master:fixed_load1 parametersPSCAD Fixed Load L-L
Every parameter of the PSCAD Fixed Load L-L (master:fixed_load1): 12 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().
What master:fixed_load1 is
Fixed Load L-L (Single Phase L-L Fixed Load), a component of PSCAD's Master Library, filed under passive branches, loads and filters.
- Definition
master:fixed_load1- PSCAD name
- Fixed Load L-L
- Category
- Passive branches, loads and filters
- Parameters
- 12, in 2 groups; 4 carry a unit
- Read from
- PSCAD 5.0.0, 2026-11-07
Read and write master:fixed_load1 in Python
import mhi.pscad
pscad = mhi.pscad.connect() # the PSCAD that is open; launch() starts one
project = pscad.project("my_case") # a case loaded in the workspace
for comp in project.find_all("master:fixed_load1"): # the exact definition, namespace first
params = comp.parameters() # every parameter, as PSCAD holds it
print(str(params["FR"])) # Fundamental Frequency, in Hz
comp = project.find_all("master:fixed_load1")[0]
comp.parameters(FR="120 [Hz]") # a value that carries a unit is written with it
- A parameter is named exactly as in the table, letter case included:
parameters()gives every one of them in a dictionary, and a name the component does not have is refused. - A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (
str(...)) or the unit is lost. PSCAD keeps a written unit as it is given:"2500 [mohm]"stays in mohm. - A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
find_all()takes the exact definition only. A wildcard or a bare name withoutmaster:comes back empty; the Builder'spx_findwalks the pages for those.
The Builder's runtime does the same with the unit handled for you: px_get(comp, "FR") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.
Internal Outputs
| Parameter | Unit | Default | Description |
|---|---|---|---|
C1Text | · | · | Effective capacitance [uF]Range 0 to 0 |
L1Text | · | · | Effective inductance [H]Range 0 to 0 |
R1Text | · | · | Effective resistance [ohm]Range 0 to 0 |
Parameters
| Parameter | Unit | Default | Description |
|---|---|---|---|
FRReal | Hz | 60 | Fundamental FrequencyAt least 1E-307 |
KPFReal | · | 0 | Freq Index for Power (dP/dF)Range -5 to 5 |
KQFReal | · | 0 | Freq Index for Q (dQ/dF)Range -5 to 5 |
NPReal | · | 2 | Volt Index for Power (dP/dV)Range -5 to 5 |
NQReal | · | 2 | Volt Index for Q (dQ/dV)Range -5 to 5 |
NameText | · | · | Name for IdentificationEnter a name for identificationRange 0 to 0 |
POReal | MW | 100 | Rated Real PowerAt least 0 |
QOReal | MVAR | 25 | Rated Reactive Power(+inductive) |
VBOReal | kV | 230 | Rated Load Voltage (RMS)At least 0 |