ElmXnet attributesPowerFactory External Grid

Every attribute of the PowerFactory External Grid (ElmXnet): 284 input parameters and 980 result variables, with units and meaning. Copy a name into GetAttribute or SetAttribute.

What ElmXnet is

An external grid: the network beyond the edge of the model, set by its short-circuit power and a voltage setpoint. It is often the slack of the load flow.

Class
ElmXnet, element class
PowerFactory name
External Grid
Terminal suffix
:bus1 terminal
Attributes
284 input parameters and 980 result variables, in 7 calculations

Most used ElmXnet attributes

AttributeUnitDescriptionWhere
m:P:bus1MWActive Powerslack active powerLoad flow
m:Q:bus1MvarReactive PowerLoad flow
bustpยทBus TypeSL, PV or PQinput data
usetpp.u.Voltage Setpointinput data
snssMVAShort-Circuit Power Sk''maxmaximum short-circuit powerinput data
snssminMVAShort-Circuit Power Sk''mininput data
outservยทOut of Serviceinput data

Read and write ElmXnet in Python

import powerfactory

app = powerfactory.GetApplication()          # GetApplicationExt() from outside PowerFactory
app.GetFromStudyCase("ComLdf").Execute()      # results exist after a calculation

for grid in app.GetCalcRelevantObjects("*.ElmXnet"):
    p_bus1 = grid.GetAttribute("m:P:bus1")        # Active Power, MW
    q_bus1 = grid.GetAttribute("m:Q:bus1")        # Reactive Power, Mvar
    print(grid.loc_name, p_bus1, q_bus1)

grid = app.GetCalcRelevantObjects("*.ElmXnet")[0]
grid.SetAttribute("usetp", 1.02)              # voltage setpoint 1.02 p.u.
  • A result at a terminal of the external grid needs the terminal in its name: m:P:bus1, not m:P, which raises AttributeError.
  • An input parameter is read and written with or without its e: prefix: GetAttribute("outserv") and GetAttribute("e:outserv") give the same value.
  • RMS and EMT variables change over time: record them in a results object (ElmRes) to read the whole curve. GetAttribute after a run gives the value at the last time step.

ElmXnet input parameters

The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.

