TypTr2 attributesPowerFactory 2-Winding Transformer Type

Every attribute of the PowerFactory 2-Winding Transformer Type (TypTr2): 155 input parameters, with units and meaning. Copy a name into GetAttribute or SetAttribute.

What TypTr2 is

A 2-winding transformer type: rated power and voltages, short-circuit voltage, losses, vector group and tap changer.

Class
TypTr2, type class
PowerFactory name
2-Winding Transformer Type
Used by
ElmTr2
Attributes
155 input parameters

Most used TypTr2 attributes

AttributeUnitDescriptionWhere
strnMVARated Powerrated powerinput data
utrn_hkVHV-Sideinput data
utrn_lkVLV-Sideinput data
uktr%Short-Circuit Voltage ukshort-circuit voltageinput data
pcutrkWCopper Lossescopper lossesinput data
pfekWNo Load Lossesinput data
curmg%No Load Currentinput data
tr2cn_h·HV-Sideinput data
tr2cn_l·LV-Sideinput data
nt2ag·Phase Shiftphase shiftinput data
dutap%Additional voltage per tapvoltage per tapinput data
nntap0·Neutral Positioninput data
ntpmn·Minimum Positioninput data
ntpmx·Maximum Positioninput data

Read and write TypTr2 in Python

import powerfactory

app = powerfactory.GetApplication()          # GetApplicationExt() from outside PowerFactory

# Types live in the equipment library of the project.
types = app.GetProjectFolder("equip").GetContents("*.TypTr2", 1)
for typ in types:
    print(typ.loc_name, typ.GetAttribute("strn")) # Rated Power, MVA

# An element points to its type with typ_id; t: reads a type value through the element.
for trafo in app.GetCalcRelevantObjects("*.ElmTr2"):
    print(trafo.loc_name, trafo.typ_id.loc_name, trafo.GetAttribute("t:strn"))

types[0].SetAttribute("strn", 200)            # rated power 200 MVA: every element of this type changes
  • An input parameter is read and written with or without its e: prefix: GetAttribute("outserv") and GetAttribute("e:outserv") give the same value.
  • A type is shared: a change to it changes every element that uses it. Read a type value through an element with the t: prefix.

TypTr2 input parameters

The element data, as typed in GetAttribute and SetAttribute (the e: prefix is optional). Setting one changes the model.

