ElmVoltreg attributesPowerFactory Step-Voltage Regulator

Every attribute of the PowerFactory Step-Voltage Regulator (ElmVoltreg): 140 input parameters and 877 result variables, with units and meaning. Copy a name into GetAttribute or SetAttribute.

What ElmVoltreg is

A step-voltage regulator: an autotransformer with a tap changer that holds the voltage along a distribution feeder.

Class
ElmVoltreg, element class
PowerFactory name
Step-Voltage Regulator
Terminal suffix
:buss s-side, :busl l-side
Attributes
140 input parameters and 877 result variables, in 7 calculations

Read and write ElmVoltreg in Python

import powerfactory

app = powerfactory.GetApplication()          # GetApplicationExt() from outside PowerFactory
app.GetFromStudyCase("ComLdf").Execute()      # results exist after a calculation

for obj in app.GetCalcRelevantObjects("*.ElmVoltreg"):
    loading = obj.GetAttribute("c:loading")       # Loading, %
    print(obj.loc_name, loading)

obj = app.GetCalcRelevantObjects("*.ElmVoltreg")[0]
obj.SetAttribute("outserv", 1)                # take it out of service
  • A result at a terminal of the step-voltage regulator needs the terminal in its name: m:P:buss, not m:P, which raises AttributeError.
  • An input parameter is read and written with or without its e: prefix: GetAttribute("outserv") and GetAttribute("e:outserv") give the same value.
  • RMS and EMT variables change over time: record them in a results object (ElmRes) to read the whole curve. GetAttribute after a run gives the value at the last time step.

ElmVoltreg input parameters

The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.

AttributeUnitDescription
loc_nameยทName
chr_nameยทCharacteristic Name
for_nameยทForeign Key
dat_srcยทData source
sernumยทSerial Number
commissionDateยทCommissioning Date
appr_modbyยทModified by
outservยทOut of Service
iZoneBusยทZone
iAreaBusยทArea
lossAssignยทLoss assignment
constrยทYear of Construction
appr_statusยทStatus
i_pcReglimยทLimited voltage control range
pcReglimยทLimit (in % of max. range)
pcReglimMinยทLimit (in % of max. range)
nntap1ยทTap 1 position
nntap2ยทTap 2 position
nntap3ยทTap 3 position
igangยทGang operated taps
ilcphยทPhase
ildc_lmยทVoltage limit
ldcrxcompยทInternally adjust Rset, Xset for closed- and open-delta configurations
ntrcnยทAutomatic tap changing
ildcยทLine drop compensation (LDC)
i_contยทTap changer
iRevPQยทReverse power operation
ictrlModRevยทControl mode
ildcRevยทLine drop compensation (LDC)
i_tapiniยทEstimate tap position
iIntTapCtrlยทUse integrated tap controller
iperfectยทIdeal component
i_uoptยทTap Changer
ionlyPreยทOptimise in DC OPF
i_uoptContยทControl mode
iOPFCloadยทMax. loading constraint
isCtrlTapยทTap Changer
isCtrlTapContยทControl Mode
isConstrLoadingยทMax. loading constraint for Unit Commitment
isMaxLoadSoftNlinยทPenalty costs for soft constraints
allowOutDistFacFiltยทAllow filtering by outage distribution factor
allowMarginFiltยทAllow filtering by constraint margin
allowCntConstrFiltยทAllow contingency filtering by number of critical constraints
isSepCntConstrTypeยทSeparate constraint type
cntConstrTypeยทContingency-constraint type
isSepCntMaxAllowedLoadingยทSeparate max. allowed loading
ctrlUsageยทTap Changer
curativeLimยทMax. curative tap deviation
isConstrLoadingPlacementยทMax. loading constraint for Optimal Equipment Placement
isCtrlTapPlacementยทPosition of tap 1
ratfacยทRating factor
re0OhmResistance, Re
xe0OhmReactance, Xe
ldcctACurrent transformer rating
ldcptยทVoltage transformer ratio
ldcrsVRset
ldcxsVXset
ldc_lmupp.u.Upper
ldc_lmlowp.u.Lower
ldc_deadband%Deadband
usetpp.u.Voltage setpoint
usp_upp.u.Upper voltage bound
usp_lowp.u.Lower voltage bound
TctrlsController time constant
RevThresh%Current deadband (+/-)
usetpRevp.u.Voltage setpoint
usp_upRevp.u.Upper voltage bound
usp_lowRevp.u.Lower voltage bound
ldcrsRevVRset
ldcxsRevVXset
maxload%Max. loading
GPSlatdegLatitude / Northing
GPSlondegLongitude / Easting
scalingFacSoftConstrOpfยทWeighting factor for soft constraint penalty
scalingFacSoftConstrCostยทCost scaling factor
cntMaxAllowedLoading%Max. allowed loading in Contingencies
penaltyCostsUSDPenalty costs per tap deviation
curativeCostsUSDCosts per curative tap deviation
installCostUSDInstallation costs
maintenCostUSD/aMaintenance costs
appr_modifยทModified
cimRdfIdยทRDF ID
descยทDescription
sOpCommentยทOperator comment
fold_idยทIn Folder
typ_idยทTypeObject: TypVoltreg
bussยทS-SideObject: StaCubic
buslยทL-SideObject: StaCubic
busslยทSL-NeutralObject: StaCubic
pRatingยทThermal ratingObject: IntThrating
doc_idยทAdditional Data
pOwnerยทOwnerObject: ElmOwner
pOperatorยทOperatorObject: ElmOperator
pStochStoTyptrfElement model
cpHeadFoldยทHead Folder
buss_barยทS-Side
busl_barยทL-Side
bussl_barยทSL-Neutral
cpGridยทGridObject: ElmNet
cpZoneยทZoneObject: ElmZone
cpAreaยทAreaObject: ElmArea
cpFeedยทFeederObject: ElmFeeder
ciDistยทDistance from infeed in number of buses
ciLaterยทLateral Index
ciDistRootยทDistance from first infeed in number of buses
ciDistAllยทDistance from infeed in number of buses including switches
ciDistAllRootยทDistance from first infeed in number of buses including switches
cpOwnerยทOwnerObject: ElmOwner
cpOperatorยทOperatorObject: ElmOperator
cpBranchยทBranchObject: ElmBranch
cpSiteยทSiteObject: ElmSite
cpSubstatยทSubstationObject: ElmSubstat,ElmTrfstat
cpMeteostatยทMeteo StationObject: ElmMeteostat
ciOutagedยทPlanned Outage
ciEnergizedยทEnergized
ciEarthedยทEarthed
cDisplayNameยทDisplay Name
cpSupplyTransformerยทSupplying TransformerObject: ElmTr?,ElmTrmult
cpSupplyTrfStationยทSupplying Secondary SubstationObject: ElmTrfstat
cpSupplySubstationยทSupplying SubstationObject: ElmSubstat
Inom_aANominal current (act.)
InomANominal current
SnomkVANominal Power
Snom_akVANominal Power (act.)
cgndยทStar point
cneutconยทN-Connection
dutap%Additional voltage per tap
cInomAContinuous current rating at selected voltage control range
FOR11/aForced Outage Rate
FOEh/aForced Outage Expectancy
FODhForced Outage Duration
pTypStochStoTyptrfType model
CCEarFr1/aFrequency of single earth faults
CCEarRepMuhRepair duration
CCEarProb%Conditional probability of a second earth fault
cAllowOutDistFacFiltยทAllow filtering by outage distribution factor
cAllowMarginFiltยทAllow filtering by constraint margin
cAllowCntConstrFiltยทAllow contingency filtering by number of critical constraints
cIsSepCntConstrTypeยทSeparate constraint type
cIsSepCntMaxAllowedLoadingยทSeparate max. allowed loading