AttributeUnitDescription
loc_nameยทName
chr_nameยทCharacteristic Name
for_nameยทForeign Key
dat_srcยทData source
sernumยทSerial Number
manufยทManufacturer
commissionDateยทCommissioning Date
appr_modbyยทModified by
bustpยทBus Type
mode_inpยทInput Mode
outservยทOut of Service
constrยทYear of Construction
appr_statusยทStatus
cusedยทUse for calculation
cusedhrmยทUse for calculation
iintgndยทN-Connection
priorityยทMerit Order
fixedยทMust run
dispatchยทGenerator Dispatch
iInterPolยทApproximation
ictpgยทActive Power
ictqgยทReactive Power
iOPFCPminยทMin.
iOPFCPmaxยทMax.
iOPFCQminยทMin.
iOPFCQmaxยทMax.
QtargetBaseยทBase
isVREยทGenerator usage
isCtrlPยทActive power
isCtrlQยทReactive power
isLimPmaxยทMax.
isLimPminยทMin.
isLimQmaxยทMax.
isLimQminยทMin.
isMustRunUCยทMust run
isCtrlFixedToLdfValยทFix controls to Load Flow values
is4SpinReserveยทConsider for region spinning reserve
allowConsumModeยทSeparate consumption mode
isConsCostOpยทOperating costs
discMethCostOpยทPiecewise linearisation for LP
numBreakpointsCostOpยทNumber of breakpoints
isConsCostsRedispatchยทAdditional active power redispatch costs
isConsStartUpCostยทStart-up costs
isConsShutDownCostยทShut-down costs
isConstrRampยทRamp rate constraints
isConstrUpDownยทStart-up/shut-down time constraints
isDiscreteCtrlPยทRestriction to discrete active power values
isPcurrAllowedยทAllow current active power value
consCostsRedispatchQยทAdditional reactive power redispatch costs
refValueQยทReference value for redispatch costs
refValueLdfQยทReference value for redispatch costs
refValueVยทReference value for redispatch costs
ctrlUsagePยทActive Power
ctrlUsageQยทReactive Power
isConsCostOp_QยทReactive power operating costs
iInterPol_QยทApproximation
polyDegree_QยทPolynomial degree
discMethCostOp_QยทPiecewise linearisation for LP
PctrlยทActive power steps
i_prtyยทPriority
uset_modeยทSetpoint
iHmcTypeยทType of Harmonic Voltages
chaInputOptยทDefined for
outServPzeroยทOut of service when active power is zero
iAstabintยทA-stable integration algorithm
isCtrlPplacementยทOptimise active power
pginiMWActive Power
qginiMvarReactive Power
snssMVAShort-Circuit Power Sk''max
rntxnยทR/X Ratio (max.)
xntrnยทX/R Ratio (max.)
cmaxยทc-Factor (max.)
cminยทc-Factor (min.)
z2tz1ยทZ2/Z1 max.
x0tx1ยทX0/X1 max.
r0tx0ยทR0/X0 max.
C0uFC0 max.
ReOhmResistance, Re
XeOhmReactance, Xe
usetpp.u.Voltage Setpoint
snssminMVAShort-Circuit Power Sk''min
rntxnminยทR/X Ratio (min.)
xntrnminยทX/R Ratio (min.)
curpreldkACurrent
cospreldยทPower Factor
curpreldminkACurrent
cospreldminยทPower Factor
z2tz1minยทZ2/Z1 min.
x0tx1minยทX0/X1 min.
r0tx0minยทR0/X0 min.
C0minuFC0 min.
MaxSMWMax.
ecostUSD/kWhEnergy Cost
cmonthUSD/MNo load costs (monthly)
round%Smoothing factor
smoothfac_Q%Smoothing Factor
Pmin_ucMWMin.
KpfMW/HzPrimary Frequency Bias
P1hrmMWActive power
Q1hrmMvarReactive power
u1hrmp.u.Positive sequence voltage
SkVMVAShort-Circuit Power, Sk
psikVdegImpedance Angle, psik
z2tz1kVยทZ2/Z1
x0tx1kVยทX0/X1
r0tx0kVยทR0/X0
C0kVuFC0
cosnยทPower Factor
tdssTd'
tqssTq'
tdsssTd''
tqsssTq''
xdp.u.xd
xdsp.u.xd'
xqp.u.xq
xqsp.u.xq'
GPSlatdegLatitude / Northing
GPSlondegLongitude / Easting
phiinidegAngle
tagsAcceleration Time Constant
KMW/HzSecondary Frequency Bias
QtargetRPR%Q target value
genShiftKey%Generation shift key
PminInvMWMin.
PmaxInvMWMax.
costCurtailmentUSD/MWhCosts for curtailment
penaltyCostsUSD/MWhPenalty costs
fixedCostsUSD/hFixed costs
consumCostsUSD/MWhConsumption costs
costRedispatchUpUSD/MWhUpward active power redispatch costs
costRedispatchDownUSD/MWhDownward active power redispatch costs
costRedispatchQUSD/MvarhCosts for reactive power deviation
cost_upUSDWarm-start costs
costColdStartUSDCold-start costs
coldStartTimehCold-start time
costShutDownUSDShut-down costs
limRampUpMW/hRamp-up limit
limRampDownMW/hRamp-down limit
limRampStartUpMWStart-up ramp limit
limRampShutDownMWShut-down ramp limit
minUpTimehMinimum up-time
minDownTimehMinimum down-time
targetQMvarQ target value
targetVp.u.Target voltage setpoint
fixedCostsSetpChangeQUSDFixed costs per setpoint deviation
zeroFixedCostsSetpChangeQUSDFixed costs per setpoint deviation
costRedispatchVUSD/p.u.Costs for voltage setpoint deviation
curativeLimPMWMax. curative active power deviation
curativeLimQMvarMax. curative reactive power deviation
curativeCostsUSD/MVAhCosts for curative power deviation
penaltyCosts_QUSD/MvarhPenalty costs
