master:Cable_PipeType parametersPSCAD Pipe-Type Cable
Every parameter of the PSCAD Pipe-Type Cable (master:Cable_PipeType): 454 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().
What master:Cable_PipeType is
Pipe-Type Cable (Cable Constants Pipe-Type Cable Data), a component of PSCAD's Master Library, filed under lines, cables and towers.
- Definition
master:Cable_PipeType- PSCAD name
- Pipe-Type Cable
- Category
- Lines, cables and towers
- Parameters
- 454, in 18 groups; 200 carry a unit
- Read from
- PSCAD 5.0.0, 2026-11-07
Read and write master:Cable_PipeType in Python
import mhi.pscad
pscad = mhi.pscad.connect() # the PSCAD that is open; launch() starts one
project = pscad.project("my_case") # a case loaded in the workspace
for comp in project.find_all("master:Cable_PipeType"): # the exact definition, namespace first
params = comp.parameters() # every parameter, as PSCAD holds it
print(str(params["FLT"])) # Loss Tangent is Defined at, in Hz
comp = project.find_all("master:Cable_PipeType")[0]
comp.parameters(FLT="120 [Hz]") # a value that carries a unit is written with it
- A parameter is named exactly as in the table, letter case included:
parameters()gives every one of them in a dictionary, and a name the component does not have is refused. - A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (
str(...)) or the unit is lost. PSCAD keeps a written unit as it is given:"2500 [mohm]"stays in mohm. - A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
find_all()takes the exact definition only. A wildcard or a bare name withoutmaster:comes back empty; the Builder'spx_findwalks the pages for those.
The Builder's runtime does the same with the unit handled for you: px_get(comp, "FLT") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.
- Inner Cable 1 Configuration15
- Inner Cable 2 Configuration15
- Inner Cable 3 Configuration15
- Inner Cable 4 Configuration15
- Inner Cable 5 Configuration15
- Inner Cable 6 Configuration15
- Inner Cable 7 Configuration15
- Inner Cable 8 Configuration15
- Inner Cable 1 Data38
- Inner Cable 2 Data39
- Inner Cable 3 Data39
- Inner Cable 4 Data39
- Inner Cable 5 Data39
- Inner Cable 6 Data39
- Inner Cable 7 Data39
- Inner Cable 8 Data39
- Pipe Data11
- Pipe Configuration12
Inner Cable 1 Configuration
| Parameter | Unit | Default | Description |
|---|---|---|---|
CBC11Choice | ยท | NO | Transposition of Conducting CoreWritten as NO (No), YES (Yes)Used when (CROSSBOND1==1) |
CBC21Choice | ยท | YES | Cross-bonding of 1st Conducting LayerWritten as YES (Yes), NO (No), TRANSPOSE_ONLY (Transpose only)Used when (CROSSBOND1==1) && (LL1>=2) |
CBC31Choice | ยท | NO | Transposition of 2nd Conducting LayerWritten as NO (No), YES (Yes)Used when (CROSSBOND1==1) && (LL1>=4) |
CBC41Choice | ยท | NO | Transposition of 3rd Conducting LayerWritten as NO (No), YES (Yes)Used when (CROSSBOND1==1) && (LL1>=6) |
CROSSBOND1Choice | ยท | DISABLED | Ideal Cross-bonding/Transposition isWritten as DISABLED (Disabled), ENABLED (Enabled) |
GROUPNO1Choice | ยท | 1 | Cross-bonding/Transposition GroupEnter the group number to which this cable belongs.Written as 1 = 1, 2 = 2, 3 = 3, 4 = 4Used when (CROSSBOND1==1) |
LC1Choice | ยท | NONE | Conductors to EliminateChoose which conducting layers to eliminate (if any).Written as NONE (None), OUTERMOST_ONLY (Outermost only), ALL_CONCENTRIC (All concentric), SPECIFY (Specify)Used when (LL1==3)||(LL1==5)||(LL1==7) |
LL1Choice | ยท | C1_I1_C2_I2 | Layer ConfigurationSelect the configuration of the coax cable layers. C and I represent conducting and insulating layer respectively.Written as C1, C1_I1 (C1 | I1), C1_I1_C2 (C1 | I1 | C2), C1_I1_C2_I2 (C1 | I1 | C2 | I2), C1_I1_C2_I2_C3 (C1 | I1 | C2 | I2 | C3), C1_I1_C2_I2_C3_I3 (C1 | I1 | C2 | I2 | C3 | I3), C1_I1_C2_I2_C3_I3_C4 (C1 | I1 | C2 | I2 | C3 | I3 | C4), C1_I1_C2_I2_C3_I3_C4_I4 (C1 | I1 | C2 | I2 | C3 | I3 | C4 | I4) |
NC1Integer | ยท | 1 | Cable NumberEnter a unique number for this coax cable to coincide with the external node connection.Range 1 to 8 |
RorT1Choice | ยท | RADIAL_FROM_CENTRE | Layer Thickness is Specified asSelect the manner in which the layer thicknesses are specified. If radial from centre is selected, enter the distance from the centre-point to the outer radius of the layer.Written as RADIAL_FROM_CENTRE (Radial from centre), ACTUAL_THICKNESS (Actual thickness) |
ang1Real | deg | 270.0 | Angular Position of Cable CentreEnter a value to represent the angular position of the centre of this coax cable, in relation to the origin. |
dcc1Real | m | 0.022 | Distance from Pipe Centre to Cable CentreEnter a value to represent the distance between the centre of this coax cable, and the centre of the encompassing pipe.Range -1E+38 to 1E+38 |
elim11Choice | ยท | RETAIN | 1st Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINATE (Eliminate)Used when (LC1 == 3) && ((LL1 == 3) || (LL1 == 5) || (LL1 == 7)) |
elim21Choice | ยท | RETAIN | 2nd Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINATE (Eliminate)Used when (LC1 == 3) && ((LL1 == 5) || (LL1 == 7)) |
elim31Choice | ยท | RETAIN | 3rd Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINATE (Eliminate)Used when (LC1 == 3) && (LL1 == 7) |
Inner Cable 2 Configuration
| Parameter | Unit | Default | Description |
|---|---|---|---|
CBC12Choice | ยท | NO | Transposition of Conducting CoreWritten as NO (No), YES (Yes)Used when (CROSSBOND2==1) |
CBC22Choice | ยท | YES | Cross-bonding of 1st Conducting LayerWritten as YES (Yes), NO (No), TRANSPOSE_ONLY (Transpose only)Used when (CROSSBOND2==1) && (LL2>=2) |
CBC32Choice | ยท | NO | Transposition of 2nd Conducting LayerWritten as NO (No), YES (Yes)Used when (CROSSBOND2==1) && (LL2>=4) |
CBC42Choice | ยท | NO | Transposition of 3rd Conducting LayerWritten as NO (No), YES (Yes)Used when (CROSSBOND2==1) && (LL2>=6) |
CROSSBOND2Choice | ยท | DISABLED | Ideal Cross-bonding/Transposition isWritten as DISABLED (Disabled), ENABLED (Enabled) |
GROUPNO2Choice | ยท | 1 | Cross-bonding/Transposition GroupEnter the group number to which this cable belongs.Written as 1 = 1, 2 = 2, 3 = 3, 4 = 4Used when (CROSSBOND2==1) |
LC2Choice | ยท | NONE | Conductors to EliminateChoose which conducting layers to eliminate (if any).Written as NONE (None), OUTERMOST_ONLY (Outermost only), ALL_CONCENTRIC (All concentric), SPECIFY (Specify)Used when (LL2==3)||(LL2==5)||(LL2==7) |
LL2Choice | ยท | C1_I1_C2_I2 | Layer ConfigurationSelect the configuration of the coax cable layers. C and I represent conducting and insulating layer respectively.Written as C1, C1_I1 (C1 | I1), C1_I1_C2 (C1 | I1 | C2), C1_I1_C2_I2 (C1 | I1 | C2 | I2), C1_I1_C2_I2_C3 (C1 | I1 | C2 | I2 | C3), C1_I1_C2_I2_C3_I3 (C1 | I1 | C2 | I2 | C3 | I3), C1_I1_C2_I2_C3_I3_C4 (C1 | I1 | C2 | I2 | C3 | I3 | C4), C1_I1_C2_I2_C3_I3_C4_I4 (C1 | I1 | C2 | I2 | C3 | I3 | C4 | I4) |
NC2Integer | ยท | 2 | Cable NumberEnter a unique number for this coax cable to coincide with the external node connection.Range 1 to 8 |
