ElmVac attributesPowerFactory AC Voltage Source

Every attribute of the PowerFactory AC Voltage Source (ElmVac): 129 input parameters and 835 result variables, with units and meaning. Copy a name into GetAttribute or SetAttribute.

What ElmVac is

An AC voltage source behind an impedance, used for ideal sources and test circuits.

Class
ElmVac, element class
PowerFactory name
AC Voltage Source
Terminal suffix
:bus1 terminal
Attributes
129 input parameters and 835 result variables, in 7 calculations

Read and write ElmVac in Python

import powerfactory

app = powerfactory.GetApplication()          # GetApplicationExt() from outside PowerFactory
app.GetFromStudyCase("ComLdf").Execute()      # results exist after a calculation

for obj in app.GetCalcRelevantObjects("*.ElmVac"):
    urnet_bus1 = obj.GetAttribute("m:urnet:bus1") # Voltage, Real Part, referred to network, p.u.
    print(obj.loc_name, urnet_bus1)

obj = app.GetCalcRelevantObjects("*.ElmVac")[0]
obj.SetAttribute("outserv", 1)                # take it out of service
  • A result at a terminal of the ac voltage source needs the terminal in its name: m:P:bus1, not m:P, which raises AttributeError.
  • An input parameter is read and written with or without its e: prefix: GetAttribute("outserv") and GetAttribute("e:outserv") give the same value.
  • RMS and EMT variables change over time: record them in a results object (ElmRes) to read the whole curve. GetAttribute after a run gives the value at the last time step.

ElmVac input parameters

The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.

AttributeUnitDescription
loc_name·Name
chr_name·Characteristic Name
for_name·Foreign Key
dat_src·Data source
sernum·Serial Number
manuf·Manufacturer
commissionDate·Commissioning Date
appr_modby·Modified by
outserv·Out of Service
iPossibleSlack·Slack Priority
iztreqz·Transient = Subtransient Impedance
iFreZ·Use Frequency Related Impedance for X/R Ratio Calculation
itype·Type
chaInputOpt·Defined for
nphase·No. of Phases
iAstabint·A-stable integration algorithm
leadUinput·Voltage input
leadUinputEMT·Voltage input
leadFinput·Frequency input
cosimModel·Used for Co-simulation
constr·Year of Construction
appr_status·Status
iHmcType·Type of Harmonic Voltages
UnomkVLine-Line
usetpp.u.Voltage, Magnitude
phisetpdegVoltage, Angle
usetp2p.u.Voltage, Magnitude
phisetp2degVoltage, Angle
usetp0p.u.Voltage, Magnitude
phisetp0degVoltage, Angle
dudfp.u./HzSpectral Density of Voltage Magnitude
dphidfdeg/HzSpectral Density of Voltage Angle
KpfMW/HzPrim. Frequency Bias
KsfMW/HzSec. Frequency Bias
P1hrmMWActive power
Q1hrmMvarReactive power
u1hrmp.u.Positive sequence voltage
curpreldkACurrent
cospreld·Power Factor
IkdkAIkd
tdsssTd''
tdssTd'
GPSlatdegLatitude / Northing
GPSlondegLongitude / Easting
R1OhmResistance, R1
X1OhmReactance, X1
R1sOhmResistance, R1s
X1sOhmReactance, X1s
R0OhmResistance, R0
X0OhmReactance, X0
R2OhmResistance, R2
X2OhmReactance, X2
PgenMWActive Power
QgenMvarReactive Power
PloadMWActive Power
QloadMvarReactive Power
PzloadMWActive Power
QzloadMvarReactive Power
RextOhmResistance
XextOhmReactance
phiSlackRefradInitial rotor angle
phiiniRefradInitial angle of bus voltage
appr_modif·Modified
ifreqs·Harm. Order
u1_magp.u.u1, Mag.
u1_phasedegu1, Ang.
u2_magp.u.u2, Mag.
u2_phasedegu2, Ang.
u0_magp.u.u0, Mag.
u0_phasedegu0, Ang.
umag_iec1p.u.U_h
ifreqs_iec2·Harm. Order
umag_iec2p.u.U_h
matZOhmFrequency related impedances (Positive, Negative and Zero sequence)
cimRdfId·RDF ID
desc·Description
fold_id·In Folder
bus1·TerminalObject: StaCubic
fcharduChaPol,ChaVec,ChaMatFrequency Dependency
fchardphiChaPol,ChaVec,ChaMatFrequency Dependency
p_phictrl·Angle ControlObject: ElmLdfctrl*
p_uctrl·Voltage ControlObject: ElmLdfctrl*
contbar·Controlled NodeObject: ElmTerm
phmc·Harmonic VoltagesObject: TypHmcvolt,TypHmcopvolt
fcharR1ChaPol,ChaVec,ChaMat,ChaOpfreqR1(f)
fcharL1ChaPol,ChaVec,ChaMat,ChaOpfreqL1(f)
fcharR0ChaPol,ChaVec,ChaMat,ChaOpfreqR0(f)
fcharL0ChaPol,ChaVec,ChaMat,ChaOpfreqL0(f)
fcharR2ChaPol,ChaVec,ChaMat,ChaOpfreqR2(f)
fcharL2ChaPol,ChaVec,ChaMat,ChaOpfreqL2(f)
fcharX1ChaPol,ChaVec,ChaMat,ChaOpfreqX1(f)
fcharX0ChaPol,ChaVec,ChaMat,ChaOpfreqX0(f)
fcharX2ChaPol,ChaVec,ChaMat,ChaOpfreqX2(f)
doc_id·Additional Data
pOwner·OwnerObject: ElmOwner
pOperator·OperatorObject: ElmOperator
cpHeadFold·Head Folder
bus1_bar·Terminal
cpGrid·GridObject: ElmNet
cpZone·ZoneObject: ElmZone
cpArea·AreaObject: ElmArea
cpFeed·FeederObject: ElmFeeder
ciDist·Distance from infeed in number of buses
ciLater·Lateral Index
ciDistRoot·Distance from first infeed in number of buses
ciDistAll·Distance from infeed in number of buses including switches
ciDistAllRoot·Distance from first infeed in number of buses including switches
cpOwner·OwnerObject: ElmOwner
cpOperator·OperatorObject: ElmOperator
cpBranch·BranchObject: ElmBranch
cpSite·SiteObject: ElmSite
cpSubstat·SubstationObject: ElmSubstat,ElmTrfstat
cpMeteostat·Meteo StationObject: ElmMeteostat
ciOutaged·Planned Outage
ciEnergized·Energized
ciEarthed·Earthed
cDisplayName·Display Name
cpSupplyTransformer·Supplying TransformerObject: ElmTr?,ElmTrmult
cpSupplyTrfStation·Supplying Secondary SubstationObject: ElmTrfstat
cpSupplySubstation·Supplying SubstationObject: ElmSubstat
UnnomkVLine-Ground
cfreqsHzFrequency
cTypHmc·Type of harmonic sources
L1mHInductance, L1
L0mHInductance, L0
L2mHInductance, L2
c_psecc·Ext. Secondary ControllerObject: ElmSecctrl
qdslCtrl·Quasi-Dynamic ModelObject: ElmQdsl
c_pmod·ModelObject: ElmComp