dpl1ยทdpl1
dpl2ยทdpl2
dpl3ยทdpl3
dpl4ยทdpl4
dpl5ยทdpl5
scaleQmin%Scaling Factor (min.)
scaleQmax%Scaling Factor (max.)
cQ_minMvarMin.
cQ_maxMvarMax.
appr_modifยทModified
cpowerMWFrom
ccostUSD/MWhCosts
vecBreakpointsPMWPower
vecStartUpTimes>=hDown-time
vecStartUpCostsUSDStart-up costs
vecDiscreteCtrlPvals%Valid active power values
cpower_QMvarPower
ccost_QUSD/hCosts
vecBreakpointsQMvarPower
ifreqsยทHarm. Order
u1_magp.u.u1, Mag.
u1_phasedegu1, Ang.
u2_magp.u.u2, Mag.
u2_phasedegu2, Ang.
u0_magp.u.u0, Mag.
u0_phasedegu0, Ang.
umag_iec1p.u.U_h
ifreqs_iec2ยทHarm. Order
umag_iec2p.u.U_h
descยทDescription
cimRdfIdยทRDF ID
sOpCommentยทOperator Comment
fold_idยทIn Folder
bus1ยทTerminalObject: StaCubic
bus1nยทNeutralObject: StaCubic
doc_idยทAdditional Data
pOwnerยทOwnerObject: ElmOwner
pOperatorยทOperatorObject: ElmOperator
p_uctrlยทReference BusbarObject: ElmTerm*,StaBar*,ElmLdfctrl*
pBMUยทVirtual Power PlantObject: ElmBmu
efficiencyCurveGenยทEfficiency curve (generation)Object: IntEffcurve
efficiencyCurveConsumยทEfficiency curve (consumption)Object: IntEffcurve
pOpCostCurveยทGenerator cost curveObject: IntCostcurvegen
phmcยทHarmonic VoltagesObject: TypHmcvolt,TypHmcopvolt
fcharR1ChaPol,ChaVec,ChaMat,ChaOpfreqR1(f)
fcharL1ChaPol,ChaVec,ChaMat,ChaOpfreqL1(f)
fcharR0ChaPol,ChaVec,ChaMat,ChaOpfreqR0(f)
fcharL0ChaPol,ChaVec,ChaMat,ChaOpfreqL0(f)
fcharR2ChaPol,ChaVec,ChaMat,ChaOpfreqR2(f)
fcharL2ChaPol,ChaVec,ChaMat,ChaOpfreqL2(f)
fcharX1ChaPol,ChaVec,ChaMat,ChaOpfreqX1(f)
fcharX2ChaPol,ChaVec,ChaMat,ChaOpfreqX2(f)
fcharX0ChaPol,ChaVec,ChaMat,ChaOpfreqX0(f)
fcharC0ChaPol,ChaVec,ChaMat,ChaOpfreqC0(f)
pQlimTypeยทCapability CurveObject: IntQlim
cpHeadFoldยทHead Folder
bus1_barยทTerminal
bus1n_barยทNeutral
cpGridยทGridObject: ElmNet
cpZoneยทZoneObject: ElmZone
cpAreaยทAreaObject: ElmArea
cpFeedยทFeederObject: ElmFeeder
ciDistยทDistance from infeed in number of buses
ciLaterยทLateral Index
ciDistRootยทDistance from first infeed in number of buses
ciDistAllยทDistance from infeed in number of buses including switches
ciDistAllRootยทDistance from first infeed in number of buses including switches
cpOwnerยทOwnerObject: ElmOwner
cpOperatorยทOperatorObject: ElmOperator
cpBranchยทBranchObject: ElmBranch
cpSiteยทSiteObject: ElmSite
cpSubstatยทSubstationObject: ElmSubstat,ElmTrfstat
cpMeteostatยทMeteo StationObject: ElmMeteostat
ciOutagedยทPlanned Outage
ciEnergizedยทEnergized
ciEarthedยทEarthed
cDisplayNameยทDisplay Name
cpSupplyTransformerยทSupplying TransformerObject: ElmTr?,ElmTrmult
cpSupplyTrfStationยทSupplying Secondary SubstationObject: ElmTrfstat
cpSupplySubstationยทSupplying SubstationObject: ElmSubstat
sginiMVAApparent Power
cosginiยทPower Factor
pf_recapยทPower Factor
p_direcยทPower Direction
iksskAShort-Circuit Current Ik''max
cgndยทStar Point
cpeterยทPetersen Coil
c_pseccยทExternal Secondary ControllerObject: ElmSecctrl
ikssminkAShort-Circuit Current Ik''min
c_pstacยทExternal Station ControllerObject: ElmStactrl
costRedispatchPUSD/MWhCosts for active power deviation
cStorageยทStorage modelObject: ElmStorage
cIsMustRunUCยทMust run
efficiencyLPgenยทUsed efficiency (generation)
efficiencyLPconsumยทUsed efficiency (consumption)
allowGenModeยทSeparate generation mode
PminInvPUp.u.Min.
PmaxInvPUp.u.Max.
avgCostsUcUSD/MWhAverage costs
cfixedCostsUSD/hFixed costs
limRampUpPUp.u./hRamp-up limit
limRampDownPUp.u./hRamp-down limit
limRampStartUpPUp.u.Start-up ramp limit
limRampShutDownPUp.u.Shut-down ramp limit
cIsDiscreteCtrlPยทRestriction to discrete active power values
cVecDiscreteCtrlPvals%Valid active power values
cIsPcurrAllowedยทAllow current active power value
cCtrlUsagePยทActive Power
cCtrlUsageQยทReactive Power
cCurativeLimP_PUp.u.Max. curative active power deviation
cCurativeLimQ_PUp.u.Max. curative reactive power deviation
avgCostsUc_QUSD/MvarhAverage costs
avgCostsUc_posQUSD/MvarhAverage costs (pos. range)
avgCostsUc_negQUSD/MvarhAverage costs (neg. range)
PnomMWPn
Pmax_ucPUp.u.Max.
Pmin_ucPUp.u.Min.
cpCtrlNodeยทTarget NodeObject: ElmTerm
avgCostsUSD/MWhAverage Costs
cfreqsHzFrequency
cTypHmcยทType of harmonic sources
R1OhmResistance, R1
L1mHInductance, L1
X1OhmReactance, X1
R2OhmResistance, R2
L2mHInductance, L2
X2OhmReactance, X2
R0OhmResistance, R0
L0mHInductance, L0
X0OhmReactance, X0
C0auFCapacitance, C0
qdslCtrlยทQuasi-Dynamic ModelObject: ElmQdsl
snomMVANominal Apparent Power