RorT2Choice | ยท | RADIAL_FROM_CENTRE | Layer Thickness is Specified asSelect the manner in which the layer thicknesses are specified. If radial from centre is selected, enter the distance from the centre-point to the outer radius of the layer.Written as RADIAL_FROM_CENTRE (Radial from centre), ACTUAL_THICKNESS (Actual thickness) |
ang2Real | deg | 30.0 | Angular Position of Cable CentreEnter a value to represent the angular position of the centre of this coax cable, in relation to the origin. |
dcc2Real | m | 0.022 | Distance from Pipe Centre to Cable CentreEnter a value to represent the distance between the centre of this coax cable, and the centre of the encompassing pipe.Range -1E+38 to 1E+38 |
elim12Choice | ยท | RETAIN | 1st Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINATE (Eliminate)Used when (LC2 == 3) && ((LL2 == 3) || (LL2 == 5) || (LL2 == 7)) |
elim22Choice | ยท | RETAIN | 2nd Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINATE (Eliminate)Used when (LC2 == 3) && ((LL2 == 5) || (LL2 == 7)) |
elim32Choice | ยท | RETAIN | 3rd Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINATE (Eliminate)Used when (LC2 == 3) && (LL2 == 7) |
Inner Cable 3 Configuration
| Parameter | Unit | Default | Description |
|---|---|---|---|
CBC13Choice | ยท | NO | Transposition of Conducting CoreWritten as NO (No), YES (Yes)Used when (CROSSBOND3==1) |
CBC23Choice | ยท | YES | Cross-bonding of 1st Conducting LayerWritten as YES (Yes), NO (No), TRANSPOSE_ONLY (Transpose only)Used when (CROSSBOND3==1) && (LL3>=2) |
CBC33Choice | ยท | NO | Transposition of 2nd Conducting LayerWritten as NO (No), YES (Yes)Used when (CROSSBOND3==1) && (LL3>=4) |
CBC43Choice | ยท | NO | Transposition of 3rd Conducting LayerWritten as NO (No), YES (Yes)Used when (CROSSBOND3==1) && (LL3>=6) |
CROSSBOND3Choice | ยท | DISABLED | Ideal Cross-bonding/Transposition isWritten as DISABLED (Disabled), ENABLED (Enabled) |
GROUPNO3Choice | ยท | 1 | Cross-bonding/Transposition GroupEnter the group number to which this cable belongs.Written as 1 = 1, 2 = 2, 3 = 3, 4 = 4Used when (CROSSBOND3==1) |
LC3Choice | ยท | NONE | Conductors to EliminateChoose which conducting layers to eliminate (if any).Written as NONE (None), OUTERMOST_ONLY (Outermost only), ALL_CONCENTRIC (All concentric), SPECIFY (Specify)Used when (LL3==3)||(LL3==5)||(LL3==7) |
LL3Choice | ยท | C1_I1_C2_I2 | Layer ConfigurationSelect the configuration of the coax cable layers. C and I represent conducting and insulating layer respectively.Written as C1, C1_I1 (C1 | I1), C1_I1_C2 (C1 | I1 | C2), C1_I1_C2_I2 (C1 | I1 | C2 | I2), C1_I1_C2_I2_C3 (C1 | I1 | C2 | I2 | C3), C1_I1_C2_I2_C3_I3 (C1 | I1 | C2 | I2 | C3 | I3), C1_I1_C2_I2_C3_I3_C4 (C1 | I1 | C2 | I2 | C3 | I3 | C4), C1_I1_C2_I2_C3_I3_C4_I4 (C1 | I1 | C2 | I2 | C3 | I3 | C4 | I4) |
NC3Integer | ยท | 3 | Cable NumberEnter a unique number for this coax cable to coincide with the external node connection.Range 1 to 8 |
RorT3Choice | ยท | RADIAL_FROM_CENTRE | Layer Thickness is Specified asSelect the manner in which the layer thicknesses are specified. If radial from centre is selected, enter the distance from the centre-point to the outer radius of the layer.Written as RADIAL_FROM_CENTRE (Radial from centre), ACTUAL_THICKNESS (Actual thickness) |
ang3Real | deg | 150.0 | Angular Position of Cable CentreEnter a value to represent the angular position of the centre of this coax cable, in relation to the origin. |
dcc3Real | m | 0.022 | Distance from Pipe Centre to Cable CentreEnter a value to represent the distance between the centre of this coax cable, and the centre of the encompassing pipe.Range -1E+38 to 1E+38 |
elim13Choice | ยท | RETAIN | 1st Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC3 == 3) && ((LL3 == 3) || (LL3 == 5) || (LL3 == 7)) |
elim23Choice | ยท | RETAIN | 2nd Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC3 == 3) && ((LL3 == 5) || (LL3 == 7)) |
elim33Choice | ยท | RETAIN | 3rd Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC3 == 3) && (LL3 == 7) |
Inner Cable 4 Configuration
| Parameter | Unit | Default | Description |
|---|---|---|---|
CBC14Choice | ยท | NO | Transposition of Conducting CoreWritten as NO (No), YES (Yes)Used when (CROSSBOND4==1) |
CBC24Choice | ยท | YES | Cross-bonding of 1st Conducting LayerWritten as YES (Yes), NO (No), TRANSPOSE_ONLY (Transpose only)Used when (CROSSBOND4==1) && (LL4>=2) |
CBC34Choice | ยท | NO | Transposition of 2nd Conducting LayerWritten as NO (No), YES (Yes)Used when (CROSSBOND4==1) && (LL4>=4) |
CBC44Choice | ยท | NO | Transposition of 3rd Conducting LayerWritten as NO (No), YES (yes)Used when (CROSSBOND4==1) && (LL4>=6) |
CROSSBOND4Choice | ยท | DISABLED | Ideal Cross-bonding/Transposition isWritten as DISABLED (Disabled), ENABLED (Enabled) |
GROUPNO4Choice | ยท | 1 | Cross-bonding/Transposition GroupEnter the group number to which this cable belongs.Written as 1 = 1, 2 = 2, 3 = 3, 4 = 4Used when (CROSSBOND4==1) |
LC4Choice | ยท | NONE | Conductors to EliminateChoose which conducting layers to eliminate (if any).Written as NONE (None), OUTERMOST_ONLY (Outermost only), ALL_CONCENTRIC (All concentric), SPECIFY (Specify)Used when (LL4==3)||(LL4==5)||(LL4==7) |
LL4Choice | ยท | C1_I1_C2_I2 | Layer ConfigurationSelect the configuration of the coax cable layers. C and I represent conducting and insulating layer respectively.Written as C1, C1_I1 (C1 | I1), C1_I1_C2 (C1 | I1 | C2), C1_I1_C2_I2 (C1 | I1 | C2 | I2), C1_I1_C2_I2_C3 (C1 | I1 | C2 | I2 | C3), C1_I1_C2_I2_C3_I3 (C1 | I1 | C2 | I2 | C3 | I3), C1_I1_C2_I2_C3_I3_C4 (C1 | I1 | C2 | I2 | C3 | I3 | C4), C1_I1_C2_I2_C3_I3_C4_I4 (C1 | I1 | C2 | I2 | C3 | I3 | C4 | I4) |
NC4Integer | ยท | 4 | Cable NumberEnter a unique number for this coax cable to coincide with the external node connection.Range 1 to 8 |
RorT4Choice | ยท | RADIAL_FROM_CENTRE | Layer Thickness is Specified asSelect the manner in which the layer thicknesses are specified. If radial from centre is selected, enter the distance from the centre-point to the outer radius of the layer.Written as RADIAL_FROM_CENTRE (Radial from centre), ACTUAL_THICKNESS (Actual thickness) |
ang4Real | deg | 0.0 | Angular Position of Cable CentreEnter a value to represent the angular position of the centre of this coax cable, in relation to the origin. |
dcc4Real | m | 0.01 | Distance from Pipe Centre to Cable CentreEnter a value to represent the distance between the centre of this coax cable, and the centre of the encompassing pipe.Range -1E+38 to 1E+38 |
elim14Choice | ยท | RETAIN | 1st Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC4 == 3) && ((LL4 == 3) || (LL4 == 5) || (LL4 == 7)) |
elim24Choice | ยท | RETAIN | 2nd Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC4 == 3) && ((LL4 == 5) || (LL4 == 7)) |
elim34Choice | ยท | RETAIN | 3rd Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC4 == 3) && (LL4 == 7) |