ElmVoltreg load flow results

Read after ComLdf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bussor :buslp.u.Voltage, Real Part, referred to network
m:uinet:bussor :buslp.u.Voltage, Imaginary Part, referred to network
m:u1r:bussor :buslp.u.Positive-Sequence-Voltage, Real Part
m:u1i:bussor :buslp.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bussor :buslp.u.Positive-Sequence-Voltage, Magnitude
m:U1:bussor :buslkVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bussor :buslkVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bussor :busldegPositive-Sequence-Voltage, Angle
m:irnet:bussor :buslp.u.Current, Real Part, referred to network
m:iinet:bussor :buslp.u.Current, Imaginary Part, referred to network
m:inet:bussor :buslp.u.Current, Magnitude, referred to network
m:I:bussor :buslkACurrent, Magnitude
m:phii:bussor :busldegCurrent, Angle
m:i1r:bussor :buslp.u.Positive-Sequence Current, Real Part
m:i1i:bussor :buslp.u.Positive-Sequence Current, Imaginary Part
m:i1:bussor :buslp.u.Positive-Sequence Current, Magnitude
m:I1:bussor :buslkAPositive-Sequence Current, Magnitude
m:phii1:bussor :busldegPositive-Sequence Current, Angle
m:P:bussor :buslMWActive Power
m:Q:bussor :buslMvarReactive Power
m:S:bussor :buslMVAApparent Power
m:cosphi:bussor :buslยทPower Factor
m:tanphi:bussor :buslยทtan(phi)
m:Psum:bussor :buslMWTotal Active Power
m:Qsum:bussor :buslMvarTotal Reactive Power
m:Ssum:bussor :buslMVATotal Apparent Power
m:cosphisum:bussor :buslยทTotal Power Factor
m:tanphisum:bussor :buslยทTotal tan(phi)
m:i1P:bussor :buslp.u.Positive-Sequence Active Current
m:i1Q:bussor :buslp.u.Positive-Sequence Reactive Current
m:I1P:bussor :buslkAPositive-Sequence Active Current
m:I1Q:bussor :buslkAPositive-Sequence Reactive Current
m:ur:bussor :buslp.u.Voltage, Real Part
m:ui:bussor :buslp.u.Voltage, Imaginary Part
m:u:bussor :buslp.u.Voltage, Magnitude
m:ir:bussor :buslp.u.Current, Real Part
m:ii:bussor :buslp.u.Current, Imaginary Part
m:i:bussor :buslp.u.Current, Magnitude
m:phiui:bussor :busldegAngle between Voltage and Current
m:phiu1i1:bussor :busldegAngle between Voltage and Current in positive sequence system
m:Tfct:bussor :buslsFault Clearing Time
m:Brkload:bussor :busl%Breaker Loading
m:Spu:bussor :buslMVA/p.u.Apparent Power per p.u. Voltage
m:urnet:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bussor :buslp.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bussor :busldegZero-Sequence-Voltage, Angle
m:u2:bussor :buslp.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bussor :busldegNegative-Sequence-Voltage, Angle
m:irnet:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part, referred to network
m:iinet:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part, referred to network
m:inet:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude, referred to network
m:I:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bussor :buslp.u.Zero-Sequence Current, Real Part
m:i0i:bussor :buslp.u.Zero-Sequence Current, Imaginary Part
m:i0:bussor :buslp.u.Zero-Sequence Current, Magnitude
m:I0:bussor :buslkAZero-Sequence Current, Magnitude
m:I0x3:bussor :buslkA3*I0
m:phii0:bussor :busldegZero-Sequence Current, Angle
m:i2r:bussor :buslp.u.Negative-Sequence Current, Real Part
m:i2i:bussor :buslp.u.Negative-Sequence Current, Imaginary Part
m:i2:bussor :buslp.u.Negative-Sequence Current, Magnitude
m:I2:bussor :buslkANegative-Sequence Current, Magnitude
m:phii2:bussor :busldegNegative-Sequence Current, Angle
m:ubfacI:bussor :busl%Current Unbalance Factor
m:ubfacS:bussor :busl%Power Unbalance Factor
m:P:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyยทPower Factor
m:tanphi:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyยทtan(phi)
m:Pln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bussor :buslMWPositive Sequence Active Power
m:Q1:bussor :buslMvarPositive Sequence Reactive Power
m:P2:bussor :buslMWNegative Sequence Active Power
m:Q2:bussor :buslMvarNegative Sequence Reactive Power
m:P0:bussor :buslMWZero Sequence Active Power
m:Q0:bussor :buslMvarZero Sequence Reactive Power
m:i2P:bussor :buslp.u.Negative-Sequence Active Current
m:i2Q:bussor :buslp.u.Negative-Sequence Reactive Current
m:I2P:bussor :buslkANegative-Sequence Active Current
m:I2Q:bussor :buslkANegative-Sequence Reactive Current
m:ur:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bussor :busldegAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bussor :busldegAngle between Voltage and Current in negative sequence system
