master:Line_Tower_Universal parametersPSCAD Universal Tower
Every parameter of the PSCAD Universal Tower (master:Line_Tower_Universal): 109 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().
What master:Line_Tower_Universal is
Universal Tower (Line Constants Manual Entry of XY Positions), a component of PSCAD's Master Library, filed under lines, cables and towers.
- Definition
master:Line_Tower_Universal- PSCAD name
- Universal Tower
- Category
- Lines, cables and towers
- Parameters
- 109, in 7 groups; 71 carry a unit
- Read from
- PSCAD 5.0.0, 2026-11-07
Read and write master:Line_Tower_Universal in Python
import mhi.pscad
pscad = mhi.pscad.connect() # the PSCAD that is open; launch() starts one
project = pscad.project("my_case") # a case loaded in the workspace
for comp in project.find_all("master:Line_Tower_Universal"): # the exact definition, namespace first
params = comp.parameters() # every parameter, as PSCAD holds it
print(str(params["BSP"])) # Sub-conductor spacing, in m
comp = project.find_all("master:Line_Tower_Universal")[0]
comp.parameters(BSP="0.9144 [m]") # a value that carries a unit is written with it
- A parameter is named exactly as in the table, letter case included:
parameters()gives every one of them in a dictionary, and a name the component does not have is refused. - A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (
str(...)) or the unit is lost. PSCAD keeps a written unit as it is given:"2500 [mohm]"stays in mohm. - A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
find_all()takes the exact definition only. A wildcard or a bare name withoutmaster:comes back empty; the Builder'spx_findwalks the pages for those.
The Builder's runtime does the same with the unit handled for you: px_get(comp, "BSP") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.
- Conductor Data16
- Ground Wire Data14
- Phase/Node Connection Information14
- Configuration7
- Asymmetrical Bundling Position Data30
- Conductor Coordinates24
- Ground Wires Coordinates4
Conductor Data
| Parameter | Unit | Default | Description |
|---|---|---|---|
BSPReal | m | 0.4572 | Sub-conductor spacingEnter the distance between sub-conductors in the bundle.Range 1E-38 to 100Used when (NCondB>=2)&&(BundSym==0) |
BundSymChoice | · | SYMMETRICAL | Bundle configuration isSelect whether or not the bundle is symmetrical. If not, then the individual sub-conductor positions must be entered.Written as SYMMETRICAL (symmetrical), ASYMMETRICAL (asymmetrical)Used when NCondB>=2 |
CDataTypeChoice | · | DIRECT | Data entry methodSelect direct to enter data values within this dialog.Written as FROM_LIBRARY_FILE (from library file), DIRECT (direct) |
CLNameText | · | ..\conductor.clb | Path to conductor library fileEnter the path to the library file, including the filename.Used when CDataType==0 |
CNameText | · | chukar | NameEnter a descriptive name for this conductor type. |
DCResCReal | ohm/km | 0.03206 | DC resistance per unit length (entire conductor)Enter the DC resistance of the entire conductor assembly per unit length (i.e. all strands included if stranded) [ohm/km].Range 1E-38 to 100Used when CDataType==1 |
HollowChoice | · | SOLID_CORE | Conductor style isEnter the style of conductor on this tower. This can be solid core, hollow or stranded.Written as SOLID_CORE (solid core), HOLLOW (hollow), STRANDED (stranded)Used when CDataType == 1 |
NCondBChoice | · | 1 | Total bundled sub-conductorsEnter the total number of sub-conductors per bundle (maximum 15).Written as 1 = 1, 2 = 2, 3 = 3, 4 = 4, 5 = 5, 6 = 6, 7 = 7, 8 = 8, 9 = 9, 10 = 10, 11 = 11, 12 = 12, 13 = 13, 14 = 14, 15 = 15 |