Inner Cable 5 Configuration
| Parameter | Unit | Default | Description |
|---|---|---|---|
CBC15Choice | ยท | NO | Transposition of Conducting CoreWritten as NO (No), YES (Yes)Used when (CROSSBOND5==1) |
CBC25Choice | ยท | YES | Cross-bonding of 1st Conducting LayerWritten as YES (Yes), NO (No), TRANSPOSE_ONLY (Transpose only)Used when (CROSSBOND5==1) && (LL5>=2) |
CBC35Choice | ยท | NO | Transposition of 2nd Conducting LayerWritten as NO (No), YES (Yes)Used when (CROSSBOND5==1) && (LL5>=4) |
CBC45Choice | ยท | NO | Transposition of 3rd Conducting LayerWritten as NO (No), YES (Yes)Used when (CROSSBOND5==1) && (LL5>=6) |
CROSSBOND5Choice | ยท | DISABLED | Ideal Cross-bonding/Transposition isWritten as DISABLED (Disabled), ENABLED (Enabled) |
GROUPNO5Choice | ยท | 1 | Cross-bonding/Transposition GroupEnter the group number to which this cable belongs.Written as 1 = 1, 2 = 2, 3 = 3, 4 = 4Used when (CROSSBOND5==1) |
LC5Choice | ยท | NONE | Conductors to EliminateChoose which conducting layers to eliminate (if any).Written as NONE (None), OUTERMOST_ONLY (Outermost only), ALL_CONCENTRIC (All concentric), SPECIFY (Specify)Used when (LL5==3)||(LL5==5)||(LL5==7) |
LL5Choice | ยท | C1_I1_C2_I2 | Layer ConfigurationSelect the configuration of the coax cable layers. C and I represent conducting and insulating layer respectively.Written as C1, C1_I1 (C1 | I1), C1_I1_C2 (C1 | I1 | C2), C1_I1_C2_I2 (C1 | I1 | C2 | I2), C1_I1_C2_I2_C3 (C1 | I1 | C2 | I2 | C3), C1_I1_C2_I2_C3_I3 (C1 | I1 | C2 | I2 | C3 | I3), C1_I1_C2_I2_C3_I3_C4 (C1 | I1 | C2 | I2 | C3 | I3 | C4), C1_I1_C2_I2_C3_I3_C4_I4 (C1 | I1 | C2 | I2 | C3 | I3 | C4 | I4) |
NC5Integer | ยท | 5 | Cable NumberEnter a unique number for this coax cable to coincide with the external node connection.Range 1 to 8 |
RorT5Choice | ยท | RADIAL_FROM_CENTRE | Layer Thickness is Specified asSelect the manner in which the layer thicknesses are specified. If radial from centre is selected, enter the distance from the centre-point to the outer radius of the layer.Written as RADIAL_FROM_CENTRE (Radial from centre), ACTUAL_THICKNESS (Actual thickness) |
ang5Real | deg | 0.0 | Angular Position of Cable CentreEnter a value to represent the angular position of the centre of this coax cable, in relation to the origin. |
dcc5Real | m | 0.01 | Distance from Pipe Centre to Cable CentreEnter a value to represent the distance between the centre of this coax cable, and the centre of the encompassing pipe.Range -1E+38 to 1E+38 |
elim15Choice | ยท | RETAIN | 1st Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC5 == 3) && ((LL5 == 3) || (LL5 == 5) || (LL5 == 7)) |
elim25Choice | ยท | RETAIN | 2nd Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC5 == 3) && ((LL5 == 5) || (LL5 == 7)) |
elim35Choice | ยท | RETAIN | 3rd Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC5 == 3) && (LL5 == 7) |
Inner Cable 6 Configuration
| Parameter | Unit | Default | Description |
|---|---|---|---|
CBC16Choice | ยท | NO | Transposition of Conducting CoreWritten as NO (No), YES (Yes)Used when (CROSSBOND6==1) |
CBC26Choice | ยท | YES | Cross-bonding of 1st Conducting LayerWritten as YES (Yes), NO (No), TRANSPOSE_ONLY (Transpose only)Used when (CROSSBOND6==1) && (LL6>=2) |
CBC36Choice | ยท | NO | Transposition of 2nd Conducting LayerWritten as NO (No), YES (Yes)Used when (CROSSBOND6==1) && (LL6>=4) |
CBC46Choice | ยท | NO | Transposition of 3rd Conducting LayerWritten as NO (No), YES (Yes)Used when (CROSSBOND6==1) && (LL6>=6) |
CROSSBOND6Choice | ยท | DISABLED | Ideal cross-bonding/Transposition isWritten as DISABLED (Disabled), ENABLED (Enabled) |
GROUPNO6Choice | ยท | 1 | Cross-bonding/Transposition GroupEnter the group number to which this cable belongs.Written as 1 = 1, 2 = 2, 3 = 3, 4 = 4Used when (CROSSBOND6==1) |
LC6Choice | ยท | NONE | Conductors to EliminateChoose which conducting layers to eliminate (if any).Written as NONE (None), OUTERMOST_ONLY (Outermost only), ALL_CONCENTRIC (All concentric), SPECIFY (Specify)Used when (LL6==3)||(LL6==5)||(LL6==7) |
LL6Choice | ยท | C1_I1_C2_I2 | Layer ConfigurationSelect the configuration of the coax cable layers. C and I represent conducting and insulating layer respectively.Written as C1, C1_I1 (C1 | I1), C1_I1_C2 (C1 | I1 | C2), C1_I1_C2_I2 (C1 | I1 | C2 | I2), C1_I1_C2_I2_C3 (C1 | I1 | C2 | I2 | C3), C1_I1_C2_I2_C3_I3 (C1 | I1 | C2 | I2 | C3 | I3), C1_I1_C2_I2_C3_I3_C4 (C1 | I1 | C2 | I2 | C3 | I3 | C4), C1_I1_C2_I2_C3_I3_C4_I4 (C1 | I1 | C2 | I2 | C3 | I3 | C4 | I4) |
NC6Integer | ยท | 6 | Cable NumberEnter a unique number for this coax cable to coincide with the external node connection.Range 1 to 8 |
RorT6Choice | ยท | RADIAL_FROM_CENTRE | Layer Thickness is Specified asSelect the manner in which the layer thicknesses are specified. If radial from centre is selected, enter the distance from the centre-point to the outer radius of the layer.Written as RADIAL_FROM_CENTRE (Radial from centre), ACTUAL_THICKNESS (Actual thickness) |
ang6Real | deg | 0.0 | Angular Position of Cable CentreEnter a value to represent the angular position of the centre of this coax cable, in relation to the origin. |
dcc6Real | m | 0.01 | Distance from Pipe Centre to Cable CentreEnter a value to represent the distance between the centre of this coax cable, and the centre of the encompassing pipe.Range -1E+38 to 1E+38 |
elim16Choice | ยท | RETAIN | 1st concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC6 == 3) && ((LL6 == 3) || (LL6 == 5) || (LL6 == 7)) |
elim26Choice | ยท | RETAIN | 2nd Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC6 == 3) && ((LL6 == 5) || (LL6 == 7)) |
elim36Choice | ยท | RETAIN | 3rd Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC6 == 3) && (LL6 == 7) |
Inner Cable 7 Configuration
| Parameter | Unit | Default | Description |
|---|---|---|---|
CBC17Choice | ยท | NO | Transposition of Conducting CoreWritten as NO (No), YES (Yes)Used when (CROSSBOND7==1) |
CBC27Choice | ยท | YES | Cross-bonding of 1st Conducting LayerWritten as YES (Yes), NO (No), TRANSPOSE_ONLY (Transpose only)Used when (CROSSBOND7==1) && (LL7>=2) |
CBC37Choice | ยท | NO | Transposition of 2nd Conducting LayerWritten as NO (No), YES (Yes)Used when (CROSSBOND7==1) && (LL7>=4) |
CBC47Choice | ยท | NO | Transposition of 3rd Conducting LayerWritten as NO (No), YES (Yes)Used when (CROSSBOND7==1) && (LL7>=6) |
CROSSBOND7Choice | ยท | DISABLED | Ideal Cross-bonding/Transposition isWritten as DISABLED (Disabled), ENABLED (Enabled) |
GROUPNO7Choice | ยท | 1 | Cross-bonding/Transposition GroupEnter the group number to which this cable belongs.Written as 1 = 1, 2 = 2, 3 = 3, 4 = 4Used when (CROSSBOND7==1) |
LC7Choice | ยท | NONE | Conductors to EliminateChoose which conducting layers to eliminate (if any).Written as NONE (None), OUTERMOST_ONLY (Outermost only), ALL_CONCENTRIC (All concentric), SPECIFY (Specify)Used when (LL7==3)||(LL7==5)||(LL7==7) |