ElmXnet load flow results

Read after ComLdf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bus1p.u.Voltage, Real Part, referred to network
m:uinet:bus1p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1degPositive-Sequence-Voltage, Angle
m:irnet:bus1p.u.Current, Real Part, referred to network
m:iinet:bus1p.u.Current, Imaginary Part, referred to network
m:inet:bus1p.u.Current, Magnitude, referred to network
m:I:bus1kACurrent, Magnitude
m:phii:bus1degCurrent, Angle
m:i1r:bus1p.u.Positive-Sequence Current, Real Part
m:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:S:bus1MVAApparent Power
m:cosphi:bus1ยทPower Factor
m:tanphi:bus1ยทtan(phi)
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:Ssum:bus1MVATotal Apparent Power
m:cosphisum:bus1ยทTotal Power Factor
m:tanphisum:bus1ยทTotal tan(phi)
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:ur:bus1p.u.Voltage, Real Part
m:ui:bus1p.u.Voltage, Imaginary Part
m:u:bus1p.u.Voltage, Magnitude
m:ir:bus1p.u.Current, Real Part
m:ii:bus1p.u.Current, Imaginary Part
m:i:bus1p.u.Current, Magnitude
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1sFault Clearing Time
m:Brkload:bus1%Breaker Loading
m:Spu:bus1MVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bus1p.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bus1degZero-Sequence-Voltage, Angle
m:u2:bus1p.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bus1degNegative-Sequence-Voltage, Angle
m:irnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part, referred to network
m:iinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part, referred to network
m:inet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude, referred to network
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bus1p.u.Zero-Sequence Current, Real Part
m:i0i:bus1p.u.Zero-Sequence Current, Imaginary Part
m:i0:bus1p.u.Zero-Sequence Current, Magnitude
m:I0:bus1kAZero-Sequence Current, Magnitude
m:I0x3:bus1kA3*I0
m:phii0:bus1degZero-Sequence Current, Angle
m:i2r:bus1p.u.Negative-Sequence Current, Real Part
m:i2i:bus1p.u.Negative-Sequence Current, Imaginary Part
m:i2:bus1p.u.Negative-Sequence Current, Magnitude
m:I2:bus1kANegative-Sequence Current, Magnitude
m:phii2:bus1degNegative-Sequence Current, Angle
m:ubfacI:bus1%Current Unbalance Factor
m:ubfacS:bus1%Power Unbalance Factor
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bus1:Aper phase :A, :B, :C, unbalanced onlyยทPower Factor
m:tanphi:bus1:Aper phase :A, :B, :C, unbalanced onlyยทtan(phi)
m:Pln:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bus1MWPositive Sequence Active Power
m:Q1:bus1MvarPositive Sequence Reactive Power
m:P2:bus1MWNegative Sequence Active Power
m:Q2:bus1MvarNegative Sequence Reactive Power
m:P0:bus1MWZero Sequence Active Power
m:Q0:bus1MvarZero Sequence Reactive Power
m:i2P:bus1p.u.Negative-Sequence Active Current
m:i2Q:bus1p.u.Negative-Sequence Reactive Current
m:I2P:bus1kANegative-Sequence Active Current
m:I2Q:bus1kANegative-Sequence Reactive Current
m:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1degAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bus1degAngle between Voltage and Current in negative sequence system
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bus1:Aper phase :A, :B, :C, unbalanced only%Breaker Loading
c:pMWTotal Active Power
c:qMvarTotal Reactive Power
c:sgnnMVATotal rated apparent power (ngnum*sgn)
c:cosnยทNominal-Power factor
c:c2ยทVoltage Coefficient (uknom/ugn)
c:uinip.u.Voltage Setpoint for PV and Slack
c:iPowerOnยทFlag
c:xdqp.u.Synchronous Reactance
c:rsp.u.Resistance
c:i_qlimยทReactive power limit reached
c:QminMvarLower limit of reactive power
c:QmaxMvarUpper limit of reactive power
c:smMVAComplex Power
c:phiiniยทInitial Angle
c:PdispMWPower (Eco-Dispatch)
c:KfMW/HzFrequency Bias
c:Kpp.u.Active Power Participation
c:iRefElementยทReference Element
c:nCtrlIterยทNo. of CTRL-iterations
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:z2p.u.Negative Sequence Impedance
c:z0p.u.Zero Sequence Impedance
c:zep.u.Grounding Impedance
c:MaxSMVAMax. Apparent Power
c:cst_dispUSD/hOperating Costs
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bus1MWGeneration, Active Power
n:Qgen:bus1MvarGeneration, Reactive Power
n:Pmot:bus1MWMotor Load, Active Power
n:Qmot:bus1MvarMotor Load, Reactive Power
n:Pload:bus1MWGeneral Load, Active Power
n:Qload:bus1MvarGeneral Load, Reactive Power
n:Pcomp:bus1MWCompensation (Losses)
n:Qcomp:bus1MvarCompensation
n:Pnet:bus1MWExternal Networks, Active Power
n:Qnet:bus1MvarExternal Networks, Reactive Power
n:Pflow:bus1MWPower Flow, Active Power
n:Qflow:bus1MvarPower Flow, Reactive Power
n:Pout:bus1MWOutgoing Flow, Active Power
n:Qout:bus1MvarOutgoing Power, Reactive Power
n:Sout:bus1MVAOutgoing Power, Apparent Power
n:cosphiout:bus1ยทOutgoing Power, Power Factor
n:Pbalance:bus1MWActive Power Balance (=0)
n:Qbalance:bus1MvarReactive Power Balance (=0)
n:LossPdown:bus1MWLosses, downstream
n:LossQdown:bus1MvarLosses, downstream (Reactive Power)
n:LossPdownload:bus1MWLoad losses, downstream
n:LossQdownload:bus1MvarLoad losses, downstream
n:LossPdownnoload:bus1MWNo load losses, downstream
n:LossQdownnoload:bus1MvarNo load losses, downstream
n:du_feed:bus1%Difference from voltage at start of feeder
n:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aper phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1kV3*U0
n:phiu0:bus1degZero-Sequence Voltage, Angle
n:U1:bus1kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1degPositive-Sequence Voltage, Angle
n:u2:bus1p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1degNegative-Sequence Voltage, Angle
n:U1l:bus1kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1degNeutral-Ground Voltage, Angle
n:upht:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bus1p.u.Average-Voltage, Magnitude
n:Um:bus1kVAverage-Voltage, Magnitude
n:uphtmin:bus1p.u.Minimum of Phase Technology dependent Voltage, Magnitude
n:uphtmax:bus1p.u.Maximum of Phase Technology dependent Voltage, Magnitude
n:ubfac:bus1%Unbalance Factor
s:psetMWActive Power Setpoint
s:qsetMvarReactive Power Setpoint
s:dFinHzFrequency Deviation
s:dFHzFrequency Deviation Output

