master:Line_Tower_Universal parametersPSCAD Universal Tower

Every parameter of the PSCAD Universal Tower (master:Line_Tower_Universal): 109 names, with the unit, the default and the meaning PSCAD gives each one. Copy a name into parameters().

What master:Line_Tower_Universal is

Universal Tower (Line Constants Manual Entry of XY Positions), a component of PSCAD's Master Library, filed under lines, cables and towers.

Definition
master:Line_Tower_Universal
PSCAD name
Universal Tower
Category
Lines, cables and towers
Parameters
109, in 7 groups; 71 carry a unit
Read from
PSCAD 5.0.0, 2026-11-07

Read and write master:Line_Tower_Universal in Python

import mhi.pscad

pscad = mhi.pscad.connect()              # the PSCAD that is open; launch() starts one
project = pscad.project("my_case")       # a case loaded in the workspace

for comp in project.find_all("master:Line_Tower_Universal"):   # the exact definition, namespace first
    params = comp.parameters()           # every parameter, as PSCAD holds it
    print(str(params["BSP"]))            # Sub-conductor spacing, in m

comp = project.find_all("master:Line_Tower_Universal")[0]
comp.parameters(BSP="0.9144 [m]")        # a value that carries a unit is written with it
  • A parameter is named exactly as in the table, letter case included: parameters() gives every one of them in a dictionary, and a name the component does not have is refused.
  • A value that carries a unit comes back as a number whose unit is only in its text, so read it as text first (str(...)) or the unit is lost. PSCAD keeps a written unit as it is given: "2500 [mohm]" stays in mohm.
  • A Choice is read and written as its symbol (the capitals in "Written as"), not as the words PSCAD shows in the dialog.
  • find_all() takes the exact definition only. A wildcard or a bare name without master: comes back empty; the Builder's px_find walks the pages for those.

The Builder's runtime does the same with the unit handled for you: px_get(comp, "BSP") and px_set(...), which also records the old value so the case is put back at the end. Getting started shows them.

Conductor Data

ParameterUnitDefaultDescription
BSPRealm0.4572Sub-conductor spacingEnter the distance between sub-conductors in the bundle.Range 1E-38 to 100Used when (NCondB>=2)&&(BundSym==0)
BundSymChoice·SYMMETRICALBundle configuration isSelect whether or not the bundle is symmetrical. If not, then the individual sub-conductor positions must be entered.Written as SYMMETRICAL (symmetrical), ASYMMETRICAL (asymmetrical)Used when NCondB>=2
CDataTypeChoice·DIRECTData entry methodSelect direct to enter data values within this dialog.Written as FROM_LIBRARY_FILE (from library file), DIRECT (direct)
CLNameText·..\conductor.clbPath to conductor library fileEnter the path to the library file, including the filename.Used when CDataType==0
CNameText·chukarNameEnter a descriptive name for this conductor type.
DCResCRealohm/km0.03206DC resistance per unit length (entire conductor)Enter the DC resistance of the entire conductor assembly per unit length (i.e. all strands included if stranded) [ohm/km].Range 1E-38 to 100Used when CDataType==1
HollowChoice·SOLID_COREConductor style isEnter the style of conductor on this tower. This can be solid core, hollow or stranded.Written as SOLID_CORE (solid core), HOLLOW (hollow), STRANDED (stranded)Used when CDataType == 1
NCondBChoice·1Total bundled sub-conductorsEnter the total number of sub-conductors per bundle (maximum 15).Written as 1 = 1, 2 = 2, 3 = 3, 4 = 4, 5 = 5, 6 = 6, 7 = 7, 8 = 8, 9 = 9, 10 = 10, 11 = 11, 12 = 12, 13 = 13, 14 = 14, 15 = 15
PERMCReal·1.0Relative permeabilityEnter the relative permeability of the conductor.Range 1E-38 to 1Used when CDataType==1
RadiusCRealm0.0203454Outer radiusEnter the outer radius of the conductor assembly. If stranded, then this value is the radius to the edge of the outer strands [m].Range 1E-38 to 10Used when CDataType==1
RadiusCinRealm0.0Inner radiusEnter the inner radius of the conductor assembly if hollow style.Range 0 to 10Used when (CDataType==1) && (Hollow==1)
RadiusSRealm0.003Strand radiusEnter the radius of a single conductor strand [m].Range 1E-38 to 1E+38Used when Hollow == 2
SAGCRealm10.0Sag (all conductors)Enter the sag for all conductors. This is the difference between the height at the tower, to the height mid-span [m].Range 0 to 10000
SHBundChoice·VISIBLEBundle graphic isWritten as HIDDEN (hidden), VISIBLE (visible)Used when NCondB>=2
num_out_strndInteger·12Total number of outer strandsEnter the total number of strands that line the outer circumference of the conductor assembly.Range 1 to 1000Used when Hollow == 2
num_tot_strndInteger·19Total number of strandsEnter the total number of strands that make up the entire conductor.Range 1 to 1000Used when Hollow == 2