LL7Choice | ยท | C1_I1_C2_I2 | Layer ConfigurationSelect the configuration of the coax cable layers. C and I represent conducting and insulating layer respectively.Written as C1, C1_I1 (C1 | I1), C1_I1_C2 (C1 | I1 | C2), C1_I1_C2_I2 (C1 | I1 | C2 | I2), C1_I1_C2_I2_C3 (C1 | I1 | C2 | I2 | C3), C1_I1_C2_I2_C3_I3 (C1 | I1 | C2 | I2 | C3 | I3), C1_I1_C2_I2_C3_I3_C4 (C1 | I1 | C2 | I2 | C3 | I3 | C4), C1_I1_C2_I2_C3_I3_C4_I4 (C1 | I1 | C2 | I2 | C3 | I3 | C4 | I4) |
NC7Integer | ยท | 7 | Cable NumberEnter a unique number for this coax cable to coincide with the external node connection.Range 1 to 8 |
RorT7Choice | ยท | RADIAL_FROM_CENTRE | Layer Thickness is Specified asSelect the manner in which the layer thicknesses are specified. If radial from centre is selected, enter the distance from the centre-point to the outer radius of the layer.Written as RADIAL_FROM_CENTRE (Radial from centre), ACTUAL_THICKNESS (Actual thickness) |
ang7Real | deg | 0.0 | Angular Position of Cable CentreEnter a value to represent the angular position of the centre of this coax cable, in relation to the origin. |
dcc7Real | m | 0.01 | Distance from Pipe Centre to Cable CentreEnter a value to represent the distance between the centre of this coax cable, and the centre of the encompassing pipe.Range -1E+38 to 1E+38 |
elim17Choice | ยท | RETAIN | 1st Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC7 == 3) && ((LL7 == 3) || (LL7 == 5) || (LL7 == 7)) |
elim27Choice | ยท | RETAIN | 2nd Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC7 == 3) && ((LL7 == 5) || (LL7 == 7)) |
elim37Choice | ยท | RETAIN | 3rd Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC7 == 3) && (LL7 == 7) |
Inner Cable 8 Configuration
| Parameter | Unit | Default | Description |
|---|---|---|---|
CBC18Choice | ยท | NO | Transposition of Conducting CoreWritten as NO (No), YES (Yes)Used when (CROSSBOND8==1) |
CBC28Choice | ยท | YES | Cross-bonding of 1st Conducting LayerWritten as YES (Yes), NO (No), TRANSPOSE_ONLY (Transpose only)Used when (CROSSBOND8==1) && (LL8>=2) |
CBC38Choice | ยท | NO | Transposition of 2nd Conducting LayerWritten as NO (No), YES (Yes)Used when (CROSSBOND8==1) && (LL8>=4) |
CBC48Choice | ยท | NO | Transposition of 3rd Conducting LayerWritten as NO (No), YES (Yes)Used when (CROSSBOND8==1) && (LL8>=6) |
CROSSBOND8Choice | ยท | DISABLED | Ideal Cross-bonding/Transposition isWritten as DISABLED (Disabled), ENABLED (Enabled) |
GROUPNO8Choice | ยท | 1 | Cross-bonding/Transposition GroupEnter the group number to which this cable belongs.Written as 1 = 1, 2 = 2, 3 = 3, 4 = 4Used when (CROSSBOND8==1) |
LC8Choice | ยท | NONE | Conductors to EliminateChoose which conducting layers to eliminate (if any).Written as NONE (None), OUTERMOST_ONLY (Outermost only), ALL_CONCENTRIC (All concentric), SPECIFY (Specify)Used when (LL7==3)||(LL7==5)||(LL7==7) |
LL8Choice | ยท | C1_I1_C2_I2 | Layer ConfigurationSelect the configuration of the coax cable layers. C and I represent conducting and insulating layer respectively.Written as C1, C1_I1 (C1 | I1), C1_I1_C2 (C1 | I1 | C2), C1_I1_C2_I2 (C1 | I1 | C2 | I2), C1_I1_C2_I2_C3 (C1 | I1 | C2 | I2 | C3), C1_I1_C2_I2_C3_I3 (C1 | I1 | C2 | I2 | C3 | I3), C1_I1_C2_I2_C3_I3_C4 (C1 | I1 | C2 | I2 | C3 | I3 | C4), C1_I1_C2_I2_C3_I3_C4_I4 (C1 | I1 | C2 | I2 | C3 | I3 | C4 | I4) |
NC8Integer | ยท | 8 | Cable NumberEnter a unique number for this coax cable to coincide with the external node connection.Range 1 to 8 |
RorT8Choice | ยท | RADIAL_FROM_CENTRE | Layer Thickness is Specified asSelect the manner in which the layer thicknesses are specified. If radial from centre is selected, enter the distance from the centre-point to the outer radius of the layer.Written as RADIAL_FROM_CENTRE (Radial from centre), ACTUAL_THICKNESS (Actual thickness) |
ang8Real | deg | 0.0 | Angular Position of Cable CentreEnter a value to represent the angular position of the centre of this coax cable, in relation to the origin. |
dcc8Real | m | 0.01 | Distance from Pipe Centre to Cable CentreEnter a value to represent the distance between the centre of this coax cable, and the centre of the encompassing pipe.Range -1E+38 to 1E+38 |
elim18Choice | ยท | RETAIN | 1st Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC8 == 3) && ((LL8 == 3) || (LL8 == 5) || (LL8 == 7)) |
elim28Choice | ยท | RETAIN | 2nd Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC8 == 3) && ((LL8 == 5) || (LL8 == 7)) |
elim38Choice | ยท | RETAIN | 3rd Concentric ConductorSpecify whether or not to eliminate this layer.Written as RETAIN (Retain), ELIMINIATE (Eliminiate)Used when (LC8 == 3) && (LL8 == 7) |
Inner Cable 1 Data
| Parameter | Unit | Default | Description |
|---|---|---|---|
EPS11Real | ยท | 3.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS21Real | ยท | 3.72 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS31Real | ยท | 1.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS41Real | ยท | 1.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
LF21Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF31Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF41Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
PERM11Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM21Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM31Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM41Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERMA1Real | ยท | 400.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMC1Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMO1Real | ยท | 400.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMS1Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
R11Real | m | 0.0 | Inner Radius (Enter 0.0 for a Solid Core)Enter the inner radius of the centre or core conductor [m]. If this conductor is solid (i.e. not hollow), then enter 0.0.Range 0 to 1E+38 |
R21Real | m | 0.00915 | Outer RadiusEnter the outer radius of the centre or core conductor [m].Range 1E-38 to 1E+38 |
R31Real | m | 0.01535 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R41Real | m | 0.01642 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 1E+38 |
R51Real | m | 0.01792 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R61Real | m | 0.0583 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 10 |
R71Real | m | 0.0635 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R81Real | m | 0.07 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 1E+38 |
R91Real | m | 0.08 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
RHOA1Real | ohm*m | 1.8e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOC1Real | ohm*m | 1.72e-8 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOO1Real | ohm*m | 1.8e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOS1Real | ohm*m | 1.72e-8 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
SL11Real | m | 0.001 | Inner Semi-conductor Layer ThicknessEnter the thickness of the inner semi-conducting layer (between insulator and core conductor) [m].Range 1E-38 to 1E+38 |