ElmXnet short-circuit results

Read after ComShc with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:I:bus1kAShort-Circuit Current, Magnitude
m:phii:bus1degPhase Current, Angle
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in Positive-Sequence System
m:Tfct:bus1sFault Clearing Time
m:Ikss:bus1kAInitial Short-Circuit Current
m:ikss:bus1p.u.Initial Short-Circuit Current, Magnitude
m:Skss:bus1MVAInitial Short-Circuit Power
m:ip:bus1kAPeak Short-Circuit Current
m:maxIkss:bus1kAMax. Initial Short-Circuit Current
m:maxip:bus1kAMax. Peak Short-Circuit Current
m:maxIth:bus1kAMax. Thermal equivalent Short-Circuit Current
m:maxIb:bus1kAMax. Breaking Current
m:R:bus1OhmFault Impedance, Real Part
m:X:bus1OhmFault Impedance, Imaginary Part
m:Z:bus1OhmFault Impedance, Magnitude
m:phiz:bus1degFault Impedance, Angle
m:Rs:bus1OhmSource Impedance, Real Part
m:Xs:bus1OhmSource Impedance, Imaginary Part
m:Zs:bus1OhmSource Impedance, Magnitude
m:phizs:bus1degSource Impedance, Angle
m:BrkIpload:bus1%Breaker Loading (peak)
m:Ib:bus1kAShort-Circuit Breaking Current
m:Sb:bus1MVAShort-Circuit Breaking Power
m:Ith:bus1kAThermal equivalent Short-Circuit Current
m:zSbase:bus1p.u.Fault Impedance, Magnitude
m:XtoR:bus1ยทX/R ratio
m:cosphiui:bus1ยทcosphi
m:BrkIbload:bus1%Breaker Loading (breaking)
m:BrkmaxIb:bus1kAMax. Breaking Current (breaker time)
m:Ik:bus1kASteady-State Short-Circuit Current
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, Magnitude
m:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:I0:bus1kAZero-Sequence Current, Magnitude
m:I0x3:bus1kA3*I0
m:phii0:bus1degZero-Sequence Current, Angle
m:I2:bus1kANegative-Sequence Current, Magnitude
m:phii2:bus1degNegative-Sequence Current, Angle
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:cosphisum:bus1ยทTotal Power Factor
m:P2:bus1MWP2
m:Q2:bus1MvarQ2
m:P0:bus1MWP0
m:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1degAngle between Voltage and Current in Zero-Sequence System
m:phiu2i2:bus1degAngle between Voltage and Current in Negative-Sequence System
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:Ikss:bus1:Aper phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
m:ikss:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Initial Short-Circuit Current, Magnitude
m:Skss:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
m:Skssx3:bus1:Aper phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
m:ip:bus1:Aper phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
m:Z:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmFault Impedance, Magnitude
m:phiz:bus1:Aper phase :A, :B, :C, unbalanced onlydegFault Impedance, Angle
m:Zl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmLine-Line Fault Impedance, Magnitude
m:phizl:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Fault Impedance, Angle
m:Z0:bus1OhmZero-Sequence Fault Impedance, Magnitude
m:phiz0:bus1degZero-Sequence Fault Impedance, Angle
m:z0Sbase:bus1p.u.Zero-Sequence Fault Impedance, Magnitude
m:cosphiu1i1:bus1ยทPositive-Sequence cosphi
m:I0x3watt:bus1kAEarth-Fault Residual Current
m:I0x3var:bus1kACapacitive Earth-Fault Current
m:Q0cap:bus1MvarQ0 capacitive
m:Rfrel:bus1OhmRelay Impedance, Real Part
m:Xfrel:bus1OhmRelay Impedance, Imaginary Part
m:Zfrel:bus1OhmRelay Impedance, Magnitude
m:phizfrel:bus1degRelay Impedance, Angle
m:Zf:bus1OhmMeas. Fault Impedance, Magnitude
m:phizf:bus1degMeas. Fault Impedance, Angle
c:z1p.u.Positive-sequence impedance
c:uini1p.u.Internal positive-sequence voltage
c:z2p.u.Negative-sequence impedance
c:z0p.u.Zero-sequence impedance
c:zep.u.Grounding impedance
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:Ikss:bus1kAInitial Short-Circuit Current
n:I:bus1kAShort-Circuit Current
n:phii:bus1degPhase Current, Angle
n:Skss:bus1MVAInitial Short-Circuit Power
n:ip:bus1kAPeak Short-Circuit Current
n:Ib:bus1kAShort-Circuit Breaking Current
n:Sb:bus1MVAShort-Circuit Breaking Power
n:idc:bus1kADecaying Component
n:Ith:bus1kAThermal equivalent Short-Circuit Current
n:R1toX1:bus1ยทR1/X1 ratio (Zk")
n:X1toR1:bus1ยทX1/R1 ratio (Zk")
n:R:bus1OhmShort-Circuit Impedance, Real Part
n:X:bus1OhmShort-Circuit Impedance, Imaginary Part
n:Z:bus1OhmShort-Circuit Impedance, Magnitude
n:phiz:bus1degShort-Circuit Impedance, Angle
n:urpref:bus1p.u.Pre-fault Voltage, Real Part
n:uipref:bus1p.u.Pre-fault Voltage, Imaginary Part
n:upref:bus1p.u.Pre-fault Voltage, Magnitude
n:uprefpc:bus1%Pre-fault Voltage, Magnitude
n:Upref:bus1kVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bus1kVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bus1degPre-fault Voltage, Angle
n:phiui:bus1degAngle between Voltage and Current
n:Ithload:bus1%Loading, Thermal equivalent Current
n:Ipload:bus1%Loading, Peak Short-Circuit Current
n:Ithrtk:bus1kARated Short-Time Current (Tk)
n:XtoR:bus1ยทX/R ratio (peak)
n:RtoX:bus1ยทR/X ratio (peak)
n:XtoR_b:bus1ยทX/R ratio (dc)
n:RtoX_b:bus1ยทR/X ratio (dc)
n:fctof_b:bus1ยทEquivalent Frequency fc/f (dc)
n:rSbase:bus1p.u.Short-Circuit Impedance, Real Part
n:xSbase:bus1p.u.Short-Circuit Impedance, Imaginary Part
n:zSbase:bus1p.u.Short-Circuit Impedance, Magnitude
n:Tn:bus1msGrid Time Constant
n:Ik:bus1kASteady-State Short-Circuit Current
n:cfac:bus1ยทVoltage Factor
n:Iasy:bus1kAAsymmetrical Breaking Current
n:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aper phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1kV3*U0
n:phiu0:bus1degZero-Sequence Voltage, Angle
n:U1:bus1kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1degPositive-Sequence Voltage, Angle
n:u2:bus1p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1degNegative-Sequence Voltage, Angle
n:U1l:bus1kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1degNeutral-Ground Voltage, Angle
n:upht:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:Ikss:bus1:Aper phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
n:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
n:Skss:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
n:Skssx3:bus1:Aper phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
n:ip:bus1:Aper phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
n:Ib:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Breaking Current
n:Sb:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAShort-Circuit Breaking Power
n:Ith:bus1:Aper phase :A, :B, :C, unbalanced onlykAThermal equivalent Short-Circuit Current
n:Ithmax:bus1kAMax. Thermal equivalent Short-Circuit Current
n:R0:bus1OhmZero-Sequence Impedance, Real Part
n:X0:bus1OhmZero-Sequence Impedance, Imaginary Part
n:Z0:bus1OhmZero-Sequence Impedance, Magnitude
n:phiz0:bus1degZero-Sequence Impedance, Angle
n:r0Sbase:bus1p.u.Zero-Sequence Impedance, Real Part
n:x0Sbase:bus1p.u.Zero-Sequence Impedance, Imaginary Part
n:z0Sbase:bus1p.u.Zero-Sequence Impedance, Magnitude
n:R1:bus1OhmPositive-Sequence Impedance, Real Part
n:X1:bus1OhmPositive-Sequence Impedance, Imaginary Part
n:Z1:bus1OhmPositive-Sequence Impedance, Magnitude
n:phiz1:bus1degPositive-Sequence Impedance, Angle
n:r1Sbase:bus1p.u.Positive-Sequence Impedance, Real Part
n:x1Sbase:bus1p.u.Positive-Sequence Impedance, Imaginary Part
n:z1Sbase:bus1p.u.Positive-Sequence Impedance, Magnitude
n:R2:bus1OhmNegative-Sequence Impedance, Real Part
n:X2:bus1OhmNegative-Sequence Impedance, Imaginary Part
n:Z2:bus1OhmNegative-Sequence Impedance, Magnitude
n:phiz2:bus1degNegative-Sequence Impedance, Angle
n:r2Sbase:bus1p.u.Negative-Sequence Impedance, Real Part
n:x2Sbase:bus1p.u.Negative-Sequence Impedance, Imaginary Part
n:z2Sbase:bus1p.u.Negative-Sequence Impedance, Magnitude
n:R0toX0:bus1ยทR0/X0 ratio (Zk")
n:X0toR0:bus1ยทX0/R0 ratio (Zk")
n:R2toX2:bus1ยทR2/X2 ratio (Zk")
n:X2toR2:bus1ยทX2/R2 ratio (Zk")
n:R:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Ground
n:X:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Ground
n:Z:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Ground
n:phiz:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Ground
n:Rl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Line
n:Xl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Line
n:Zl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Line
n:phizl:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Line
n:Rln:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Neutral
n:Xln:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Neutral
n:Zln:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Neutral
n:phizln:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Neutral
n:Rn:bus1OhmNetwork Resistance, Neutral
n:Xn:bus1OhmNetwork Reactance, Neutral
n:Zn:bus1OhmNetwork Impedance, Neutral
n:phizn:bus1degAngle of Network Impedance, Neutral
n:eff:bus1:Aper phase :A, :B, :C, unbalanced onlyยทEarth Fault Factor
n:X0toX1:bus1ยทX0/X1
n:In:bus1kANeutral Current, Magnitude
n:phiin:bus1degNeutral Current, Angle
n:I0:bus1kAZero-Sequence Current, Magnitude
n:I0x3:bus1kA3*I0
n:phii0:bus1degZero-Sequence Current, Angle
n:I1:bus1kAPositive-Sequence Current, Magnitude
n:phii1:bus1degPositive-Sequence Current, Angle
n:I2:bus1kANegative-Sequence Current, Magnitude
n:phii2:bus1degNegative-Sequence Current, Angle
n:urpref:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Real Part
n:uipref:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Imaginary Part
n:upref:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Magnitude
n:uprefpc:bus1:Aper phase :A, :B, :C, unbalanced only%Pre-fault Voltage, Magnitude
n:Upref:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bus1:Aper phase :A, :B, :C, unbalanced onlydegPre-fault Voltage, Angle
n:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
n:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
n:phiu2i2:bus1degAngle between Voltage and Current in negative sequence system
n:phiu0i0:bus1degAngle between Voltage and Current in zero-sequence system
n:Ik:bus1:Aper phase :A, :B, :C, unbalanced onlykASteady-State Short-Circuit Current
n:in:bus1p.u.Neutral Current, Magnitude
n:i0r:bus1p.u.Zero-Sequence Current, Real Part
n:i0i:bus1p.u.Zero-Sequence Current, Imaginary Part
n:i0:bus1p.u.Zero-Sequence Current, Magnitude
n:i1r:bus1p.u.Positive-Sequence Current, Real Part
n:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
n:i1:bus1p.u.Positive-Sequence Current, Magnitude
n:i2r:bus1p.u.Negative-Sequence Current, Real Part
n:i2i:bus1p.u.Negative-Sequence Current, Imaginary Part
n:i2:bus1p.u.Negative-Sequence Current, Magnitude

