master:dir_neg32 parametersPSCAD Negative Sequence Directional Element

Every parameter of the PSCAD Negative Sequence Directional Element (master:dir_neg32): 9 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().

What master:dir_neg32 is

Negative Sequence Directional Element (Negatives sequence directional element), a component of PSCAD's Master Library, filed under protection.

Definition
master:dir_neg32
PSCAD name
Negative Sequence Directional Element
Category
Protection
Parameters
9, in 2 groups
Read from
PSCAD 5.0.0, 2026-11-07

Read and write master:dir_neg32 in Python

import mhi.pscad

pscad = mhi.pscad.connect()              # the PSCAD that is open; launch() starts one
project = pscad.project("my_case")       # a case loaded in the workspace

for comp in project.find_all("master:dir_neg32"):   # the exact definition, namespace first
    params = comp.parameters()           # every parameter, as PSCAD holds it
    print(str(params["KI1"]))            # I1 Restraint Factor

comp = project.find_all("master:dir_neg32")[0]
comp.parameters(KI1="0.2")               # written as text
  • A parameter is named exactly as in the table, letter case included: parameters() gives every one of them in a dictionary, and a name the component does not have is refused.
  • A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (str(...)) or the unit is lost. PSCAD keeps a written unit as it is given: "2500 [mohm]" stays in mohm.
  • A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
  • find_all() takes the exact definition only. A wildcard or a bare name without master: comes back empty; the Builder's px_find walks the pages for those.

The Builder's runtime does the same with the unit handled for you: px_get(comp, "KI1") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.

Configuration

ParameterUnitDefaultDescription
ASChoice·DEGREESInput Angles are Given inSelect degrees or radiansWritten as RADIANS (Radians), DEGREES (Degrees)
KI1Real·0.1I1 Restraint FactorRestraint factor for the fundamentalRange 0.02 to 0.5
NameText··Name for IdentificationEnter a name for identification
QF50Real·0.5Forward OC SettingRange 0.001 to 1000000
QR50Real·0.25Reverse OC SettingRange 0.001 to 1000000
S1Real·85.0Line AnglePhase angle of the line impedance at system frequencyRange 0 to 90
Z2FReal·0.5Z2 Forward ThresholdZone 2 forward threshold
Z2RReal·0.6Z2 Reverse ThresholdZone 2 reverse threshold

Internal Output Variables

ParameterUnitDefaultDescription
IntZ2Text·IntZ2Negative Impedance

Related