SL21Real | m | 0.001 | Outer Semi-conductor Layer ThicknessEnter the thickness of the outer semi-conducting layer (between insulator and 1st conducting layer) [m].Range 1E-38 to 1E+38 |
SemiCL1Choice | ยท | ABSENT | Semi-conducting LayersWritten as ABSENT (Absent), PRESENT (Present) |
T31Real | m | 0.0175 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T41Real | m | 0.0045 | ThicknessEnter the thickness of this conductor [m].Range 1E-38 to 1E+38 |
T51Real | m | 0.0035 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T61Real | m | 0.0035 | ThicknessEnter the thickness of this conducting layer [m].Range 1E-38 to 1E+38 |
T71Real | m | 0.0035 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T81Real | m | 0.0065 | ThicknessEnter the thickness of this conducting layer [m].Range 1E-38 to 1E+38 |
T91Real | m | 0.01 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
Inner Cable 2 Data
| Parameter | Unit | Default | Description |
|---|---|---|---|
EPS12Real | ยท | 3.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS22Real | ยท | 3.72 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS32Real | ยท | 1.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS42Real | ยท | 1.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
LF12Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF22Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF32Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF42Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
PERM12Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM22Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM32Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM42Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERMA2Real | ยท | 400.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMC2Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMO2Real | ยท | 400.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMS2Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
R12Real | m | 0.0 | Inner Radius (Enter 0.0 for a Solid Core)Enter the inner radius of the centre or core conductor [m]. If this conductor is solid (i.e. not hollow), then enter 0.0.Range 0 to 1E+38 |
R22Real | m | 0.00915 | Outer RadiusEnter the outer radius of the centre or core conductor [m].Range 1E-38 to 1E+38 |
R32Real | m | 0.01535 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R42Real | m | 0.01642 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 1E+38 |
R52Real | m | 0.01792 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R62Real | m | 0.0583 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 10 |
R72Real | m | 0.0635 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R82Real | m | 0.07 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 1E+38 |
R92Real | m | 0.08 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
RHOA2Real | ohm*m | 1.8e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOC2Real | ohm*m | 1.72e-8 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOO2Real | ohm*m | 1.8e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOS2Real | ohm*m | 1.72e-8 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
SL12Real | m | 0.001 | Inner Semi-conductor Layer ThicknessEnter the thickness of the inner semi-conducting layer (between insulator and core conductor) [m].Range 1E-38 to 1E+38 |
SL22Real | m | 0.001 | Outer Semi-conductor Layer ThicknessEnter the thickness of the outer semi-conducting layer (between insulator and 1st conducting layer) [m].Range 1E-38 to 1E+38 |
SemiCL2Choice | ยท | ABSENT | Semi-conducting LayersWritten as ABSENT (Absent), PRESENT (Present) |
T32Real | m | 0.0175 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T42Real | m | 0.0045 | ThicknessEnter the thickness of this conductor [m].Range 1E-38 to 1E+38 |
T52Real | m | 0.0035 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T62Real | m | 0.0035 | ThicknessEnter the thickness of this conducting layer [m].Range 1E-38 to 1E+38 |
T72Real | m | 0.0035 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T82Real | m | 0.0065 | ThicknessEnter the thickness of this conducting layer [m].Range 1E-38 to 1E+38 |
T92Real | m | 0.01 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
Inner Cable 3 Data
| Parameter | Unit | Default | Description |
|---|---|---|---|
EPS13Real | ยท | 3.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS23Real | ยท | 3.72 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS33Real | ยท | 1.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS43Real | ยท | 1.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
LF13Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF23Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF33Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF43Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
PERM13Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM23Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM33Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM43Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERMA3Real | ยท | 400.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMC3Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMO3Real | ยท | 400.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMS3Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
R13Real | m | 0.0 | Inner Radius (Enter 0.0 for a Solid Core)Enter the inner radius of the centre or core conductor [m]. If this conductor is solid (i.e. not hollow), then enter 0.0.Range 0 to 1E+38 |
R23Real | m | 0.00915 | Outer RadiusEnter the outer radius of the centre or core conductor [m].Range 1E-38 to 1E+38 |
R33Real | m | 0.01535 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R43Real | m | 0.01642 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 1E+38 |
R53Real | m | 0.01792 | Outer radiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R63Real | m | 0.0583 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 10 |
R73Real | m | 0.0635 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R83Real | m | 0.07 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 1E+38 |
R93Real | m | 0.08 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
RHOA3Real | ohm*m | 1.8e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOC3Real | ohm*m | 1.72e-8 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOO3Real | ohm*m | 1.8e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOS3Real | ohm*m | 1.72e-8 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
SL13Real | m | 0.001 | Inner Semi-conductor Layer ThicknessEnter the thickness of the inner semi-conducting layer (between insulator and core conductor) [m].Range 1E-38 to 1E+38 |
SL23Real | m | 0.001 | Outer Semi-conductor Layer ThicknessEnter the thickness of the outer semi-conducting layer (between insulator and 1st conducting layer) [m].Range 1E-38 to 1E+38 |
SemiCL3Choice | ยท | ABSENT | Semi-conducting LayersWritten as ABSENT (Absent), PRESENT (Present) |