ElmXnet rms simulation results

Read after ComInc (RMS) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bus1p.u.Voltage, Real Part, referred to network
m:uinet:bus1p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1degPositive-Sequence-Voltage, Angle
m:irnet:bus1p.u.Current, Real Part, referred to network
m:iinet:bus1p.u.Current, Imaginary Part, referred to network
m:inet:bus1p.u.Current, Magnitude, referred to network
m:I:bus1kACurrent, Magnitude
m:phii:bus1degCurrent, Angle
m:i1r:bus1p.u.Positive-Sequence Current, Real Part
m:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:S:bus1MVAApparent Power
m:cosphi:bus1ยทPower Factor
m:tanphi:bus1ยทtan(phi)
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:Ssum:bus1MVATotal Apparent Power
m:cosphisum:bus1ยทTotal Power Factor
m:tanphisum:bus1ยทTotal tan(phi)
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:ur:bus1p.u.Voltage, Real Part
m:ui:bus1p.u.Voltage, Imaginary Part
m:u:bus1p.u.Voltage, Magnitude
m:ir:bus1p.u.Current, Real Part
m:ii:bus1p.u.Current, Imaginary Part
m:i:bus1p.u.Current, Magnitude
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1sFault Clearing Time
m:Brkload:bus1%Breaker Loading
m:Spu:bus1MVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bus1p.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bus1degZero-Sequence-Voltage, Angle
m:u2:bus1p.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bus1degNegative-Sequence-Voltage, Angle
m:irnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:iinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:inet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bus1p.u.Zero-Sequence Current, Real Part
m:i0i:bus1p.u.Zero-Sequence Current, Imaginary Part
m:i0:bus1p.u.Zero-Sequence Current, Magnitude
m:I0:bus1kAZero-Sequence Current, Magnitude
m:I0x3:bus1kA3*I0
m:phii0:bus1degZero-Sequence Current, Angle
m:i2r:bus1p.u.Negative-Sequence Current, Real Part
m:i2i:bus1p.u.Negative-Sequence Current, Imaginary Part
m:i2:bus1p.u.Negative-Sequence Current, Magnitude
m:I2:bus1kANegative-Sequence Current, Magnitude
m:phii2:bus1degNegative-Sequence Current, Angle
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bus1:Aper phase :A, :B, :C, unbalanced onlyยทPower Factor
m:tanphi:bus1:Aper phase :A, :B, :C, unbalanced onlyยทtan(phi)
m:Pln:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bus1MWPositive Sequence Active Power
m:Q1:bus1MvarPositive Sequence Reactive Power
m:P2:bus1MWNegative Sequence Active Power
m:Q2:bus1MvarNegative Sequence Reactive Power
m:P0:bus1MWZero Sequence Active Power
m:Q0:bus1MvarZero Sequence Reactive Power
m:i2P:bus1p.u.Negative-Sequence Active Current
m:i2Q:bus1p.u.Negative-Sequence Reactive Current
m:I2P:bus1kANegative-Sequence Active Current
m:I2Q:bus1kANegative-Sequence Reactive Current
m:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1degAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bus1degAngle between Voltage and Current in negative sequence system
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bus1:Aper phase :A, :B, :C, unbalanced only%Breaker Loading
c:sgnnMVATotal rated apparent power (ngnum*sgn)
c:c2ยทVoltage Coefficient (uknom/ugn)
c:TesExcitation-Time constant
c:TDsTime constant of D-winding
c:TxsTime Constant of x-winding
c:TQsTime Constant of Q-winding
c:TagsAcceleration Time
c:xmep.u.Electrical Torque
c:Ydp.u.Inverted reactance matrix
c:Yqp.u.Inverted reactance matrix
c:frnomHzNominal frequency
c:hpirad/sNominal angular frequency
c:loading%Loading
c:idยทDirect Axis Current
c:iqยทQuadrature Axis Current
c:ieยทExcitation Current
c:xmtp.u.Mechanical Torque
c:addmtยทAdditional Torque
c:psidยทFlux in d-axis
c:psiqยทFlux in q-axis
c:pgtp.u.Active power
c:fep.u.El. frequency
c:xdssp.u.Subtransient reactance (d-axis)
c:xqssp.u.Subtransient reactance (q-axis)
c:PtspinMWTotal Turbine Power of Area
c:PnomspinMWTotal Nominal Power of Spinning Machines in Area
c:PresspinMWSpinning Reserve of Area
c:TagavsSystem Inertia of Area
c:p_magยทParticipation, Magnitude
c:p_phidegParticipation, Angle
c:p_magsยทParticipation, Magnitude (signed)
c:lEVec_magยทControllability, Magnitude
c:lEVec_phidegControllability, Angle
c:lEVec_magsยทControllability, Magnitude (signed)
c:rEVec_magยทObservability, Magnitude
c:rEVec_phidegObservability, Angle
c:rEVec_magsยทObservability, Magnitude (signed)
c:droopยทSystem regulation
c:dpp.u.Power adjustment due to speed deviation
c:psidssp.u.Subtransient Flux (d-axis)
c:psiqssp.u.Subtransient Flux (q-axis)
c:r0ยทZero Sequence Resistance
c:x0ยทZero Sequence Reactance
c:r2ยทNegative Sequence Resistance
c:x2ยทNegative Sequence Reactance
c:rearthยทGrounding Resistance
c:xearthยทGrounding Reactance
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:ishc:bus1p.u.Short-Circuit Current, magnitude
n:Ishc:bus1kAShort-Circuit Current, magnitude
n:fe:bus1p.u.Electrical Frequency
n:dfehz:bus1HzDeviation of the El. Frequency
n:fehz:bus1HzElectrical Frequency
n:frnom:bus1HzNominal Frequency
n:ishcr:bus1p.u.Short-Circuit Current, real
n:ishci:bus1p.u.Short-Circuit Current, imag
n:dfedt:bus1p.u./sDerivative of El. Frequency
n:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aper phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1kV3*U0
n:phiu0:bus1degZero-Sequence Voltage, Angle
n:U1:bus1kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1degPositive-Sequence Voltage, Angle
n:u2:bus1p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1degNegative-Sequence Voltage, Angle
n:U1l:bus1kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1degNeutral-Ground Voltage, Angle
n:upht:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bus1p.u.Average-Voltage, Magnitude
n:Um:bus1kVAverage-Voltage, Magnitude
n:ishc:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, magnitude
n:Ishc:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, magnitude
n:inshc:bus1p.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bus1kANeutral Short-Circuit Current, magnitude
n:ishcr:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, real
n:ishci:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, imag
s:psisrp.u.Stator Flux, Real Part
s:psisip.u.Stator Flux, Imaginary Part
s:psiep.u.Excitation-Flux
s:psiDp.u.Flux in D-winding
s:psixp.u.Flux in x-winding
s:psiQp.u.Flux in Q-winding
s:speedp.u.Speed
s:phip.u.Rotor-angle
s:vep.u.Excitation voltage
s:ptp.u.Turbine Power
s:xmdmp.u.Mechanical Torque
s:uoutp.u.Voltage
s:xspeedp.u.Speed
s:frefp.u.Reference Frequency

