master:fixed_load parametersPSCAD Fixed Load

Every parameter of the PSCAD Fixed Load (master:fixed_load): 26 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().

What master:fixed_load is

The fixed load: a load with set real and reactive power that depends on voltage and frequency through its indices.

Definition
master:fixed_load
PSCAD name
Fixed Load
Category
Passive branches, loads and filters
Parameters
26, in 2 groups; 5 carry a unit
Read from
PSCAD 5.0.0, 2026-11-07

Most used master:fixed_load parameters

ParameterUnitDescription
POMWRated Real Power per Phaserated real power per phase
QOMVARRated Reactive Power(+inductive) per Phaserated reactive power per phase
VBOkVRated Load Voltage (RMS L-G)rated voltage, line to ground RMS
NP·Voltage Index for P (dP/dV) - Part Avoltage index for P
NQ·Voltage Index for Q (dQ/dV) - Part Avoltage index for Q

Read and write master:fixed_load in Python

import mhi.pscad

pscad = mhi.pscad.connect()              # the PSCAD that is open; launch() starts one
project = pscad.project("my_case")       # a case loaded in the workspace

for comp in project.find_all("master:fixed_load"):   # the exact definition, namespace first
    params = comp.parameters()           # every parameter, as PSCAD holds it
    print(str(params["PO"]))             # Rated Real Power per Phase, in MW

comp = project.find_all("master:fixed_load")[0]
comp.parameters(PO="200 [MW]")           # a value that carries a unit is written with it
  • A parameter is named exactly as in the table, letter case included: parameters() gives every one of them in a dictionary, and a name the component does not have is refused.
  • A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (str(...)) or the unit is lost. PSCAD keeps a written unit as it is given: "2500 [mohm]" stays in mohm.
  • A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
  • find_all() takes the exact definition only. A wildcard or a bare name without master: comes back empty; the Builder's px_find walks the pages for those.

The Builder's runtime does the same with the unit handled for you: px_get(comp, "PO") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.

Internal Outputs

ParameterUnitDefaultDescription
C1Text··Effective Capacitance [uF] per PhaseEnter a name to monitor effective capacitanceRange 0 to 0
L1Text··Effective Inductance [H] per PhaseEnter a name to monitor effective inductanceRange 0 to 0
R1Text··Effective Resistance [ohm] per PhaseEnter a name to monitor effective resistanceRange 0 to 0

Parameters

ParameterUnitDefaultDescription
DtlsChoice·NODisplay details?Written as NO (No), YES (Yes)
FRRealHz60Fundamental FrequencyAt least 1E-307
KPAReal·1.0Contribution of P at Specified Condition - Part ARange 0 to 1
KPBReal·0.0Contribution of P at Specified Condition - Part BRange 0 to 1
KPFReal·0.0Frequency Index for P (dP/dF)Range -5 to 5
KQAReal·1.0Contribution of Q at Specified Condition - Part ARange 0 to 1
KQBReal·0.0Contribution of Q at Specified Condition - Part BRange 0 to 1
KQFReal·0.0Frequency Index for Q (dQ/dF)Range -5 to 5
NCYCReal·10.0Number of Cycles before Load ReleaseRange 1 to 20
NPReal·2.0Voltage Index for P (dP/dV) - Part ARange -5 to 5
NPBReal·2.0Voltage Index for P (dP/dV) - Part BRange -5 to 5
NPCReal·2.0Voltage Index for P (dP/dV) - Part CRange -5 to 5
NQReal·2.0Voltage Index for Q (dQ/dV) - Part ARange -5 to 5
NQBReal·2.0Voltage Index for Q (dQ/dV) - Part BRange -5 to 5
NQCReal·2.0Voltage Index for Q (dQ/dV) - Part CRange -5 to 5
NameText··NameName for easy identificationRange 0 to 0
PORealMW100Rated Real Power per PhaseAt least 0
PQdefChoice·RATEDPQ Defined atSelect Rated Voltage or Initial Terminal VoltageWritten as RATED (Rated Voltage), INITIAL_TERMINAL (Initial Terminal Voltage)
PartsChoice·1Number of Parts in the Composite LoadSelect number of parts in the composite load 1, 2 or 3Written as 1 = 1, 2 = 2, 3 = 3
QORealMVAR25Rated Reactive Power(+inductive) per Phase
ScaleReal·1.0Scaling FactorRange 1E-10 to 10
VBORealkV132.790562Rated Load Voltage (RMS L-G)At least 0
VPURealpu1.0Initial Terminal VoltageInitial terminal voltageAt least 0

Related

← master:Dload Delta connected configurable load · master:fixed_load1 Fixed Load L-L →