PERMCReal | · | 1.0 | Relative permeabilityEnter the relative permeability of the conductor.Range 1E-38 to 1Used when CDataType==1 |
RadiusCReal | m | 0.0203454 | Outer radiusEnter the outer radius of the conductor assembly. If stranded, then this value is the radius to the edge of the outer strands [m].Range 1E-38 to 10Used when CDataType==1 |
RadiusCinReal | m | 0.0 | Inner radiusEnter the inner radius of the conductor assembly if hollow style.Range 0 to 10Used when (CDataType==1) && (Hollow==1) |
RadiusSReal | m | 0.003 | Strand radiusEnter the radius of a single conductor strand [m].Range 1E-38 to 1E+38Used when Hollow == 2 |
SAGCReal | m | 10.0 | Sag (all conductors)Enter the sag for all conductors. This is the difference between the height at the tower, to the height mid-span [m].Range 0 to 10000 |
SHBundChoice | · | VISIBLE | Bundle graphic isWritten as HIDDEN (hidden), VISIBLE (visible)Used when NCondB>=2 |
num_out_strndInteger | · | 12 | Total number of outer strandsEnter the total number of strands that line the outer circumference of the conductor assembly.Range 1 to 1000Used when Hollow == 2 |
num_tot_strndInteger | · | 19 | Total number of strandsEnter the total number of strands that make up the entire conductor.Range 1 to 1000Used when Hollow == 2 |
Ground Wire Data
| Parameter | Unit | Default | Description |
|---|---|---|---|
DCResGReal | ohm/km | 2.8645 | DC resistance per unit lengthEnter the DC resistance of the conducting material per unit length [ohm/km].Range 1E-32 to 100Used when (GDataType==1)&&(NG>0) |
DCResG2Real | ohm/km | 2.8645 | DC resistance per unit lengthEnter the DC resistance of the conducting material per unit length [ohm/km].Range 1E-32 to 100Used when (GDataType==1)&&(NG>1)&&(GWSame==0) |
ElimGWChoice | · | ENABLED | Ground wire elimination isSelect whether or not to mathematically eliminate the ground wires.Written as DISABLED (disabled), ENABLED (enabled)Used when NG>0 |
G2NameText | · | 1/2_HighStrengthSteel | NameEnter a descriptive name for this ground wire type.Used when (GWSame==0)&&(NG>1) |
GDataTypeChoice | · | DIRECT | Data entry methodSelect direct to enter data values within this dialog.Written as FROM_LIBRARY_FILE (from library file), DIRECT (direct)Used when (NG>0) |
GLNameText | · | ..\conductor.clb | Path to ground wire library fileEnter the path to the library file, including the filename.Used when (GDataType==0)&&(NG>0) |
GNameText | · | 1/2_HighStrengthSteel | NameEnter a descriptive name for this ground wire type.Used when NG>0 |
GWSameChoice | · | IDENTICAL | Ground wires areSelect whether or not the ground wires are identical.Written as IDENTICAL (identical), DIFFERENT (different)Used when (NG>1) |
NGChoice | · | 2 | Total number of ground wires isSelect the number of ground wires (1 or 2).Written as 0 = 0, 1 = 1, 2 = 2 |
PERMGReal | · | 1.0 | Relative permeabilityEnter the relative permeability of the conductor.Range 0 to 1Used when (GDataType==1)&&(NG>0) |
PERMG2Real | · | 1.0 | Relative permeabilityEnter the relative permeability of the conductor.Range 0 to 1Used when (GDataType==1)&&(NG>1)&&(GWSame==0) |
RadiusGReal | m | 0.0055245 | Outer radiusEnter the outer radius of the ground wire [m].Range 0 to 10Used when (GDataType==1)&&(NG>0) |
RadiusG2Real | m | 0.0055245 | Outer radiusEnter the outer radius of the ground wire [m].Range 0 to 10Used when (GDataType==1)&&(NG>1)&&(GWSame==0) |
SAGGReal | m | 10.0 | Sag (all ground wires)Enter the sag for all ground wires. This is the difference between the height at the tower, to the height mid-span [m].Range 0 to 10000Used when (NG>0) |