T33Real | m | 0.0175 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T43Real | m | 0.0045 | ThicknessEnter the thickness of this conductor [m].Range 1E-38 to 1E+38 |
T53Real | m | 0.0035 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T63Real | m | 0.0035 | ThicknessEnter the thickness of this conducting layer [m].Range 1E-38 to 1E+38 |
T73Real | m | 0.0035 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T83Real | m | 0.0065 | ThicknessEnter the thickness of this conducting layer [m].Range 1E-38 to 1E+38 |
T93Real | m | 0.01 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
Inner Cable 4 Data
| Parameter | Unit | Default | Description |
|---|---|---|---|
EPS14Real | ยท | 4.1 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS24Real | ยท | 2.3 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS34Real | ยท | 1.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS44Real | ยท | 1.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
LF14Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF24Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF34Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF44Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
PERM14Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM24Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM34Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM44Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERMA4Real | ยท | 400.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMC4Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMO4Real | ยท | 400.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMS4Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
R14Real | m | 0.0 | Inner Radius (Enter 0.0 for a Solid Core)Enter the inner radius of the centre or core conductor [m]. If this conductor is solid (i.e. not hollow), then enter 0.0.Range 0 to 1E+38 |
R24Real | m | 0.022 | Outer RadiusEnter the outer radius of the centre or core conductor [m].Range 1E-38 to 1E+38 |
R34Real | m | 0.0395 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R44Real | m | 0.044 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 1E+38 |
R54Real | m | 0.0475 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R64Real | m | 0.0583 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 10 |
R74Real | m | 0.0635 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R84Real | m | 0.07 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 1E+38 |
R94Real | m | 0.08 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
RHOA4Real | ohm*m | 1.8e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOC4Real | ohm*m | 1.68e-8 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOO4Real | ohm*m | 1.8e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOS4Real | ohm*m | 2.2e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
SL14Real | m | 0.001 | Inner Semi-conductor Layer ThicknessEnter the thickness of the inner semi-conducting layer (between insulator and core conductor) [m].Range 1E-38 to 1E+38 |
SL24Real | m | 0.001 | Outer Semi-conductor Layer ThicknessEnter the thickness of the outer semi-conducting layer (between insulator and 1st conducting layer) [m].Range 1E-38 to 1E+38 |
SemiCL4Choice | ยท | ABSENT | Semi-conducting LayersWritten as ABSENT (Absent), PRESENT (Present) |
T34Real | m | 0.0175 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T44Real | m | 0.0045 | ThicknessEnter the thickness of this conductor [m].Range 1E-38 to 1E+38 |
T54Real | m | 0.0035 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T64Real | m | 0.0035 | ThicknessEnter the thickness of this conducting layer [m].Range 1E-38 to 1E+38 |
T74Real | m | 0.0035 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T84Real | m | 0.0065 | ThicknessEnter the thickness of this conducting layer [m].Range 1E-38 to 1E+38 |
T94Real | m | 0.01 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
Inner Cable 5 Data
| Parameter | Unit | Default | Description |
|---|---|---|---|
EPS15Real | ยท | 4.1 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS25Real | ยท | 2.3 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS35Real | ยท | 1.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS45Real | ยท | 1.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
LF15Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF25Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF35Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF45Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
PERM15Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM25Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM35Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM45Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERMA5Real | ยท | 400.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMC5Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMO5Real | ยท | 400.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMS5Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
R15Real | m | 0.0 | Inner Radius (Enter 0.0 for a Solid Core)Enter the inner radius of the centre or core conductor [m]. If this conductor is solid (i.e. not hollow), then enter 0.0.Range 0 to 1E+38 |
R25Real | m | 0.022 | Outer RadiusEnter the outer radius of the centre or core conductor [m].Range 1E-38 to 1E+38 |
R35Real | m | 0.0395 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R45Real | m | 0.044 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 1E+38 |
R55Real | m | 0.0475 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R65Real | m | 0.0583 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 10 |
R75Real | m | 0.0635 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R85Real | m | 0.07 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 1E+38 |
R95Real | m | 0.08 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
RHOA5Real | ohm*m | 1.8e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOC5Real | ohm*m | 1.68e-8 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOO5Real | ohm*m | 1.8e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOS5Real | ohm*m | 2.2e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
SL15Real | m | 0.001 | Inner Semi-conductor Layer ThicknessEnter the thickness of the inner semi-conducting layer (between insulator and core conductor) [m].Range 1E-38 to 1E+38 |
SL25Real | m | 0.001 | Outer Semi-conductor Layer ThicknessEnter the thickness of the outer semi-conducting layer (between insulator and 1st conducting layer) [m].Range 1E-38 to 1E+38 |
SemiCL5Choice | ยท | ABSENT | Semi-conducting LayersWritten as ABSENT (Absent), PRESENT (Present) |
T35Real | m | 0.0175 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T45Real | m | 0.0045 | ThicknessEnter the thickness of this conductor [m].Range 1E-38 to 1E+38 |
T55Real | m | 0.0035 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T65Real | m | 0.0035 | ThicknessEnter the thickness of this conducting layer [m].Range 1E-38 to 1E+38 |