ElmVac load flow results

Read after ComLdf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bus1p.u.Voltage, Real Part, referred to network
m:uinet:bus1p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1degPositive-Sequence-Voltage, Angle
m:irnet:bus1p.u.Current, Real Part, referred to network
m:iinet:bus1p.u.Current, Imaginary Part, referred to network
m:inet:bus1p.u.Current, Magnitude, referred to network
m:I:bus1kACurrent, Magnitude
m:phii:bus1degCurrent, Angle
m:i1r:bus1p.u.Positive-Sequence Current, Real Part
m:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:S:bus1MVAApparent Power
m:cosphi:bus1·Power Factor
m:tanphi:bus1·tan(phi)
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:Ssum:bus1MVATotal Apparent Power
m:cosphisum:bus1·Total Power Factor
m:tanphisum:bus1·Total tan(phi)
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:ur:bus1p.u.Voltage, Real Part
m:ui:bus1p.u.Voltage, Imaginary Part
m:u:bus1p.u.Voltage, Magnitude
m:ir:bus1p.u.Current, Real Part
m:ii:bus1p.u.Current, Imaginary Part
m:i:bus1p.u.Current, Magnitude
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1sFault Clearing Time
m:Brkload:bus1%Breaker Loading
m:Spu:bus1MVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bus1p.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bus1degZero-Sequence-Voltage, Angle
m:u2:bus1p.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bus1degNegative-Sequence-Voltage, Angle
m:irnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part, referred to network
m:iinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part, referred to network
m:inet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude, referred to network
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bus1p.u.Zero-Sequence Current, Real Part
m:i0i:bus1p.u.Zero-Sequence Current, Imaginary Part
m:i0:bus1p.u.Zero-Sequence Current, Magnitude
m:I0:bus1kAZero-Sequence Current, Magnitude
m:I0x3:bus1kA3*I0
m:phii0:bus1degZero-Sequence Current, Angle
m:i2r:bus1p.u.Negative-Sequence Current, Real Part
m:i2i:bus1p.u.Negative-Sequence Current, Imaginary Part
m:i2:bus1p.u.Negative-Sequence Current, Magnitude
m:I2:bus1kANegative-Sequence Current, Magnitude
m:phii2:bus1degNegative-Sequence Current, Angle
m:ubfacI:bus1%Current Unbalance Factor
m:ubfacS:bus1%Power Unbalance Factor
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bus1:Aper phase :A, :B, :C, unbalanced only·Power Factor
m:tanphi:bus1:Aper phase :A, :B, :C, unbalanced only·tan(phi)
m:Pln:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bus1MWPositive Sequence Active Power
m:Q1:bus1MvarPositive Sequence Reactive Power
m:P2:bus1MWNegative Sequence Active Power
m:Q2:bus1MvarNegative Sequence Reactive Power
m:P0:bus1MWZero Sequence Active Power
m:Q0:bus1MvarZero Sequence Reactive Power
m:i2P:bus1p.u.Negative-Sequence Active Current
m:i2Q:bus1p.u.Negative-Sequence Reactive Current
m:I2P:bus1kANegative-Sequence Active Current
m:I2Q:bus1kANegative-Sequence Reactive Current
m:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1degAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bus1degAngle between Voltage and Current in negative sequence system
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bus1:Aper phase :A, :B, :C, unbalanced only%Breaker Loading
c:uinip.u.Voltage
c:phiuradVoltage Angle
c:KpfMW/HzPrimary Frequency Bias
c:KsfMW/HzSecondary Frequency Bias
c:Kp·Secondary Factor
c:iRefElement·Reference Element
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
c:uini0·0-Sequ. Voltage
c:uini2·2-Sequ. Voltage
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bus1MWGeneration, Active Power
n:Qgen:bus1MvarGeneration, Reactive Power
n:Pmot:bus1MWMotor Load, Active Power
n:Qmot:bus1MvarMotor Load, Reactive Power
n:Pload:bus1MWGeneral Load, Active Power
n:Qload:bus1MvarGeneral Load, Reactive Power
n:Pcomp:bus1MWCompensation (Losses)
n:Qcomp:bus1MvarCompensation
n:Pnet:bus1MWExternal Networks, Active Power
n:Qnet:bus1MvarExternal Networks, Reactive Power
n:Pflow:bus1MWPower Flow, Active Power
n:Qflow:bus1MvarPower Flow, Reactive Power
n:Pout:bus1MWOutgoing Flow, Active Power
n:Qout:bus1MvarOutgoing Power, Reactive Power
n:Sout:bus1MVAOutgoing Power, Apparent Power
n:cosphiout:bus1·Outgoing Power, Power Factor
n:Pbalance:bus1MWActive Power Balance (=0)
n:Qbalance:bus1MvarReactive Power Balance (=0)
n:LossPdown:bus1MWLosses, downstream
n:LossQdown:bus1MvarLosses, downstream (Reactive Power)
n:LossPdownload:bus1MWLoad losses, downstream
n:LossQdownload:bus1MvarLoad losses, downstream
n:LossPdownnoload:bus1MWNo load losses, downstream
n:LossQdownnoload:bus1MvarNo load losses, downstream
n:du_feed:bus1%Difference from voltage at start of feeder
n:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aper phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1kV3*U0
n:phiu0:bus1degZero-Sequence Voltage, Angle
n:U1:bus1kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1degPositive-Sequence Voltage, Angle
n:u2:bus1p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1degNegative-Sequence Voltage, Angle
n:U1l:bus1kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1degNeutral-Ground Voltage, Angle
n:upht:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bus1p.u.Average-Voltage, Magnitude
n:Um:bus1kVAverage-Voltage, Magnitude
n:uphtmin:bus1p.u.Minimum of Phase Technology dependent Voltage, Magnitude
n:uphtmax:bus1p.u.Maximum of Phase Technology dependent Voltage, Magnitude
n:ubfac:bus1%Unbalance Factor
s:U_AkVVoltage, Magnitude, Phase a
s:U_BkVVoltage, Magnitude, Phase b
s:U_CkVVoltage, Magnitude, Phase c
s:phiu_BdegVoltage, Angle, Phase b
s:phiu_CdegVoltage, Angle, Phase c
s:u0p.u.Voltage-Input
s:Ul0kVVoltage-Input (Line-Line)
s:dphiuradVoltage Angle Input
s:dFinHzFrequency Deviation
s:dFHzFrequency Deviation Output