Phase/Node Connection Information
| Parameter | Unit | Default | Description |
|---|---|---|---|
NC1Integer | · | 1 | Conductor 1 (C1)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30 |
NC10Integer | · | 10 | Conductor 10 (C10)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=10 |
NC11Integer | · | 11 | Conductor 11 (C11)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=11 |
NC12Integer | · | 12 | Conductor 12 (C12)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=12 |
NC2Integer | · | 2 | Conductor 2 (C2)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=2 |
NC3Integer | · | 3 | Conductor 3 (C3)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=3 |
NC4Integer | · | 4 | Conductor 4 (C4)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=4 |
NC5Integer | · | 5 | Conductor 5 (C5)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=5 |
NC6Integer | · | 6 | Conductor 6 (C6)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=6 |
NC7Integer | · | 7 | Conductor 7 (C7)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=7 |
NC8Integer | · | 8 | Conductor 8 (C8)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=8 |
NC9Integer | · | 9 | Conductor 9 (C9)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=9 |
NG1Integer | · | 4 | Ground Wire 1 (G1)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when (NG>0)&&(ElimGW==0) |
NG2Integer | · | 5 | Ground Wire 2 (G2)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when (NG>1)&&(ElimGW==0) |
Configuration
| Parameter | Unit | Default | Description |
|---|---|---|---|
NcChoice | · | 3 | Total number of conductorsEnter the total number of conductors, excluding ground wires (maximum 12).Written as 1 = 1, 2 = 2, 3 = 3, 4 = 4, 5 = 5, 6 = 6, 7 = 7, 8 = 8, 9 = 9, 10 = 10, 11 = 11, 12 = 12 |
SHSagChoice | · | HIDDEN | Graphic of conductor sag isSelect whether or not to diplay conductor sag graphic.Written as HIDDEN (hidden), VISIBLE (visible) |
STLChoice | · | NONE | GroupingEnable grouping of conductors if you would like to organize them into circuits. This is important for the display of double-circuit line constants in load flow RXB format in the output file.Written as NONE (None), ORGANIZE_CONDUCTORS_INTO_CIRCUITS (Organize conductors into circuits)Used when ((Nc==6) || (Nc==9) || (Nc==12)) && (Transp==1) |
ShuntGReal | mho/m | 1.0E-11 | Shunt conductanceEnter a shunt conductance value for all conductors in this tower. Typically this value is around 1e-11 [mho/m].Range 1E-38 to 1 |
TNameText | · | 3H5 | NameEnter a descriptive name for this tower. |
TranspChoice | · | ENABLED | Ideal transposition of circuit(s)Select whether or not to ideally transpose the circuit(s). Ideal transposition ensures a perfectly balanced impedance.Written as DISABLED (disabled), ENABLED (enabled) |
XReal | m | 0.0 | Relative x-position of tower centreEnter the local horizontal placement of the tower. This value is relational to other towers in this cross-section [m].Range -1E+38 to 1E+38 |
Asymmetrical Bundling Position Data
| Parameter | Unit | Default | Description |
|---|---|---|---|
XB1Real | m | -0.1 | Sub-Conductor 1 - X Position |
XB10Real | m | -0.1 | Sub-Conductor 10 - X PositionUsed when NCondB>=10 |
XB11Real | m | -0.1 | Sub-Conductor 11 - X PositionUsed when NCondB>=11 |
XB12Real | m | -0.1 | Sub-Conductor 12 - X PositionUsed when NCondB>=12 |
XB13Real | m | -0.1 | Sub-Conductor 13 - X PositionUsed when NCondB>=13 |
XB14Real | m | -0.1 | Sub-Conductor 14 - X PositionUsed when NCondB>=14 |