ElmXnet emt simulation results

Read after ComInc (EMT) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:u0:bus1p.u.Zero-Sequence-Voltage
m:u1r:bus1p.u.Voltage Phasor, Real Part
m:u1i:bus1p.u.Voltage Phasor, Imaginary Part
m:u1:bus1p.u.Voltage Phasor, Magnitude
m:U1:bus1kVLine-Ground Voltage Phasor, Magnitude
m:U1l:bus1kVLine-Line Voltage Phasor, Magnitude
m:phiu1:bus1degVoltage Phasor, Angle
m:inet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, referred to network
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAPhase Current
m:i0:bus1p.u.Zero-Sequence Current
m:I0:bus1kAZero-Sequence Current
m:I0x3:bus1kA3*I0
m:i1r:bus1p.u.Current Phasor, Real Part
m:i1i:bus1p.u.Current Phasor, Imaginary Part
m:i1:bus1p.u.Current Phasor, Magnitude
m:I1:bus1kACurrent Phasor, Magnitude
m:phii1:bus1degCurrent Phasor, Angle
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Psum:bus1MWPower-Phasor, Active Power
m:Qsum:bus1MvarPower Phasor, Reactive Part
m:Ssum:bus1MVAPower Phasor, Apparent Power
m:i1P:bus1p.u.Current Phasor, Active Current
m:i1Q:bus1p.u.Current Phasor, Reactive Current
m:I1P:bus1kACurrent Phasor, Active Current
m:I1Q:bus1kACurrent Phasor, Reactive Current
m:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
m:i:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current
m:phiu1i1:bus1degAngle between Voltage and Current Phasor
m:Tfct:bus1sFault Clearing Time
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:unet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, referred to network
m:cosphi1:bus1ยทPower-Phasor, Power-Factor
c:sgnnMVATotal rated apparent power (ngnum*sgn)
c:c2ยทVoltage Coefficient (uknom/ugn)
c:TesExcitation-Time constant
c:TDsTime constant of D-winding
c:TxsTime Constant of x-winding
c:TQsTime Constant of Q-winding
c:TagsAcceleration Time
c:xmep.u.Electrical Torque
c:Ydp.u.Inverted reactance matrix
c:Yqp.u.Inverted reactance matrix
c:frnomHzNominal frequency
c:hpirad/sNominal angular frequency
c:idp.u.Direct Axis current
c:iqp.u.Quadrature Axis current
c:ieยทExcitation Current
c:xmtp.u.Mechanical Torque
c:r0p.u.Zero Sequence Resistance
c:x0p.u.Zero Sequence Reactance
c:rearthp.u.Grounding Resistance
c:xearthp.u.Grounding Reactance
c:addmtยทAdditional Torque
c:psidp.u.Flux in d-axis
c:psiqp.u.Flux in q-axis
c:pgtp.u.Active power
c:fep.u.El. frequency
c:xdssp.u.Subtransient reactance (d-axis)
c:xqssp.u.Subtransient reactance (q-axis)
c:PtspinMWTotal Turbine Power of Area
c:PnomspinMWTotal Nominal Power of Spinning Machines in Area
c:PresspinMWSpinning Reserve of Area
c:TagavsSystem Inertia of Area
c:p_magยทParticipation, Magnitude
c:p_phidegParticipation, Angle
c:p_magsยทParticipation, Magnitude (signed)
c:lEVec_magยทControllability, Magnitude
c:lEVec_phidegControllability, Angle
c:lEVec_magsยทControllability, Magnitude (signed)
c:rEVec_magยทObservability, Magnitude
c:rEVec_phidegObservability, Angle
c:rEVec_magsยทObservability, Magnitude (signed)
c:droopยทSystem regulation
c:dpp.u.Power adjustment due to speed deviation
c:igenยทIndex
c:ussp.u.Subtransient Voltage
c:xssp.u.Subtransient Reactance
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Phase Voltage
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Voltage
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage
n:u0:bus1p.u.Zero-Sequence-Voltage
n:U0:bus1kVZero-Sequence-Voltage
n:U0x3:bus1kV3*U0
n:u1:bus1p.u.Voltage Phasor, Magnitude
n:u1pc:bus1%Voltage Phasor, Magnitude
n:u1r:bus1p.u.Voltage Phasor, Real Part
n:u1i:bus1p.u.Voltage Phasor, Imaginary Part
n:U1:bus1kVVoltage Phasor, Magnitude
n:phiu1:bus1degVoltage Phasor, Angle
n:U1l:bus1kVLine-Line Voltage Phasor, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage
n:un:bus1p.u.Neutral-Ground Voltage
n:Un:bus1kVNeutral-Ground Voltage
n:ishc:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current
n:Ishc:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:inshc:bus1p.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bus1kANeutral Short-Circuit Current, magnitude
n:fe:bus1p.u.Electrical Frequency
n:dfehz:bus1HzDeviation of the El. Frequency
n:fehz:bus1HzElectrical Frequency
n:frnom:bus1HzNominal Frequency
s:psiep.u.Excitation-Flux
s:psiDp.u.Flux in D-winding
s:psixp.u.Flux in x-winding
s:psiQp.u.Flux in Q-winding
s:speedp.u.Speed
s:phip.u.Rotor-angle
s:ptp.u.Turbine Power
s:xmdmp.u.Mechanical Torque
s:uoutp.u.Voltage
s:xspeedp.u.Speed
s:usdp.u.Transient Voltage (d-axis)
s:usqp.u.Transient Voltage (q-axis)

ElmXnet dc load flow results

Read after ComLdf (DC) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
c:pMWTotal Active Power
c:cosnยทNominal-Power factor
c:uinip.u.Voltage Setpoint for PV and Slack
c:iPowerOnยทFlag
c:PdispMWPower (Eco-Dispatch)
c:KfMW/HzFrequency Bias
c:iRefElementยทReference Element
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:Pgen:bus1MWGeneration, Active Power
n:Pmot:bus1MWMotor Load, Active Power
n:Pload:bus1MWGeneral Load, Active Power
n:Pcomp:bus1MWCompensation (Losses)
n:Pnet:bus1MWExternal Networks, Active Power
n:Pflow:bus1MWPower Flow, Active Power
s:psetMWActive Power Setpoint
s:dFinHzFrequency Deviation
s:dFHzFrequency Deviation Output

Read after ComMod with GetAttribute. c: calculation parameter, s: signal (state or model variable).