ElmVac short-circuit results

Read after ComShc with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:I:bus1kAShort-Circuit Current, Magnitude
m:phii:bus1degPhase Current, Angle
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in Positive-Sequence System
m:Tfct:bus1sFault Clearing Time
m:Ikss:bus1kAInitial Short-Circuit Current
m:ikss:bus1p.u.Initial Short-Circuit Current, Magnitude
m:Skss:bus1MVAInitial Short-Circuit Power
m:ip:bus1kAPeak Short-Circuit Current
m:maxIkss:bus1kAMax. Initial Short-Circuit Current
m:maxip:bus1kAMax. Peak Short-Circuit Current
m:maxIth:bus1kAMax. Thermal equivalent Short-Circuit Current
m:maxIb:bus1kAMax. Breaking Current
m:R:bus1OhmFault Impedance, Real Part
m:X:bus1OhmFault Impedance, Imaginary Part
m:Z:bus1OhmFault Impedance, Magnitude
m:phiz:bus1degFault Impedance, Angle
m:Rs:bus1OhmSource Impedance, Real Part
m:Xs:bus1OhmSource Impedance, Imaginary Part
m:Zs:bus1OhmSource Impedance, Magnitude
m:phizs:bus1degSource Impedance, Angle
m:BrkIpload:bus1%Breaker Loading (peak)
m:Ib:bus1kAShort-Circuit Breaking Current
m:Sb:bus1MVAShort-Circuit Breaking Power
m:Ith:bus1kAThermal equivalent Short-Circuit Current
m:zSbase:bus1p.u.Fault Impedance, Magnitude
m:XtoR:bus1·X/R ratio
m:cosphiui:bus1·cosphi
m:BrkIbload:bus1%Breaker Loading (breaking)
m:BrkmaxIb:bus1kAMax. Breaking Current (breaker time)
m:Ik:bus1kASteady-State Short-Circuit Current
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, Magnitude
m:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:I0:bus1kAZero-Sequence Current, Magnitude
m:I0x3:bus1kA3*I0
m:phii0:bus1degZero-Sequence Current, Angle
m:I2:bus1kANegative-Sequence Current, Magnitude
m:phii2:bus1degNegative-Sequence Current, Angle
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:cosphisum:bus1·Total Power Factor
m:P2:bus1MWP2
m:Q2:bus1MvarQ2
m:P0:bus1MWP0
m:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1degAngle between Voltage and Current in Zero-Sequence System
m:phiu2i2:bus1degAngle between Voltage and Current in Negative-Sequence System
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:Ikss:bus1:Aper phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
m:ikss:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Initial Short-Circuit Current, Magnitude
m:Skss:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
m:Skssx3:bus1:Aper phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
m:ip:bus1:Aper phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
m:Z:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmFault Impedance, Magnitude
m:phiz:bus1:Aper phase :A, :B, :C, unbalanced onlydegFault Impedance, Angle
m:Zl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmLine-Line Fault Impedance, Magnitude
m:phizl:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Fault Impedance, Angle
m:Z0:bus1OhmZero-Sequence Fault Impedance, Magnitude
m:phiz0:bus1degZero-Sequence Fault Impedance, Angle
m:z0Sbase:bus1p.u.Zero-Sequence Fault Impedance, Magnitude
m:cosphiu1i1:bus1·Positive-Sequence cosphi
m:I0x3watt:bus1kAEarth-Fault Residual Current
m:I0x3var:bus1kACapacitive Earth-Fault Current
m:Q0cap:bus1MvarQ0 capacitive
m:Rfrel:bus1OhmRelay Impedance, Real Part
m:Xfrel:bus1OhmRelay Impedance, Imaginary Part
m:Zfrel:bus1OhmRelay Impedance, Magnitude
m:phizfrel:bus1degRelay Impedance, Angle
m:Zf:bus1OhmMeas. Fault Impedance, Magnitude
m:phizf:bus1degMeas. Fault Impedance, Angle
c:uinip.u.Voltage
c:phiuradVoltage Angle
c:ROhmResistance
c:XOhmReactance
c:ZOhmImpedance
c:GMWLoad Conductance
c:BMvarLoad Susceptance
c:YMVALoad Admittance
c:uini0p.u.0-Sequ. Voltage
c:uini2p.u.2-Sequ. Voltage
c:R1OhmResistance
c:X1OhmReactance
c:Z1OhmImpedance
c:G1MWLoad Conductance
c:B1MvarLoad Susceptance
c:Y1MVALoad Admittance
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:Ikss:bus1kAInitial Short-Circuit Current
n:I:bus1kAShort-Circuit Current
n:phii:bus1degPhase Current, Angle
n:Skss:bus1MVAInitial Short-Circuit Power
n:ip:bus1kAPeak Short-Circuit Current
n:Ib:bus1kAShort-Circuit Breaking Current
n:Sb:bus1MVAShort-Circuit Breaking Power
n:idc:bus1kADecaying Component
n:Ith:bus1kAThermal equivalent Short-Circuit Current
n:R1toX1:bus1·R1/X1 ratio (Zk")
n:X1toR1:bus1·X1/R1 ratio (Zk")
n:R:bus1OhmShort-Circuit Impedance, Real Part
n:X:bus1OhmShort-Circuit Impedance, Imaginary Part
n:Z:bus1OhmShort-Circuit Impedance, Magnitude
n:phiz:bus1degShort-Circuit Impedance, Angle
n:urpref:bus1p.u.Pre-fault Voltage, Real Part
n:uipref:bus1p.u.Pre-fault Voltage, Imaginary Part
n:upref:bus1p.u.Pre-fault Voltage, Magnitude
n:uprefpc:bus1%Pre-fault Voltage, Magnitude
n:Upref:bus1kVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bus1kVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bus1degPre-fault Voltage, Angle
n:phiui:bus1degAngle between Voltage and Current
n:Ithload:bus1%Loading, Thermal equivalent Current
n:Ipload:bus1%Loading, Peak Short-Circuit Current
n:Ithrtk:bus1kARated Short-Time Current (Tk)
n:XtoR:bus1·X/R ratio (peak)
n:RtoX:bus1·R/X ratio (peak)
n:XtoR_b:bus1·X/R ratio (dc)
n:RtoX_b:bus1·R/X ratio (dc)
n:fctof_b:bus1·Equivalent Frequency fc/f (dc)
n:rSbase:bus1p.u.Short-Circuit Impedance, Real Part
n:xSbase:bus1p.u.Short-Circuit Impedance, Imaginary Part
n:zSbase:bus1p.u.Short-Circuit Impedance, Magnitude
n:Tn:bus1msGrid Time Constant
n:Ik:bus1kASteady-State Short-Circuit Current
n:cfac:bus1·Voltage Factor
n:Iasy:bus1kAAsymmetrical Breaking Current
n:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aper phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1kV3*U0
n:phiu0:bus1degZero-Sequence Voltage, Angle
n:U1:bus1kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1degPositive-Sequence Voltage, Angle
n:u2:bus1p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1degNegative-Sequence Voltage, Angle
n:U1l:bus1kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1degNeutral-Ground Voltage, Angle
n:upht:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:Ikss:bus1:Aper phase :A, :B, :C, unbalanced onlykAInitial Short-Circuit Current
n:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
n:Skss:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAInitial Short-Circuit Power
n:Skssx3:bus1:Aper phase :A, :B, :C, unbalanced onlyMVA3*Initial Short-Circuit Power
n:ip:bus1:Aper phase :A, :B, :C, unbalanced onlykAPeak Short-Circuit Current
n:Ib:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Breaking Current
n:Sb:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAShort-Circuit Breaking Power
n:Ith:bus1:Aper phase :A, :B, :C, unbalanced onlykAThermal equivalent Short-Circuit Current
n:Ithmax:bus1kAMax. Thermal equivalent Short-Circuit Current
n:R0:bus1OhmZero-Sequence Impedance, Real Part
n:X0:bus1OhmZero-Sequence Impedance, Imaginary Part
n:Z0:bus1OhmZero-Sequence Impedance, Magnitude
n:phiz0:bus1degZero-Sequence Impedance, Angle
n:r0Sbase:bus1p.u.Zero-Sequence Impedance, Real Part
n:x0Sbase:bus1p.u.Zero-Sequence Impedance, Imaginary Part
n:z0Sbase:bus1p.u.Zero-Sequence Impedance, Magnitude
n:R1:bus1OhmPositive-Sequence Impedance, Real Part
n:X1:bus1OhmPositive-Sequence Impedance, Imaginary Part
n:Z1:bus1OhmPositive-Sequence Impedance, Magnitude
n:phiz1:bus1degPositive-Sequence Impedance, Angle
n:r1Sbase:bus1p.u.Positive-Sequence Impedance, Real Part
n:x1Sbase:bus1p.u.Positive-Sequence Impedance, Imaginary Part
n:z1Sbase:bus1p.u.Positive-Sequence Impedance, Magnitude
n:R2:bus1OhmNegative-Sequence Impedance, Real Part
n:X2:bus1OhmNegative-Sequence Impedance, Imaginary Part
n:Z2:bus1OhmNegative-Sequence Impedance, Magnitude
n:phiz2:bus1degNegative-Sequence Impedance, Angle
n:r2Sbase:bus1p.u.Negative-Sequence Impedance, Real Part
n:x2Sbase:bus1p.u.Negative-Sequence Impedance, Imaginary Part
n:z2Sbase:bus1p.u.Negative-Sequence Impedance, Magnitude
n:R0toX0:bus1·R0/X0 ratio (Zk")
n:X0toR0:bus1·X0/R0 ratio (Zk")
n:R2toX2:bus1·R2/X2 ratio (Zk")
n:X2toR2:bus1·X2/R2 ratio (Zk")
n:R:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Ground
n:X:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Ground
n:Z:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Ground
n:phiz:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Ground
n:Rl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Line
n:Xl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Line
n:Zl:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Line
n:phizl:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Line
n:Rln:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Resistance, Line-Neutral
n:Xln:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Reactance, Line-Neutral
n:Zln:bus1:Aper phase :A, :B, :C, unbalanced onlyOhmNetwork Impedance, Line-Neutral
n:phizln:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle of Network Impedance, Line-Neutral
n:Rn:bus1OhmNetwork Resistance, Neutral
n:Xn:bus1OhmNetwork Reactance, Neutral
n:Zn:bus1OhmNetwork Impedance, Neutral
n:phizn:bus1degAngle of Network Impedance, Neutral
n:eff:bus1:Aper phase :A, :B, :C, unbalanced only·Earth Fault Factor
n:X0toX1:bus1·X0/X1
n:In:bus1kANeutral Current, Magnitude
n:phiin:bus1degNeutral Current, Angle
n:I0:bus1kAZero-Sequence Current, Magnitude
n:I0x3:bus1kA3*I0
n:phii0:bus1degZero-Sequence Current, Angle
n:I1:bus1kAPositive-Sequence Current, Magnitude
n:phii1:bus1degPositive-Sequence Current, Angle
n:I2:bus1kANegative-Sequence Current, Magnitude
n:phii2:bus1degNegative-Sequence Current, Angle
n:urpref:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Real Part
n:uipref:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Imaginary Part
n:upref:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Pre-fault Voltage, Magnitude
n:uprefpc:bus1:Aper phase :A, :B, :C, unbalanced only%Pre-fault Voltage, Magnitude
n:Upref:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Pre-fault Voltage, Magnitude
n:Ulpref:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Pre-fault Voltage, Magnitude
n:phiupref:bus1:Aper phase :A, :B, :C, unbalanced onlydegPre-fault Voltage, Angle
n:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
n:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
n:phiu2i2:bus1degAngle between Voltage and Current in negative sequence system
n:phiu0i0:bus1degAngle between Voltage and Current in zero-sequence system
n:Ik:bus1:Aper phase :A, :B, :C, unbalanced onlykASteady-State Short-Circuit Current
n:in:bus1p.u.Neutral Current, Magnitude
n:i0r:bus1p.u.Zero-Sequence Current, Real Part
n:i0i:bus1p.u.Zero-Sequence Current, Imaginary Part
n:i0:bus1p.u.Zero-Sequence Current, Magnitude
n:i1r:bus1p.u.Positive-Sequence Current, Real Part
n:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
n:i1:bus1p.u.Positive-Sequence Current, Magnitude
n:i2r:bus1p.u.Negative-Sequence Current, Real Part
n:i2i:bus1p.u.Negative-Sequence Current, Imaginary Part
n:i2:bus1p.u.Negative-Sequence Current, Magnitude