Ground Wire Data

ParameterUnitDefaultDescription
DCResGRealohm/km2.8645DC resistance per unit lengthEnter the DC resistance of the conducting material per unit length [ohm/km].Range 1E-32 to 100Used when (GDataType==1)&&(NG>0)
DCResG2Realohm/km2.8645DC resistance per unit lengthEnter the DC resistance of the conducting material per unit length [ohm/km].Range 1E-32 to 100Used when (GDataType==1)&&(NG>1)&&(GWSame==0)
ElimGWChoice·ENABLEDGround wire elimination isSelect whether or not to mathematically eliminate the ground wires.Written as DISABLED (disabled), ENABLED (enabled)Used when NG>0
G2NameText·1/2_HighStrengthSteelNameEnter a descriptive name for this ground wire type.Used when (GWSame==0)&&(NG>1)
GDataTypeChoice·DIRECTData entry methodSelect direct to enter data values within this dialog.Written as FROM_LIBRARY_FILE (from library file), DIRECT (direct)Used when (NG>0)
GLNameText·..\conductor.clbPath to ground wire library fileEnter the path to the library file, including the filename.Used when (GDataType==0)&&(NG>0)
GNameText·1/2_HighStrengthSteelNameEnter a descriptive name for this ground wire type.Used when NG>0
GWSameChoice·IDENTICALGround wires areSelect whether or not the ground wires are identical.Written as IDENTICAL (identical), DIFFERENT (different)Used when (NG>1)
NGChoice·2Total number of ground wires isSelect the number of ground wires (1 or 2).Written as 0 = 0, 1 = 1, 2 = 2
PERMGReal·1.0Relative permeabilityEnter the relative permeability of the conductor.Range 0 to 1Used when (GDataType==1)&&(NG>0)
PERMG2Real·1.0Relative permeabilityEnter the relative permeability of the conductor.Range 0 to 1Used when (GDataType==1)&&(NG>1)&&(GWSame==0)
RadiusGRealm0.0055245Outer radiusEnter the outer radius of the ground wire [m].Range 0 to 10Used when (GDataType==1)&&(NG>0)
RadiusG2Realm0.0055245Outer radiusEnter the outer radius of the ground wire [m].Range 0 to 10Used when (GDataType==1)&&(NG>1)&&(GWSame==0)
SAGGRealm10.0Sag (all ground wires)Enter the sag for all ground wires. This is the difference between the height at the tower, to the height mid-span [m].Range 0 to 10000Used when (NG>0)

Phase/Node Connection Information

ParameterUnitDefaultDescription
NC1Integer·1Conductor 1 (C1)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30
NC10Integer·10Conductor 10 (C10)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=10
NC11Integer·11Conductor 11 (C11)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=11
NC12Integer·12Conductor 12 (C12)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=12
NC2Integer·2Conductor 2 (C2)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=2
NC3Integer·3Conductor 3 (C3)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=3
NC4Integer·4Conductor 4 (C4)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=4
NC5Integer·5Conductor 5 (C5)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=5
NC6Integer·6Conductor 6 (C6)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=6
NC7Integer·7Conductor 7 (C7)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=7
NC8Integer·8Conductor 8 (C8)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=8
NC9Integer·9Conductor 9 (C9)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when Nc>=9
NG1Integer·4Ground Wire 1 (G1)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when (NG>0)&&(ElimGW==0)
NG2Integer·5Ground Wire 2 (G2)Enter a number for this conductor to coincide with the external node connection.Range 1 to 30Used when (NG>1)&&(ElimGW==0)

Configuration

ParameterUnitDefaultDescription
NcChoice·3Total number of conductorsEnter the total number of conductors, excluding ground wires (maximum 12).Written as 1 = 1, 2 = 2, 3 = 3, 4 = 4, 5 = 5, 6 = 6, 7 = 7, 8 = 8, 9 = 9, 10 = 10, 11 = 11, 12 = 12
SHSagChoice·HIDDENGraphic of conductor sag isSelect whether or not to diplay conductor sag graphic.Written as HIDDEN (hidden), VISIBLE (visible)
STLChoice·NONEGroupingEnable grouping of conductors if you would like to organize them into circuits. This is important for the display of double-circuit line constants in load flow RXB format in the output file.Written as NONE (None), ORGANIZE_CONDUCTORS_INTO_CIRCUITS (Organize conductors into circuits)Used when ((Nc==6) || (Nc==9) || (Nc==12)) && (Transp==1)
ShuntGRealmho/m1.0E-11Shunt conductanceEnter a shunt conductance value for all conductors in this tower. Typically this value is around 1e-11 [mho/m].Range 1E-38 to 1
TNameText·3H5NameEnter a descriptive name for this tower.
TranspChoice·ENABLEDIdeal transposition of circuit(s)Select whether or not to ideally transpose the circuit(s). Ideal transposition ensures a perfectly balanced impedance.Written as DISABLED (disabled), ENABLED (enabled)
XRealm0.0Relative x-position of tower centreEnter the local horizontal placement of the tower. This value is relational to other towers in this cross-section [m].Range -1E+38 to 1E+38