m:TfctPh:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:buss:Aor :busl; per phase :A, :B, :C, unbalanced only%Breaker Loading
c:loading%Loading
c:maxload%Max. Loading
c:ntpminยทTap, Min. Position
c:ntpmaxยทTap, Max. Position
c:dutยทTap
c:ratfacยทRating Factor
c:snomMVARated Power
c:zsp.u.Series Impedance
c:dup.u.Voltage Drop
c:dupc%Voltage Drop
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:usetp2p.u.Voltage Setpoint^2
c:usetpinip.u.Complex Voltage Setpoint
c:i_uplimยทTap at max.
c:i_lowlimยทTap at min.
c:nCtrlIterยทNo. of CTRL-iterations
c:TctrlsController Time Constant
c:ctrl_setp.u.Setpoint
c:ctrl_upp.u.Upper Bound
c:ctrl_lowp.u.Lower Bound
c:i_fixedtapยทFlag
c:ildcยทFlag
c:ldc_reffp.u.Effective compensation resistance
c:ldc_xeffp.u.Effective compensation reactance
c:i_contยทContinuous Tap
c:maxloadpup.u.Max. Loading
c:nntapยทTap, Current Position
c:nntap1ยทTap 1, Current Position
c:nntap2ยทTap 2, Current Position
c:nntap3ยทTap 3, Current Position
c:i_uplim:Aper phase :A, :B, :C, unbalanced onlyยทTap at max.
c:i_lowlim:Aper phase :A, :B, :C, unbalanced onlyยทTap at min.
c:loading_st%Short Term Loading
c:UstarkVStar-Point Voltage
c:IstarkAStar-Point Current
n:ur:bussor :buslp.u.Voltage, Real Part
n:ui:bussor :buslp.u.Voltage, Imaginary Part
n:u:bussor :buslp.u.Voltage, Magnitude
n:upc:bussor :busl%Voltage, Magnitude
n:du:bussor :busl%Voltage Deviation
n:U:bussor :buslkVLine-Ground Voltage, Magnitude
n:phiu:bussor :busldegVoltage, Angle
n:phiurel:bussor :busldegVoltage, Relative Angle
n:Ul:bussor :buslkVLine-Line Voltage, Magnitude
n:u1:bussor :buslp.u.Voltage, Magnitude
n:u1pc:bussor :busl%Voltage, Magnitude
n:u1r:bussor :buslp.u.Positive-Sequence Voltage, Real Part
n:u1i:bussor :buslp.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bussor :buslMWGeneration, Active Power
n:Qgen:bussor :buslMvarGeneration, Reactive Power
n:Pmot:bussor :buslMWMotor Load, Active Power
n:Qmot:bussor :buslMvarMotor Load, Reactive Power
n:Pload:bussor :buslMWGeneral Load, Active Power
n:Qload:bussor :buslMvarGeneral Load, Reactive Power
n:Pcomp:bussor :buslMWCompensation (Losses)
n:Qcomp:bussor :buslMvarCompensation
n:Pnet:bussor :buslMWExternal Networks, Active Power
n:Qnet:bussor :buslMvarExternal Networks, Reactive Power
n:Pflow:bussor :buslMWPower Flow, Active Power
n:Qflow:bussor :buslMvarPower Flow, Reactive Power
n:Pout:bussor :buslMWOutgoing Flow, Active Power
n:Qout:bussor :buslMvarOutgoing Power, Reactive Power
n:Sout:bussor :buslMVAOutgoing Power, Apparent Power
n:cosphiout:bussor :buslยทOutgoing Power, Power Factor
n:Pbalance:bussor :buslMWActive Power Balance (=0)
n:Qbalance:bussor :buslMvarReactive Power Balance (=0)
n:LossPdown:bussor :buslMWLosses, downstream
n:LossQdown:bussor :buslMvarLosses, downstream (Reactive Power)
n:LossPdownload:bussor :buslMWLoad losses, downstream
n:LossQdownload:bussor :buslMvarLoad losses, downstream
n:LossPdownnoload:bussor :buslMWNo load losses, downstream
n:LossQdownnoload:bussor :buslMvarNo load losses, downstream
n:du_feed:bussor :busl%Difference from voltage at start of feeder
n:ur:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:buss:Aor :busl; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:buss:Aor :busl; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:buss:Aor :busl; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bussor :buslp.u.Zero-Sequence Voltage, Magnitude
n:U0:bussor :buslkVZero-Sequence Voltage, Magnitude
n:U0x3:bussor :buslkV3*U0
n:phiu0:bussor :busldegZero-Sequence Voltage, Angle
n:U1:bussor :buslkVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bussor :busldegPositive-Sequence Voltage, Angle
n:u2:bussor :buslp.u.Negative-Sequence Voltage, Magnitude
n:U2:bussor :buslkVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bussor :busldegNegative-Sequence Voltage, Angle
n:U1l:bussor :buslkVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bussor :buslkVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bussor :buslp.u.Neutral-Ground Voltage, Magnitude
n:Un:bussor :buslkVNeutral-Ground Voltage, Magnitude
n:phiun:bussor :busldegNeutral-Ground Voltage, Angle
n:upht:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bussor :buslp.u.Average-Voltage, Magnitude
n:Um:bussor :buslkVAverage-Voltage, Magnitude
n:uphtmin:bussor :buslp.u.Minimum of Phase Technology dependent Voltage, Magnitude
n:uphtmax:bussor :buslp.u.Maximum of Phase Technology dependent Voltage, Magnitude
n:ubfac:bussor :busl%Unbalance Factor
s:nt_inยทTap, Input
s:nt_in1ยทTap 1, Input
s:nt_in2ยทTap 2, Input
s:nt_in3ยทTap 3, Input