ElmVac rms simulation results

Read after ComInc (RMS) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:urnet:bus1p.u.Voltage, Real Part, referred to network
m:uinet:bus1p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1degPositive-Sequence-Voltage, Angle
m:irnet:bus1p.u.Current, Real Part, referred to network
m:iinet:bus1p.u.Current, Imaginary Part, referred to network
m:inet:bus1p.u.Current, Magnitude, referred to network
m:I:bus1kACurrent, Magnitude
m:phii:bus1degCurrent, Angle
m:i1r:bus1p.u.Positive-Sequence Current, Real Part
m:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:S:bus1MVAApparent Power
m:cosphi:bus1·Power Factor
m:tanphi:bus1·tan(phi)
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:Ssum:bus1MVATotal Apparent Power
m:cosphisum:bus1·Total Power Factor
m:tanphisum:bus1·Total tan(phi)
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:ur:bus1p.u.Voltage, Real Part
m:ui:bus1p.u.Voltage, Imaginary Part
m:u:bus1p.u.Voltage, Magnitude
m:ir:bus1p.u.Current, Real Part
m:ii:bus1p.u.Current, Imaginary Part
m:i:bus1p.u.Current, Magnitude
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1sFault Clearing Time
m:Brkload:bus1%Breaker Loading
m:Spu:bus1MVA/p.u.Apparent Power per p.u. Voltage
m:urnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part, referred to network
m:uinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part, referred to network
m:u0:bus1p.u.Zero-Sequence-Voltage, Magnitude
m:phiu0:bus1degZero-Sequence-Voltage, Angle
m:u2:bus1p.u.Negative-Sequence-Voltage, Magnitude
m:phiu2:bus1degNegative-Sequence-Voltage, Angle
m:irnet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:iinet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:inet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAPhase Current, Magnitude
m:phii:bus1:Aper phase :A, :B, :C, unbalanced onlydegPhase Current, Angle
m:i0r:bus1p.u.Zero-Sequence Current, Real Part
m:i0i:bus1p.u.Zero-Sequence Current, Imaginary Part
m:i0:bus1p.u.Zero-Sequence Current, Magnitude
m:I0:bus1kAZero-Sequence Current, Magnitude
m:I0x3:bus1kA3*I0
m:phii0:bus1degZero-Sequence Current, Angle
m:i2r:bus1p.u.Negative-Sequence Current, Real Part
m:i2i:bus1p.u.Negative-Sequence Current, Imaginary Part
m:i2:bus1p.u.Negative-Sequence Current, Magnitude
m:I2:bus1kANegative-Sequence Current, Magnitude
m:phii2:bus1degNegative-Sequence Current, Angle
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Q:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power
m:S:bus1:Aper phase :A, :B, :C, unbalanced onlyMVAApparent Power
m:cosphi:bus1:Aper phase :A, :B, :C, unbalanced only·Power Factor
m:tanphi:bus1:Aper phase :A, :B, :C, unbalanced only·tan(phi)
m:Pln:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power (Line-Neutral)
m:Qln:bus1:Aper phase :A, :B, :C, unbalanced onlyMvarReactive Power (Line-Neutral)
m:P1:bus1MWPositive Sequence Active Power
m:Q1:bus1MvarPositive Sequence Reactive Power
m:P2:bus1MWNegative Sequence Active Power
m:Q2:bus1MvarNegative Sequence Reactive Power
m:P0:bus1MWZero Sequence Active Power
m:Q0:bus1MvarZero Sequence Reactive Power
m:i2P:bus1p.u.Negative-Sequence Active Current
m:i2Q:bus1p.u.Negative-Sequence Reactive Current
m:I2P:bus1kANegative-Sequence Active Current
m:I2Q:bus1kANegative-Sequence Reactive Current
m:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Real Part
m:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Imaginary Part
m:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, Magnitude
m:ir:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Real Part
m:ii:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Imaginary Part
m:i:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, Magnitude