T75Real | m | 0.0035 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T85Real | m | 0.0065 | ThicknessEnter the thickness of this conducting layer [m].Range 1E-38 to 1E+38 |
T95Real | m | 0.01 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
Inner Cable 6 Data
| Parameter | Unit | Default | Description |
|---|---|---|---|
EPS16Real | ยท | 4.1 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS26Real | ยท | 2.3 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS36Real | ยท | 1.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS46Real | ยท | 1.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
LF11Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF26Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF36Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF46Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
PERM16Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM26Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM36Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM46Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERMA6Real | ยท | 400.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMC6Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMO6Real | ยท | 400.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMS6Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
R16Real | m | 0.0 | Inner Radius (Enter 0.0 for a Solid Core)Enter the inner radius of the centre or core conductor [m]. If this conductor is solid (i.e. not hollow), then enter 0.0.Range 0 to 1E+38 |
R26Real | m | 0.022 | Outer RadiusEnter the outer radius of the centre or core conductor [m].Range 1E-38 to 1E+38 |
R36Real | m | 0.0395 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R46Real | m | 0.044 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 1E+38 |
R56Real | m | 0.0475 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R66Real | m | 0.0583 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 10 |
R76Real | m | 0.0635 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R86Real | m | 0.07 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 1E+38 |
R96Real | m | 0.08 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
RHOA6Real | ohm*m | 1.8e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOC6Real | ohm*m | 1.68e-8 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOO6Real | ohm*m | 1.8e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOS6Real | ohm*m | 2.2e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
SL16Real | m | 0.001 | Inner Semi-conductor Layer ThicknessEnter the thickness of the inner semi-conducting layer (between insulator and core conductor) [m].Range 1E-38 to 1E+38 |
SL26Real | m | 0.001 | Outer Semi-conductor Layer ThicknessEnter the thickness of the outer semi-conducting layer (between insulator and 1st conducting layer) [m].Range 1E-38 to 1E+38 |
SemiCL6Choice | ยท | ABSENT | Semi-conducting LayersWritten as ABSENT (Absent), PRESENT (Present) |
T36Real | m | 0.0175 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T46Real | m | 0.0045 | ThicknessEnter the thickness of this conductor [m].Range 1E-38 to 1E+38 |
T56Real | m | 0.0035 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T66Real | m | 0.0035 | ThicknessEnter the thickness of this conducting layer [m].Range 1E-38 to 1E+38 |
T76Real | m | 0.0035 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T86Real | m | 0.0065 | ThicknessEnter the thickness of this conducting layer [m].Range 1E-38 to 1E+38 |
T96Real | m | 0.01 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
Inner Cable 7 Data
| Parameter | Unit | Default | Description |
|---|---|---|---|
EPS17Real | ยท | 4.1 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS27Real | ยท | 2.3 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS37Real | ยท | 1.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS47Real | ยท | 1.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
LF17Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF27Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF37Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF47Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
PERM17Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM27Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM37Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM47Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERMA7Real | ยท | 400.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMC7Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMO7Real | ยท | 400.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMS7Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
R17Real | m | 0.0 | Inner Radius (enter 0.0 for a solid core)Enter the inner radius of the centre or core conductor [m]. If this conductor is solid (i.e. not hollow), then enter 0.0.Range 0 to 1E+38 |
R27Real | m | 0.022 | Outer RadiusEnter the outer radius of the centre or core conductor [m].Range 1E-38 to 1E+38 |
R37Real | m | 0.0395 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R47Real | m | 0.044 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 1E+38 |
R57Real | m | 0.0475 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R67Real | m | 0.0583 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 10 |
R77Real | m | 0.0635 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R87Real | m | 0.07 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 1E+38 |
R97Real | m | 0.08 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
RHOA7Real | ohm*m | 1.8e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOC7Real | ohm*m | 1.68e-8 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOO7Real | ohm*m | 1.8e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOS7Real | ohm*m | 2.2e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
SL17Real | m | 0.001 | Inner Semi-conductor Layer ThicknessEnter the thickness of the inner semi-conducting layer (between insulator and core conductor) [m].Range 1E-38 to 1E+38 |
SL27Real | m | 0.001 | Outer Semi-conductor Layer ThicknessEnter the thickness of the outer semi-conducting layer (between insulator and 1st conducting layer) [m].Range 1E-38 to 1E+38 |
SemiCL7Choice | ยท | ABSENT | Semi-conducting LayersWritten as ABSENT (Absent), PRESENT (Present) |
T37Real | m | 0.0175 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T47Real | m | 0.0045 | ThicknessEnter the thickness of this conductor [m].Range 1E-38 to 1E+38 |
T57Real | m | 0.0035 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T67Real | m | 0.0035 | ThicknessEnter the thickness of this conducting layer [m].Range 1E-38 to 1E+38 |
T77Real | m | 0.0035 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T87Real | m | 0.0065 | ThicknessEnter the thickness of this conducting layer [m].Range 1E-38 to 1E+38 |
T97Real | m | 0.01 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
Inner Cable 8 Data
