Loading
c:loading_st%Short term loading
c:maxload%Max. loading
c:ratfactยทRating factor
c:um_1p.u.Magnetising flux (Real part)
c:ymp.u.Magnetising admittance
c:tapRatioยทComplex winding ratio
c:ntapยทCurrent tap position
c:ntap_intยทTap, relative position
c:i_uplimยทTap at maximum
c:i_lowlimยทTap at minimum
c:nCtrlIterยทNo. of CTRL-iterations
c:TctrlsController time constant
c:i_fixedtapยทFlag
c:PmeasMWMeasured active power
c:GmloadkWIron losses
c:XmloadkvarMagnetising losses
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:isatยทSaturated model
c:dphiudegVoltage drop angle
c:Inom_wkANominal current
c:maxloadpup.u.Max. loading
n:ur:busNbusN: the terminalp.u.Voltage, Real Part
n:ui:busNbusN: the terminalp.u.Voltage, Imaginary Part
n:u:busNbusN: the terminalp.u.Voltage, Magnitude
n:upc:busNbusN: the terminal%Voltage, Magnitude
n:du:busNbusN: the terminal%Voltage Deviation
n:U:busNbusN: the terminalkVLine-Ground Voltage, Magnitude
n:phiu:busNbusN: the terminaldegVoltage, Angle
n:phiurel:busNbusN: the terminaldegVoltage, Relative Angle
n:Ul:busNbusN: the terminalkVLine-Line Voltage, Magnitude
n:u1:busNbusN: the terminalp.u.Voltage, Magnitude
n:u1pc:busNbusN: the terminal%Voltage, Magnitude
n:u1r:busNbusN: the terminalp.u.Positive-Sequence Voltage, Real Part
n:u1i:busNbusN: the terminalp.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:busNbusN: the terminalMWGeneration, Active Power
n:Qgen:busNbusN: the terminalMvarGeneration, Reactive Power
n:Pmot:busNbusN: the terminalMWMotor Load, Active Power
n:Qmot:busNbusN: the terminalMvarMotor Load, Reactive Power
n:Pload:busNbusN: the terminalMWGeneral Load, Active Power
n:Qload:busNbusN: the terminalMvarGeneral Load, Reactive Power
n:Pcomp:busNbusN: the terminalMWCompensation (Losses)
n:Qcomp:busNbusN: the terminalMvarCompensation
n:Pnet:busNbusN: the terminalMWExternal Networks, Active Power
n:Qnet:busNbusN: the terminalMvarExternal Networks, Reactive Power
n:Pflow:busNbusN: the terminalMWPower Flow, Active Power
n:Qflow:busNbusN: the terminalMvarPower Flow, Reactive Power
n:Pout:busNbusN: the terminalMWOutgoing Flow, Active Power
n:Qout:busNbusN: the terminalMvarOutgoing Power, Reactive Power
n:Sout:busNbusN: the terminalMVAOutgoing Power, Apparent Power
n:cosphiout:busNbusN: the terminalยทOutgoing Power, Power Factor
n:Pbalance:busNbusN: the terminalMWActive Power Balance (=0)
n:Qbalance:busNbusN: the terminalMvarReactive Power Balance (=0)
n:LossPdown:busNbusN: the terminalMWLosses, downstream
n:LossQdown:busNbusN: the terminalMvarLosses, downstream (Reactive Power)
n:LossPdownload:busNbusN: the terminalMWLoad losses, downstream
n:LossQdownload:busNbusN: the terminalMvarLoad losses, downstream
n:LossPdownnoload:busNbusN: the terminalMWNo load losses, downstream
n:LossQdownnoload:busNbusN: the terminalMvarNo load losses, downstream
n:du_feed:busNbusN: the terminal%Difference from voltage at start of feeder

ElmTrmult basic data