XB15Real | m | -0.1 | Sub-Conductor 15 - X PositionUsed when NCondB==15 |
XB2Real | m | -0.1 | Sub-Conductor 2 - X Position |
XB3Real | m | -0.1 | Sub-Conductor 3 - X PositionUsed when NCondB>=3 |
XB4Real | m | -0.1 | Sub-Conductor 4 - X PositionUsed when NCondB>=4 |
XB5Real | m | -0.1 | Sub-Conductor 5 - X PositionUsed when NCondB>=5 |
XB6Real | m | -0.1 | Sub-Conductor 6 - X PositionUsed when NCondB>=6 |
XB7Real | m | -0.1 | Sub-Conductor 7 - X PositionUsed when NCondB>=7 |
XB8Real | m | -0.1 | Sub-Conductor 8 - X PositionUsed when NCondB>=8 |
XB9Real | m | -0.1 | Sub-Conductor 9 - X PositionUsed when NCondB>=9 |
YB1Real | m | 0.1 | Sub-Conductor 1 - Y Position |
YB10Real | m | 0.1 | Sub-Conductor 10 - Y PositionUsed when NCondB>=10 |
YB11Real | m | 0.1 | Sub-Conductor 11 - Y PositionUsed when NCondB>=11 |
YB12Real | m | 0.1 | Sub-Conductor 12 - Y PositionUsed when NCondB>=12 |
YB13Real | m | 0.1 | Sub-Conductor 13 - Y PositionUsed when NCondB>=13 |
YB14Real | m | 0.1 | Sub-Conductor 14 - Y PositionUsed when NCondB>=14 |
YB15Real | m | 0.1 | Sub-Conductor 15 - Y PositionUsed when NCondB==15 |
YB2Real | m | 0.1 | Sub-Conductor 2 - Y Position |
YB3Real | m | 0.1 | Sub-Conductor 3 - Y PositionUsed when NCondB>=3 |
YB4Real | m | 0.1 | Sub-Conductor 4 - Y PositionUsed when NCondB>=4 |
YB5Real | m | 0.1 | Sub-Conductor 5 - Y PositionUsed when NCondB>=5 |
YB6Real | m | 0.1 | Sub-Conductor 6 - Y PositionUsed when NCondB>=6 |
YB7Real | m | 0.1 | Sub-Conductor 7 - Y PositionUsed when NCondB>=7 |
YB8Real | m | 0.1 | Sub-Conductor 8 - Y PositionUsed when NCondB>=8 |
YB9Real | m | 0.1 | Sub-Conductor 9 - Y PositionUsed when NCondB>=9 |
Conductor Coordinates
| Parameter | Unit | Default | Description |
|---|---|---|---|
XC1Real | m | -5 | Conductor 1 - X Position |
XC10Real | m | 40 | Conductor 10 - X PositionUsed when Nc>=10 |
XC11Real | m | 45 | Conductor 11 - X PositionUsed when Nc>=11 |
XC12Real | m | 50 | Conductor 12 - X PositionUsed when Nc>=12 |
XC2Real | m | 0 | Conductor 2 - X PositionUsed when Nc>=2 |
XC3Real | m | 5 | Conductor 3 - X PositionUsed when Nc>=3 |
XC4Real | m | 10 | Conductor 4 - X PositionUsed when Nc>=4 |
XC5Real | m | 15 | Conductor 5 - X PositionUsed when Nc>=5 |
XC6Real | m | 20 | Conductor 6 - X PositionUsed when Nc>=6 |
XC7Real | m | 25 | Conductor 7 - X PositionUsed when Nc>=7 |
XC8Real | m | 30 | Conductor 8 - X PositionUsed when Nc>=8 |
XC9Real | m | 35 | Conductor 9 - X PositionUsed when Nc>=9 |
YC1Real | m | 30 | Conductor 1 - Y Position |
YC10Real | m | 30 | Conductor 10 - Y PositionUsed when Nc>=10 |
YC11Real | m | 30 | Conductor 11 - Y PositionUsed when Nc>=11 |
YC12Real | m | 30 | Conductor 12 - Y PositionUsed when Nc>=12 |
YC2Real | m | 30 | Conductor 2 - Y PositionUsed when Nc>=2 |
YC3Real | m | 30 | Conductor 3 - Y PositionUsed when Nc>=3 |
YC4Real | m | 30 | Conductor 4 - Y PositionUsed when Nc>=4 |
YC5Real | m | 30 | Conductor 5 - Y PositionUsed when Nc>=5 |
YC6Real | m | 30 | Conductor 6 - Y PositionUsed when Nc>=6 |
YC7Real | m | 30 | Conductor 7 - Y PositionUsed when Nc>=7 |
YC8Real | m | 30 | Conductor 8 - Y PositionUsed when Nc>=8 |
YC9Real | m | 30 | Conductor 9 - Y PositionUsed when Nc>=9 |
Ground Wires Coordinates
| Parameter | Unit | Default | Description |
|---|---|---|---|
XG1Real | m | -2.5 | Ground Wire G1 - X PositionUsed when NG>0 |
XG2Real | m | 2.5 | Ground Wire G2 - X PositionUsed when NG>1 |
YG1Real | m | 40 | Ground Wire G1 - Y PositionUsed when NG>0 |
YG2Real | m | 40 | Ground Wire G2 - Y PositionUsed when NG>1 |
Related