m:phiui:bus1:Aper phase :A, :B, :C, unbalanced onlydegAngle between Voltage and Current
m:phiu0i0:bus1degAngle between Voltage and Current in zero-sequence system
m:phiu2i2:bus1degAngle between Voltage and Current in negative sequence system
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:BrkloadPh:bus1:Aper phase :A, :B, :C, unbalanced only%Breaker Loading
c:hpirad/sNominal-Angular-Frequency
c:uini0·0-Sequ. Voltage
c:uini2·2-Sequ. Voltage
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:ishc:bus1p.u.Short-Circuit Current, magnitude
n:Ishc:bus1kAShort-Circuit Current, magnitude
n:fe:bus1p.u.Electrical Frequency
n:dfehz:bus1HzDeviation of the El. Frequency
n:fehz:bus1HzElectrical Frequency
n:frnom:bus1HzNominal Frequency
n:ishcr:bus1p.u.Short-Circuit Current, real
n:ishci:bus1p.u.Short-Circuit Current, imag
n:dfedt:bus1p.u./sDerivative of El. Frequency
n:ur:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Real Part
n:ui:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Imaginary Part
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Ground Voltage, Magnitude
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Ground Voltage, Magnitude
n:du:bus1:Aper phase :A, :B, :C, unbalanced only%Voltage Deviation
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Ground Voltage, Magnitude
n:phiu:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Ground Voltage, Angle
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage, Magnitude
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage, Magnitude
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage, Magnitude
n:phiul:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Line Voltage, Angle
n:u0:bus1p.u.Zero-Sequence Voltage, Magnitude
n:U0:bus1kVZero-Sequence Voltage, Magnitude
n:U0x3:bus1kV3*U0
n:phiu0:bus1degZero-Sequence Voltage, Angle
n:U1:bus1kVLine-Ground Positive-Sequence Voltage, Magnitude
n:phiu1:bus1degPositive-Sequence Voltage, Angle
n:u2:bus1p.u.Negative-Sequence Voltage, Magnitude
n:U2:bus1kVLine-Ground Negative-Sequence Voltage, Magnitude
n:phiu2:bus1degNegative-Sequence Voltage, Angle
n:U1l:bus1kVLine-Line Positive-Sequence Voltage, Magnitude
n:U2l:bus1kVLine-Line Negative-Sequence Voltage, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage, Magnitude
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage, Magnitude
n:phiuln:bus1:Aper phase :A, :B, :C, unbalanced onlydegLine-Neutral Voltage, Angle
n:un:bus1p.u.Neutral-Ground Voltage, Magnitude
n:Un:bus1kVNeutral-Ground Voltage, Magnitude
n:phiun:bus1degNeutral-Ground Voltage, Angle
n:upht:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Technology dependent Voltage, Magnitude
n:Upht:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Technology dependent Voltage, Magnitude
n:um:bus1p.u.Average-Voltage, Magnitude
n:Um:bus1kVAverage-Voltage, Magnitude
n:ishc:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, magnitude
n:Ishc:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current, magnitude
n:inshc:bus1p.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bus1kANeutral Short-Circuit Current, magnitude
n:ishcr:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, real
n:ishci:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current, imag
s:U_AkVVoltage, Magnitude, Phase a
s:U_BkVVoltage, Magnitude, Phase b
s:U_CkVVoltage, Magnitude, Phase c
s:phiu_BdegVoltage, Angle, Phase b
s:phiu_CdegVoltage, Angle, Phase c
s:xspeedp.u.Frequency
s:frefp.u.Reference Frequency
s:U1kVVoltage-Input
s:phiu1degVoltage-Angle
s:u0p.u.Voltage-Input
s:Ul0kVVoltage-Input (Line-Line)
s:dphiuradAdditional Angle
s:f0p.u.Frequency-Input
s:F0HzHzFrequency-Input
s:phiuradVoltage-Angle
s:phiu_AdegVoltage, Angle, Phase a
s:UikVVoltage (Line-Earth), Magnitude