| Parameter | Unit | Default | Description |
|---|---|---|---|
EPS18Real | ยท | 4.1 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS28Real | ยท | 2.3 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS38Real | ยท | 1.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPS48Real | ยท | 1.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
LF18Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF28Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF38Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
LF48Real | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0.0 to 100 |
PERM18Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM28Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM38Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERM48Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERMA8Real | ยท | 400.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMC8Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMO8Real | ยท | 400.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMS8Real | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
R18Real | m | 0.0 | Inner Radius (Enter 0.0 for a Solid Core)Enter the inner radius of the centre or core conductor [m]. If this conductor is solid (i.e. not hollow), then enter 0.0.Range 0 to 1E+38 |
R28Real | m | 0.022 | Outer RadiusEnter the outer radius of the centre or core conductor [m].Range 1E-38 to 1E+38 |
R38Real | m | 0.0395 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R48Real | m | 0.044 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 1E+38 |
R58Real | m | 0.0475 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R68Real | m | 0.0583 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 10 |
R78Real | m | 0.0635 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
R88Real | m | 0.07 | Outer RadiusEnter the outer radius of this conducting layer [m].Range 1E-38 to 1E+38 |
R98Real | m | 0.08 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38 |
RHOA8Real | ohm*m | 1.8e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOC8Real | ohm*m | 1.68e-8 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOO8Real | ohm*m | 1.8e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RHOS8Real | ohm*m | 2.2e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
SL18Real | m | 0.001 | Inner Semi-conductor Layer ThicknessEnter the thickness of the inner semi-conducting layer (between insulator and core conductor) [m].Range 1E-38 to 1E+38 |
SL28Real | m | 0.001 | Outer Semi-conductor Layer ThicknessEnter the thickness of the outer semi-conducting layer (between insulator and 1st conducting layer) [m].Range 1E-38 to 1E+38 |
SemiCL8Choice | ยท | ABSENT | Semi-conducting LayersWritten as ABSENT (Absent), PRESENT (Present) |
T38Real | m | 0.0175 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T48Real | m | 0.0045 | ThicknessEnter the thickness of this conductor [m].Range 1E-38 to 1E+38 |
T58Real | m | 0.0035 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T68Real | m | 0.0035 | ThicknessEnter the thickness of this conducting layer [m].Range 1E-38 to 1E+38 |
T78Real | m | 0.0035 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
T88Real | m | 0.0065 | ThicknessEnter the thickness of this conducting layer [m].Range 1E-38 to 1E+38 |
T98Real | m | 0.01 | ThicknessEnter the thickness of this insulator [m].Range 1E-38 to 1E+38 |
Pipe Data
| Parameter | Unit | Default | Description |
|---|---|---|---|
EPSPipeIReal | ยท | 3.0 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100 |
EPSPipeOReal | ยท | 2.3 | Relative PermittivityEnter the relative permittivity of this insulator.Range 1E-38 to 100Used when poins |
LFPipeIReal | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0 to 100 |
LFPipeOReal | ยท | 0.0001 | Loss TangentEnter the loss tangent of this insulator.Range 0 to 100Used when poins |
PERMPipeReal | ยท | 200.0 | Relative PermeabilityEnter the relative permeability of this conductor.Range 1E-38 to 500 |
PERMPipeIReal | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500 |
PERMPipeOReal | ยท | 1.0 | Relative PermeabilityEnter the relative permeability of this insulator.Range 1E-38 to 500Used when poins |
RHOPipeReal | ohm*m | 1.71e-7 | ResistivityEnter the resistivity of this conductor [ohm*m].Range 1E-38 to 100 |
RP1Real | m | 0.041 | Outer RadiusEnter the outer radius of the outer pipe insulator [m].Range 1E-38 to 1E+38 |
RP2Real | m | 0.042 | Outer RadiusEnter the outer radius of the pipe conductor [m].Range 1E-38 to 1E+38 |
RP3Real | m | 0.043 | Outer RadiusEnter the outer radius of this insulator [m].Range 1E-38 to 1E+38Used when poins |
Pipe Configuration
| Parameter | Unit | Default | Description |
|---|---|---|---|
FLTReal | Hz | 60.0 | Loss Tangent is Defined atEnter the frequency at which loss tangents are defined [Hz].Range 1e-6 to 1000 |
NameText | ยท | ยท | Name for IdentificationEnter a name for identification |
OHCChoice | ยท | UNDERGROUND | Placement in Relation to Ground PlaneChoose whether this cable is placed above or below the ground plane.Written as UNDERGROUND (Underground), AERIAL (Aerial) |
SHRadChoice | ยท | SHOW | Detailed Graphic LabelsSelect whether or not to show detailed graphic labelsWritten as HIDE (Hide), SHOW (Show) |
XReal | m | 0.0 | Horizontal Translation from CentreEnter the translation of the pipe centre-point along the horizontal (x) axis [m]. This value is relative to a local x=0 point, which is derived given the position of all cables in this segment. The x-coordinate of all coax cables included in this pipe must be relative to this depth.Range -1E+38 to 1E+38 |
YReal | m | 1.0 | Depth Below Ground SurfaceEnter the depth of the pipe centre-point below the earth surface [m]. The y-coordinate of all coax cables included in this pipe must be relative to this depth.Range 1E-38 to 1E+38Used when OHC==0 |
Y10Real | m | 3.0 | Height Above Ground SurfaceEnter the height of the pipe centre-point above the earth surface [m]. The y-coordinate of all coax cables included in this pipe must be relative to this height.Range 1E-38 to 1E+38Used when OHC==1 |
cnumChoice | ยท | 3 | Number of Inner CablesSelect the number of cables to be included within this pipe.Written as 0 = 0, 1 = 1, 2 = 2, 3 = 3, 4 = 4, 5 = 5, 6 = 6, 7 = 7, 8 = 8 |
elimpBoolean | ยท | False | Eliminate PipeSelect whether or not to eliminate the pipe mathematicallyWritten as False, TrueUsed when poins |
icabsameBoolean | ยท | False | Each Inner Cable isIndicate whether or not all inner cables are identical. This option can be used to simplify data entry.Written as False, True |
pnumChoice | ยท | 1 | Pipe NumberSelect the pipe numberWritten as 1 = 1, 2 = 2, 3 = 3, 4 = 4, 5 = 5 |
poinsBoolean | ยท | True | Pipe Outer Insulation LayerSelect whether or not insulation layer exists outside the pipeWritten as False, True |
Related
โ master:pi_section2 pi_section2 ยท master:tline_interface_v2 tline_interface_v2 โ