ElmVoltreg short-circuit results

Read after ComShc with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:I:bussor :buslkAShort-Circuit Current, Magnitude
m:phii:bussor :busldegPhase Current, Angle
m:i1:bussor :buslp.u.Positive-Sequence Current, Magnitude
m:I1:bussor :buslkAPositive-Sequence Current, Magnitude
m:phii1:bussor :busldegPositive-Sequence Current, Angle
m:P:bussor :buslMWActive Power
m:Q:bussor :buslMvarReactive Power
m:i1P:bussor :buslp.u.Positive-Sequence Active Current
m:i1Q:bussor :buslp.u.Positive-Sequence Reactive Current
m:I1P:bussor :buslkAPositive-Sequence Active Current
m:I1Q:bussor :buslkAPositive-Sequence Reactive Current
m:phiui:bussor :busldegAngle between Voltage and Current
m:phiu1i1:bussor :busldegAngle between Voltage and Current in Positive-Sequence System
m:Tfct:bussor :buslsFault Clearing Time
m:Ikss:bussor :buslkAInitial Short-Circuit Current
m:ikss:bussor :buslp.u.Initial Short-Circuit Current, Magnitude
m:Skss:bussor :buslMVAInitial Short-Circuit Power
m:ip:bussor :buslkAPeak Short-Circuit Current
m:maxIkss:bussor :buslkAMax. Initial Short-Circuit Current
m:maxip:bussor :buslkAMax. Peak Short-Circuit Current
m:maxIth:bussor :buslkAMax. Thermal equivalent Short-Circuit Current
m:maxIb:bussor :buslkAMax. Breaking Current
m:R:bussor :buslOhmFault Impedance, Real Part
m:X:bussor :buslOhmFault Impedance, Imaginary Part
m:Z:bussor :buslOhmFault Impedance, Magnitude
m:phiz:bussor :busldegFault Impedance, Angle
m:Rs:bussor :buslOhmSource Impedance, Real Part
m:Xs:bussor :buslOhmSource Impedance, Imaginary Part
m:Zs:bussor :buslOhmSource Impedance, Magnitude
m:phizs:bussor :busldegSource Impedance, Angle
m:BrkIpload:bussor :busl%Breaker Loading (peak)
m:Ib:bussor :buslkAShort-Circuit Breaking Current
m:Sb:bussor :buslMVAShort-Circuit Breaking Power
m:Ith:bussor :buslkAThermal equivalent Short-Circuit Current
m:zSbase:bussor :buslp.u.Fault Impedance, Magnitude
m:XtoR:bussor :buslยทX/R ratio
m:cosphiui:bussor :buslยทcosphi
m:BrkIbload:bussor :busl%Breaker Loading (breaking)
m:BrkmaxIb:bussor :buslkAMax. Breaking Current (breaker time)
m:Ik:bussor :buslkASteady-State Short-Circuit Current
m:I:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, Magnitude
m:phii:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:I0:bussor :buslkAZero-Sequence Current, Magnitude
m:I0x3:bussor :buslkA3*I0
m:phii0:bussor :busldegZero-Sequence Current, Angle
m:I2:bussor :buslkANegative-Sequence Current, Magnitude
m:phii2:bussor :busldegNegative-Sequence Current, Angle
m:P:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:Psum:bussor :buslMWTotal Active Power
m:Qsum:bussor :buslMvarTotal Reactive Power
m:cosphisum:bussor :buslยทTotal Power Factor
m:P2:bussor :buslMWP2
m:Q2:bussor :buslMvarQ2
m:P0:bussor :buslMWP0
m:phiui:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bussor :busldegAngle between Voltage and Current in Zero-Sequence System
m:phiu2i2:bussor :busldegAngle between Voltage and Current in Negative-Sequence System
m:TfctPh:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:Ikss:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
m:ikss:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Initial Short-Circuit Current, Magnitude
m:Skss:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
m:Skssx3:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
m:ip:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
m:Z:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyOhmFault Impedance, Magnitude
m:phiz:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegFault Impedance, Angle
m:Zl:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyOhmLine-Line Fault Impedance, Magnitude
m:phizl:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegLine-Line Fault Impedance, Angle
m:Z0:bussor :buslOhmZero-Sequence Fault Impedance, Magnitude
m:phiz0:bussor :busldegZero-Sequence Fault Impedance, Angle
m:z0Sbase:bussor :buslp.u.Zero-Sequence Fault Impedance, Magnitude
m:cosphiu1i1:bussor :buslยทPositive-Sequence cosphi
m:I0x3watt:bussor :buslkAEarth-Fault Residual Current
m:I0x3var:bussor :buslkACapacitive Earth-Fault Current
m:Q0cap:bussor :buslMvarQ0 capacitive
m:Rfrel:bussor :buslOhmRelay Impedance, Real Part
m:Xfrel:bussor :buslOhmRelay Impedance, Imaginary Part
m:Zfrel:bussor :buslOhmRelay Impedance, Magnitude
m:phizfrel:bussor :busldegRelay Impedance, Angle
m:Zf:bussor :buslOhmMeas. Fault Impedance, Magnitude
m:phizf:bussor :busldegMeas. Fault Impedance, Angle
c:snomMVARated Power
c:zsp.u.Series Impedance
c:pT%Range of Voltage Adjustment
c:UstarkVStar-Point Voltage
c:IstarkAStar-Point Current
n:ur:bussor :buslp.u.Voltage, Real Part
n:ui:bussor :buslp.u.Voltage, Imaginary Part
n:u:bussor :buslp.u.Voltage, Magnitude
n:upc:bussor :busl%Voltage, Magnitude
n:du:bussor :busl%Voltage Deviation
n:U:bussor :buslkVLine-Ground Voltage, Magnitude
n:phiu:bussor :busldegVoltage, Angle
n:Ul:bussor :buslkVLine-Line Voltage, Magnitude
n:u1:bussor :buslp.u.Voltage, Magnitude
n:u1pc:bussor :busl%Voltage, Magnitude
n:u1r:bussor :buslp.u.Positive-Sequence Voltage, Real Part
n:u1i:bussor :buslp.u.Positive-Sequence Voltage, Imaginary Part
n:Ikss:bussor :buslkAInitial Short-Circuit Current
n:I:bussor :buslkAShort-Circuit Current
n:phii:bussor :busldegPhase Current, Angle
n:Skss:bussor :buslMVAInitial Short-Circuit Power
n:ip:bussor :buslkAPeak Short-Circuit Current
n:Ib:bussor :buslkAShort-Circuit Breaking Current
n:Sb:bussor :buslMVAShort-Circuit Breaking Power
n:idc:bussor :buslkADecaying Component
n:Ith:bussor :buslkAThermal equivalent Short-Circuit Current
n:R1toX1:bussor :buslยทR1/X1 ratio (Zk")
n:X1toR1:bussor :buslยทX1/R1 ratio (Zk")
n:R:bussor :buslOhmShort-Circuit Impedance, Real Part
n:X:bussor :buslOhmShort-Circuit Impedance, Imaginary Part
n:Z:bussor :buslOhmShort-Circuit Impedance, Magnitude
n:phiz:bussor :busldegShort-Circuit Impedance, Angle
n:urpref:bussor :buslp.u.Pre-fault Voltage, Real Part
n:uipref:bussor :buslp.u.Pre-fault Voltage, Imaginary Part
n:upref:bussor :buslp.u.Pre-fault Voltage, Magnitude
n:uprefpc:bussor :busl%Pre-fault Voltage, Magnitude
n:Upref:bussor :buslkVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bussor :buslkVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bussor :busldegPre-fault Voltage, Angle
n:phiui:bussor :busldegAngle between Voltage and Current
n:Ithload:bussor :busl%Loading, Thermal equivalent Current
n:Ipload:bussor :busl%Loading, Peak Short-Circuit Current
n:Ithrtk:bussor :buslkARated Short-Time Current (Tk)
n:XtoR:bussor :buslยทX/R ratio (peak)
n:RtoX:bussor :buslยทR/X ratio (peak)
n:XtoR_b:bussor :buslยทX/R ratio (dc)