AttributeUnitDescription
loc_name·Name
chr_name·Characteristic Name
for_name·Foreign Key
dat_src·Data source
tr2cn_h·HV-Side
tr2cn_l·LV-Side
ansiclass·Class
manuf·Manufacturer
appr_modby·Modified by
ntpmx·Maximum Position
ntpmn·Minimum Position
nntap0·Neutral Position
itapch·Tap Changer 1
itapch2·Tap Changer 2
ntpmx2·Maximum Position
ntpmn2·Minimum Position
nntap02·Neutral Position
tap_side2·at Side
tapchtype2·Type
iTapLoading·Configuration
nt2ph·Technology
iIntDelta·Internal Delta Winding
itrmt·Type
iFinalSlope·Set final slope (peak values)
ksat·Saturation Exponent
iLimb·Core
iInterPol·Interpolation
iFit·Data fitting
iHyster·Model
itrtype·Transformer Type
tap_side·at Side
tapchtype·Type
oltc·On-load Tap Changer
oltc2·On-load Tap Changer 2
itapzdep·Tap dependent impedance for tap changer 1
appr_status·Status
itrldf·Type
iIntPola·Interpolation
itratioadpt·Transformer Ratio Adaptation
strnMVARated Power
utrn_hkVHV-Side
utrn_lkVLV-Side
uktr%Short-Circuit Voltage uk
pcutrkWCopper Losses
curmg%No Load Current
dutap%Additional voltage per tap
phitrdegPhase of du
dphitapdegAdditional angle per tap
dutap2%Additional voltage per tap
phitr2degPhase of du
dphitap2degAdditional angle per Tap
uk0_hlo%HV-SHC-Voltage uk0 (LV open)
ur0_hlo%HV-SHC-Voltage Re(uk0) (LV open)
uk0_lho%LV-SHC-Voltage uk0 (HV open)
ur0_lho%LV-SHC-Voltage Re(uk0) (HV open)
uk0_hls%HV-SHC-Voltage uk0 (LV short-circuit)
ur0_hls%HV-SHC-Voltage Re(uk0) (LV short-circuit)
uk0tr%Short-Circuit Voltage uk0
ur0tr%SHC-Voltage (Re(uk0)) uk0r
nt2ag·Phase Shift
itrdl·x,Pos.Seq. HV-Side
itrdr·r,Pos.Seq. HV-Side
psi0p.u.Knee Flux
xmlinp.u.Linear Reactance
xmairp.u.Saturated Reactance
smoothfac%Smoothing Factor
Lwidth%Loop width
itrdl0·x0, Zero.Seq. HV-Side
itrdr0·r0, Zero.Seq. HV-Side
zx0hl_n·Mag. Impedance/uk0
rtox0_n·Mag. R/X
pict1p.u.Ratio Ip/In (1)
pitt1sMax. Time (1)
pict2p.u.Ratio Ip/In (2)
pitt2sMax. Time (2)
frnomHzNominal Frequency
pfekWNo Load Losses
strnfcMVARated Power (forced cooling)
uktmn%uk (min. tap)
pcutmnkWPcu (min. tap)
uktmx%uk (max. tap)
pcutmxkWPcu (max. tap)
uk0tmn%uk0 (min. tap)
uk0rtmn%Re(uk0) (min. tap)
uk0tmx%uk0 (max. tap)
uk0rtmx%Re(uk0) (max. tap)
smoothf%Smoothing Factor
eddypc·Ratio
appr_modif·Modified
satcurp.u.Current (peak)
satfluxp.u.Flux (peak)
satcue%Current (RMS)
satvolp.u.Voltage (RMS)
typemetadata_version·Version
typemetadata_key·Type Key
typemetadata_changeLog·Change Log
desc·Description
doc_id·Additional Data
pStochStoTyptrfStochastic model
fcharl1ChaPol,ChaVec,ChaMatl1(f)
fcharr1ChaPol,ChaVec,ChaMatr1(f)
fcharl0ChaPol,ChaVec,ChaMatl0(f)
fcharr0ChaPol,ChaVec,ChaMatr0(f)
fcharbmChaPol,ChaVec,ChaMat1/lm(f)
fchargmChaPol,ChaVec,ChaMatgm(f)
uktrr%SHC-Voltage (Re(uk)) ukr
xtor·Ratio X/R
r1pup.u.Resistance r1
x1pup.u.Reactance x1
l1pup.u.Inductance l1
xtr0_hlo·HV-Ratio X0/R0 (LV open)
xtr0_lho·LV-Ratio X0/R0 (HV open)
xtr0_hls·HV-Ratio X0/R0 (LV short-circuit)
r0pu_hlop.u.HV-Resistance r0 (LV open)
r0pu_lhop.u.LV-Resistance r0 (HV open)
r0pu_hlsp.u.HV-Resistance r0 (LV short-circuit)
x0pu_hlop.u.HV-Reactance x0 (LV open)
x0pu_lhop.u.LV-Reactance x0 (HV open)
x0pu_hlsp.u.HV-Reactance x0 (LV short-circuit)
x0tor0·Ratio X0/R0
r0pup.u.Resistance r0
x0pup.u.Reactance x0
l0pup.u.Inductance l0
uk0delta%Delta Winding, uk0
ur0delta%Delta Winding, Re(uk0)
x0deltap.u.Delta Winding, x0
r0deltap.u.Delta Winding, r0
x0tor0delta·Delta Winding, X0/R0
itrdl0_lv·x0, Zero.Seq. LV-Side
itrdr0_lv·r0, Zero.Seq. LV-Side
aFrolich·Frolich equation coefficient a
bFrolich·Frolich equation coefficient b
cFrolich·Frolich equation coefficient c
xsatFrolich·Frolich equation saturated reactance (p.u.)
mseFrolich·Frolich equation, mean squared error
itrdl_lv·x,Pos.Seq. LV-Side
itrdr_lv·r,Pos.Seq. LV-Side
bm1p.u.1/lm
gm1p.u.gm
ukrtmn%Re(uk) (min. tap)
ukrtmx%Re(uk) (max. tap)
xtortmx·X/R (max. tap)
xtortmn·X/R (min. tap)
r1putmxp.u.r1 (max. tap)
r1putmnp.u.r1 (min. tap)
x1putmxp.u.x1 (max. tap)
x1putmnp.u.x1 (min. tap)
x0tor0tmx·X0/R0 (max. tap)
x0tor0tmn·X0/R0 (min. tap)
r0putmxp.u.r0 (max. tap)
r0putmnp.u.r0 (min. tap)
x0putmxp.u.x0 (max. tap)
x0putmnp.u.x0 (min. tap)
vecgrp·Name
pT·Voltage Range

Related