ElmVac emt simulation results

Read after ComInc (EMT) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:u0:bus1p.u.Zero-Sequence-Voltage
m:u1r:bus1p.u.Voltage Phasor, Real Part
m:u1i:bus1p.u.Voltage Phasor, Imaginary Part
m:u1:bus1p.u.Voltage Phasor, Magnitude
m:U1:bus1kVLine-Ground Voltage Phasor, Magnitude
m:U1l:bus1kVLine-Line Voltage Phasor, Magnitude
m:phiu1:bus1degVoltage Phasor, Angle
m:inet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current, referred to network
m:I:bus1:Aper phase :A, :B, :C, unbalanced onlykAPhase Current
m:i0:bus1p.u.Zero-Sequence Current
m:I0:bus1kAZero-Sequence Current
m:I0x3:bus1kA3*I0
m:i1r:bus1p.u.Current Phasor, Real Part
m:i1i:bus1p.u.Current Phasor, Imaginary Part
m:i1:bus1p.u.Current Phasor, Magnitude
m:I1:bus1kACurrent Phasor, Magnitude
m:phii1:bus1degCurrent Phasor, Angle
m:P:bus1:Aper phase :A, :B, :C, unbalanced onlyMWActive Power
m:Psum:bus1MWPower-Phasor, Active Power
m:Qsum:bus1MvarPower Phasor, Reactive Part
m:Ssum:bus1MVAPower Phasor, Apparent Power
m:i1P:bus1p.u.Current Phasor, Active Current
m:i1Q:bus1p.u.Current Phasor, Reactive Current
m:I1P:bus1kACurrent Phasor, Active Current
m:I1Q:bus1kACurrent Phasor, Reactive Current
m:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
m:i:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Current
m:phiu1i1:bus1degAngle between Voltage and Current Phasor
m:Tfct:bus1sFault Clearing Time
m:TfctPh:bus1:Aper phase :A, :B, :C, unbalanced onlysFault Clearing Time
m:unet:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage, referred to network
m:cosphi1:bus1·Power-Phasor, Power-Factor
c:hpirad/sNominal-Angular-Frequency
c:uini0·0-Sequ. Voltage
c:uini2·2-Sequ. Voltage
c:phiini0rad0-Sequ. Voltage, Angle
c:phiini2rad2-Sequ. Voltage, Angle
n:u:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Phase Voltage
n:upc:bus1:Aper phase :A, :B, :C, unbalanced only%Phase Voltage
n:U:bus1:Aper phase :A, :B, :C, unbalanced onlykVPhase Voltage
n:ul:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Line Voltage
n:ulpc:bus1:Aper phase :A, :B, :C, unbalanced only%Line-Line Voltage
n:Ul:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Line Voltage
n:u0:bus1p.u.Zero-Sequence-Voltage
n:U0:bus1kVZero-Sequence-Voltage
n:U0x3:bus1kV3*U0
n:u1:bus1p.u.Voltage Phasor, Magnitude
n:u1pc:bus1%Voltage Phasor, Magnitude
n:u1r:bus1p.u.Voltage Phasor, Real Part
n:u1i:bus1p.u.Voltage Phasor, Imaginary Part
n:U1:bus1kVVoltage Phasor, Magnitude
n:phiu1:bus1degVoltage Phasor, Angle
n:U1l:bus1kVLine-Line Voltage Phasor, Magnitude
n:uln:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Line-Neutral Voltage
n:Uln:bus1:Aper phase :A, :B, :C, unbalanced onlykVLine-Neutral Voltage
n:un:bus1p.u.Neutral-Ground Voltage
n:Un:bus1kVNeutral-Ground Voltage
n:ishc:bus1:Aper phase :A, :B, :C, unbalanced onlyp.u.Short-Circuit Current
n:Ishc:bus1:Aper phase :A, :B, :C, unbalanced onlykAShort-Circuit Current
n:inshc:bus1p.u.Neutral Short-Circuit Current, magnitude
n:Inshc:bus1kANeutral Short-Circuit Current, magnitude
n:fe:bus1p.u.Electrical Frequency
n:dfehz:bus1HzDeviation of the El. Frequency
n:fehz:bus1HzElectrical Frequency
n:frnom:bus1HzNominal Frequency
s:U_AkVVoltage, Magnitude, Phase a
s:U_BkVVoltage, Magnitude, Phase b
s:U_CkVVoltage, Magnitude, Phase c
s:xspeedp.u.Speed
s:phiuRefradVoltage - Angle Reference
s:u0p.u.Voltage-Input
s:Ul0kVVoltage-Input (Line-Line)
s:dphiuradAdditional Angle
s:f0p.u.Frequency-Input
s:F0HzHzFrequency-Input
s:phiuradVoltage-Angle
s:UikVVoltage-Input (Line-Earth)

ElmVac dc load flow results

Read after ComLdf (DC) with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal, s: signal (state or model variable).

AttributeUnitDescription
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
c:phiuradVoltage Angle
c:KpfMW/HzPrimary Frequency Bias
c:KsfMW/HzSecondary Frequency Bias
c:iRefElement·Reference Element
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:Pgen:bus1MWGeneration, Active Power
n:Pmot:bus1MWMotor Load, Active Power
n:Pload:bus1MWGeneral Load, Active Power
n:Pcomp:bus1MWCompensation (Losses)
n:Pnet:bus1MWExternal Networks, Active Power
n:Pflow:bus1MWPower Flow, Active Power
s:dFinHzFrequency Deviation
s:dFHzFrequency Deviation Output

Read after ComMod with GetAttribute. c: calculation parameter, s: signal (state or model variable).

AttributeUnitDescription
c:hpirad/sNominal-Angular-Frequency
s:U_AkVVoltage, Magnitude, Phase a
s:U_BkVVoltage, Magnitude, Phase b
s:U_CkVVoltage, Magnitude, Phase c
s:phiu_BdegVoltage, Angle, Phase b
s:phiu_CdegVoltage, Angle, Phase c
s:xspeedp.u.Frequency
s:frefp.u.Reference Frequency
s:U1kVVoltage-Input
s:phiu1degVoltage-Angle
s:u0p.u.Voltage-Input
s:Ul0kVVoltage-Input (Line-Line)
s:dphiuradAdditional Angle
s:f0p.u.Frequency-Input
s:F0HzHzFrequency-Input
s:phiuradVoltage-Angle

ElmVac optimal power flow results

Read after ComOpf with GetAttribute. m: currents, voltages and powers, c: calculation parameter, n: bus result at a terminal.