n:RtoX_b:bussor :buslยทR/X ratio (dc)
n:fctof_b:bussor :buslยทEquivalent Frequency fc/f (dc)
n:rSbase:bussor :buslp.u.Short-Circuit Impedance, Real Part
n:xSbase:bussor :buslp.u.Short-Circuit Impedance, Imaginary Part
n:zSbase:bussor :buslp.u.Short-Circuit Impedance, Magnitude
n:Tn:bussor :buslmsGrid Time Constant
n:Ik:bussor :buslkASteady-State Short-Circuit Current
n:cfac:bussor :buslยทVoltage Factor
n:Iasy:bussor :buslkAAsymmetrical Breaking Current
n:ur:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:buss:Aor :busl; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:buss:Aor :busl; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:buss:Aor :busl; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bussor :buslp.u.Zero-Sequence Voltage, Magnitude
n:U0:bussor :buslkVZero-Sequence Voltage, Magnitude
n:U0x3:bussor :buslkV3*U0
n:phiu0:bussor :busldegZero-Sequence Voltage, Angle
n:U1:bussor :buslkVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bussor :busldegPositive-Sequence Voltage, Angle
n:u2:bussor :buslp.u.Negative-Sequence Voltage, Magnitude
n:U2:bussor :buslkVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bussor :busldegNegative-Sequence Voltage, Angle
n:U1l:bussor :buslkVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bussor :buslkVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bussor :buslp.u.Neutral-Ground Voltage, Magnitude
n:Un:bussor :buslkVNeutral-Ground Voltage, Magnitude
n:phiun:bussor :busldegNeutral-Ground Voltage, Angle
n:upht:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:Ikss:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
n:I:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:phii:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
n:Skss:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
n:Skssx3:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
n:ip:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
n:Ib:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Breaking Current
n:Sb:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMVAShort-Circuit Breaking Power
n:Ith:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykAThermal equivalent Short-Circuit Current
n:Ithmax:bussor :buslkAMax. Thermal equivalent Short-Circuit Current
n:R0:bussor :buslOhmZero-Sequence Impedance, Real Part
n:X0:bussor :buslOhmZero-Sequence Impedance, Imaginary Part
n:Z0:bussor :buslOhmZero-Sequence Impedance, Magnitude
n:phiz0:bussor :busldegZero-Sequence Impedance, Angle
n:r0Sbase:bussor :buslp.u.Zero-Sequence Impedance, Real Part
n:x0Sbase:bussor :buslp.u.Zero-Sequence Impedance, Imaginary Part
n:z0Sbase:bussor :buslp.u.Zero-Sequence Impedance, Magnitude
n:R1:bussor :buslOhmPositive-Sequence Impedance, Real Part
n:X1:bussor :buslOhmPositive-Sequence Impedance, Imaginary Part
n:Z1:bussor :buslOhmPositive-Sequence Impedance, Magnitude
n:phiz1:bussor :busldegPositive-Sequence Impedance, Angle
n:r1Sbase:bussor :buslp.u.Positive-Sequence Impedance, Real Part
n:x1Sbase:bussor :buslp.u.Positive-Sequence Impedance, Imaginary Part
n:z1Sbase:bussor :buslp.u.Positive-Sequence Impedance, Magnitude
n:R2:bussor :buslOhmNegative-Sequence Impedance, Real Part
n:X2:bussor :buslOhmNegative-Sequence Impedance, Imaginary Part
n:Z2:bussor :buslOhmNegative-Sequence Impedance, Magnitude
n:phiz2:bussor :busldegNegative-Sequence Impedance, Angle
n:r2Sbase:bussor :buslp.u.Negative-Sequence Impedance, Real Part
n:x2Sbase:bussor :buslp.u.Negative-Sequence Impedance, Imaginary Part
n:z2Sbase:bussor :buslp.u.Negative-Sequence Impedance, Magnitude
n:R0toX0:bussor :buslยทR0/X0 ratio (Zk")
n:X0toR0:bussor :buslยทX0/R0 ratio (Zk")
n:R2toX2:bussor :buslยทR2/X2 ratio (Zk")
n:X2toR2:bussor :buslยทX2/R2 ratio (Zk")
n:R:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Ground
n:X:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Ground
n:Z:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Ground
n:phiz:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Ground
n:Rl:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Line
n:Xl:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Line
n:Zl:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Line
n:phizl:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Line
n:Rln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Neutral
n:Xln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Neutral
n:Zln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Neutral
n:phizln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Neutral
n:Rn:bussor :buslOhmNetwork Resistance, Neutral
n:Xn:bussor :buslOhmNetwork Reactance, Neutral
n:Zn:bussor :buslOhmNetwork Impedance, Neutral
n:phizn:bussor :busldegAngle of Network Impedance, Neutral
n:eff:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyยทEarth Fault Factor
n:X0toX1:bussor :buslยทX0/X1
n:In:bussor :buslkANeutral Current, Magnitude
n:phiin:bussor :busldegNeutral Current, Angle
n:I0:bussor :buslkAZero-Sequence Current, Magnitude
n:I0x3:bussor :buslkA3*I0
n:phii0:bussor :busldegZero-Sequence Current, Angle
n:I1:bussor :buslkAPositive-Sequence Current, Magnitude
n:phii1:bussor :busldegPositive-Sequence Current, Angle
n:I2:bussor :buslkANegative-Sequence Current, Magnitude
n:phii2:bussor :busldegNegative-Sequence Current, Angle
n:urpref:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Real Part
n:uipref:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Imaginary Part
n:upref:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Magnitude
n:uprefpc:buss:Aor :busl; per phase :A, :B, :C, unbalanced only%Pre-fault Voltage, Magnitude
n:Upref:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegPre-fault Voltage, Angle
n:phiui:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
n:phiu1i1:bussor :busldegAngle between Voltage and Current in positive sequence system
n:phiu2i2:bussor :busldegAngle between Voltage and Current in negative sequence system
n:phiu0i0:bussor :busldegAngle between Voltage and Current in zero-sequence system
n:Ik:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykASteady-State Short-Circuit Current
n:in:bussor :buslp.u.Neutral Current, Magnitude
n:i0r:bussor :buslp.u.Zero-Sequence Current, Real Part
n:i0i:bussor :buslp.u.Zero-Sequence Current, Imaginary Part
n:i0:bussor :buslp.u.Zero-Sequence Current, Magnitude
n:i1r:bussor :buslp.u.Positive-Sequence Current, Real Part
n:i1i:bussor :buslp.u.Positive-Sequence Current, Imaginary Part
n:i1:bussor :buslp.u.Positive-Sequence Current, Magnitude
n:i2r:bussor :buslp.u.Negative-Sequence Current, Real Part
n:i2i:bussor :buslp.u.Negative-Sequence Current, Imaginary Part
n:i2:bussor :buslp.u.Negative-Sequence Current, Magnitude