AttributeUnitDescription
c:sgnnMVATotal rated apparent power (ngnum*sgn)
c:c2ยทVoltage Coefficient (uknom/ugn)
c:TesExcitation-Time constant
c:TDsTime constant of D-winding
c:TxsTime Constant of x-winding
c:TQsTime Constant of Q-winding
c:TagsAcceleration Time
c:xmep.u.Electrical Torque
c:Ydp.u.Inverted reactance matrix
c:Yqp.u.Inverted reactance matrix
c:frnomHzNominal frequency
c:hpirad/sNominal angular frequency
c:loading%Loading
c:idยทDirect Axis Current
c:iqยทQuadrature Axis Current
c:ieยทExcitation Current
c:xmtp.u.Mechanical Torque
c:addmtยทAdditional Torque
c:psidยทFlux in d-axis
c:psiqยทFlux in q-axis
c:pgtp.u.Active power
c:fep.u.El. frequency
c:xdssp.u.Subtransient reactance (d-axis)
c:xqssp.u.Subtransient reactance (q-axis)
c:PtspinMWTotal Turbine Power of Area
c:PnomspinMWTotal Nominal Power of Spinning Machines in Area
c:PresspinMWSpinning Reserve of Area
c:TagavsSystem Inertia of Area
c:p_magยทParticipation, Magnitude
c:p_phidegParticipation, Angle
c:p_magsยทParticipation, Magnitude (signed)
c:lEVec_magยทControllability, Magnitude
c:lEVec_phidegControllability, Angle
c:lEVec_magsยทControllability, Magnitude (signed)
c:rEVec_magยทObservability, Magnitude
c:rEVec_phidegObservability, Angle
c:rEVec_magsยทObservability, Magnitude (signed)
c:droopยทSystem regulation
c:dpp.u.Power adjustment due to speed deviation
c:psidssp.u.Subtransient Flux (d-axis)
c:psiqssp.u.Subtransient Flux (q-axis)
s:psisrp.u.Stator Flux, Real Part
s:psisip.u.Stator Flux, Imaginary Part
s:psiep.u.Excitation-Flux
s:psiDp.u.Flux in D-winding
s:psixp.u.Flux in x-winding
s:psiQp.u.Flux in Q-winding
s:speedp.u.Speed
s:phip.u.Rotor-angle
s:vep.u.Excitation voltage
s:ptp.u.Turbine Power
s:xmdmp.u.Mechanical Torque
s:uoutp.u.Voltage
s:xspeedp.u.Speed
s:frefp.u.Reference Frequency

ElmXnet optimal power flow results

Read after ComOpf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:bus1p.u.Voltage, Real Part, referred to network
m:uinet:bus1p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1degPositive-Sequence-Voltage, Angle
m:irnet:bus1p.u.Current, Real Part, referred to network
m:iinet:bus1p.u.Current, Imaginary Part, referred to network
m:inet:bus1p.u.Current, Magnitude, referred to network
m:I:bus1kACurrent, Magnitude
m:phii:bus1degCurrent, Angle
m:i1r:bus1p.u.Positive-Sequence Current, Real Part
m:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:S:bus1MVAApparent Power
m:cosphi:bus1ยทPower Factor
m:tanphi:bus1ยทtan(phi)
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:Ssum:bus1MVATotal Apparent Power
m:cosphisum:bus1ยทTotal Power Factor
m:tanphisum:bus1ยทTotal tan(phi)
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:ur:bus1p.u.Voltage, Real Part
m:ui:bus1p.u.Voltage, Imaginary Part
m:u:bus1p.u.Voltage, Magnitude
m:ir:bus1p.u.Current, Real Part
m:ii:bus1p.u.Current, Imaginary Part
m:i:bus1p.u.Current, Magnitude
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1sFault Clearing Time
m:Brkload:bus1%Breaker Loading
m:Spu:bus1MVA/p.u.Apparent Power per p.u. Voltage
c:pMWTotal Active Power
c:qMvarTotal Reactive Power
c:sgnnMVATotal rated apparent power (ngnum*sgn)
c:cosnยทNominal-Power factor
c:c2ยทVoltage Coefficient (uknom/ugn)
c:uinip.u.Voltage Setpoint for PV and Slack
c:iPowerOnยทFlag
c:xdqp.u.Synchronous Reactance
c:rsp.u.Resistance
c:i_qlimยทReactive power limit reached
c:QminMvarLower limit of reactive power
c:QmaxMvarUpper limit of reactive power
c:smMVAComplex Power
c:phiiniยทInitial Angle
c:MaxSMVAMax. Apparent Power
c:PdispMWPower (Eco-Dispatch)
c:cst_dispUSD/hOperating Costs
c:avgCostsUSD/MWhAverage Costs per MWh
c:KfMW/HzFrequency Bias
c:Kpp.u.Active Power Participation
c:iRefElementยทReference Element
c:nCtrlIterยทNo. of CTRL-iterations
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:QtargetMvarQ target value
c:QtargetDeltaMvarDeviation from Q target value
c:PtargetMWP target value
c:totRedispatchPMWhTotal redispatched energy
c:totRedispatchQMvarhTotal redispatched energy
c:totRedispatchCostsUSDTotal redispatch costs
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bus1MWGeneration, Active Power
n:Qgen:bus1MvarGeneration, Reactive Power
n:Pmot:bus1MWMotor Load, Active Power
n:Qmot:bus1MvarMotor Load, Reactive Power
n:Pload:bus1MWGeneral Load, Active Power
n:Qload:bus1MvarGeneral Load, Reactive Power
n:Pcomp:bus1MWCompensation (Losses)
n:Qcomp:bus1MvarCompensation
n:Pnet:bus1MWExternal Networks, Active Power
n:Qnet:bus1MvarExternal Networks, Reactive Power
n:Pflow:bus1MWPower Flow, Active Power
n:Qflow:bus1MvarPower Flow, Reactive Power
n:Pout:bus1MWOutgoing Flow, Active Power
n:Qout:bus1MvarOutgoing Power, Reactive Power
n:Sout:bus1MVAOutgoing Power, Apparent Power
n:cosphiout:bus1ยทOutgoing Power, Power Factor
n:Pbalance:bus1MWActive Power Balance (=0)
n:Qbalance:bus1MvarReactive Power Balance (=0)
n:LossPdown:bus1MWLosses, downstream
n:LossQdown:bus1MvarLosses, downstream (Reactive Power)
n:LossPdownload:bus1MWLoad losses, downstream
n:LossQdownload:bus1MvarLoad losses, downstream
n:LossPdownnoload:bus1MWNo load losses, downstream
n:LossQdownnoload:bus1MvarNo load losses, downstream
n:du_feed:bus1%Difference from voltage at start of feeder

ElmXnet basic data

b: values are worked out from the input data. Read them; they are not set.

AttributeUnitDescription
b:loc_nameยทName

Related

โ† ElmVac AC Voltage Source ยท ElmFilter Harmonic Filter โ†’