TypSym attributesPowerFactory Synchronous Machine Type

Every attribute of the PowerFactory Synchronous Machine Type (TypSym): 148 input parameters, with units and meaning. Copy a name into GetAttribute or SetAttribute.

What TypSym is

A synchronous machine type: rated power and voltage, power factor, the synchronous, transient and subtransient reactances and time constants, and the inertia H.

Class
TypSym, type class
PowerFactory name
Synchronous Machine Type
Used by
ElmSym
Attributes
148 input parameters

Most used TypSym attributes

AttributeUnitDescriptionWhere
sgnMVARated apparent powerinput data
ugnkVRated voltageinput data
cosn·Rated power factorinput data
xdp.u.xdinput data
xqp.u.xqinput data
xdsp.u.xd'input data
xdssp.u.xd''input data
tdssTd'input data
tdsssTd''input data
hsInertia constant H (rated to Sgn)inertia constantinput data
xlp.u.xlinput data
rstrp.u.rstrinput data

Read and write TypSym in Python

import powerfactory

app = powerfactory.GetApplication()          # GetApplicationExt() from outside PowerFactory

# Types live in the equipment library of the project.
types = app.GetProjectFolder("equip").GetContents("*.TypSym", 1)
for typ in types:
    print(typ.loc_name, typ.GetAttribute("sgn"))  # Rated apparent power, MVA

# An element points to its type with typ_id; t: reads a type value through the element.
for gen in app.GetCalcRelevantObjects("*.ElmSym"):
    print(gen.loc_name, gen.typ_id.loc_name, gen.GetAttribute("t:sgn"))

types[0].SetAttribute("h", 4.5)               # inertia constant 4.5 s: every element of this type changes
  • An input parameter is read and written with or without its e: prefix: GetAttribute("outserv") and GetAttribute("e:outserv") give the same value.
  • A type is shared: a change to it changes every element that uses it. Read a type value through an element with the t: prefix.

TypSym input parameters

The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.

AttributeUnitDescription
loc_name·Name
chr_name·Characteristic Name
for_name·Foreign Key
dat_src·Data source
model_inp·Model
manuf·Manufacturer
appr_modby·Modified by
iner_inp·Input mode
i_condenser·Used as condenser
iTdcManual·Enter Tdc manually
iamort·with amortisseur windings
iusesat·Use saturated value
satur·Machine type IEC909/IEC60909
iturbo·Rotor type
iuseXdk·Ik" instead of reactances
nphase·No. of phases
nslty·Connection
i_trans·Use frequency transfer functions
i_xl·xl is current dependent
iopt_data·Input parameters
appr_status·Status
i_speedD·Speed deviation based on
polepairs·No. of pole pairs
isat·Main flux saturation
isatSalient·Saturation
i_extModel·Model
i_exactConv·Exact conversion of time constants
i_xme2·Consider negative sequence torque
i_speedVar·Effect of speed variation
sgnMVARated apparent power
ugnkVRated voltage
cosn·Rated power factor
tagsAcceleration time const. Tag (rated to Pgn)
tdssTd'
tqssTq'
tdsssTd''
TdcsTdc
tqsssTq''
Ikdp.u.Ikd
xdp.u.xd
xdsp.u.xd'
xdssp.u.xd''
xqp.u.xq
xqsp.u.xq'
xqssp.u.xq''
xdsatp.u.Reciprocal of short-circuit ratio (xdsat)
xdsssp.u.saturated value xd''sat
xtor·Ratio X/R
rstrp.u.rstr
x2syp.u.Reactance x2
r2syp.u.Resistance r2
x0syp.u.Reactance x0
r0syp.u.Resistance r0
q_minp.u.Minimum value
q_maxp.u.Maximum value
Q_minMvarMinimum value
Q_maxMvarMaximum value
curkkA3-phase Ik"
curk1pkA1-phase Ik"
curk2pkA2-phase Ik"
tds0sTd0'
tqs0sTq0'
tdss0sTd0''
tqss0sTq0''
depSmoothFac%Dependency curve smoothing factor
slipmin%Minimum slip
frequHzNominal frequency
sg10p.u.SG10
sg12p.u.SG12
smoothFac%Smoothing factor
sg10qp.u.SG10 q-axis
sg12qp.u.SG12 q-axis
iinrushp.u.Ratio Ip/In
TinrushsMax. time
TcoldsCold
ThotsHot
xstrp.u.xstr
xlp.u.xl
xrlp.u.xrld
xrlqp.u.xrlq
kwp.u.kw
xadp.u.xad
xaqp.u.xaq
xrl2dp.u.xrl2d
x1dp.u.x1d
r1dp.u.r1d
x2dp.u.x2d
r2dp.u.r2d
xfdp.u.xfd
rfdp.u.rfd
x1qp.u.x1q
r1qp.u.r1q
x2qp.u.x2q
r2qp.u.r2q
x3qp.u.x3q
r3qp.u.r3q
t1dst1d
t2dst2d
t3dst3d
t4dst4d
t5dst5d
t6dst6d
t7dst7d
t8dst8d
t1qst1q
t2qst2q
t3qst3q
t4qst4q
t5qst5q
t6qst6q
x1dcp.u.x1dc
x1dep.u.x1de
r1dep.u.r1de
xfdep.u.xfde
rfdep.u.rfde
x1qcp.u.x1qc
x1qep.u.x1qe
r1qep.u.r1qe
psimp.u.Rotor flux
dpu·Turbine shaft friction torque coefficient
dpe·Damping torque coefficient based on power
dkd·Damping torque coefficient
appr_modif·Modified
curTabp.u.Current
xlTabp.u.xl
satvp.u.Term. voltage
satsep.u.SG(u)
satvqp.u.Term. voltage
satseqp.u.SG(u)
typemetadata_version·Version
typemetadata_key·Type Key
typemetadata_changeLog·Change Log
desc·Description
fcharrstrChaPol,ChaVec,ChaMatrs(f)
fcharlssChaPol,ChaVec,ChaMatl''(f)
fcharr2ChaPol,ChaVec,ChaMatr2(f)
fcharl2ChaPol,ChaVec,ChaMatl2(f)
fcharr0ChaPol,ChaVec,ChaMatr0(f)
fcharl0ChaPol,ChaVec,ChaMatl0(f)
doc_id·Additional Data
cTdcsTdc
tagssAcceleration time const. Tag (rated to Sgn)
hsInertia constant H (rated to Sgn)
lssp.u.l''
hpnsInertia constant H (rated to Pgn)
Jkgm^2Moment of inertia J
ifd%ie
ifdq%ie

Related

← TypSwitch Switch Type · TypTow Tower Type →