ElmVoltreg rms simulation results

Read after ComInc (RMS) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bussor :buslp.u.Voltage, Real Part, referred to network
m:uinet:bussor :buslp.u.Voltage, Imaginary Part, referred to network
m:u1r:bussor :buslp.u.Positive-Sequence-Voltage, Real Part
m:u1i:bussor :buslp.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bussor :buslp.u.Positive-Sequence-Voltage, Magnitude
m:U1:bussor :buslkVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bussor :buslkVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bussor :busldegPositive-Sequence-Voltage, Angle
m:irnet:bussor :buslp.u.Current, Real Part, referred to network
m:iinet:bussor :buslp.u.Current, Imaginary Part, referred to network
m:inet:bussor :buslp.u.Current, Magnitude, referred to network
m:I:bussor :buslkACurrent, Magnitude
m:phii:bussor :busldegCurrent, Angle
m:i1r:bussor :buslp.u.Positive-Sequence Current, Real Part
m:i1i:bussor :buslp.u.Positive-Sequence Current, Imaginary Part
m:i1:bussor :buslp.u.Positive-Sequence Current, Magnitude
m:I1:bussor :buslkAPositive-Sequence Current, Magnitude
m:phii1:bussor :busldegPositive-Sequence Current, Angle
m:P:bussor :buslMWActive Power
m:Q:bussor :buslMvarReactive Power
m:S:bussor :buslMVAApparent Power
m:cosphi:bussor :buslยทPower Factor
m:tanphi:bussor :buslยทtan(phi)
m:Psum:bussor :buslMWTotal Active Power
m:Qsum:bussor :buslMvarTotal Reactive Power
m:Ssum:bussor :buslMVATotal Apparent Power
m:cosphisum:bussor :buslยทTotal Power Factor
m:tanphisum:bussor :buslยทTotal tan(phi)
m:i1P:bussor :buslp.u.Positive-Sequence Active Current
m:i1Q:bussor :buslp.u.Positive-Sequence Reactive Current
m:I1P:bussor :buslkAPositive-Sequence Active Current
m:I1Q:bussor :buslkAPositive-Sequence Reactive Current
m:ur:bussor :buslp.u.Voltage, Real Part
m:ui:bussor :buslp.u.Voltage, Imaginary Part
m:u:bussor :buslp.u.Voltage, Magnitude
m:ir:bussor :buslp.u.Current, Real Part
m:ii:bussor :buslp.u.Current, Imaginary Part
m:i:bussor :buslp.u.Current, Magnitude
m:phiui:bussor :busldegAngle between Voltage and Current
m:phiu1i1:bussor :busldegAngle between Voltage and Current in positive sequence system
m:Tfct:bussor :buslsFault Clearing Time
m:Brkload:bussor :busl%Breaker Loading
m:Spu:bussor :buslMVA/p.u.Apparent Power per p.u. Voltage
m:urnet:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bussor :buslp.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bussor :busldegZero-Sequence-Voltage, Angle
m:u2:bussor :buslp.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bussor :busldegNegative-Sequence-Voltage, Angle
m:irnet:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:iinet:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:inet:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:I:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bussor :buslp.u.Zero-Sequence Current, Real Part
m:i0i:bussor :buslp.u.Zero-Sequence Current, Imaginary Part
m:i0:bussor :buslp.u.Zero-Sequence Current, Magnitude
m:I0:bussor :buslkAZero-Sequence Current, Magnitude
m:I0x3:bussor :buslkA3*I0
m:phii0:bussor :busldegZero-Sequence Current, Angle
m:i2r:bussor :buslp.u.Negative-Sequence Current, Real Part
m:i2i:bussor :buslp.u.Negative-Sequence Current, Imaginary Part
m:i2:bussor :buslp.u.Negative-Sequence Current, Magnitude
m:I2:bussor :buslkANegative-Sequence Current, Magnitude
m:phii2:bussor :busldegNegative-Sequence Current, Angle
m:P:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyยทPower Factor
m:tanphi:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyยทtan(phi)
m:Pln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bussor :buslMWPositive Sequence Active Power
m:Q1:bussor :buslMvarPositive Sequence Reactive Power
m:P2:bussor :buslMWNegative Sequence Active Power
m:Q2:bussor :buslMvarNegative Sequence Reactive Power
m:P0:bussor :buslMWZero Sequence Active Power
m:Q0:bussor :buslMvarZero Sequence Reactive Power
m:i2P:bussor :buslp.u.Negative-Sequence Active Current
m:i2Q:bussor :buslp.u.Negative-Sequence Reactive Current
m:I2P:bussor :buslkANegative-Sequence Active Current
m:I2Q:bussor :buslkANegative-Sequence Reactive Current
m:ur:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bussor :busldegAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bussor :busldegAngle between Voltage and Current in negative sequence system
m:TfctPh:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:buss:Aor :busl; per phase :A, :B, :C, unbalanced only%Breaker Loading
c:loading%Loading
c:ntpminยทTap, Min. Position
c:ntpmaxยทTap, Max. Position
c:dutยทTap
c:ratfacยทRating Factor
c:snomMVARated Power
c:zsp.u.Series Impedance
c:TctrlsController Time Constant
c:ctrl_setp.u.Setpoint
c:ctrl_upp.u.Upper Bound
c:ctrl_lowp.u.Lower Bound
c:ildcยทFlag
c:ldc_reffp.u.effective Compensation Resistance
c:ldc_xeffp.u.effective Compensation Reactance
c:nntapยทTap, Current Position
c:iAutoTapยทController Mode
c:Inom_HVkANominal Current (Source-Side)
c:Inom_LVkANominal Current (Load-Side)
c:nntap1ยทTap 1, Current Position
c:nntap2ยทTap 2, Current Position
c:nntap3ยทTap 3, Current Position
c:UstarkVStar-Point Voltage
c:IstarkAStar-Point Current
n:ur:bussor :buslp.u.Voltage, Real Part
n:ui:bussor :buslp.u.Voltage, Imaginary Part
n:u:bussor :buslp.u.Voltage, Magnitude
n:upc:bussor :busl%Voltage, Magnitude
n:du:bussor :busl%Voltage Deviation
n:U:bussor :buslkVLine-Ground Voltage, Magnitude
n:phiu:bussor :busldegVoltage, Angle
n:phiurel:bussor :busldegVoltage, Relative Angle
n:Ul:bussor :buslkVLine-Line Voltage, Magnitude
n:u1:bussor :buslp.u.Voltage, Magnitude
n:u1pc:bussor :busl%Voltage, Magnitude
n:u1r:bussor :buslp.u.Positive-Sequence Voltage, Real Part
n:u1i:bussor :buslp.u.Positive-Sequence Voltage, Imaginary Part
n:ishc:bussor :buslp.u.Short-Circuit Current, magnitude
n:Ishc:bussor :buslkAShort-Circuit Current, magnitude
n:fe:bussor :buslp.u.Electrical Frequency
n:dfehz:bussor :buslHzDeviation of the El. Frequency
n:fehz:bussor :buslHzElectrical Frequency
n:frnom:bussor :buslHzNominal Frequency
n:ishcr:bussor :buslp.u.Short-Circuit Current, real
n:ishci:bussor :buslp.u.Short-Circuit Current, imag
n:dfedt:bussor :buslp.u./sDerivative of El. Frequency
n:ur:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:buss:Aor :busl; per phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:buss:Aor :busl; per phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:buss:Aor :busl; per phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bussor :buslp.u.Zero-Sequence Voltage, Magnitude
n:U0:bussor :buslkVZero-Sequence Voltage, Magnitude
n:U0x3:bussor :buslkV3*U0
n:phiu0:bussor :busldegZero-Sequence Voltage, Angle
n:U1:bussor :buslkVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bussor :busldegPositive-Sequence Voltage, Angle
n:u2:bussor :buslp.u.Negative-Sequence Voltage, Magnitude
n:U2:bussor :buslkVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bussor :busldegNegative-Sequence Voltage, Angle
n:U1l:bussor :buslkVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bussor :buslkVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bussor :buslp.u.Neutral-Ground Voltage, Magnitude
n:Un:bussor :buslkVNeutral-Ground Voltage, Magnitude
n:phiun:bussor :busldegNeutral-Ground Voltage, Angle
n:upht:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bussor :buslp.u.Average-Voltage, Magnitude
n:Um:bussor :buslkVAverage-Voltage, Magnitude
n:ishc:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, magnitude
n:Ishc:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, magnitude
n:inshc:bussor :buslp.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bussor :buslkANeutral Short-Circuit Current, magnitude
n:ishcr:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, real
n:ishci:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, imag
s:nntapin1ยทTap 1, Controller Input
s:nntapin2ยทTap 2, Controller Input
s:nntapin3ยทTap 3, Controller Input