Asymmetrical Bundling Position Data

ParameterUnitDefaultDescription
XB1Realm-0.1Sub-Conductor 1 - X Position
XB10Realm-0.1Sub-Conductor 10 - X PositionUsed when NCondB>=10
XB11Realm-0.1Sub-Conductor 11 - X PositionUsed when NCondB>=11
XB12Realm-0.1Sub-Conductor 12 - X PositionUsed when NCondB>=12
XB13Realm-0.1Sub-Conductor 13 - X PositionUsed when NCondB>=13
XB14Realm-0.1Sub-Conductor 14 - X PositionUsed when NCondB>=14
XB15Realm-0.1Sub-Conductor 15 - X PositionUsed when NCondB==15
XB2Realm-0.1Sub-Conductor 2 - X Position
XB3Realm-0.1Sub-Conductor 3 - X PositionUsed when NCondB>=3
XB4Realm-0.1Sub-Conductor 4 - X PositionUsed when NCondB>=4
XB5Realm-0.1Sub-Conductor 5 - X PositionUsed when NCondB>=5
XB6Realm-0.1Sub-Conductor 6 - X PositionUsed when NCondB>=6
XB7Realm-0.1Sub-Conductor 7 - X PositionUsed when NCondB>=7
XB8Realm-0.1Sub-Conductor 8 - X PositionUsed when NCondB>=8
XB9Realm-0.1Sub-Conductor 9 - X PositionUsed when NCondB>=9
YB1Realm0.1Sub-Conductor 1 - Y Position
YB10Realm0.1Sub-Conductor 10 - Y PositionUsed when NCondB>=10
YB11Realm0.1Sub-Conductor 11 - Y PositionUsed when NCondB>=11
YB12Realm0.1Sub-Conductor 12 - Y PositionUsed when NCondB>=12
YB13Realm0.1Sub-Conductor 13 - Y PositionUsed when NCondB>=13
YB14Realm0.1Sub-Conductor 14 - Y PositionUsed when NCondB>=14
YB15Realm0.1Sub-Conductor 15 - Y PositionUsed when NCondB==15
YB2Realm0.1Sub-Conductor 2 - Y Position
YB3Realm0.1Sub-Conductor 3 - Y PositionUsed when NCondB>=3
YB4Realm0.1Sub-Conductor 4 - Y PositionUsed when NCondB>=4
YB5Realm0.1Sub-Conductor 5 - Y PositionUsed when NCondB>=5
YB6Realm0.1Sub-Conductor 6 - Y PositionUsed when NCondB>=6
YB7Realm0.1Sub-Conductor 7 - Y PositionUsed when NCondB>=7
YB8Realm0.1Sub-Conductor 8 - Y PositionUsed when NCondB>=8
YB9Realm0.1Sub-Conductor 9 - Y PositionUsed when NCondB>=9

Conductor Coordinates

ParameterUnitDefaultDescription
XC1Realm-5Conductor 1 - X Position
XC10Realm40Conductor 10 - X PositionUsed when Nc>=10
XC11Realm45Conductor 11 - X PositionUsed when Nc>=11
XC12Realm50Conductor 12 - X PositionUsed when Nc>=12
XC2Realm0Conductor 2 - X PositionUsed when Nc>=2
XC3Realm5Conductor 3 - X PositionUsed when Nc>=3
XC4Realm10Conductor 4 - X PositionUsed when Nc>=4
XC5Realm15Conductor 5 - X PositionUsed when Nc>=5
XC6Realm20Conductor 6 - X PositionUsed when Nc>=6
XC7Realm25Conductor 7 - X PositionUsed when Nc>=7
XC8Realm30Conductor 8 - X PositionUsed when Nc>=8
XC9Realm35Conductor 9 - X PositionUsed when Nc>=9
YC1Realm30Conductor 1 - Y Position
YC10Realm30Conductor 10 - Y PositionUsed when Nc>=10
YC11Realm30Conductor 11 - Y PositionUsed when Nc>=11
YC12Realm30Conductor 12 - Y PositionUsed when Nc>=12
YC2Realm30Conductor 2 - Y PositionUsed when Nc>=2
YC3Realm30Conductor 3 - Y PositionUsed when Nc>=3
YC4Realm30Conductor 4 - Y PositionUsed when Nc>=4
YC5Realm30Conductor 5 - Y PositionUsed when Nc>=5
YC6Realm30Conductor 6 - Y PositionUsed when Nc>=6
YC7Realm30Conductor 7 - Y PositionUsed when Nc>=7
YC8Realm30Conductor 8 - Y PositionUsed when Nc>=8
YC9Realm30Conductor 9 - Y PositionUsed when Nc>=9

Ground Wires Coordinates

ParameterUnitDefaultDescription
XG1Realm-2.5Ground Wire G1 - X PositionUsed when NG>0
XG2Realm2.5Ground Wire G2 - X PositionUsed when NG>1
YG1Realm40Ground Wire G1 - Y PositionUsed when NG>0
YG2Realm40Ground Wire G2 - Y PositionUsed when NG>1