AttributeUnitDescription
m:urnet:bus1p.u.Voltage, Real Part, referred to network
m:uinet:bus1p.u.Voltage, Imaginary Part, referred to network
m:u1r:bus1p.u.Positive-Sequence-Voltage, Real Part
m:u1i:bus1p.u.Positive-Sequence-Voltage, Imaginary Part
m:u1:bus1p.u.Positive-Sequence-Voltage, Magnitude
m:U1:bus1kVLine-Ground Positive-Sequence-Voltage, Magnitude
m:U1l:bus1kVLine-Line Positive-Sequence-Voltage, Magnitude
m:phiu1:bus1degPositive-Sequence-Voltage, Angle
m:irnet:bus1p.u.Current, Real Part, referred to network
m:iinet:bus1p.u.Current, Imaginary Part, referred to network
m:inet:bus1p.u.Current, Magnitude, referred to network
m:I:bus1kACurrent, Magnitude
m:phii:bus1degCurrent, Angle
m:i1r:bus1p.u.Positive-Sequence Current, Real Part
m:i1i:bus1p.u.Positive-Sequence Current, Imaginary Part
m:i1:bus1p.u.Positive-Sequence Current, Magnitude
m:I1:bus1kAPositive-Sequence Current, Magnitude
m:phii1:bus1degPositive-Sequence Current, Angle
m:P:bus1MWActive Power
m:Q:bus1MvarReactive Power
m:S:bus1MVAApparent Power
m:cosphi:bus1·Power Factor
m:tanphi:bus1·tan(phi)
m:Psum:bus1MWTotal Active Power
m:Qsum:bus1MvarTotal Reactive Power
m:Ssum:bus1MVATotal Apparent Power
m:cosphisum:bus1·Total Power Factor
m:tanphisum:bus1·Total tan(phi)
m:i1P:bus1p.u.Positive-Sequence Active Current
m:i1Q:bus1p.u.Positive-Sequence Reactive Current
m:I1P:bus1kAPositive-Sequence Active Current
m:I1Q:bus1kAPositive-Sequence Reactive Current
m:ur:bus1p.u.Voltage, Real Part
m:ui:bus1p.u.Voltage, Imaginary Part
m:u:bus1p.u.Voltage, Magnitude
m:ir:bus1p.u.Current, Real Part
m:ii:bus1p.u.Current, Imaginary Part
m:i:bus1p.u.Current, Magnitude
m:phiui:bus1degAngle between Voltage and Current
m:phiu1i1:bus1degAngle between Voltage and Current in positive sequence system
m:Tfct:bus1sFault Clearing Time
m:Brkload:bus1%Breaker Loading
m:Spu:bus1MVA/p.u.Apparent Power per p.u. Voltage
c:uinip.u.Voltage
c:phiuradVoltage Angle
c:KpfMW/HzPrimary Frequency Bias
c:KsfMW/HzSecondary Frequency Bias
c:Kp·Secondary Factor
c:iRefElement·Reference Element
c:PlossMWLosses (total)
c:QlossMvarReactive-Losses (total)
c:PlossldMWLosses (load)
c:QlossldMvarReactive-Losses (load)
c:PlossnldMWLosses (no load)
c:QlossnldMvarReactive-Losses (no load)
n:ur:bus1p.u.Voltage, Real Part
n:ui:bus1p.u.Voltage, Imaginary Part
n:u:bus1p.u.Voltage, Magnitude
n:upc:bus1%Voltage, Magnitude
n:du:bus1%Voltage Deviation
n:U:bus1kVLine-Ground Voltage, Magnitude
n:phiu:bus1degVoltage, Angle
n:phiurel:bus1degVoltage, Relative Angle
n:Ul:bus1kVLine-Line Voltage, Magnitude
n:u1:bus1p.u.Voltage, Magnitude
n:u1pc:bus1%Voltage, Magnitude
n:u1r:bus1p.u.Positive-Sequence Voltage, Real Part
n:u1i:bus1p.u.Positive-Sequence Voltage, Imaginary Part
n:Pgen:bus1MWGeneration, Active Power
n:Qgen:bus1MvarGeneration, Reactive Power
n:Pmot:bus1MWMotor Load, Active Power
n:Qmot:bus1MvarMotor Load, Reactive Power
n:Pload:bus1MWGeneral Load, Active Power
n:Qload:bus1MvarGeneral Load, Reactive Power
n:Pcomp:bus1MWCompensation (Losses)
n:Qcomp:bus1MvarCompensation
n:Pnet:bus1MWExternal Networks, Active Power
n:Qnet:bus1MvarExternal Networks, Reactive Power
n:Pflow:bus1MWPower Flow, Active Power
n:Qflow:bus1MvarPower Flow, Reactive Power
n:Pout:bus1MWOutgoing Flow, Active Power
n:Qout:bus1MvarOutgoing Power, Reactive Power
n:Sout:bus1MVAOutgoing Power, Apparent Power
n:cosphiout:bus1·Outgoing Power, Power Factor
n:Pbalance:bus1MWActive Power Balance (=0)
n:Qbalance:bus1MvarReactive Power Balance (=0)
n:LossPdown:bus1MWLosses, downstream
n:LossQdown:bus1MvarLosses, downstream (Reactive Power)
n:LossPdownload:bus1MWLoad losses, downstream
n:LossQdownload:bus1MvarLoad losses, downstream
n:LossPdownnoload:bus1MWNo load losses, downstream
n:LossQdownnoload:bus1MvarNo load losses, downstream
n:du_feed:bus1%Difference from voltage at start of feeder

ElmVac basic data

b: values are worked out from the input data. Read them; they are not set.

AttributeUnitDescription
b:loc_name·Name

Related

← ElmSym Synchronous Machine · ElmXnet External Grid →