ElmVoltreg emt simulation results

Read after ComInc (EMT) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:u0:bussor :buslp.u.Zero-Sequence-Voltage
m:u1r:bussor :buslp.u.Voltage Phasor, Real Part
m:u1i:bussor :buslp.u.Voltage Phasor, Imaginary Part
m:u1:bussor :buslp.u.Voltage Phasor, Magnitude
m:U1:bussor :buslkVLine-Ground Voltage Phasor, Magnitude
m:U1l:bussor :buslkVLine-Line Voltage Phasor, Magnitude
m:phiu1:bussor :busldegVoltage Phasor, Angle
m:inet:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current, referred to network
m:I:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykAPhase Current
m:i0:bussor :buslp.u.Zero-Sequence Current
m:I0:bussor :buslkAZero-Sequence Current
m:I0x3:bussor :buslkA3*I0
m:i1r:bussor :buslp.u.Current Phasor, Real Part
m:i1i:bussor :buslp.u.Current Phasor, Imaginary Part
m:i1:bussor :buslp.u.Current Phasor, Magnitude
m:I1:bussor :buslkACurrent Phasor, Magnitude
m:phii1:bussor :busldegCurrent Phasor, Angle
m:P:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyMWActive Power
m:Psum:bussor :buslMWPower-Phasor, Active Power
m:Qsum:bussor :buslMvarPower Phasor, Reactive Part
m:Ssum:bussor :buslMVAPower Phasor, Apparent Power
m:i1P:bussor :buslp.u.Current Phasor, Active Current
m:i1Q:bussor :buslp.u.Current Phasor, Reactive Current
m:I1P:bussor :buslkACurrent Phasor, Active Current
m:I1Q:bussor :buslkACurrent Phasor, Reactive Current
m:u:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
m:i:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Current
m:phiu1i1:bussor :busldegAngle between Voltage and Current Phasor
m:Tfct:bussor :buslsFault Clearing Time
m:TfctPh:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:unet:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, referred to network
m:cosphi1:bussor :buslยทPower-Phasor, Power-Factor
c:nntap1ยทTap 1, Current Position
c:nntap2ยทTap 2, Current Position
c:nntap3ยทTap 3, Current Position
c:ntpminยทTap, Min. Position
c:ntpmaxยทTap, Max. Position
c:dutยทTap
c:UstarkVStar-Point Voltage
c:IstarkAStar-Point Current
c:rs:Aper phase :A, :B, :C, unbalanced onlyp.u.Leakage Resistance
c:hpirad/sAngular frequency
n:u:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
n:upc:buss:Aor :busl; per phase :A, :B, :C, unbalanced only%Phase Voltage
n:U:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVPhase Voltage
n:ul:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage
n:ulpc:buss:Aor :busl; per phase :A, :B, :C, unbalanced only%Line-Line Voltage
n:Ul:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVLine-Line Voltage
n:u0:bussor :buslp.u.Zero-Sequence-Voltage
n:U0:bussor :buslkVZero-Sequence-Voltage
n:U0x3:bussor :buslkV3*U0
n:u1:bussor :buslp.u.Voltage Phasor, Magnitude
n:u1pc:bussor :busl%Voltage Phasor, Magnitude
n:u1r:bussor :buslp.u.Voltage Phasor, Real Part
n:u1i:bussor :buslp.u.Voltage Phasor, Imaginary Part
n:U1:bussor :buslkVVoltage Phasor, Magnitude
n:phiu1:bussor :busldegVoltage Phasor, Angle
n:U1l:bussor :buslkVLine-Line Voltage Phasor, Magnitude
n:uln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage
n:Uln:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage
n:un:bussor :buslp.u.Neutral-Ground Voltage
n:Un:bussor :buslkVNeutral-Ground Voltage
n:ishc:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current
n:Ishc:buss:Aor :busl; per phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:inshc:bussor :buslp.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bussor :buslkANeutral Short-Circuit Current, magnitude
n:fe:bussor :buslp.u.Electrical Frequency
n:dfehz:bussor :buslHzDeviation of the El. Frequency
n:fehz:bussor :buslHzElectrical Frequency
n:frnom:bussor :buslHzNominal Frequency
s:nntapin1ยทTap 1, Controller Input
s:nntapin2ยทTap 2, Controller Input
s:nntapin3ยทTap 3, Controller Input

ElmVoltreg dc load flow results

Read after ComLdf (DC) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:P:bussor :buslMWActive Power
m:Q:bussor :buslMvarReactive Power
c:loading%Loading
c:maxload%Max. Loading
c:ntpminยทTap, Min. Position
c:ntpmaxยทTap, Max. Position
c:dutยทTap
c:ratfacยทRating Factor
c:snomMVARated Power
c:zsp.u.Series Impedance
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:maxloadpup.u.Max. Loading
c:nntapยทTap, Current Position
c:dphiudegVoltage Drop Angle
n:u:bussor :buslp.u.Voltage, Magnitude
n:upc:bussor :busl%Voltage, Magnitude
n:U:bussor :buslkVLine-Ground Voltage, Magnitude
n:phiu:bussor :busldegVoltage, Angle
n:phiurel:bussor :busldegVoltage, Relative Angle
n:Ul:bussor :buslkVLine-Line Voltage, Magnitude
n:u1:bussor :buslp.u.Voltage, Magnitude
n:Pgen:bussor :buslMWGeneration, Active Power
n:Pmot:bussor :buslMWMotor Load, Active Power
n:Pload:bussor :buslMWGeneral Load, Active Power
n:Pcomp:bussor :buslMWCompensation (Losses)
n:Pnet:bussor :buslMWExternal Networks, Active Power
n:Pflow:bussor :buslMWPower Flow, Active Power

Read after ComMod with GetAttribute. c: calculation parameter, s: signal (state or model variable).

AttributeUnitDescription
c:loading%Loading
c:ntpminยทTap, Min. Position
c:ntpmaxยทTap, Max. Position
c:dutยทTap
c:ratfacยทRating Factor
c:snomMVARated Power
c:zsp.u.Series Impedance
c:TctrlsController Time Constant
c:ctrl_setp.u.Setpoint
c:ctrl_upp.u.Upper Bound
c:ctrl_lowp.u.Lower Bound
c:ildcยทFlag
c:ldc_reffp.u.effective Compensation Resistance
c:ldc_xeffp.u.effective Compensation Reactance
c:nntapยทTap, Current Position
c:iAutoTapยทController Mode
c:Inom_HVkANominal Current (Source-Side)
c:Inom_LVkANominal Current (Load-Side)
s:nntapin1ยทTap 1, Controller Input

ElmVoltreg optimal power flow results

Read after ComOpf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:bussor :buslp.u.Voltage, Real Part, referred to network
m:uinet:bussor :buslp.u.Voltage, Imaginary Part, referred to network
m:u1r:bussor :buslp.u.Positive-Sequence-Voltage, Real Part
m:u1i:bussor :buslp.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bussor :buslp.u.Positive-Sequence-Voltage, Magnitude
m:U1:bussor :buslkVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bussor :buslkVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bussor :busldegPositive-Sequence-Voltage, Angle
m:irnet:bussor :buslp.u.Current, Real Part, referred to network
m:iinet:bussor :buslp.u.Current, Imaginary Part, referred to network
m:inet:bussor :buslp.u.Current, Magnitude, referred to network
m:I:bussor :buslkACurrent, Magnitude
m:phii:bussor :busldegCurrent, Angle
m:i1r:bussor :buslp.u.Positive-Sequence Current, Real Part
m:i1i:bussor :buslp.u.Positive-Sequence Current, Imaginary Part
m:i1:bussor :buslp.u.Positive-Sequence Current, Magnitude
m:I1:bussor :buslkAPositive-Sequence Current, Magnitude
m:phii1:bussor :busldegPositive-Sequence Current, Angle
m:P:bussor :buslMWActive Power
m:Q:bussor :buslMvarReactive Power
m:S:bussor :buslMVAApparent Power
m:cosphi:bussor :buslยทPower Factor
m:tanphi:bussor :buslยทtan(phi)
m:Psum:bussor :buslMWTotal Active Power
m:Qsum:bussor :buslMvarTotal Reactive Power
m:Ssum:bussor :buslMVATotal Apparent Power
m:cosphisum:bussor :buslยทTotal Power Factor
m:tanphisum:bussor :buslยทTotal tan(phi)
m:i1P:bussor :buslp.u.Positive-Sequence Active Current
m:i1Q:bussor :buslp.u.Positive-Sequence Reactive Current
m:I1P:bussor :buslkAPositive-Sequence Active Current
m:I1Q:bussor :buslkAPositive-Sequence Reactive Current
m:ur:bussor :buslp.u.Voltage, Real Part
m:ui:bussor :buslp.u.Voltage, Imaginary Part
m:u:bussor :buslp.u.Voltage, Magnitude
m:ir:bussor :buslp.u.Current, Real Part
m:ii:bussor :buslp.u.Current, Imaginary Part
m:i:bussor :buslp.u.Current, Magnitude
m:phiui:bussor :busldegAngle between Voltage and Current
m:phiu1i1:bussor :busldegAngle between Voltage and Current in positive sequence system
m:Tfct:bussor :buslsFault Clearing Time
m:Brkload:bussor :busl%Breaker Loading
m:Spu:bussor :buslMVA/p.u.Apparent Power per p.u. Voltage
c:loading%Loading
c:maxload%Max. Loading
c:ntpminยทTap, Min. Position
c:ntpmaxยทTap, Max. Position
c:dutยทTap
c:ratfacยทRating Factor
c:snomMVARated Power
c:zsp.u.Series Impedance
c:dup.u.Voltage Drop
c:dupc%Voltage Drop
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:usetp2p.u.Voltage Setpoint^2
c:usetpinip.u.Complex Voltage Setpoint
c:i_uplimยทTap at max.
c:i_lowlimยทTap at min.
c:nCtrlIterยทNo. of CTRL-iterations
c:TctrlsController Time Constant
c:ctrl_setp.u.Setpoint
c:ctrl_upp.u.Upper Bound
c:ctrl_lowp.u.Lower Bound
c:i_fixedtapยทFlag
c:ildcยทFlag
c:ldc_reffp.u.Effective compensation resistance
c:ldc_xeffp.u.Effective compensation reactance
c:i_contยทContinuous Tap
c:maxloadpup.u.Max. Loading
c:nntapยทTap, Current Position
c:nntapTargetยทTap 1 - target value
c:totPenaltyCostsUSDTotal penalty costs
c:totTapDeviationยทTotal tap deviation
n:ur:bussor :buslp.u.Voltage, Real Part
n:ui:bussor :buslp.u.Voltage, Imaginary Part
n:u:bussor :buslp.u.Voltage, Magnitude
n:upc:bussor :busl%Voltage, Magnitude
n:du:bussor :busl%Voltage Deviation
n:U:bussor :buslkVLine-Ground Voltage, Magnitude
n:phiu:bussor :busldegVoltage, Angle
n:phiurel:bussor :busldegVoltage, Relative Angle
n:Ul:bussor :buslkVLine-Line Voltage, Magnitude
n:u1:bussor :buslp.u.Voltage, Magnitude
n:u1pc:bussor :busl%Voltage, Magnitude
n:u1r:bussor :buslp.u.Positive-Sequence Voltage, Real Part
n:u1i:bussor :buslp.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bussor :buslMWGeneration, Active Power
n:Qgen:bussor :buslMvarGeneration, Reactive Power
n:Pmot:bussor :buslMWMotor Load, Active Power
n:Qmot:bussor :buslMvarMotor Load, Reactive Power
n:Pload:bussor :buslMWGeneral Load, Active Power
n:Qload:bussor :buslMvarGeneral Load, Reactive Power
n:Pcomp:bussor :buslMWCompensation (Losses)
n:Qcomp:bussor :buslMvarCompensation
n:Pnet:bussor :buslMWExternal Networks, Active Power
n:Qnet:bussor :buslMvarExternal Networks, Reactive Power
n:Pflow:bussor :buslMWPower Flow, Active Power
n:Qflow:bussor :buslMvarPower Flow, Reactive Power
n:Pout:bussor :buslMWOutgoing Flow, Active Power
n:Qout:bussor :buslMvarOutgoing Power, Reactive Power
n:Sout:bussor :buslMVAOutgoing Power, Apparent Power
n:cosphiout:bussor :buslยทOutgoing Power, Power Factor
n:Pbalance:bussor :buslMWActive Power Balance (=0)
n:Qbalance:bussor :buslMvarReactive Power Balance (=0)
n:LossPdown:bussor :buslMWLosses, downstream
n:LossQdown:bussor :buslMvarLosses, downstream (Reactive Power)
n:LossPdownload:bussor :buslMWLoad losses, downstream
n:LossQdownload:bussor :buslMvarLoad losses, downstream
n:LossPdownnoload:bussor :buslMWNo load losses, downstream
n:LossQdownnoload:bussor :buslMvarNo load losses, downstream
n:du_feed:bussor :busl%Difference from voltage at start of feeder

ElmVoltreg basic data

b: values are worked out from the input data. Read them; they are not set.

AttributeUnitDescription
b:loc_nameยทName
b:ntrcnยทAutomatic Tap Changer on/off
b:i_contยทContinuous Tap

Related

โ† ElmTrmult Multi-Winding Transformer ยท ElmZpu Common Impedance โ†’